Simplicity 040589-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

Copyright©Briggs & Stratton Corporation
Milwaukee, WI, USA. All Rights Reserved.
80081732
Revision C
Not for
Reproduction
2
Table of Contents:
California Proposition 65..................................................... 3
Thank You..............................................................................3
Where to Find Us..................................................................3
For Future Reference........................................................... 3
Important Safety Instructions..............................................3
Safety Alert Symbol and Signal Words............................ 3
Safety Symbols and Meanings.........................................3
Safety Messages.............................................................. 4
FCC Part 15 Information To User.................................... 7
General Information..............................................................8
Equipment Description..................................................... 8
Installer Responsibilities...................................................8
Owner Responsibilities.....................................................8
Installation Factors to Consider........................................8
Delivery Inspection........................................................... 8
Shipment Contents........................................................... 8
Generator Placement............................................................9
Generator Location Considerations..................................9
Reduce the Risk of Carbon Monoxide Poisoning.............9
Reduce The Risk of Fire................................................ 11
Other General Location Guidelines................................13
Installation........................................................................... 14
Lifting the Generator...................................................... 14
Cold Weather Kit............................................................ 14
Anchoring and Wind Rating........................................... 14
Electrical and Fuel Inlet Locations................................. 15
Access Panels................................................................ 15
Fuel Installation Plan......................................................16
Electrical Field Connections........................................... 20
Final Installation Considerations.................................... 22
System Control Board.................................................... 23
Initial Start-Up (No Load)............................................... 24
Operation............................................................................. 26
Features and Controls - 17kW and 20kW
Generators......................................................................26
Important Owner's Considerations................................. 28
Automatic Operation Sequence..................................... 28
Setting the Exercise Timer.............................................28
Maintenance.........................................................................30
Servicing the System..................................................... 30
Maintenance Schedule...................................................30
Generator Maintenance..................................................30
Cleaning the Generator..................................................30
Engine Maintenance.......................................................31
Changing Engine Oil and Oil Filter.................................31
Adjust Valve Lash.......................................................... 32
Electronic Governor System...........................................33
Electronic Governing Check...........................................33
Service the Spark Plugs.................................................34
Engine Air Cleaner......................................................... 34
Exhaust System Maintenance........................................35
Fuel System Maintenance..............................................35
Mixer/Throttle Control Device.........................................35
Alarms (Service Code Detection System)......................35
Acknowledge and Reset the Alarms (Service Code
Detection System).......................................................... 35
Electrical System Maintenance...................................... 36
Troubleshooting..................................................................38
Troubleshooting.............................................................. 38
Diagrams and Schematics................................................. 40
Wiring Diagram and Schematic......................................40
Specifications......................................................................41
Generator Specifications: 17kW and 20KW...................41
Engine Specifications..................................................... 41
Not for
Reproduction
3
California Proposition 65
WARNING
This product can expose you to chemicals including used
engine oil, which is known to the State of California to
cause cancer, and carbon monoxide, which is known
to the State of California to cause birth defects or
other reproductive harm. For more information go
towww.P65Warnings.ca.gov.
Thank You
Thank you for purchasing this quality-built Briggs & Stratton®
generator. We are pleased that you have placed your
confidence in the Briggs & Stratton brand. When operated
and maintained according to the instructions in this manual,
your generator will provide many years of dependable
service.
This manual contains safety information to make you aware
of the hazards and risks associated with standby generators
and how to avoid them. This product is only for use as an
optional generator system which provides an alternate
source of electric power and to serve loads such as heating,
refrigeration systems, and communication systems that, when
stopped during any power outage, could cause discomfort or
inconvenience.
SAVE THESE INSTRUCTIONS -This manual contains
important instructions that must be obeyed during installation,
operation, and maintenance of the generator and batteries.
This generator system requires professional installation
before use.The installermust obeythe instructions
completely.
Where to Find Us
You never have to look far to find support and service for
your equipment. There are many authorized service dealers
worldwide that provide quality service. You can also contact
Customer Service by phone at800-732-2989between 8:00
AM and 5:00 PM central time or click on Dealer Locator
at www.briggsandstratton.com, which provides a list of
authorized dealers.
For Future Reference
Please fill out the information below and keep with your
receipt. Have this information at hand if it becomes necessary
to contact your installer or authorized dealer regarding service
or repair of the unit.
Date of Purchase: ________________________________
Dealer / Retailer: _________________________________
Dealer's / Retailer'sPhone Number: __________________
GENERATOR:
Model Number: ____________________________
Model Revision: ____________________________
Serial Number: ____________________________
ENGINE:
Model Number: __________________________________
Serial Number: ___________________________________
Important Safety Instructions
Every effort has been made to make sure that the information
in this manual is accurate and current. However, we reserve
the right to change, or improve the product and this document
without notification.
The manufacturer cannot possibly anticipate every possible
circumstance that can involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not recommend, you must satisfy yourself that it is safe for
you and others. You must also make sure that the procedure,
work method or operating technique that you choose does not
render the equipment unsafe.
Safety Alert Symbol and Signal Words
The safety alert symbol identifies safety information
about hazards that can result in personal injury. A signal
word (DANGER,WARNING, orCAUTION) is used with
the alert symbol to indicate the likelihood and the potential
severity of injury. In addition, a hazard symbol may be used
to represent the type of hazard.
DANGERindicates a hazard which, if not
avoided,willresult in death or serious injury.
WARNINGindicates a hazard which, if not
avoided,couldresult in death or serious injury.
CAUTIONindicates a hazard which, if not
avoided,couldresult in minor or moderate injury.
NOTICEIndicates information considered important but not
hazard-related.
Safety Symbols and Meanings
Symbol Meaning
Safety alert symbol. Indicates a potential personal injury
hazard.
Not for
Reproduction
4
Symbol Meaning
Read Manual. Failure to obey warnings, instructions,
installation manual, and operator’s manual could result in
death or serious injury.
Fire
Explosion
Electric Shock
Toxic Fumes
Moving Parts
Wear Eye Protection
Hazardous Chemical
Hot Surface
Rotating Parts
Crush and Cut
Explosive Pressure
Symbol Meaning
Auto Start
Safety Messages
WARNING
Failure to read and obey the operator’s manual, all
warnings, and operating instructions could result in death or
serious injury.
WARNING
Engine exhaust contains carbon monoxide, a
poisonous gas that could kill you in minutes. You cannot
smell it, see it, or taste it. Even if you do not smell exhaust
fumes, you could still be exposed to carbon monoxide gas.
Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
Direct exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open
garage doors or other openings that can allow exhaust
gas to enter inside or be drawn into a potentially
occupied building or structure.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
If you start to feel sick, dizzy, weak, or your carbon
monoxide alarm sounds while using this product, get to
fresh air right away. Call emergency services. You may
have carbon monoxide poisoning.
WARNING
Storage batteries give off explosive hydrogen gas
during recharging. Slightest spark could ignite hydrogen
and cause explosion, resulting in death or serious injury.
DO NOT dispose of battery in a fire. Recycle battery.
DO NOT allow any open flame, spark, heat, or lit
cigarette during and for several minutes after charging a
battery.
Not for
Reproduction
5
WARNING
Battery electrolyte fluid contains acid and is extremely
caustic. Contact with battery contents could cause severe
chemical burns.
DO NOT open or mutilate the battery
Wear protective goggles, rubber apron, rubber boots
and rubber gloves.
Immediately wash electrolyte from skin with water.
If electrolyte contacts eyes, immediately flush with
water and seek medical attention.
Spilled electrolyte is to be washed down with an acid
neutralizing agent.
WARNING
A battery presents a risk of high short circuit current.
Remove watches, rings, or other metal objects.
Use tools having insulated handles.
Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not lay tools or metal parts on top of batteries.
Disconnect the negative (-) cable at the battery during
installation and maintenance.
WARNING
Failure to isolate generator from utility power could
result in death or serious injury to electric utility workers due
to backfeed of electrical energy.
Use a listed transfer switch to connect to a building
electrical system.
WARNING
Generator and utility voltage could cause electrical
shock or burn resulting in death or serious injury.
Installation must be performed by a licensed
professional.
Disconnect all sources of electricity before installing or
servicing equipment.
Ground system before applying power.
WARNING
Hazardous Voltage -Installing low and high voltage
wire in same conduit could cause electric shock or burns,
resulting in death or serious injury.
Do not run low and high voltage wire in the same
conduit unless the insulation rating on ALL wiring is
rated for 600V. See NFPA 70 for more information.
WARNING
Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
Exhaust outlet of enclosure must have at least 5 ft.
(1.5m) minimum clearance from any structure, shrubs,
trees, or any kind of vegetation.
Enclosure must be at least 5 ft (1.5m) from windows,
doors, any wall opening, shrubs, or vegetation over 12
inches (30.5 cm) in height.
Enclosure must have a minimum of 5 ft. (1.5 m)
overhead clearance from any structure, overhang, or
trees.
DO NOT place enclosure under a deck or other type of
structure that may confine airflow.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions.
Carbon monoxide alarms cannot detect smoke.
Do not place enclosure in a manner other than shown in
illustrations.
WARNING
Exhaust heat/gases could ignite combustibles
causing a fire, resulting in death or serious injury.
Remove all combustible materials from in and around
the generator compartment.
WARNING
Gaseous vapors are extremely flammable and
explosive. Fire or explosion can cause severe burns or
death.
Never start and run the engine with the air cleaner
assembly (if equipped) or the air filter (if equipped)
removed.
Not for
Reproduction
6
WARNING
With the battery connected, the generator may crank
and start without warning resulting in death or serious injury.
Do not connect the negative (-) cable at the battery until
the installation is complete.
WARNING
With the battery connected, the generator may crank
and start without warning resulting in death or serious injury.
Before servicing, stop the generator and disconnect the
negative (-) cable at the battery.
WARNING
Hazardous Voltage - Contact with power lines could
cause electric shock or burns, resulting in death or serious
injury.
If lifting or hoisting equipment is used, DO NOT contact
any power lines.
DO NOT lift or move generator without assistance.
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
Installation must be performed by a licensed
professional.
Install the fuel supply system according to NFPA 37 and
other applicable fuel-gas codes.
Before placing the generator into service, the fuel
system lines must be properly purged and leak tested.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present.
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
The generator is equipped with an automatic safety
gasfuel shut-off valve.
DO NOT operate the equipment if the fuel shut-off valve
is missing or inoperative.
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
LP gas is heavier than air and will settle in low areas.
Natural gas is lighter than air and will collect in high
areas.
The slightest spark could ignite these fuels and cause
an explosion.
DO NOT light a cigarette or smoke.
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
Inspect the fuel system periodically.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present.
WARNING
Generatorand utilityvoltage could cause electrical
shock or burn resulting in death or serious injury.
DO NOT allow unqualified persons to operate or
servicethis equipment.
WARNING
Unintentional sparking could cause fire or electric shock
resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR
GENERATOR
Disconnect the spark plug wire from the spark plug and
place the wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
Use approved spark plug tester.
DO NOT check for spark with spark plug removed.
Not for
Reproduction
7
NOTICE Improper treatment of generator could damage it
and shorten its life.
Use generator only for intended uses.
If you have questions about intended use, contact your
authorized dealer.
Operate generator only on level surfaces.
Adequate, unobstructed flow of cooling and ventilating
air is critical to correct generator operation.
The access panels/doors must be installed whenever
the unit is running.
DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
Remain alert at all times while working on this
equipment. Never work on the equipment when you are
physically or mentally fatigued.
DO NOT insert any objects through cooling slots.
DO NOT use the generator or any of its parts as a
step. Stepping on the unit could cause stress and
break parts. This may result in dangerous operating
conditions from leaking exhaust gases, fuel leakage, oil
leakage, etc.
Shut off generator if:
electrical output is lost.
equipment sparks, smokes, or emits flames.
unit vibrates excessively or makes unusual noises.
FCC Part 15 Information To User
Pursuant to part 15.21 of the FCC Rules, you are cautioned
that changes or modifications to the product not expressly
approved by Briggs & Strattoncould void your authority to
operate the product.
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this
device must accept any interference received, including
interference that may cause undesired operation.
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is
no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference
to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following
measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and
receiver.
Connect the equipment into an outlet on a circuit different
from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician
for help.
Not for
Reproduction
8
General Information
For most applications, this manual contains the information
necessary for the correct installation, operation, and
maintenance of the equipment. All efforts have been made to
make sure that the information in this manual is accurate and
current. We reserve the right to change the product and this
document without notification.
Equipment Description
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
Emergency generator systems are intended to
automatically supply illumination, power, or both, to
designated areas and equipment in the event of failure
of the normal supply. Emergency systems can also
provide power for such functions as ventilation where
essential to maintain life, where current interruption of the
normal supply would produce serious life safety or health
hazards.
Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source which
can create hazards or hamper rescue or fire-fighting
operations.
Installer Responsibilities
Read and obey the safety instructions.
Install only aNRTL-approved transfer switch that is
compatible with the generator.
Read and obey the instructions in this Installation and
Operation Manual.
Installation must strictly comply with all applicable codes,
industry standards, laws, and regulations.
Allow sufficient room on all sides of the generator for
maintenance and service.
Discuss the generator placement with owner.
Make sure that ALL manualsare given to the owner after
the installation has been completed.
Owner Responsibilities
Read and obey the instructions in this Installation and
Operation Manual.
Follow a regular schedule for maintaining and using the
generator, as specified in this manual.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions and recommendations. Smoke alarms cannot
detect carbon monoxide gas.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions and
recommendations. Carbon monoxide alarms cannot
detect smoke.
Installation Factors to Consider
The illustrations shown in this manual are for typical
circumstances. They are meant to familiarize you with the
installation options available for the generator.
Federal and local codes, appearance, noise levels, fuel types,
and distances are installation factors that must be considered.
Remember that, as the distance increases from the existing
electrical service and gaseous fuel supply, and the number
of bends in the fuel supply increases, compensations must
be made for piping and wiring materials. This is necessary
to comply with local codes and overcome electrical voltage
drops and gaseous fuel pressure drops.
Delivery Inspection
Avoid damage from dropping, bumping, or collision with the
shipping carton.
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is found at the time of delivery, have the
person(s) making the delivery notate the loss or damage on
the freight bill and affix his signature under the consignor’s
memo of loss or damage. If the loss or damage is notated
after delivery, separate the damaged materials and then
contact the carrier for claim procedures. Missing or damaged
parts are notwarranted.
Shipment Contents
The generator system is supplied with:
Oil (5W30 Synthetic)
Flexible fuel line
Quick Operation Manual
Product and emissions warranty booklet
Two access keys
Two 15 Amp ATO-type fuses
Four lifting hole caps
Touch up paint
Not included (You will need):
Carbon monoxide detector(s)
Smoke detector(s)
Starting battery
Connecting wire and conduit
Fuel supply valves/plumbing
Crane, lifting straps, chains or cables
Two 60” (152cm) lengths of 3/4” (1.9cm) nominal
minimum Schedule 40 steel pipe (NOT conduit)
Torque screwdriver, 5 to 50 inch-pound range
Multi-meter
Not for
Reproduction
9
Generator Placement
Before installing the generator, consult with the owner
and convey the following requirements, which must be
satisfied before the installation is complete. There are two
equally important safety concerns in regards to carbon
monoxide poisoning and fire. There are also several general
location guidelines that must be met before the installation is
considered complete.
WARNING
Engine exhaust contains carbon monoxide, a
poisonous gas that could kill you in minutes. You cannot
smell it, see it, or taste it. Even if you do not smell exhaust
fumes, you could still be exposed to carbon monoxide gas.
Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
Direct exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open
garage doors or other openings that can allow exhaust
gas to enter inside or be drawn into a potentially
occupied building or structure.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
If you start to feel sick, dizzy, weak, or your carbon
monoxide alarm sounds while using this product, get to
fresh air right away. Call emergency services. You may
have carbon monoxide poisoning.
DO NOT run this product inside homes, garages,
basements, crawlspaces, sheds, or other partially-
enclosed spaces even if using fans or opening doors and
windows for ventilation. Carbon monoxide can quickly
build up in these spaces and can linger for hours, even
after this product has shut off.
ALWAYS place this product downwind and point the
engine exhaust (A) away from occupied spaces.
 (A) Exhaust outlet side of enclosure.
 (B)Air inlet side of enclosure.
Generator Location Considerations
The installation location of the generator has a direct effect
on:
1. The amount and size of the plumbing required to fuel the
generator.
2. The amount and size of the wiring required to control and
connect the generator.
3. The safety of the installation regarding exhaust gas and
carbon monoxide hazards, fire risks, proximity to other
utilities, and exposure to weather elements.
Specific location guidelines are discussed in the next
section. The owner and installer must consult one another
to determine how the site can affect installation costs and
compliance with local codes andstandards.
There are two critical safety concerns to be addressed -
carbon monoxide poisoning and the risk of fire, as follows:
Reduce the Risk of Carbon Monoxide Poisoning
The arrows in the figure below point to potential points of entry for Carbon Monoxide Gas.
Not for
Reproduction
10
All fossil fuel burning equipment, such as standby generators (A), contains carbon monoxide (CO) gas in the engine exhaust
(H). CO gas is odorless, colorless and tasteless and is unlikely to be noticed until a person is overcome. CO gas can kill you
so it is required that the following is included as part of the installation.
Install generator (A) outdoors in an area that will not accumulate deadly exhaust gas (H).
DO NOT install the generator (A) where exhaust gas (H) can accumulate and enter inside or be drawn into a potentially
occupied building or structure.
In many states it is required by law to have a Carbon Monoxide (CO) detector that works in your home. Carbon monoxide
detector(s) MUST be installed and maintained indoors according to the manufacturer’s instructions / recommendations. A
CO detector is an electronic device that detects hazardous levels of CO. When there is a buildup of CO, the detector will
alert the occupants with an alarm and by flashing a visual indicator light. Smoke alarms cannot detect CO gas.
Your neighbor(s) home can be exposed to the engine exhaust (H) from your standby generator (A) and must be
considered when installing your standby generator.
Make sure exhaust gas (H) is kept away from:
(B) Windows
(C) Doors
(D) Ventilation Intakes
(E) Soffit Vents
(F) Garage Doors
(G)Crawl spaces or other openings that can allow exhaust gas to enter inside or be drawninto a potentially occupied building
or structure.
Not for
Reproduction
11
Nearby structures may be exposed to the engine exhaust (H) from the generator (A) and must be considered when
installing the standby generator.
Wind and air currents should be taken into consideration when positioning the generator (A). Place the generator in an
area where winds will carry the exhaust gas (H) away from any potentially occupied building or structure.
DO NOT place the standby generator (A) in any area where leaves or debris can accumulate.
Reduce The Risk of Fire
Obey the installation requirements listed below. The figures below illustrate the minimum distances from structures and
vegetation to reduce the risk of fire.
The National Fire Protection Association (NFPA) standard NFPA 37 establishes criteria for minimizing the hazard of fire
during the installation and operation of stationary combustion engines. NFPA 37 limits the spacing of an enclosed generator
from openings in walls, structures and combustible materials outside the enclosure. The following generator placement
requirements are based on compliance to NFPA 37.
WARNING
Exhaust heat/gases could ignite combustibles or structures resulting in death or serious injury.
Exhaust outlet of enclosure must have at least 5 ft. (1.5m) minimum clearance from any structure, shrubs, trees, or any
kind of vegetation.
Enclosure must be at least 5 ft (1.5m) from windows, doors, any wall opening, shrubs, or vegetation over 12 inches (30.5
cm) in height.
Enclosure must have a minimum of 5 ft. (1.5 m) overhead clearance from any structure, overhang, or trees.
DO NOT place enclosure under a deck or other type of structure that may confine airflow.
Smoke detector(s) MUST be installed and maintained indoors according to the manufacturer’s instructions. Carbon
monoxide alarms cannot detect smoke.
Do not place enclosure in a manner other than shown in illustrations.
Not for
Reproduction
12
Legend for Generator Locations to reduce the risk of fire:
(A) Standby Generator
Not for
Reproduction
13
(B)Standby enclosure must be at least 5 ft (1.5 m) from windows, doors, any wall opening, shrubs or vegetation over 12
inches (30.5 cm) in height.
(C)Exhaust outlet of standby enclosure must have at least 5 ft (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
(D)Standby enclosure must have a minimum of 5 feet (1.5 m) overhead clearance from any structure, overhang or trees.
(E)Standby enclosure must have a minimum of 18 inches (45.7 cm) clearance from any structures with or without a fire
rating.
Other General Location Guidelines
Place the standby generator in a prepared location that is
flat and has provisions for water drainage.
Install the standby generator in a location where sump
pump discharge, rain gutter down spouts, roof run-off,
landscape irrigation, or water sprinklers will not flood the
unit or spray the enclosure and enter any air inlet or outlet
openings.
Install the standby generator where it will not affect or
obstruct any services (including covered, concealed and
underground), such as telephone, electric, fuel (natural
gas / LPG vapor), irrigation, air conditioning, cable, septic,
sewer, well and so forth.
Install the standby generator where leaves, grass, snow,
etc will not obstruct air inlet and outlet openings. If
prevailing winds will cause blowing or drifting, you may
need to construct a windbreak to protect the unit.
Not for
Reproduction
14
Installation
This product is only for use as an optional generator system
which provides an alternate source of electric power
and to serve loads such as heating, refrigeration, and
communication systems that, when stopped during any power
outage, can cause discomfort or inconvenience.
Every effort has been made to make sure that the information
in this manual is accurate and current. However, we reserve
the right to change, alter, or otherwise improve the product
and this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
can attempt generator system installations. Installations must
strictly comply with all applicable codes, industry standards,
laws and regulations.
Lifting the Generator
WARNING
Hazardous Voltage - Contact with power lines could
cause electric shock or burns, resulting in death or serious
injury.
If lifting or hoisting equipment is used, DO NOT contact
any power lines.
DO NOT lift or move generator without assistance.
Proper tools, equipment, and qualified personnel must be
used in all phases of handling and moving the generator. The
approximate weight of the generator is listed in theGenerator
Specificationssection.
Use the lifting holes (A) in the base of the generator to lift
the generator onto the concrete pad. Lift the generator in
accordance with OSHA or local lifting regulations. Retouch
any chipped paint with the supplied touch-up paint.
Cold Weather Kit
If the generator operates in temperatures below 30°F (-1°C),
it is HIGHLY RECOMMENDED that a Cold Weather Kit be
installed.
Cold Weather Kit, Part No. 6578 (Fortress models) includes:
Battery warmer
Battery stand
Cold Weather Kit, Part No. 6567 (Briggs & Stratton models)
includes:
Oil warmer
Battery warmer
Battery stand
Wire harness
These items are available at your local service dealer.
If you need more information, please
call800-732-2989between 8:00 AM and 5:00 PM CT.
Anchoring and Wind Rating
Concrete Anchoring of Unit to Poured or
Existing Slab
To achieve the listed wind rating, the generator must be
installed in strict compliance with this installation manual.
The product components must be of the material specified
and all screws must be installed in accordance with the
applicable provisions and the anchor manufacturer’s
published installation instructions.
The concrete slab/pad must meet the requirements below
and the generator must be anchored with the anchors
ofAnchor Types1 or 2.
Anchor Types
1. Qty (4) 3/8” SS ITW RED HEAD LDT, Anchor embedded
2 ½” (63.5mm) in 3000 psi concrete. 3” (76.2mm) from
the edge minimum, 6” (152.4mm) spacing minimum.
Not for
Reproduction
15
2. Qty (4) 3/8” SS Powers/Dewalt Power Stud +SD2
Anchor embedded 2 ½” (63.5mm) in 3000 psi concrete.
3” (76.2mm) from the edge minimum, 6” (152.4mm)
spacing minimum.
There are four 7/16” hole locations (A) in the base of the
generator in which to anchor the unit.
Concrete Slab/Pad Types
PAD DIMENSIONSWIND
RATING
MPH
PAD
MODEL
Width Length Thickness
CONCRETE
SPEC
Up to 140 Pre-cast
Pad
(contact
dealer)
37in
(939.8mm)
54.4in
(1381.8mm)
3in
(76.2mm)
3000 PSI
140 to 175 Pre-cast
Pad
(contact
dealer)
37in
(939.8mm)
54.4in
(1381.8mm)
4in
(101.6mm)
3000 PSI
140 to 175 Poured 38in
(965.2mm)
55in
(1397mm)
5in
(127mm)
3000 PSI
These items are available at your local service dealer.
NOTICE Unless mandated by local or state codes, or
required to achieve wind rating, a concrete slab/pad is not
required
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (A) and electrical inlet
locations (B) are shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate a
maximum conduit size of 1-½ inches. Make sure that the
installed conduit(s) enter the unit in zone (C) as shown in the
drawing below so that they properly enter the electrical box
and do not interfere with the fully opened roof.
Access Panels
The generator enclosure has several access panels, as
shown.
The access panels and the components located behind them
are listed below:
(A) Roof (Control Panel, air filter, oil dipstick, and circuit
breaker)
(C) Rear Access Panel (fuel regulator, fuel selector, and
engine starter)
(D) Control Panel Cover (field wiring and control wires)
(F) Battery Panel (battery and generator data label)
(H) Front Access Panel (oil drain and oil filter)
Not for
Reproduction
16
Each generator is shipped with a set of identical keys
fastened to the fuel solenoid.
Open the roof (A):
1. Insert key into lock (G) of front panel (H). Gently push
down on the roof above the lock to assist in turning the
key. Turn the key one quarter turn clockwise.
2. Lift the roof (A) to the open position.
Front panel removal (H):
1. Remove the two bolts (J) that secure the panel (H) to the
unit.
2. Lift the panel (H) to remove from unit.
Attach the front panel (H):
1. Put the panel (H) in the unit.
2. Attach the panel (H) with the two bolts (J).
Rear panel removal (C):
1. Make sure that the roof (A) is in the open position.
2. Remove the two bolts (B) that secure the panel (C) to the
unit.
3. Lift the panel (C) to remove it from the unit.
Attach the rear panel (C):
1. Slide the panel (C) into place on the unit.
2. Attach the panel with the two bolts (B).
Battery panel removal (G):
1. Make sure that the roof is in the open position.
2. Remove the two bolts (F) that secure the panel (G) to the
unit.
3. Lift up on the panel (G) and remove it.
Note:Fuse holder (E) is located behind the battery panel (G).
Attach battery panel (G):
1. Put the panel (G) in the unit.
2. Attach the panel (G) with the two bolts (F).
Fuel Installation Plan
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
Installation must be performed by a licensed
professional.
Install the fuel supply system according to NFPA 37 and
other applicable fuel-gas codes.
Before placing the generator into service, the fuel
system lines must be properly purged and leak tested.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present.
NOTICE The supplied flexible fuel line is not to be
installed underground or in contact with the ground.
The entire flexible fuel line must be visible for periodic
inspection and must not be concealed within nor contact
nor run through any wall, floor, or partition.
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
The generator is equipped with an automatic safety
gasfuel shut-off valve.
DO NOT operate the equipment if the fuel shut-off valve
is missing or inoperative.
Not for
Reproduction
17
WARNING
Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or explosion
resulting in death or serious injury.
LP gas is heavier than air and will settle in low areas.
Natural gas is lighter than air and will collect in high
areas.
The slightest spark could ignite these fuels and cause
an explosion.
DO NOT light a cigarette or smoke.
TO THE INSTALLER:Consult with the generator owner(s)
and convey any technical considerations that can affect their
installation plans before applying these general guidelines.
The following general rules apply to gaseous fuel system
piping:
The piping material must conform to federal and local
codes, be rigidly mounted, and be protected against
vibration.
Piping should be protected from physical damage,
especially where it passes through flower beds, shrub
beds, and other cultivated areas where damage can
occur.
Install the provided flexible fuel line (B) between the
generator fuel inlet port (A) and the rigid piping to
prevent thermal expansion and contraction from causing
excessive stress on the piping material.
A union (C) or a flanged connection must be provided
downstream to permit removal.
A manometer test port (D) should be installed for
vapor fuels. Use the port to install a manometer and
check if the engine receives the correct fuel pressure
for operation. A digital manometer (P/N 19495) or an
analogmanometeris available at your service center for
vapor fuels only. When the initial test runs are completed,
the manometer is removed and the port is plugged.
For vapor fuels only: Where the formation of hydrates or
ice is known to occur, piping should be protected against
freezing. The termination of hard piping must include
a sediment trap (E) where condensate is not likely to
freeze.
A minimum of one accessible, approved manual shutoff
valve (F) shall be installed in the fuel supply line within 6
ft (180 cm) of the generator.
You must install a manual fuel shut-off valve in the interior
of the building.
Where local conditions include earthquake, tornado,
unstable ground, or flood hazards, special consideration
shall be given to increase strength and flexibility of piping
supports and connections.
Piping must be of the correct size to maintain the
required supply pressures and volume flow under
varying generator load conditions with all gas appliances
connected to the fuel system turned on andoperating.
Use a pipe sealant or joint compound approved for
use with NG/LP on all threaded fittings to reduce the
possibility of leakage.
NOTICE Keep thread sealant out of the gas piping to
prevent component part damage.
Installed piping must be properly purged and leak tested,
in accordance with applicable codes andstandards.
(A) Generator Fuel Inlet
(B)Flexible Fuel Line
(C)Union Fitting
(D)Manometer Test Port
(E)Sediment Trap
(F)Manual Shut-off Valve
Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown below.
LP Vapor (Propane)
20 kW 17 kW
Cu Ft/Hr 135 118
Gal/Hr (liquid) 3.75 3.28
Full Load
BTU/Hr 337500 295000
Cu Ft/Hr 109 99
Gal/Hr (liquid) 3.03 2.75
3/4 Load
BTU/Hr 272500 247500
Cu Ft/Hr 83 74
Gal/Hr (liquid) 2.31 2.06
1/2 Load
BTU/Hr 207500 185000
Cu Ft/Hr 56 54
Gal/Hr (liquid) 1.56 1.5
1/4 Load
BTU/Hr 140000 135000
Cu Ft/Hr 40 40
Gal/Hr (liquid) 1.11 1.11
Exercise
BTU/Hr 100000 100000
Natural Gas
Not for
Reproduction
18
20 kW
(18 kW)
17 kW
15.3 kW
Cu Ft/Hr 260 248Full Load
BTU/Hr 260000 248000
Cu Ft/Hr 240 2183/4 Load
BTU/Hr 240000 218000
Cu Ft/Hr 187 1701/2 Load
BTU/Hr 187000 170000
Cu Ft/Hr 135 1281/4 Load
BTU/Hr 135000 128000
Cu Ft/Hr 99 99Exercise
BTU/Hr 99000 99000
Recommended
Energy Content of
FuelHeating Value:
LP Vapor Natural Gas
Heating Value:
BTU per gallon (gross**)
Cubic feet (gas)
91,547
2,500
1,000
Fuel Type
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using natural gas, but can be
converted to use LP vapor. For correct engine function,
factors that are inherent to each of these fuels, like your
location and the duration of possible utility interruptions, are
important considerations in the following fuel guidelines:
Use clean, dry fuel that is free of moisture or
any particulate material. Using fuels outside the
recommendation values that follow can cause
performance problems.
In engines set up to run on propane (LP), commercial
grade HD5 propane with a minimum fuel energy of 2500
BTUs/ft3 with maximum propylene content of 5% and
butane and heavier gas content of 2.5% and minimum
propane content of 90% is required.
Natural gas rating will depend on specific fuel, but typical
derates are between 10 and20% of the LP gas rating.
Natural gas or LP engines are certified to operate on natural
or liquid propane gas. The emissions control system for this
engine is EM (Engine Modifications).
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure at the
generator’s fuel inlet port and must be between the following
levels at full load with all gas appliances turned on and in
operation.
NG is 3.5-7” W.C.
LP is 11-14” W.C.
Make sure that all gas line shutoff valves are OPEN and
that adequate fuel pressure is available whenever automatic
operation is desired.
For Natural Gas fuel pressure levels of 3.5 - 5" W.C., replace
the regulator assembly with service kit 6331-00 (available at
your local service dealer).
Power Loss
Air density is less at high altitudes, resulting in less available
engine power. Engine power will decrease by 3.5% for each
1,000 feet (300 m) above sea level and by 1% for each
10° F (5.6°C) above 77°F (25°C). Generators located in
these conditions must have their transfer switch adjusted
appropriately for this power decrease. See your Automatic
Transfer Switch manual on how to adjust for the power
decrease.
The Gaseous Fuel System
Fuel Pipe Sizing
NFPA 54 and 58 are common resources. The installer must
consider the specific gravity of gas, compensate for a nominal
amount of restriction from bends and fittings, and refer to
federal and local codes for guidance.
Fuel Conversion
The engine of your home generator system is factory
Calibrated and set to operate on natural gas (NG). It may also
be operated on liquefied petroleum (LP) vapor.
NOTICE Units are set to NG at the factory.
To convert to either fuel, follow these steps:
1. Put the key into the lock of the front panel. Lightly push
down on the roof above the lock, and then turn the key
one quarter turn clockwise.
2. Lift the roof to the open position.
3. Push the control panel OFF button.
4. Remove the battery panel.
5. Remove the 15 Amp fuse.
6. Remove utility power to generator to de-energize the
battery charger.
7. Disconnect the negative (-) cable at the battery.
8. Remove the rear panel.
9. Find the fuel selector switch (A) on top of the fuel
regulator (B).
Not for
Reproduction
19
10. Set Fuel Selector:
A. Remove cap (C) from the Fuel Select Valve by sliding
it upward.
Note:If this is the first installation of this generator,
thecapwill be found in the parts bag.
B. LP or NG is selected by using the cap (C) as a tool to
rotate the indicator to the LP or NG mark (the image
below shows the FSV set to LP fuel).
C. Install the cap (C) after fuel selection is complete.
11. Once the fuel selection is complete, apply a drop of
cyanoacrylate (super) glue on the Fuel Select Cap.
12. Connect the negative (-) cable at the battery.
13. Install the rear panel.
14. Install 15-amp fuse.
15. Install the battery panel.
16. Push and hold the CONFIG button to access the
configuration menu.
17. Push SELECT to edit the items in the configuration menu.
18. To setup the generators control board for LP fuel you will
need to enter the Configuration Menu by using the Dealer
Password, which is available on the Power Portal.
19. Navigate to “SELECT PROFILE” and press select on the
correct profile for the generator. For example “20KW_LP”
for operating a 20kW unit running on LPfuel.
Note:Selecting a profile that is not intended for the generator
can cause the generator to run erratically and could result in
damage.
20. To Save the new fuel setting, press and hold the STOP/
CONFIG button until “Saving Settings…” is displayed.
21. For Additional information on the operation of the
generator controller please refer to the "Operation
Instructions GC1031 GENSET Controller Manual,"
PN:80086364.
22. Close the roof.
23. Restore utility power to generator.
24. Push the control board AUTO button.
Fuel Consumption
LP Vapor (Propane)
20kW 17kW
Full Load Cu Ft/Hr 135 118
Gal/Hr (liquid) 3.75 3.28
BTU/Hr 337,500 295,000
3/4 Load Cu Ft/Hr 109 99
Gal/Hr (liquid) 3.03 2.75
BTU/Hr 272,500 247,500
1/2 Load Cu Ft/Hr 83 74
Gal/Hr (liquid) 2.31 2.06
BTU/Hr 207,500 185,000
1/4 Load Cu Ft/Hr 56 54
Gal/Hr (liquid) 1.56 1.5
BTU/Hr 140,000 135,000
No Load Cu Ft/Hr 40 40
Gal/Hr (liquid) 1.11 1.11
BTU/Hr 100,000 100,000
Natural Gas
20kW 17kW
Full Load Cu Ft/Hr 260 248
BTU/Hr 260,000 248,000
3/4 Load Cu Ft/Hr 240 218
BTU/Hr 240,000 218,000
1/2 Load Cu Ft/Hr 187 170
BTU/Hr 187,000 170,000
1/4 Load Cu Ft/Hr 135 128
BTU/Hr 135,000 128,000
No Load Cu Ft/Hr 99 99
BTU/Hr 99,000 99,000
Recommended Energy
Content of Fuel:
Natural Gas Propane (LP Vapor)
Heating Value:
BTU per gallon liquid
(gross*)
N/A 91,547
Heating Value:
BTU per Cubic feet
(vapor)
1,000 2,500
Not for
Reproduction
20
Electrical Field Connections
WARNING
Generator and utility voltage could cause electrical shock or burn resulting in death or serious injury.
Installation must be performed by a licensed professional.
Disconnect all sources of electricity before installing or servicing equipment.
Ground system before applying power.
WARNING
Hazardous Voltage -Installing low and high voltage wire in same conduit could cause electric shock or burns,
resulting in death or serious injury.
Do not run low and high voltage wire in the same conduit unless the insulation rating on ALL wiring is rated for 600V.
See NFPA 70 for more information.
Low Voltage connections are made via a field connections terminal block (E) in main electrical area. Compare this illustration
with your generator to familiarize yourself with the location of these connections.
Legend for System Connector Location
(A)Two Pin Terminal Block — Used to connect utility 240 VAC from fuse block in ATS to the control board. Connect only one
wire per terminal. Use #14 [2.5mm2] AWG minimum 300 volt wire.
(B) Transfer Switch Connection — Controls Briggs & Stratton
®
transfer switch.
(C) 2-wire start—Used for optional remote start contact.
(D) E-Stop—For use with with optional external E-stop.
(E) Field Connections Terminal Block—Reference the table that follows.
(F)Power Connection (L1 and L2) — Power connection to transfer switch.
(G)Ground Connection — Connect to transfer switch ground wire.
Not for
Reproduction
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132

Simplicity 040589-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à