Venmar K10 HRV Manuel utilisateur

Taper
Manuel utilisateur
21777J
USER AND INSTALLER MANUAL
INSTALLER: READ THESE INSTRUCTIONS
SAVE THEM FOR USER
RESIDENTIAL USE ONLY
VB0200
VB0201
SIDE PORTS TOP PORTS
K7 ERV (44162)
K8 HRV (44152)
K10 HRV (44502) K10 HRV (44500)
40E (44262)
40H+ (44252)
50H (44602) 50H (44600)
Venmar Ventilation ULC, 550 Lemire Blvd., Drummondville, Québec, Canada J2C 7W9 venmar.ca 800-567-3855
2
Please take note that this manual uses the following symbols to emphasize particular information:
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
LIMITATION
For residential (domestic) installation only. Installation work and electrical wiring must be done by a qualified person in accordance with all
applicable codes and standards, including fire-rated construction codes and standards.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
2. Before servicing or cleaning this unit, disconnect power cord from electrical outlet.
3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
4. When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
5. Do not use this unit with any solid-state speed control device other than those specified in section 7.1.
6. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into a
mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances. Do
not remove the ground prong. Do not use an extension cord.
7. Do not install in a cooking area or connect directly to any appliances.
8. Do not use to exhaust hazardous or explosive materials and vapors.
9. When performing installation, servicing or cleaning this unit, it is recommended to wear safety glasses and gloves.
10. When applicable local regulation comprises more restrictive installation and/or certification requirements, the aforementioned
requirements prevail on those of this document and the installer agrees to conform to these at his own expense.
11. Due to the weight of the unit, two installers are recommended to perform installation.
CAUTION
1. To avoid prematurely clogged filters, turn the unit OFF during construction or renovation.
2. Please read specification label on product for further information and requirements.
3. Be sure to duct air outside – Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
Do not attempt to recover the exhaust air from a dryer or a range hood.
4. Intended for residential installation only in accordance with the requirements of NFPA 90B (for a unit installed in U.S.A.) or Part 9 of
the National Building Code of Canada (for a unit installed in Canada).
5. Do not run any air ducts directly above or within 2 ft (0.61 m) of a furnace or its supply plenum, boiler, or other heat producing
appliance. If a duct has to be connected to the furnace return plenum, it must be connected 10’ (3.1 m) away from plenum’s
connection to the furnace.
6. The ductwork is intended to be installed in compliance with all applicable local and national codes.
7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit
operates adequately.
8. If the ductwork passes through an unconditioned space (e.g.: attic), the unit must operate continuously except when performing
maintenance and/or repair. Also, the ambient temperature of the house should never drop below 18°C (65°F).
9. At least once a year, the unit mechanical and electronic parts should be inspected by qualified service personnel.
10. Do not use your unit during construction or renovation of your house or when sanding drywall. Certain types of dust and vapors may
damage your system.
11. During the winter season, make sure that the outside intake and exhaust hoods are free from any snow. It is important to check your
unit during a big snow storm, so it doesn’t draw in any snow. If this is the case, please turn the unit OFF for a few hours.
12. Since the electronic control system of the unit uses a microprocessor, it may not operate correctly because of external noise or very
short power failure. If this happens, unplug the unit and wait approximately 10 seconds. Then, plug the unit in again.
13. Do not make excessive use of fragrance appliances or chemicals since some may damage the unit components material.
WARNING
3
PRODUCT REGISTRATION CARD - FICHE D’ENREGISTREMENT DU PRODUIT
Country – Pays E-mail address – Courriel Language preferred – Langue de correspondance
Address – Adresse Apt. no. – App. City – Ville Province Postal code – Code postal
First name - Prénom Last name – Nom de famille
Model no.N
o
de modèle Serial N
o
de série
BACK / VERSO
Centre d’enregistrement de produit - Product registration center, 550 boulevard Lemire, Drummondville, Québec Canada J2C 7W9
IMPORTANT: Please complete and return this questionnaire within 10 days of your purchase to the address below. Note that only the questions on this side of the page are
mandatory. Your answers will be used for market research studies and reports, and will help us to better serve you in the future. IMPORTANT: Veuillez remplir ce questionnaire
et nous le retourner dans les 10 jours suivant votre achat à l’adresse inscrite en bas de la page. Veuillez noter que seules les questions de ce côté-ci de la page sont obligatoires.
Vos réponses serviront à des études de marché et nous aideront à mieux vous servir dans l’avenir.
Date of purchase – Date d’achat
//
Telephone (day) – N
o
de téléphone (jour)
--
Telephone (evening) – N
o
de téléphone (soir)
--
no.
no.
no.
FOR THE USER ......................................4
1. USING THIS UNIT ..................................... 4
1.1 Your ventilation system .......................................... 4
1.2 Integrated Control.................................................. 4
2. MAINTENANCE ......................................... 5
2.1 Quarterly Maintenance ......................................... 5
2.2 Annual Maintenance ............................................. 5
3. USER’S TROUBLESHOOTING ................. 5
4. WARRANTY ............................................... 6
FOR THE INSTALLER ............................. 7
5. AIR DISTRIBUTION ................................... 7
6. INSTALLATION .......................................... 7
6.1 Locating the Unit .................................................. 7
6.2 Installing the ductwork and registers .................... 8
6.2.1 Fully ducted system ................................................. 8
6.2.2 Central draw point system - Supply Side ................. 8
6.2.3 Central draw point system - Return Side ................. 9
6.2.4 Simplified Installation - Supply/Return .................... 9
6.2.5 Simplified Installation - Return/Return..................... 9
6.3 Installing the Exterior Hoods .............................. 10
6.4 Installing Dual Exterior Hood Using Tandem®*
Transition Kit (optional) ............................................. 10
6.5 Connecting the Ducts to the Unit ........................ 11
6.6 Connecting the Drain .......................................... 11
7. CONTROLS ...............................................12
7.1 Electrical connection to optional controls ............ 12
7.1.1 Altitude or Platinum .................................................12
7.1.2 Deco-Touch .............................................................12
7.1.3 Lite-Touch Constructo, Simple-Touch Constructo,
Lite-Touch Bronze or Simple-Touch Bronze ............13
7.1.4 Constructo or Bronze ..............................................13
7.1.5 Optional Auxiliary Controls ......................................13
7.2 Setting Extended Defrost .................................... 13
7.3 Electrical Connection to the Furnace .................. 14
8. BALANCING THE UNIT ............................14
9. WIRING DIAGRAMS .................................15
9.1 K7 ERV and 40E Units ....................................... 15
9.2 K8 HRV and 40H+ Units ..................................... 16
9.3 K10 HRV and 50H Units ..................................... 17
10. SERVICE PARTS ....................................18
11. TROUBLESHOOTING .............................19
TABLE OF CONTENTS
4
For the User
1. USING THIS UNIT
1.1 YOUR VENTILATION SYSTEM
This unit is designed to provide fresh air to your home while exhausting stale, humid air. By eliminating accumulated pollutants and
humidity, it maintains an optimum air quality and an ideal relative humidity. It is equipped with a recovery core that is designed specifically
to control excess humidity and reduce ventilation costs by recovering the heat or energy from the exhausted air, and using that same heat
or energy to warm the fresh air being supplied. This recovery process is accomplished in such a way that the stale air is never mixed with
the fresh air.
When the outdoor temperature is below -5°C (23°F), recovery creates frost in the module. To maintain proper operation, the unit is
programmed to defrost the recovery module. The defrost duration and frequency vary according to the outdoor temperature. After defrosting,
the unit returns to the operating mode selected by the user.
Before using this unit for the first time, please take the time to carefully read page 2 of this guide to ensure it is
used safely and and properly.
CAUTION
What problem were you trying to solve with
your purchase? (Check each one that applies
to you.)
Bad odors
Respiratory
problems
Excess of humidity
Temperature
standardization
Lack of fresh air
Dust
Mildew
Allergies
No specifi c
problems
Others
Who installed your unit?
Home builder
Recommended
installer
Friend / family
Contractor
Yourself
Please read the following list of criteria
carefully. Indicate the importance of your
purchase decision on a scale of 1 (less
important) to 5 (most important).
Price
Warranty
Product design
Ventilation
capacity
Filter maintenance
indicator
Filtration quality
Recirculation
Heat recovery
Controls
Ease of cleaning
Manufacturer’s
reputation
Ease of use
Noise level
Other
Quels problèmes essayez-vous de résoudre
par cet achat? (Cochez toutes les cases
pertinentes)
Mauvaises odeurs
Problèmes
respiratoires
Excès d’humidité
Uniformisation
de la température
Manque d’air frais
Poussières
Moisissures
Allergies
Pas de problèmes
spécifi ques
Autres (Précisez SVP)
Qui a installé l’appareil?
Constructeur
de la maison
Installateur
recommandé
Ami/membre
de la famille
Entrepreneur
Vous-même
Veuillez lire la liste des critères de sélection
ci-dessous. Sur une échelle de 1 (étant le moins
important) à 5 (étant le plus important), veuil-
lez indiquer l’importance de chacun d’entre
eux dans votre décision d’achat.
Prix
Garantie
Design du produit
Débit de
ventilation
Indicateur
d’entretien du fi ltre
Qualité de fi ltration
Recirculation
Récupération
de chaleur
Récupération
d’énergie
Fonctions
Facilité de
nettoyage
Réputation
du fabricant
Simplicité
d’utilisation
Niveau de bruit
Autres
(Précisez SVP)
Would you like to receive occasional informational e-mail off ers including
product updates and special promotions from us?
Yes/No
Aimeriez-vous recevoir plus de détails sur nos promotions, off res de rabais et mises à jour
de nos produits?
Oui/Non
Are you connected? Please do not hesitate to complete the product registration
card via our Web site at www.bnv.ca
Enregistrez-vous en ligne! N’hésitez pas à remplir la fi che d’enregistrement
du produit sur notre site Internet au www.bnv.ca
1.2 INTEGRATED CONTROL
Unit Booting Sequence
The unit’s booting sequence is similar to a personnal computer’s booting sequence. Each time the unit is plugged in after being unplugged,
or after a power failure, it will perform a 30-second booting sequence before starting to operate. No command will be taken until the
unit is fully booted.
This unit is equipped with an integrated control, located on its upper left side.
Use the integrated push-button (1) to go from OFF to Low Speed, to High Speed, and back to OFF.
The color of the LED indicator shows what speed the unit is running in:
If a problem occurs while the unit is running, the LED indicator (2) will blink. The color of the blinking
light indicates the type of error detected. Refer to Troubleshooting section.
For more convenience, these units can also be controlled using an optional wall control. When using an
optional control, unit must be set to OFF using the integrated push-button.
For more information about their operation modes, refer to the Main and auxiliary wall control User Guide,
included with the ventilation unit and also available at www.vanee.ca or www.venmar.ca.
LED COLOR RESULTS
AMBER Unit is on Low speed
GREEN Unit is on High speed
NO LIGHT Unit is OFF or controlled
by a main control
VE0220
1
2
5
For the User
2. MAINTENANCE
2.1 QUARTERLY MAINTENANCE
1. Unplug the unit.
2. Remove the unit door by following these steps:
A. Remove both door lower mechanical screws no. 8-32 x 1” (1) and set aside (as
illustrated below).
B. Open (2) and lift out the door (3) (as illustrated below).
3. Slide out both filters (4) from the unit (as illustrated below).
4. Slide out the core (5) from the unit (as illustrated below).
5. Clean the inside walls of the unit with a clean damp cloth, then wipe with a clean
dry one.
6. Wash both core filters under lukewarm water with mild soap. Rinse thoroughly and
let dry completely before reinstalling on the core.
7. Remove the dust on the core using a vacuum cleaner and a soft brush attachment.
8. Slide the cleaned core and filters into the unit.
9. Reinstall the door. Secure it with both mechanical screws no. 8-32 x 1” previously removed
and plug the unit. The unit will return to its previous setting after a 30-second boot sequence.
2.2 ANNUAL MAINTENANCE
Perform Quarterly Maintenance up to step 6, and clean the recovery core as follows:
K7 ERV K8 HRV, K10 HRV*,
40E 40H+*, 50H*
Remove the dust on the core using a vacuum cleaner and a soft
brush attachment.
CAUTION: DO NOT SOAK THE ENERGY RECOVERY CORE IN
WATER
Soak the heat recovery core in a mixture of lukewarm water and
mild soap. Rinse thoroughly. Shake the core to remove excess
water and let it dry.
VO0191
12
3
AB
VD0243
4
5
Follow the instructions on the core label to reinstall it correctly.
CAUTION
Risk of electric shock. Before performing any maintenance or servicing, always disconnect the unit from its
power source.
When cleaning the unit, it is recommended to wear safety glasses and gloves.
WARNING
3. USER’S TROUBLESHOOTING
PROBLEM TRY THIS...
1. Nothing works. See if the unit is plugged in and receiving power from the house circuit breaker or fuse.
2. Condensation on windows (air
too humid).
Operate the unit on maximum speed ventilation until the situation is corrected.
Leave curtains half-open to allow air circulation.
Store all firewood in a closed room with a dehumidifier or in a well ventilated room, or store the
wood outdoors.
Do not adjust the thermostat of your heating system below 18°C (64°F).
3. Indoor air too dry. Temporarily use a humidifier.
Operate the unit in recirculation mode (if available).
4. Air too cold at the air supply
grille.
Make sure that the exterior hood is not blocked.
Operate the unit in low speed ventilation, in intermittent or in recirculation mode (if available).
Install a duct heater.
5. The LED of the integrated
control is blinking GREEN.
There is a problem with the thermistor. The unit is still working, but will defrost frequently. Contact
your installer.
6. The LED of the integrated
control is blinking AMBER.
There is a problem with the motorized damper. The unit is OFF. For a 2½-hour period, the unit will
try to reset the damper every 30 minutes. After 2½ hours, if the problem is not solved, the unit stops
trying to reset damper. Contact your installer.
7. The integrated control push
button does not work.
The 30-second boot sequence is not completed.
See Section 1.2.
Contact customer service at 1-800-567-3855 for any unresolved issue.
6
For the User
4. WARRANTY
This ventilation unit is a high quality product, built and packaged with care. The manufacturer warrants to the original purchaser of its
product, that such products will be free from defects for the period stated below, from date of original purchase. For all units, the warranty
covers parts only against any operational defect. This 5-year warranty is subject to performance of the core maintenance according to the
recommendations in this manual. The heat recovery core (HRV) has a limited lifetime warranty. If any defect should occur, we urge you to
read the user guide carefully. If the problem persists, observe the following rules:
RULES TO FOLLOW
If the unit is defective, contact your ventilation contractor (see address on your manual’s cover page). The contractor will determine with
you the reason for the defect, and if needed, do the replacement or repair. If ever it is impossible to reach your ventilation contractor, call
1-800-567-3855 (North America); the personnel will be pleased to give you the phone number of a distributor or service center near you.
REPLACEMENT PARTS AND REPAIR
In order to ensure your ventilation unit remains in good working condition, you must use the manufacturers genuine replacement parts only.
The manufacturer’s genuine replacement parts are specially designed for each unit and are manufactured to comply with all the applicable
certification standards and maintain a high standard of safety. Any third party replacement part used may cause serious damage and
drastically reduce the performance level of your unit, which will result in premature failing. The manufacturer also recommends that you
contact a service depot certified by the manufacturer for all replacement parts and repair.
BILL OF PURCHASE
No replacement or repair covered by the warranty will be carried out unless the unit is accompanied by a copy of the original bill of
purchase. Please retain your original.
MISCELLANEOUS COSTS
In each case, the labor costs for the removal of a defective part and/or installation of a compliant part will not be covered by the manufacturer.
CONDITIONS AND LIMITATIONS
These units are created for residential use only and must be used in a building as defined below:
Building: All structures zoned and/or erected for the act, process or art of human or animal habitation and/or the storage or
warehousing of goods.
Residential use: Dwelling, lodging, suite: Building, or part of a building, intended to act as either the domicile to one or several people
which can include general sanitary, food consumption and rest facilities. Buildings of only one room or a group of
rooms including those occupied by a tenant or owner; comprise the lodgings, the individual rooms of the motels,
hotels, rooming/lodging houses, boarding/half-way/foster homes, dormitories, and suites, as well as the stores and the
business establishments constituted by only one room in a dwelling.
Commercial use: Agricultural establishment, commercial establishment for assembly, care, or detention: Building or part of a building that
does not contain a dwelling, situated on land dedicated to agriculture or farming and used primarily to shelter animals,
or for the production, the storage or the treatment of agricultural or horticultural products or animal food. Building or
part of a building, used for the display or retail of goods, professional or personal services, or commodities. Building,
or part of a building used by persons gathering for civic activities, religious or political assembly, tourism, educational/
vocational training, recreation or the consumption of food or drink. Building, or part of a building used to shelter persons
of impaired physical or psychological states, persons requiring palliative care or medical treatments, or persons for
reasons out of their control, cannot escape harm or threat of danger autonomously.
Industrial use: Building, or part of a building, used for the assembly, the manufacture, the creation, the treatment, the repair or the
storage of products and combustible materials and that contain fuels that when ignited or exploded in sufficient quantity
may constitute a risk of fire.
The above warranty applies to all cases where the damage is not a result of poor installation, improper use, mistreatment or negligence,
acts of God, or any other circumstances beyond the control of the manufacturer. Furthermore, the manufacturer will not be held responsible
for any bodily injury or damage to personal property or real estate, whether caused directly or indirectly by the unit. This warranty
supersedes all prior warranties.
7
For the Installer
5. AIR DISTRIBUTION
VF0051
TOP PORTS UNITS SIDE PORTS UNITS
FRONT FRONT
FRESH AIR
TO BUILDING
STALE AIR
FROM
BUILDING
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
FRESH AIR
TO BUILDING
STALE AIR
FROM
BUILDING
STALE AIR
TO OUTSIDE
FRESH AIR
FROM
OUTSIDE
6. INSTALLATION
Inspect the exterior of the unit for shipping damage. Make sure that there is no damage to the door, ports, power cord, etc.
6.1 LOCATING THE UNIT
Choose an appropriate location for the unit.
Within an area of the house where the ambient temperature is between 10°C (50°F)
and 50°C (122°F) (basement, furnace room, closet, etc.)
Away from living areas (dining room, living room, bedroom), if possible
So as to provide easy access to the interior of the unit, for maintenance
Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from
the unit
Away from hot chimneys and other fire hazards
Allow for a standard 3-prong grounding outlet within 3 feet of the unit
Close to a drain. If no drain is close by, use a pail to collect run-off
Slightly bend all 4 hooks located on both sides of the unit in order to hang it to ceiling joists with
the 4chains and springs provided. See illustration aside. VD0242
Make sure the unit is level.
CAUTION
Before installing this unit, please take the time to carefully read page 2 of this guide to ensure it is installed safely
and and properly.
CAUTION
8
For the Installer
6.2 INSTALLING THE DUCTWORK AND REGISTERS
Keep it simple. Plan for a minimum of bends and joints.
Keep the length of insulated ducts to a minimum.
If the house has two floors or more, be sure to plan for at least one exhaust register at the highest lived-in level.
6.2.1 FULLY DUCTED SYSTEM
Stale air exhaust ductwork
Install the stale air exhaust registers where the contaminants are produced:
kitchen, living room, etc. Position the registers as far from the stairway as
possible and in such a way that the air circulates in all the lived-in spaces in
the house.
If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m)
away from the range.
Install the registers on an interior wall, 6 to 12 inches (152 to 305 mm) away
from the ceiling OR in the ceiling.
Fresh air distribution ductwork
Install the fresh air distribution registers in bedrooms, dining rooms, living
room and basement.
Keep in mind that the fresh air registers must be located as far as possible
from the stale air registers.
Install the registers either in the ceiling or high on the walls, with the air flow
directed towards the ceiling.
If a register must be installed in the floor, direct the airflow up the wall.
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas
furnace, a gas water heater or a fireplace.
When performing duct connections, always use approved tools and materials. Respect all corresponding laws
and safety regulations. Please refer to your local building code.
WARNING
VH0081
6.2.2 CENTRAL DRAW POINT SYSTEM - SUPPLY SIDE
Stale air exhaust ductwork
Same as for fully ducted system (see section 6.2.1)
Fresh air distribution ductwork
Cut an opening into the furnace supply duct at least 18 inches (0.5 m) away
from the furnace/air handler.
Connect this opening to the Fresh air distribution port of the unit (use a
metal duct, see figure aside).
Make sure the unit duct forms an elbow inside the furnace/air handler
ductwork.
NOTE: For this type of installation, it is recommended, however not essential,
that the furnace blower be synchronized with the unit.
VH0126
18” (0.5 M)
MINIMUM
When performing duct connections to the furnace supply duct,
use metal ducts appropriately sized to support the additional
airflow produced by the unit.
CAUTION
9
For the Installer
6.2.3 CENTRAL DRAW POINT SYSTEM - RETURN SIDE
Stale air exhaust ductwork
Same as for fully ducted system (see section 6.2.1)
Fresh air distribution ductwork
Cut an opening into the furnace return duct not less than 10 feet (3.1 m) away
from the furnace/air handler (A+B)
Connect this opening to the Fresh air distribution port of the unit (see figure
beside)
NOTE: For this type of installation, it is recommended, however not essential,
that the furnace blower be synchronized with the unit.
VH0127
B
A
A + B = AT LEAST
10’ (3.1 M)
6.2.4 SIMPLIFIED INSTALLATION - SUPPLY/RETURN
Stale air intake
Cut an opening into the furnace return duct not less than 10 feet (3.1 m) away from
the furnace/air handler (A+B).
Connect this opening to the Exhaust air from building port of the unit.
Fresh air distribution ductwork
Cut an opening into the furnace supply duct at least 18 inches (0.5 m) away from
the furnace/air handler
Connect this opening to the Fresh air distribution port of the unit (use a metal
duct, see figure aside)
Make sure the unit duct forms an elbow inside the furnace/air handler ductwork.
NOTE: For this type of installation, it is recommended, however not essential, that the
furnace blower be synchronized with the unit.
When performing duct connections to the furnace supply duct, use
metal ducts appropriately sized to support the additional airflow
produced by the unit.
CAUTION
VH0129
AB
A + B = AT LEAST
10’ (3.1 M)
18” (0.5 M)
MINIMUM
6.2.5 SIMPLIFIED INSTALLATION - RETURN/RETURN
Stale air intake
Cut an opening into the furnace return duct not less than 10 feet (3.1 m) away from
the furnace/air handler (A+B).
Connect this opening to the Exhaust air from building port of the unit.
Fresh air distribution ductwork
Cut an opening into the furnace return duct at least 18 inches (0.5 m) away from
the furnace/air handler
Connect this opening to the Fresh air distribution port of the unit (use a metal
duct, see figure aside)
Make sure the unit duct forms an elbow inside the furnace/air handler ductwork.
Make sure that both connections to the furnace return duct are at least 3 feet (1 m) apart (C).
VH0128
C
A
B
A + B = AT LEAST
10’ (3.1 M)
C = AT LEAST
3’ (1 M)
For this type of installation, the furnace must always be synchronized
with the unit. See section 6.
CAUTION
10
For the Installer
6.4 INSTALLING DUAL EXTERIOR HOOD USING TANDEM®* TRANSITION KIT (OPTIONAL)
If desired, a dual exterior hood can be used instead of 2 exterior hoods to connect
inulated ducts. The joist opening needed to install the Tandem® transition is 9¾”
minimum. The maximum height of the Tandem® transition is 8¾”.
To connect 4” insulated flexible ducts to the 5” oval ends of the Tandem® transition
(Exhaust air to outside and Fresh air from outside), connect an adapter to the Tandem®
transition (not included) as follows.
For each duct connection:
1. Slightly squeeze a section of 4” round metal duct, at least 8” long, to insert it into
the oval opening of the Tandem® transition and push it all the way in.
2. Using silicon, seal the joint between the outside of the metal duct and Tandem®
transition, and allow silicon to dry completely.
3. From this point on, follow the instructions included with the Tandem® transition kit
(part no. 14690).
*Patented.
VJ0118A
VJ0119
CAUTION
When connecting insulated flexible duct to the Tandem® transition,
pull the interior flexible duct over the adapter all the way to the silicon
joint and secure using a tie wrap. Then pull the insulation over the
joint, making sure that no part is left without insulation.
6.3 INSTALLING THE EXTERIOR HOODS
Refer to the illustration aside to connect the insulated duct to the hoods.
Place a “FRESH AIR INTAKE” sticker on corresponding hood. An “Anti-
Gust Intake Hood” should be installed in regions where a lot of snow is
expected to fall.
Make sure that both hoods are at least 18 inches above the
ground and that the intake hood is at least 6 feet (1.8m)
away from any of the following:
• Exhaust hood
Dryer exhaust, high efficiency furnace vent, central
vacuum vent
Gas meter exhaust, gas barbecue-grill
Any exhaust from a combustion source
Garbage bin and any other source of contamination
WARNING
VD0028
EXHAUST
HOOD
INTAKE
HOOD
18
(457 MM)
18
(457 MM)
6” ø
(152 MM)
6’
(1.8 M)6’
(1.8 M)
18
(457 MM)
OPTIONAL
DUCT LOCATION
TAPE AND DUCT TIE
CAULKING
11
For the Installer
6.5 CONNECTING THE DUCTS TO THE UNIT
NOTE: This unit was designed to be connected to ducts of at least 4” in diameter, but can be connected to bigger sized ducts by using an
appropriate transition (e.g.: 4” diameter to 5” diameter transition).
1. Pull back the insulation to expose the flexible duct.
2. Attach the flexible duct to the port using a tie wrap.
3. Pull the insulation over the joint and tuck it in between the inner and outer rings of the double collar.
4. Pull down the vapor barrier (shaded part in illustrations below) over the outer ring to cover it completely. Apply duct tape to the joint to
make an airtight seal. Avoid compressing the insulation when pulling the tape tightly around the joint.
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within
the ducts. If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts.
CAUTION
VJ0127
1234
Non-insulated rigid ducts
Use metal screws and duct
tape to connect the rigid
ducts to the unit ports.
Non-insulated flexible
ducts
Use tie wraps to connect
the flexible ducts to the
unit ports.
VJ0073
6.6 CONNECTING THE DRAIN
1. Connect the plastic tube to the drain fitting located under the unit.
2. Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the
drain source. Run the tube to the floor drain or to an alternative drain pipe or pail.
VO0190
VD0240A
± 1”
TIE-WRAP
CAUTION
If using a pail to collect water, locate the tube end approximately 1” into the pail
in order to prevent water from being drawn back up into the unit.
A drain tubing (included) must be installed for all HRV units. For ERV units, it is not required, however, it is
recommended for climates where the outside temperature typically remains below -25°C (-13°F), (over a 24-hour
period) for several days in a row, combined with an indoor humidity of 40% or higher.
CAUTION
12
For the Installer
7. CONTROLS
7.1 ELECTRICAL CONNECTION TO OPTIONAL CONTROLS
Use the terminal connector included in the installation kit to perform the electrical
connection for main and optional wall controls.
Make sure all wires are correctly inserted in their corresponding holes in the terminal
block. A wire is correctly inserted when its orange receptacle is lower than another one
without wire. On picture beside, wire A is correctly inserted, but wire B is not.
WARNING
Always disconnect the unit before making any connections. Failure in disconnecting power could result in
electrical shock or damage of the wall control or electronic module inside the unit.
CAUTION
Never install more than one optional main wall control per unit. Make sure that there are no short-circuit between
the wires or with any other components on the wall control. Avoid poor wiring connections. To reduce electrical
interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming
circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.
VE0272
A
B
Use the chart below to verify compatibility with optional controls before making any connection.
Main Controls Auxiliary Controls
K7 ERV, K8 HRV, K10 HRV
• Altitude
• Deco-Touch
• Lite-Touch Constructo
• Simple Touch Constructo
• Constructo 20/40/60-minute push-button timer
20-minute lighted push button
60-minute crank timer
• Dehumidistat
40E, 40H+, 50H
• Platinum
• Deco-Touch
• Lite-Touch Bronze
• Simple Touch Bronze
• Bronze
NO C NC I OC OL Y R G B
VE0181
SMART
SET
MODE
PREF
NO C NC I OC OL Y R G B
VE0250
7.1.1 ALTITUDE OR PLATINUM 7.1.2 DECO-TOUCH
13
For the Installer
7.1.3 LITE-TOUCH CONSTRUCTO, SIMPLE-TOUCH CONSTRUCTO,
LITE-TOUCH BRONZE OR SIMPLE-TOUCH BRONZE
7.1.4 CONSTRUCTO OR BRONZE
NO C NC I OC OL Y R G B
BG
GB
Y
VE0328A
YNO C NC I OC OL Y R G B
VE0323
--5°C
23°F
5°C
41°F
C
O
M
F
O
R
T
Z
O
N
E
-20°C
-4°F
OFF
MIN MAX
#
X
X
X
X
X
0
1
/
9
8
7.1.5 OPTIONAL AUXILIARY CONTROLS
Once the control(s) connections have been made, insert the terminal connector in the electrical
compartment interface.
NO C NC I OC OL Y R G B
20/40/60-MINUTE or 20-MINUTE
PUSH-BUTTON SWITCHES
(5 MAXIMUM)
60-MINUTE
CRANK TIMER
VE0089A
DEHUMIDISTAT
VE0221
TERMINAL
CONNECTOR
7.2 SETTING EXTENDED DEFROST
These units are factory set to normal defrost. In cold region (outside temperature -27°C [-17°F] and lower), it may be necessary to setup
extended defrost. During the first 2 seconds of the booting sequence, while the integrated control LED is GREEN, press on push button for
3 seconds to set the unit in extended defrost; the LED will blink AMBER to show the unit is in extended defrost mode. After that, the LED
will shut off, and turn RED (the unit resumes its booting sequence).
14
For the Installer
For a furnace connected to a cooling system:
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing “Y” at the thermostat and
thereby turning on the cooling system. If you identify this type of thermostat, you must use the ALTERNATE FURNACE INTERLOCK WIRING.
STANDARD FURNACE INTERLOCK WIRING ALTERNATE FURNACE INTERLOCK WIRING
W R G Y
W
R
G
C
Y
UNIT TERMINAL CONNECTOR
THERMOSTAT
TERMINALS
FOUR
WIRES
TWO WIRES
heating only
FURNACE
24-VOLT
TERMINAL BLOCK TWO WIRES COOLING SYSTEM
NO C NC I OC OL Y R G B
W R G Y
W
R
Y
R
G
Y
C
THERMOSTAT
TERMINAL
4 WIRES
2 WIRES
heating only wiring
nuts
FURNACE
24-VOLT
TERMINAL BLOCK 2 WIRES COOLING SYSTEM
NO
NC
C
UNIT TERMINAL CONNECTOR
NO C NC I OC OL Y R G B
VE0108A
7.3 ELECTRICAL CONNECTION TO THE FURNACE
WARNING
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low
voltage class 2 circuit of the furnace blower control.
8. BALANCING THE UNIT
PREPARATION
Follow these steps to ensure accurate measurements:
Seal all the ductwork with tape. Close all windows and doors.
Turn off all exhaust devices such as range hood, dryer and bathroom fans.
Make sure the balancing dampers are fully open (their adjusment pin (A) must be vertical,
see illustration aside).
Make sure all filters are clean (if it is not the first time the unit is balanced).
If the installation is in any way connected to the ductwork of the cold air return of a furnace/air
handler, make sure that the furnace/air handler blower is ON. If not, leave furnace/air handler
blower OFF.
If the outside temperature is below 0°C/32°F, make sure the unit is not running in defrost while
balancing by waiting 10 minutes after plugging the unit in.
Set the unit to high speed.
BALANCING PROCEDURE
1. Place the magnehelic gauge on a level surface and adjust it to zero.
2. Connect tubing from gauge to EXHAUST air flow pressure taps (refer to label on unit for
gauge connection).
3. Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops below
zero, reverse the tubing connections.
4. Note the CFM value from balancing chart on unit.
5. Repeat steps 3 and 4, but to FRESH air flow pressure taps.
6. Using the appropriate adjustable balancing damper, lower the highest value so it matches
the lowest value. A difference up to ±10cfm is acceptable.
7. Secure both dampers in place with a fastening screw (included in the hardware kit).
8. Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your
name, phone number and business address).
VJ0033
A
SCREW
VJ0031
15
For the Installer
9. WIRING DIAGRAMS
Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its
power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit
situation. If the fuse blows, unplug the product from the outlet. Discontinue using the unit and contact technical
support.
WARNING
!
BK
W
G
A1
J6
1
2
J10
1
2
J14
10
9
8
7
6
5
4
3
2
1
12345
J12
J13
ICP
21345
J8
4321
J9
24 V Class 2
9.5 V
Class 2
C1
5 µF
2154321
12
J3
J2 J1
M2
A2
C2
F1
T1
120 VAC
60 Hz
S1
OVERRIDE SWITCH
(OPTIONAL)
FIELD WIRING
REMOTE CONTROL
FURNACE BLOWER
INTERLOCK (OPTIONAL)
THERMISTOR
DAMPER ELECTRONIC
ASSEMBLY
ELECTRONIC ASSEMBLY
DAMPER MOTOR
3A
3AG TYPE
COLOR CODE
VE0335A
M
J4-1
J9-3 J6-1 J6-2
J4-2
M
J2-1 J3-1
J3-2J2-2
J12-2
K4
K3
K2
T1
+-
~
~
L
INE
N
EUTRAL
120 VAC
A2
DAMPER MOTOR
BLOWER MOTOR
C1
M
OTOR
C
APACITOR
CPU
K2 K3 K4
3A
J12-1
J10-2 J10-1
J4-3
J9-1
24 VAC
9.5 VAC
C2
M
OTOR
S
PEED
J8-4
J8-5 J8-2
J8-1
LOGIC DIAGRAM WIRING DIAGRAM
M1 BL
BR
J4
1
2
3
BK
B
G
R
RGBK
Y
Y
OL
OC
I
LINE VOLTAGE
CLASS 2 LOW VOLTAGE FACTORY WIRING
CLASS 2 LOW VOLTAGE FIELD WIRING
13 µF
BLACK
BLUE
BROWN
GREEN
BK
BL
BR
G
ORANGE
RED
WHITE
YELLOW
O
R
W
Y
O
O
Y
Y
R1
BLOWER
MOTOR
MOTOR
CAPACITOR
K1 K5
S1
J11-2 J11-1
BK
R
W
9.1 K7 ERV AND 40E UNITS
16
For the Installer
Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its
power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit
situation. If the fuse blows, unplug the product from the outlet. Discontinue using the unit and contact technical
support.
WARNING
!
BK
W
G
A1
J6
1
2
J10
1
2
J14
10
9
8
7
6
5
4
3
2
1
12345
J12 J13
ICP
21345
J8
4321
J9
24 V Class 2
9.5 V
Class 2
C1 5 µF
2154321
12
J3
J2 J1
M2
A2
F1
T1
120 VAC
60 Hz
S1
OVERRIDE SWITCH
(OPTIONAL)
FIELD WIRING
REMOTE CONTROL
FURNACE BLOWER
INTERLOCK (OPTIONAL)
DAMPER ELECTRONIC
ASSEMBLY
ELECTRONIC ASSEMBLY
DAMPER MOTOR
3A
3AG TYPE
COLOR CODE
VE0316A
M
J4-1
J9-3
J6-1 J6-2
J4-2
M
J2-1 J3-1
J3-2J2-2
J12-2
K4
K3
K2
T1
+-
~
~
LINE NEUTRAL
120 VAC
A2
DAMPER MOTOR
M2
BLOWER MOTOR
M1
C1
M
OTOR
C
APACITOR
F1
J12-1
J10-2 J10-1
J4-3
J9-1
24 VAC
9.5 VAC
J8-4
J8-5 J8-2
J8-1
LOGIC DIAGRAM WIRING DIAGRAM
M1
BL
BR
J4
1
2
3
BK
B
G
R
RGBK
Y
Y
OL
OC
I
LINE VOLTAGE
CLASS 2 LOW VOLTAGE FACTORY WIRING
CLASS 2 LOW VOLTAGE FIELD WIRING
BLACK
BLUE
BROWN
GREEN
NO CONNECTION
BK
BL
BR
G
NC
ORANGE
PURPLE
RED
WHITE
YELLOW
O
P
R
W
Y
O
O
Y
Y
THERMISTOR
R1
BLOWER
MOTOR
MOTOR
CAPACITOR
nc
nc
BK
120 V
94 V
83 V
78 V
69 V
neutral
BL
P
BR
R
W
R
BR
P
R
BL BL
321
JU1
M H
123
JU1
H M
J9-2
94 VAC
83 VAC
78 VAC
69 VAC
nc nc
Damper system
CPU
K2 K3 K4K1 K5
S1
J11-2 J11-1
9.2 K8 HRV AND 40H+ UNITS
17
For the Installer
Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its
power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit
situation. If the fuse blows, unplug the product from the outlet. Discontinue using the unit and contact technical
support.
WARNING
!
Lin e vo l tag e f acto ry wiring
Class 2 low vo lt ag e facto ry w i r ing
Class 2 low vo lt ag e fie ld wiri n g
BK
BL
BN
BK
W
G
A1
J4
J6
ELECTRONIC ASSEMBL Y
1
2
3
1
2
J10
J14
10
9
8
7
6
5
4
3
2
1
1 2 3 4 5
J12
12
3
4
5
J8
24V
class 2
9.5V
class 2
BL
W
O
O
Y
Y
12345 12
1 2
J3
J2 J1
M2
Damper motor
A2
DAMPER E LE CTRONIC
AS SEM BLY
Fur na ce blower i n ter l ock
(op ti on al )
Thermistor
F1
3A
3AG Type
T1
12 0 Vo lt AC
60 Hz
Fi el d wir i ng
remote control
Override switch
(op ti on al )
BK
G
R
Y
B
G
R
Y
OL
OC
I
JU1
123
H
M
R1
J9-3
M
J2-1 J3-1
J3-2J2-2
J12-2
K4
K2
T1
+
-
~
~
Line
Neutral
120 Volt AC
A2 Damper Motor
M2
CPU
K2 K3 K4
F1
J12-1
J10-2
J10-1
J9-1
24 VA C
9.5VAC
J8-4
J8-5 J8-2
J8-1
J9-4
BN
GY
R
nc
BN
GY
RR
76V
10 3V
64V
55V
ne ut ra l
nc
nc
76 VA C
64 VA C
55 VA C
J9-2
JU1
3
21
MH
12 0V
BK
BL
10 3VA C
nc
K1
M
J4-1
J6-1 J6-2
J4-2
K3 Blower M otor
M1
C1 Motor Capacitor
J4-3
Dampe r sy st em
J13
ICP
12
K5
J11-2 S1 J11-1
1234
J9
C1
Motor capacitor
M1
Fan motor
S1
BL
Color Code
BK BLACK OORANGE
BL BLUE PPU RPL E
BN BROW N RRED
GGREE N WWHITE
GY GREY YYE LL OW
NC No Connection
64CFM optional low
speed selection can be
achieved by connecting
GREY to RED tap.
9.3 K10 HRV AND 50H UNITS
18
For the Installer
VL0043
1
2
3
4
5
6
7
8
9
10 11
12
13
REPLACEMENT PARTS AND REPAIR:
In order to ensure your ventilation unit remains in good working condition,
you must use the manufacturer genuine replacement parts only. The
manufacturer replacement parts are specially designed for each unit and
are manufactured to comply with all the applicable certification standards
and maintain a high standard of safety. Any third party replacement part
used may cause serious damage and drastically reduce the performance
level of your unit, which will result in premature failing. The manufacturer
recommends to contact a certified service depot for all replacement parts
and repair.
10. SERVICE PARTS
ITEM PART
NO.DESCRIPTION
K8 HRV
(44152)
K7 ERV
(44162)
40H+
(44252)
40E
(44262)
K10 HRV
(44500)
K10 HRV
(44502)
50H
(44600)
50H
(44602)
1 18854 4” ROUND METAL PORT 22222222
219206 ELECTRONIC BOARD (HRV) 1 1 1111
19207 ELECTRONIC BOARD (ERV) 1 1
3 16042 CAPACITOR 5 μF 11111111
4
17244
TRANSFORMER
11
62480 1 1
61232 1111
5 19211 CAPACITOR 13 μF 11111111
6 19208 FILTER RETAINING WIRES (PAIR) 11111111
7 18883 CORE FILTERS (PAIR) 11111111
819201 DOOR ASSEMBLY 11 11
19203 DOOR ASSEMBLY 11 11
919199 HEAT RECOVERY CORE 1 1 1111
19200 ENERGY RECOVERY CORE 11
10 18867 BLOWER ASSEMBLY 1111
62176 BLOWER ASSEMBLY 1111
11 18868 VERTICAL PORTS DAMPER SYSTEM 11111 1
18881 HORIZ. PORTS DAMPER SYSTEM*11
12 19212 4” PORTS STRAPS 22222222
13 18855 4” DOUBLE COLLAR PORT WITH DAMPER 22222222
14 19213 HARDWARE KIT* 11111111
15 16416 PCB CONNECTOR* 11111111
* PART NOT SHOWN.
19
For the Installer
11. TROUBLESHOOTING
Please start any troubleshooting by resetting the unit. To do so, unplug the unit, wait one minute, and plug it back. If the issue
persists, refer to the table below.
If the integrated LED of the unit is flashing, the unit sensors detected a problem. See the table below to know more about the nature of
the problem.
LED Signal Error Type Action Unit Status
LED flashes GREEN Thermistor error Replace damper system. Unit works but will defrost frequently
LED flashes AMBER Damper error Go to page 20 Unit does not work
Altude or
Planum wall
control does not
display the outdoor
temperature
Is the unit’s
integrated push-
buon set to off?
No
Push on the
integrated push-
buon unl the LE D
indicator of the
integrated control
turns OFF
Yes
Reset control:
simultaneously
press and hold
both arrow keys
for 8 seconds
Unplug unit
Wait 1 minute
Plug unit back
Using the wall
control, put unit in
VENT mode at
MIN or MAX
seng
Wait 5 minutes
Is temperature now
displaying?
Are both ends of
the controls RED
wire properly
connected?
Yes
No
Restore proper
connecon
Yes
No
Change the wall
control
Problem solved
Wall control does
not work
Is the power outlet
energized? No Refer to an
electrician
Yes
Unplug auxiliary controls
Uplug unit
Wait 1 minute
Plug unit back
Wait 30 seconds – Unit performs boong sequence: LED lights up, you
hear the relays, you see the dampers move
Once boong sequence is over (aer 30 sec.), try operang the unit
using the integrated push-buon.
When hing the integrate d push -buon mul ple mes , does the LE D go
from OFF to AMBER to GREEN and back to OFF?
Yes
Are the wall control
wires properly
connected? Pay
special aenon to
the BLACK and
YELLOW wires.
No
The problem is not
the wall control.
Proceed to
appropriate
troubleshoong.
No
Restore conneconsYes
Use a voltmeter. Is
there 8-12 VDC
between BLACK and
YELLOW at the unit?
Yes, but
problem not
solved.
Change the wall
control.
No
Test the wall control
using a new wire.
Does the wall
control now work?
No Change the wall
control.
Yes Change the wire.
Push-buon mer
does not work
(no light)
At unit, jump
OL and OC on the
green connector.
Does unit now work?
Wire or control is
defecve.
Yes
VM0006A
No
Change the
electronic board
Risk of electric shocks. Electronic board connections must be checked by qualified personnel only.
WARNING
!
20
For the Installer
Unplug auxiliary controls
Uplug unit
Wait 1 minute
Plug unit back
Wa it 30 seconds Uni t performs boong se quence : LE D li ght s up, you
heartherelays,youseethedampersmove
Once boong sequence is over (aer 30 sec.), try operang the unit using
the integrated push-buon.
When hing the int egrated push -buon mul ple mes , does the LE D go
from OFF to AMBER to GREEN and back to OFF?
Is the power outlet
energiz ed? No Havean electrician
fix it.
Unit does not work
Yes
Yes
Replacethe
oponalwall
control.
No
Is the fuse on the
electronic board
blown?
Yes
No
Use a voltmeter.
Is there 120 V
at J10?
No
Power cord is
defecve. Call
technical support.
Yes
Use a voltmeter.
Is there 120 V
between J9-4 and
J9-1?
NoYes Replacethe
electronic board.
Use a voltmeter.
Is there 9.5 V
between J8-4 and
J8-5?
No Replacethe
transformer.
Yes
Integrated control
LED is OFF.
Integrated control
LED is AMBER and
flashing.
Unplug auxiliary controls
Uplug unit
Wait 1 minute
Plug unit back
Wait 30 seconds Unit performs boong sequence: LED lights up, you hear
the relays, you s ee the dampers move
Oncetheboongsequenceisover(30sec),doestheintegratedcontrolLED
stay RED, and turn AMBER aer 7-8 minutes?
Yes
Change the damper
system. No
Use a voltmeter.
Is there 24 VAC
between J8-1 and
J8-2 on the
transformer (orange
wires on the
transformer)?
No
Yes
Change the damper.
Change the
transformer.
Blower does not
work
Is the jumper
present on J11?
No
Call technical
support. Yes
Using a mulmeter, verify that the ohm values on
the mo tor c onn ec tor ar e a s fo ll ows :
For BLUE and BLACK wires: ± 49.5
ohms (K8) and
±
24.5 ohms (K10)
For BLUE and BROWN wires: ± 76.5 ohms (K8 and K10)
For BROWN and BLACK wires : ± 126 ohms (K8) and ± 101 ohms (K10)
Are all the values what they should be?
Yes
Replace the
electronic board.
No
Replace the motor.
VM0011A
Disconnue using
the unit and contact
technical support.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Venmar K10 HRV Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues