INSTALLATION INSTRUCTIONS
WARNING
FIRE OR EXPLOSION HAZARD





WHAT TO DO IF YOU SMELL GAS






2
NOTE TO INSTALLER: This installlation manual focuses on installing the MQ furnace in a single zone only. The
MQ furnace may also be installed with the iQ Zone zoning system. The installation of the furnace itself does not
change. Additional details, such as the duct/damper design, and the low voltage wiring may be found in the following
publications:


TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION 3
 4
Combustion Air Quality ............................................... 5
Heating Load ............................................................... 5
 ................. 6
 ............................................... 6
Clearances to Combustible Materials ......................... 6
 7
 .................................................. 8
 ......... 8
 ........................................................ 8
 ..... 8
 ............................. 8
 ......................... 9
 ....................... 9
Alternate Method of Providing Air from Outside: ..... 10
 ...... 10
 .................................................... 10
 ................................................... 11
 .................................. 11
 ............................................... 11
 ............. 12
 .................. 13
 ......................................... 13
 ................................................ 13
 .................................................. 13
CIRCULATING AIR REQUIREMENTS 14
 ................................................... 14
Return Air Connections ............................................... 14
 ................................. 14
 ................................................. 15
 ............................................... 15
Acoustical Treatments ................................................. 15
FURNACE INSTALLATION 15
 ................................................ 15
 ....................................................... 15
 .................................................. 15
Bottom Panel Removal ............................................... 16
Alternate Bottom Panel Removal ............................. 16
 .......................................... 17
 ......................................... 17
Accessories ................................................................. 17
 ........................................................... 17
 ................................................... 17
 .................................................... 18
Typical Orientation ............................................. 18
Alternate Orientation .......................................... 18
 .......................................... 18
 .............................................. 19
 20
Leak Check ................................................................. 20
High Altitude Application ............................................. 20
Conversion to LP/Propane .......................................... 22
ELECTRICAL WIRING 22
 ..................................................... 23
 ...................... 23
 ...................................................... 23
 ....................................................... 23
 ......................................... 23
 .......................................... 23
 ................................................................... 23
25
 .................................................... 25
 .................................................. 25
 .................................................... 25
 ........................... 25
 ..................... 26
 .......................................... 26
 ...... 26
OPERATING SEQUENCE 26
Heating Cycle .............................................................. 26
Cooling Cycle .............................................................. 26
 .................................................................... 27
 ................................................. 27
MAINTENANCE 27
TROUBLESHOOTING 28
 29
 ....................... 29
 ................................................................. 29
 ............. 29
 ........................................................... 30
 ......................................... 30
 .................................. 30
 ..................................................... 31
 ...... 31
 ...... 31
 ......... 31

 .............................. 32
 ..................................................... 33
 .................. 33

 ..................................... 34

 ............................... 35
 .... 36
 .................................................. 37
 ............................. 37
 40
3
WARNING:


      






   
mechanical skills or tools, call your local dealer for
assistance.
    
  
thoroughly understand the instructions provided with






the unit: Rags, brooms, vacuum cleaners, or other
cleaning tools, spray or aerosol cans, soap powders,
  
plastic containers, paper bags or other paper products,
gasoline, kerosene, cigarette lighter fluid, dry cleaning
fluids, paint thinners, or other volatile fluids.

diagram before making any electrical connections to the
32) or the unit wiring label.
        


IMPORTANT SAFETY INFORMATION




designate a degree or level of seriousness and should
not be ignored.
WARNING

CAUTION

or property damage.
WARNING:


     


    
     

WARNING:
     


WARNING:
    


      
     


4

WARNING:
      
     

    
     

   
these instructions, all applicable local building codes



   
Refer to the furnace rating plate.
 

6).

    page 7, page 8, page
9
, page 10.

  
  12), 
12)
, 12)12).
    
Connect this furnace to an approved vent system only,
as specified on page 10, page 11, page 12 page
13
.
         
a commercially available soap solution to check all

page 20.


Consult
29) and the rating plate for the
      
important that the duct system be designed to provide
  
improperly designed duct system can result in nuisance
shutdowns, and comfort or noise issues.

to areas outside the space containing the furnace, the

furnace casing and terminating in the conditioned space.
page 14.


page 6.
       

guidelines listed on
page 6.

compliance with regulation 248 CMR 4.00 and 5.00 for
installation of through – the – wall vented gas appliances
as follows:
    

the bottom of the vent terminal and the air intake is
installed below four feet above grade the following

 
be placed on each floor level where there are



 








recognized under 527 CMR.
      


compliance with the manufacturer’s instructions.
A copy of the installation instructions shall remain

of the installation.
        

directly above the location of vent terminal. The



    

bottom of the vent terminal and the air intake is installed


 
floor level where there are bedrooms. The detector


 




      


compliance with the manufacturer’s instructions.
A copy of the installation instructions shall remain

of the installation.
5


Commercial buildings
Buildings with indoor pools




Permanent wave solutions

Chlorine based swimming pool chemicals


Carbon Tetrachloride
Halogen type refrigerants

Printing inks, paint removers, varnishes, etc.
Hydrochloric Acid
Cements and glues
Antistatic fabric softeners
Masonry acid washing materials
Heating Load
This furnace should be sized to provide the design heating

using approved methods available from Air Conditioning


or other approved engineering methods. 
       
 The ductwork should
be appropriately sized to the capacity of the furnace to
ensure its proper airflow rating.
Zoned systems may increase undesirable effects of
      
the heating load for zoned installations.

a sea level input rating large enough that it will meet the
heating load after deration for altitude.
       


furnace can function like 11 different furnaces.

         



      
heat output needed and changes the step accordingly.
         

are 5 additional steps that use different on and off times.


thermostat can control the heat delivered to the residence

The information listed below is for reference purposes only

state codes. Always consult with local authorities before
installing any gas appliance.

 

       


 
       
  
      

Electrical Connections
 
 

 
 
General Installation
     

       


 
     


 


 


CAUTION:
       

       
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use outdoor air. However,
the use of indoor air in most applications is acceptable

        

the outdoors by way of attic, crawl space, air duct, or

page 8 
6

CAUTION:



        


Operating gas furnaces in construction environments can
cause a variety of problems with the furnace. Proper use

construction is recommended. This gas furnace may be
used during construction if it is not in violation of any
applicable codes and the following criteria are met:

furnace must be permanently installed according to the
instructions supplied with the furnace including electrical
supply, gas supply, duct work and venting. The furnace
must be controlled by a thermostat properly installed
according to the instructions supplied with the furnace
and thermostat. The installation must include a properly


when necessary.
  
structure and located such that dust and gases
from construction activity are not introduced into the
combustion system.
     
does not freeze in the furnace or condensate drain lines
    
overnight if turned off.
     
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
must be cleaned and/or repaired if found to be dirty,


approved by applicable local authority even if this


     
acceptable). This information will be used to track the
    
furnaces. Proof of this submittal shall be available for

    
temperatures in ranges normally found in occupied
residences, including setbacks. Minimum continuous




Installation in a Garage
WARNING:
FIRE OR EXPLOSION HAZARD




        


garage with the provision that the burners and igniter are

The furnace must be located or protected to prevent
physical damage by vehicles.


       
combustible material listed in
. To obtain model

furnace rating plate, located inside of the furnace cabinet.
Access for positioning and servicing the unit must be
considered when locating unit. The need to provide
        




INSTALLATION CLEARANCES
 ............  ............
 ..........   ...............
 ...................  ..........
NOTE: Allow 24 inches minimum clearance for servicing. Recommended
clearance is 36 inches.
TOP
FRONT
UPFLOW
APPLICATIONS
HORIZONTAL
APPLICATIONS
VENT
SIDE
TOP
BOTTOM
VENT
FRONT
BACK
SIDE
LEFT SIDE
RIGHT SIDE


7

REQUIREMENTS
WARNING:
CARBON MONOXIDE POISONING HAZARD
      

     

      

     
while all other appliances connected to the

      






      



and windows and all doors between the space
in which the appliance(s) connected to the



      



      

     
    


     
      




corrected in accordance with the National Fuel



      
     


     

IMPORTANT INFORMATION:
   


        
        




 

with the National Fuel Gas Code (NFGC) and all

      




       


        


page 5
WARNING:
     
      
        
   
 


WARNING:
       
       
  

      
   




       
outdoors and vent combustion products back outside.



Another important consideration when selecting one or

can sometimes be contaminated with various household
8
chemicals . These chemicals can cause severe corrosion

has the additional advantage that it isolates the system
from the effects of negative pressure in the house.
CAUTION:
     





      



Air openings on top of the furnace, in closet doors or



burners. This safety device is a manually reset switch.

        
       
switch must be replaced, use only the correct sized part

Direct Vent Furnaces

from the outdoors and then vent the combustion products
back outside, isolating the entire system from the indoor

is sealed and clearances to combustibles are maintained
        


Spaces

cubic feet per 1,000 Btuh of the combined input rates of
all appliances drawing combustion air from that space.


which supply heated air to areas outside the space must
draw return air from outside the space and must have the


of their respective openings to the furnace space. Attics
or crawl spaces must connect freely with the outdoors if
they are the source of air for combustion and ventilation.

whether inside or outside air is used to support combustion,
the method by which the air is brought to the space, and

all cases, the minimum dimension of any combustion air
opening is 3 inches.



inch per 1,000 Btuh of total input of all appliances in the
not less than 
 and 
EXAMPLE


a free area of at least 100 in
2

rate of all appliances is 120,000 Btuh, each opening
must have a free area of at least 120 in
2
.

TOTAL INPUT
RATING (BTUH)
MINIMUM FREE AREA
(EACH OPENING)
ROUND DUCT
DIAMETER
40,000  12 inches
60,000  12 inches
80,000  12 inches
100,000  12 inches
120,000  13 inches
140,000  14 inches
160,000  15 inches
Vent or
Chimney
Furnace
Water
Heater
12” Max.
12” Max.
See
Notes
See
Notes
NOTES:
Each opening must be
at least 100 sq. in. or
1 sq. in. per 1,000 Btuh
of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.

Attic
        
outdoors, each opening shall have a minimum free area



9).


ducts, the openings and ducts must have a minimum free

9).
9
TOTAL INPUT
RATING (BTUH)
MINIMUM FREE AREA
(EACH OPENING)
ROUND DUCT
DIAMETER
40,000  4 inches
60,000  5 inches
80,000  5 inches
100,000  6 inches
120,000  6 inches
140,000  7 inches
160,000  8 inches
Air Duct must be
at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Ducts must
extend above
attic insulation.
Air Duct must be
at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Ventilation Louvers
at each end of attic
Attic
Insulation
12" Max
Furnace
Water
Heater
Vent or
Chimney

Through Vertical Ducts


Space or Vented Attic
Water
Heater
Vent or
Chimney
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Furnace
Ventilation Louvers For
Unheated Crawl Space
-
-
-
-
-
-
-
-
-
Inlet Air
Ventilation Louvers
(each end of attic)
NOTE: Air openings shall
each have a free area of
not less than one square
inch per 4,000 Btuh of the
total input rating of all
equipment in the enclosure.
-
-
-
-
-
-
-
-
-
Alternate
Air Inlet
Outlet
Air


ducts, the openings and ducts must have a minimum free


large as the free area of their respective openings to the
.


wall, the two openings must each have free area of at

.


Through Horizontal Ducts
TOTAL INPUT
RATING (BTUH)
MINIMUM FREE AREA
(EACH OPENING)
ROUND DUCT
DIAMETER
40,000  5 inches
60,000  6 inches
80,000  7 inches
100,000  8 inches
120,000  9 inches
140,000  10 inches
160,000  10 inches
Furnace
Water
Heater
Air Ducts must be
at least 1 sq. in.
per 2,000 Btuh of
total input rating.
Vent or
Chimney
Air Duct
Air Duct

TOTAL INPUT
RATING (BTUH)
MINIMUM FREE AREA
(EACH OPENING)
ROUND DUCT
DIAMETER
40,000  4 inches
60,000  5 inches
80,000  5 inches
100,000  6 inches
120,000  6 inches
140,000  7 inches
160,000  8 inches
NOTE: Each opening to outside
must be at least 1 sq. in. per
4,000 Btuh of total input rating.
12" Max.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Furnace
Water
Heater
Vent or
Chimney
12"
Max
See
Note
See
Note


10
EXAMPLE
A space with a water heater rated at 45,000 Btuh input





WARNING:
     
      
        
   
 


      




this section and provide air for combustion and ventilation
according to on page 7, page 8, page 9, page 10.
The length of vent and combustion air piping for either
type of installation are shown in in 10)



slightly acidic and can cause severe corrosion of ordinary

affected by restrictive vent and combustion air piping.
Alternate Method of Providing Air from
Outside:



combustion air. One opening must be within 12 inches of
the ceiling, and the other must be within 12 inches of the
floor. However, an alternative method recently adopted by

of the space. This method may be used if it is acceptable
to the local codes.
THE FOLLOWING CONDITIONS MUST BE MET:
          
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl or
attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 in2.
per 3,000 Btu per hour of the total input rating of all

3. The free area must not be less than the sum of all the
areas of the vent connectors in the enclosure.

Spaces

separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.




combustion and venting, even though the furnace is located
 above.
Table 1
Vent Pipe Lengths
FURNACE
MODELS
(BTU)
FURNACE
INSTALLATION

WITH 1 LONG RADIUS ELBOW*

WITH 1 LONG RADIUS ELBOW ON EACH PIPE*
OUTLET
2” DIAMETER
OUTLET
3” DIAMETER
INLET/OUTLET
2” DIAMETER
INLET/OUTLET
3” DIAMETER
60,000
Upflow 50 80 50 80
Horizontal 40 80 40 80
80,000
Upflow 60 90 60 90
Horizontal 50 90 50 90
100,000
Upflow 50 90 50 90
Horizontal
40 90 40 90
120,000
Upflow
 90  90
Horizontal  70  70
*NOTES:





11
The inducer assembly on this furnace can be rotated to
vent the flue products out of the left or right side of the




of the following materials in the list and must conform to

MATERIALS STANDARDS
 ..................................................
 .................................................................
 ....................................................
 .................................................................
 .................................................
 ..............................

 ...................................



instructions supplied with the PolyPro vent kits
      
        
      
       

      






      
minimum number of elbows or turns.

close to the furnace outlet as practical.


Table 1
a furnace of known input rate, when installed with piping
of selected diameter and number of elbows. To use the
table, the furnace input rate, the centerline length and the
number of elbows on each pipe must be known.


This is conveniently handled using the idea of equivalent
length



worth 7 ft.

listed in Table 1. Measure the linear length of the vent run




CAUTION:
       


clearance between vent piping and combustible surfaces.
However, it is good practice to allow space for convenience
in installation and service.

the combustion air intake is not located near a source
of solvent fumes or other chemicals which can cause

of substances on
page 5).

and the outdoors. Horizontal piping from inducer to
   


page 17
for additional information.


same atmospheric pressure zone. This means both

, 
12)
, 12)12).

does not bear on the furnace. Pipe supports must be
installed a minimum of every 5 feet along the vent run

may be at shorter intervals if necessary to ensure that
there are no sagging sections that can trap condensate.
36)
couplings along the vent pipe, on either side of the

code.


    
hose clamps can be used. These couplings can be
ordered through your local furnace distributor. To install
a coupling:

is attached to the furnace and secure it with one of the
hose clamps.

pipe from the vent.
       
ensuring that the connection is tight and leak free.
12

   
be installed as depicted in   and in
accordance with these instructions:




termination to windows and building air intakes.
    
be located to ensure proper furnace operation and
conformance to applicable codes. A vent terminal
must be located at least 3 feet above any forced air
inlet located within 10 feet. This does not apply to the


33).


.


      
horizontally from any electric meter, gas meter, regulator

     
precedence over these instructions.
     
directed into window wells, stairwells, under decks
or into alcoves or similar recessed areas, and do not
terminate above any public walkways.

according to the pipe diameter size of the installation.
       
      







obtain clearances shown in , a riser may be used
as shown in 
      


Note 2
Mechanical draft
vent terminal
Direct vent
terminal
50,000 Btuh
or less
Forced air inlet
Direct vent
terminal - more
than 50,000 Btuh
Mechanical
draft vent
terminal
Mechanical
draft vent
terminal
Less
than
10 ft.
3 ft.
NOTES:
1. All dimensions shown are
minimum requirements.
2. Exterior vent terminations must
be located at least 12” above the
maximum expected snow level.
Note 2
4 ft
4 ft
12 in.
12 in.
9 in.
Note 2
Vent Locations


12” min. to maximum
expected snow level
(both pipes)
90° Elbow
Exhaust vent
option B
Exhaust vent
option A
Mounting kit faceplate
secured to wall with screws
(both pipes)
Combustion
air inlet
Exhaust vent
option C
18” Min.
36” Max.
8” Min.
36” Max.
(all positions)

Support
NOTE: Vent Configuration to Provide
12" Minimum height above Snow Level.
1/2"
Armaflex
Insulation or
Equivalent
(if required)
12" Above
Maximum
Expected
Snow Level
19" Max.
(See Note)
Outside
Wall
Alternate Horizontal Vent Installation

Combustion Air
Exhaust Vent
12” Above Maximum
Expected Snow Level
(Both pipes)
Elbows on the combustion air
inlet must be positioned pointing
away from the exhaust vent.
8" Min.
36" Max.
Plumbing Vent Roof Boot
(Both Pipes)

13


each other are shown in . The roof penetration must
be properly flashed and waterproofed with a plumbing
    

is not in use provided that:

the chimney.

     are
maintained.

through the chimney.

CAUTION:

      





Table 2


noted in 10)



    
  



in Table 1. The restriction should be counted as 3


length of the 2 inch pipe must not be longer than 18
inches.
      
combustion system, a protective screen may be installed
over the combustion air intake opening. The screens
hole size must be large enough to prevent air restriction.



not be sized properly to vent the remaining appliances

system can result in the formation of condensate, leakage,


be brought into compliance before installing the furnace.
NOTE: 


The pipes involved in the recall are High Temperature

these pipes  This
recall does not apply to other plastic vent pipes, such


Condensate Disposal
The method for disposing of condensate varies according
to local codes. Consult your local code or authority having




run to the drain. The drain lines must be routed downward
to ensure proper drainage from furnace.

furnace. 




16).
Table 2
WINTER DESIGN
TEMPERATURE
MAXIMUM FLUE PIPE LENGTH (FEET)

WITHOUT INSULATION WITH INSULATION*
20 45 70
0 20 70
 10 60
*NOTE:         

Vent Protection
14
     
side) of the furnace or in parallel with the furnace.
      
furnace, a damper must be installed to prevent chilled
air from entering the furnace and condensing on the heat

it must be designed so that operation of the furnace is
prevented when the damper is in the cooling position
and operation of the cooling system is prevented when
the damper is in the heating position.
     
  
    
     

Return Air Connections
     
air to areas outside the space where the furnace is
installed, the return air must be delivered to the furnace

size and without interruption. 

    

opening and return air duct. NOTE: The ductwork must

29)
for return air opening size.


side, right side, or bottom of the furnace. NOTE:
the left or right side of the furnace for return air, the
) must not be removed from the
bottom of the furnace.
WARNING:







Side Return Installations: To attach the return air duct
to the left or right side of the furnace, punch out the 4


29)
. Using sharp metal cutters, cut an opening

Position the return air duct over the opening and secure
to the side with sheet metal screws.

) must
page
16
for removal instructions. Position the furnace over
the return air duct and secure together with sheet metal
screws. Make sure the screws penetrate the duct and
furnace casing.
CIRCULATING AIR REQUIREMENTS
WARNING:

      
     
     


       



       




      

      







     


29)


are recommended. NOTE:  
furnaces cannot be changed manually by resetting the
dipswitches on the motor control board.
       
removable access panel. The opening should be
accessible when the furnace is installed in service and
shall be of a size that smoke or reflected light may be
observed inside the casing to indicate the presence of

shall be attached in such a way as to prevent leaks.
      

must be designed so that the return air is not less than

and outdoor air is used, the ducts and damper system
must be designed so that the return air supply to the

indoor return air applications.
      
furnace blower to provide airflow over the indoor coil,
15


bend the flanges on the furnace upward 90° with wide

29) for furnace flange
locations. NOTE:
casing, bend the flanges on the coil casing upward 90°
before attaching the return air duct.
    
     
sure the screws penetrate the sheet metal casing and
flanges.



running full size and without interruption.
       
furnaces, bend the flanges on the furnace upward
29) for
furnace flange locations. NOTE:
includes AC coil casing, bend the flanges on the coil
casing upward 90° before attaching the supply air duct.
      
ensuring even alignment of furnace air opening and
supply air duct. NOTE: The ductwork must have an

 for supply air opening size.

      


noise eminating from the furnace. These treatments can

space. However, they can increase the pressure drop in
the duct system. Care must be taken to maintain the proper

rise and flow rate. This may mean increasing the duct
size and/or reducing the blower speed. These treatments
must be constructed and installed in accordance with
     

performance, be sure to install all the needed gaskets and
grommets around penetrations into the furnace, such as
for electrical wiring.
FURNACE INSTALLATION

or horizontal right or left positions with either right, left,
or upflow return air.



10)
     
    
stairs, etc).
  
components are protected from water.
     


in the side of the furnace when rotating the inducer.
     
  page 7, page 8, page
9
, page 10, page 11, page 12 page 13 for

Upflow Installation
WARNING:
      



installed as shown in 31)
is installed with side return air, the bottom panel must not

Bottom Panel
Removal
section.
Horizontal Installation
WARNING:

     


).

or utility room in either a right to left airflow or left to right
airflow as shown in
.


bottom panel from the furnace before attaching the duct
page 16).



),

inches past the top and front of the furnace.
16
NOTE:


    ) using slotted iron channel


rafters with lag bolts. The furnace can also be suspended
using steel straps around each end of the furnace. The
straps should be attached to the furnace with sheet metal
screws and to the rafters with bolts.
        
that cement board or sheet metal be placed between the

beyond the front of the door and top of the furnace.

The steps listed below describe how to remove the bottom
16).

       
blower deck.



of the furnace.



furnace.



Flue pipe vented
to outside
J-Trap
Height
3” Min.
Coil Plenum
Wood or
non-combustible
platform
Combustion Air
Condensate
Drain Lines


Lag
Bolt
Nuts (x2)
Washer
and
Lockwasher
Nuts (x2)
Threaded
Rod
Alternate Bottom Panel Removal

instructions, the steps below are an alternate method for
.









6. Carefully spread the bottom corner of the furnace cabinet

the front of the furnace.
7. Reassemble the furnace in reverse order.


6
7
5
1
2
3
4

1
4
2
7
3
6
5

17
Table 3
1 - PIPE INSTALLATIONS
VENT UPFLOW HORIZONTAL RIGHT HORIZONTAL LEFT
Right Option 1  Option 6
Left Option 2 Option 5 
2 - PIPE INSTALLATIONS
VENT UPFLOW HORIZONTAL RIGHT HORIZONTAL LEFT
Right Option 3  Option 8
Left Option 4 Option 7 


assembly.
       
switch.

inducer assembly.
4. Remove 4 screws securing the inducer assembly to

5. Rotate the inducer assembly to its new position.
NOTE:

        
reinstalling the 4 screws.
7. Move the cabinet plug from side of furnace and reinstall
in hole on opposite side of cabinet.
8. Reconnect the electrical harness to the inducer
assembly.
Accessories
The components in 18) are


installation, some of these components are optional and
may not be used. Please refer to the descriptions and



air pipe through the top of the furnace. NOTE:
installation, it is important that the pipe and screw holes

.
1. Position flange gasket over hole in the furnace cabinet.



supplied sheet metal screws.





.
         
between the furnace cabinet and the gas pipe. The rubber




side of the cabinet and the drain tube is routed through
the blower deck. Remove the plastic plug from the hole
and install the grommet before routing the drain tube.




disposal and, in some cases, the need to seal the furnace
cabinet.
IMPORTANT NOTE


Before using Table 3      



select the option that properly matches your installation
type from 34)35).
NOTE:
maintain an airtight flow path from the air inlet to the flue





be closed off with the plastic cap to maintain air tightness

horizontal furnaces are indicated in 29).

WARNING:
     

    
     

CAUTION:
It is good practice to label all wires prior to


18

IMPORTANT NOTE



          
18)
are used when the inducer is rotated to vent
out thru the left or right side of the furnace cabinet.
NOTE:


           

be installed from inside the cabinet with the threaded


drain line to the threaded end.
Typical Orientation


them together using appropriate primer and cement.
Refer to the typical orientation shown in .
         

together using appropriate primer and cement.

NOTE: 


alignment with other vent pipes.
Alternate Orientation


bond them together using appropriate primer and
cement. Refer to the alternate orientation shown in
.

Permanently bond them together using appropriate
primer and cement.
         

together using appropriate primer and cement.

NOTE: 


alignment with other vent pipes.

IMPORTANT NOTE









2” PVC Tee
1/2” Tubing Formed
into a Loop
(Field Supplied)
PVC
Trap
2” PVC Pipe from Inline
Drain Assembly
(Not Included)
INSTALLATION OF PVC COMPONENTS
(TYPICAL ORIENTATION)
INSTALLATION OF PVC COMPONENTS
(ALTERNATE ORIENTATION)
2” PVC Pipe from Inline
Drain Assembly
(Not Included)
2” PVC Tee
2” PVC Elbow
(Field Supplied)
PVC
Trap
1/2” x 3/4”
Hose Barb
1/2” x 3/4”
Hose Barb
1/2” Tubing Formed
into a Loop
(Field Supplied)


ø 2 1/4” Rubber
Grommet
ø 7/8” Rubber
Grommet
ø 3/4” Rubber
Grommet
Flange
Gasket
FRONT
FRONT lettering must be
located near front
of furnace
Inlet Air
Finish Flange

19
The placement of the condensate drain lines will depend
17). The
drain lines can be routed out the left or right side of the
furnace, but must maintain a downward slope to ensure
proper condensate drainage.

your setup in 34)35).


THREE GENERAL PRINCIPLES APPLY:


trapping the condensate lines, it is acceptable to
combine the drains.



venting system. NOTE:
furnace drain line must be installed above the pumps
water line.

GENERAL RULES:

Option 2Option 4).


be turned vertically with a tee. The drip leg formed
   
Option 1, Option 2,
Option 3Option 4).
      
Option 1, Option
3
, Option 5Option 7). More importantly, make sure
this drain does not sag or become twisted in the middle.
The drain tube supplied with the furnace may need to
be trimmed.
Pressure Switch Tubing
WARNING:

EXPLOSION HAZARD



     




The static tap on the inducer is located behind the


 displays the proper routing of pressure switch

have two pairs of switches. One set is connected to the
static tap on the inducer assembly and the other to the



NOTE: 
20
The furnace may be installed for either left or right side
       
clearance between the gas supply line and the entry
hole in the furnace casing to avoid unwanted noise and/
or damage to the furnace. A typical gas service hookup
is shown in .

WARNING:
FIRE OR EXPLOSION HAZARD



     
      



After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes
pipe connections at the main gas valve, emergency

The soap and water solution can be applied on each


must be retightened. Repeat the tightening and soap
check process until bubbling ceases.
IMPORTANT NOTE






High Altitude Application
The installation of this furnace at altitudes above 2,000



Please consult your local code authority.
        





  
thermostat will not use the higher of its

output. 21) lists the highest running step
and its associated manifold pressures for each altitude.

WARNING:
FIRE OR EXPLOSION HAZARD
 

 


       


WHAT TO DO IF YOU SMELL GAS
 
      

 
       


 

 





IMPORTANT NOTES:
 


21)





 

 
       

 


 



 
run to the unit as shown in
Figure 18
30) lists gas flow capacities for standard
pipe sizes as a function of length in typical applications
based on nominal pressure drop in the line.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80

Broan PGC2MQ Guide d'installation

Catégorie
Pompes à chaleur
Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues