EMKO ESM-3711-CN Manuel utilisateur

Taper
Manuel utilisateur
ESM-3711-CN 77x35 DIN Size Cooling Controller
Instruction Manual. ENG ESM-3711-CN 01 V05 07/14
- 4 Digits Display
- NTC Input or PTC Input (Must be determined in order.)
- Adjustable temperature offset
- Set value boundaries
- Operation selection of compressor operates continuously,
stops or operates periodically in case of sensor defect
- Compressor protection delays
- Defrost time easily changeable from front panel
- Manual defrost capability from front panel
- Defrost parameters
- Alarm parameters
- Adjustable internal buzzer according to the defrost, sensor
defect and alarm status
- Defrost time and/or manual defrost and/or temperature set
value protection
- Password protection for programming section
- Installing parameters using Prokey
- Remote access, data collecting and controlling with Modbus RTU
- Having CE mark according to European Norms
ESM-3711-CN 77 x 35 DIN Size
Digital , ON / OFF Cooling Controller
ENGLISH
ENGLISH
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
c
1.2 General Specifications
1.Preface
ESM-3711-CN series cooling controllers are designed for controlling cooling process. They
can be used in many applications with their easy-use, On / Off control form and defrost
properties. Some application and application fields which they are used are below:
Application Fields
Food
Machine production industries
etc...
ESM-3711-CN
Applications
Refrigerators
Air Conditioning
Storages
Freezers
etc...
2
Cooling Function
ON/OFF Operation
1.1 Environmental Ratings
Compressor Output
Power Supply
Input
Sensor Input
NTC, PTC
230V ( %15) 50/60HzV ±
Optional Supply Voltage
- 30 V Z
115 V (±%15) 50/60Hz,
24 V (±%15) 50/60Hz,
10
V
V
Standard
ENGLISH
3
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.3 Installation
1.4 Warranty
1.5 Maintenance
1.6 Manufacturer Company
Manufacturer Company Name :
Emko Elektronik A.S .DOSAB Karanfil Sk.No:6 16369 BURSA/TURKEY
Phone : +90 224 261 19 00
Fax : +90 224 261 19 12
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone +90 224 261 1900
Fax +90 224 261 1912
2.2 Panel Cut-Out
2. General Description
2.1 Front View and Dimensions of ESM-3711-CN Cooling Controller
Mounting Clamp
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Front Panel
IP65 protection
NEMA 4X
4
76 mm / 3 inch
6 mm / 0.24 inch
34,5 mm / 1.36 inch
65 mm / 2.56 inch
Maximum 15 mm / 0.59 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
29 mm / 1.14 inch
50 mm / 1.97 inch (min)
O
F
O
C
P
S
ü
ESM-3711CN
ENGLISH
5
1.Switch off the device.
2.Put in PROKEY then energize the device.
3.When the device is energized, the parameter values in PROKEY, start downloading to the device
automatically. At first, message is shown on the display, when loading has finished,
message is shown.
4.After 10 seconds device starts to operate with new parameter values.
5.Remove the PROKEY.
1-Before mounting the device in your panel,
make sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them
before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and make
the unit completely immobile within the panel
3
1-Pull mounting clamps from left and right fixing
sockets.
2-Pull the unit through the front side of the panel
Before starting to remove the unit from
panel, power off the unit and the related
system.
c
2.3 Panel Mounting
2.4 Removing from the Panel
3. Using Prokey
DOWNLOADING FROM DEVICE TO PROKEY
1.The device is programmed by using the parameters.
2.Energize the device then put in PROKEY and press button. Message is shown on the
display. When the loading has finished, message is shown.
3.Press any button to turn back to main operation screen.
4.Remove the PROKEY.
DOWNLOADING FROM PROKEY TO DEVICE
NOTE: message is shown when an error occurs while programming. If you want to reload, put
in PROKEY and press button. If you want to quit, remove PROKEY and press button. The
device will turn back to main operation screen.
NOTE: message is shown when an error occurs while programming. If you want to reload,
switch off the device and put in PROKEY then energize the device. If you want to quit remove
PROKEY and press button. The device will turn back to main operation screen.
TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’.
IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER
DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET
BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.
1
3
2
1
2
ENGLISH
ENGLISH
PROKEY
RS-485
or
5
6
7
8 9
10
a
16(8)A
@250VV1HP
L
N
230 VV ± 15%
50/60Hz - 1.5VA
2
3
41
COMP
.
NTC
L
N
16A T Sigorta
4.2 Device Label and Connection Diagram
4. Electrical Wiring Diagram
4.1 Supply Voltage Input Connection of the Device
Note-1 : External fuse is recommended.
Make sure that the power supply voltage is the same
indicated on the instrument.
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While
installing the unit, supply voltage range must be controlled
and appropriate supply voltage must be applied to the unit.
c
There is no power supply switch on the device. So a power
supply switch must be added to the supply voltage input.
Power switch must be two poled for seperating phase and
neutral, On/Off condition of power supply switch is very
important in electrical connection.
External fuse that on Vpower supply inputs must be on
phase connection.
External fuse that on Z power supply inputs must be on (+)
connection.
c
Relay Output
21 3 54 6 87 9 10
L N
a
Supply Voltage Input
Temperature Sensor
Input (NTC or PTC)
230VV CONNECTION DIAGRAM
6
Power Supply Connection
c
a
EXTERNAL
FUSE
(1A T)
Note-1
Supply
Switch
Supply Voltage
5
6
L
N
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
Z
V ±
V ±
10...30 V - 1.5 W
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
Z
V ±
V ±
10...30 V - 1.5 W
Must be determined in order.
Must be determined in order.
5.Front Panel Definition and Accessing to the Menus
BUTTON DEFINITIONS
1. Increment Button :
** It is used to increase the value in the Set screen, Defrost screen and Programming mode.
2. Decrement, Silencing Buzzer and Downloading to Prokey Button :
** It is used to decrease the value in the Set screen, Defrost screen and Programming mode.
** It is used to silence the buzzer.
** If Prc =0, it is used to download from device to prokey.
3. Defrost Button :
** In the main operation screen; if this button pressed, defrost time value will be displayed.
**In the main operation screen; if this button pressed for 3 seconds, manual defrost starts.
4. Set Button :
** In the main operation screen; if this button pressed, set value will be displayed. Value can be
changed using increment and decrement buttons. When Set button pressed again, value is
saved and returns back to main operating screen.
** To access the programming screen; in the main operation screen, press this button for 5
seconds.
** It is used to saving value in the Set screen, Defrost screen and programming screen.
LED DEFINITIONS
5. Compressor output led :
** This led indicates that compressor output is active. If any of compressor protection time
active, this led blinks.
6.Defrost led :
** This led indicates that defrost output is active.
** Blinks once in a second while Defrost delay time.
** Blinks (5 Hz) while entering Defrost time value.
7.Alarm led :
** It is active when low alarm and high alarm statuses.
8.Celcius led :
o
** Indicates that device is in C mode.
9.Fahrenheit led :
o
** Indicates that device is in F mode.
10.Set led :
** Indicates that device is in Set value changing mode.
11.Program led :
**Blinks in programming mode .
7
5 6 7 8
10
11
1
2
3
4
9
O
F
O
C
P
S
ü
ESM-3711CN
ENGLISH
ENGLISH
6. Changing and Saving Temperature Set Value
6.1 Changing and Saving Defrost Time Set Value
Main Operation Screen
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
SET Value Screen
Temperature set value can
be changed with increment
and decrement buttons.
When SET button pressed
temperature set value can be saved.
‘’S’’ will be inactive and goes back to
main operation screen.
Main Operation Screen
Temperature set value parameter (Default=50) MODBUS ADDRESS:40001
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
When defrost button is pressed, defrost
time set value is shown and defrost
output led starts to fast blink (5 Hz).
Press set button for saving the defrost
time set value
Defrost time set value is saved, defrost
output led stop the fast blink (5 Hz), main
operation screen is shown.
Main Operating Screen
Defrost Time Value Screen
Defrost Time Value Screen
If no operation is performed in defrost time set value changing mode and temperature set
value changing mode for 20 seconds, device turns to main operation screen automatically.
i
Change the defrost time set
value with increment and
decrement buttons.
Main Operating Screen
8
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
P
S
ü
ESM-3711CN
ENGLISH
Cooling
Heating
Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40007
from -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C),
from -36 to 36 °F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),
from -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C),
from -18.0 to 18.0°F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F),
Defrost Time Parameter ( Default =1 0) MODBUS ADDRESS:40009
It can be adjusted from 0 to 999 minutes. If it is selected 0 automatic or manual defrost is not
performed.
Defrost Repeat Cycle Parameter ( Default = 1) MODBUS ADDRESS:40010
It can be adjusted from 1 to 99 hours.
Defrost at Power On Parameter ( Default = 0) MODBUS ADDRESS:40011
Operating Type Parameter ( Default = 1) MODBUS ADDRESS:40008
If parameter value is ‘0’ device skips to parameter
System does not go through a defrost cycle at start up
System goes through a defrost cycle at start up
9
6.2 Programming Mode Parameter List
Hysteresis Parameter for Compressor Output ( Default = 1 )
MODBUS ADDRESS:40004
from 1 to 20°C for NTC (-50°C, 100°C) or PTC (-50°C, 150°C),
from 1 to 36°F for NTC (-58°F, 212°F) or PTC (-58°F, 302°F),
from 0.1 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC (-50.0°C,150.0°C),
from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F) or PTC (-58.0°F,302.0°F),
In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.
ON
OFF
Temperature
Control
Output
Set
HSt
Time
HSt
Time
Minimum Temperature Set Value Parameter (Default = Minimum Value of Device
Scale ) MODBUS ADDRESS:40005
Temperature set value can not be lower than this value.
This parameter value can be adjusted from minimum value of device scale to maximum
temperature set value parameter
Maximum Temperature Set Value Parameter (Default = Maximum Value of Device
Scale )MODBUS ADDRESS:40006
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale
Decimal Seperator Enabling Parameter ( Default = 0 ) MODBUS ADDRESS:40003
Disable.
Enable.
Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40002
°C selected.
°F selected.
ENGLISH
Defrost Delay at Power On Parameter ( Default = 0) MODBUS ADDRESS:40012
It can be adjusted from 0 to 99 minutes. This parameter can be observed if defrost at power
on parameter is 1.
Compressor Start Delay at Power On Parameter ( Default = 0)
MODBUS ADDRESS:40014
When power is first applied to the device, compressor is on when this time delay is expired.
It can be adjusted from 0 to 20 minutes.
Compressor Stop-Start Delay Parameter ( Default = 0) MODBUS ADRES:40015
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Compressor Start-Start Delay Parameter ( Default = 0) MODBUS ADRES:40016
This time delay must be expired between two activation of the compressor. It can be
adjusted from 0 to 20 minutes.
10
Display Status During Defrost Parameter ( Default = 3 ) MODBUS ADDRESS:40013
The temperature is displayed during defrost.
Temperature value at the start of a defrost is displayed during defrost.
Set value is displayed during defrost.
Is displayed to indicate a defrost is in progress.
Sensor Defect Parameter ( Default = 0 ) MODBUS ADRES:40017
Compressor is active during this time period in case of probe defect (Default = 0)
MODBUS ADRES:40018
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to and Time periods in
case of sensor defect.
Compressor is inactive during this time period in case of probe defect
( Default = 0 )MODBUS ADRES:40019
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Temperature Minimum Alarm Parameter (Default =Minimum Value of Device Scale)
MODBUS ADRES:40021
For temperature alarm function selection parameter = 1(Absolute alarm), this
parameter value is can be adjust from minimum value of device scale to temperature
alarm maximum parameter value , for temperature alarm function selection
parameter = 2(Relative alarm), this parameter value is can be adjusted 0 to %50 of
the device scale
Relative alarm is selected. Alarm operates according to the set value.
If temperature is below ( Set - ) or above ( Set + ), alarm occurs.
Temperature Alarm Function Selection Parameter ( Default = 0 )
MODBUS ADRES:40020
Alarm function is inactive.
Absolute alarm is selected. If temperature lower than and higher
than , then alarm is on.
Temperature Alarm Maximum Parameter ( Default = Maximum Value of Device Scale)
MODBUS ADRES:40022
For temperature alarm function selection parameter = 1(Absolute alarm), this
parameter value is can be adjust from temperature alarm minimum parameter
value to maximum value of device scale, for temperature alarm function selection
parameter = 2(Relative alarm), this parameter value is can be adjusted 0 to %50
of the device scale
ENGLISH
ON/OFF Parameter ( Default = 0 ) MODBUS ADDRESS:40030
When device energized; if (increment button) pressed for 10 seconds, device stops
controlling and screen will be displayed. If (increment button) pressed again for
10 seconds, device continues controlling and display changes back to main operating
screen.
ON/OFF function with button is not available.
ON/OFF function with button is available.
11
Temperature Alarm On Delay Time Parameter(Default = 0)MODBUS ADDRESS:40023
Temperature alarm on delay time can be defined with this parameter.
It can be adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm. It can be adjusted from 0 to 99 minutes.
( Default = 0 )
MODBUS ADRES:40024
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40025
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs.
Buzzer is active during sensor failures.
Buzzer is active during defrost operation, alarm or sensor failures.
Button Protection Parameter ( Default = 4 ) MODBUS ADDRESS:40027
There is no protection.
Defrost time can not be changed and manual defrost is not available.
Temperature Set value can not be changed.
Defrost time set value and temperature set value can not be changed. Manual
defrost is not available.
Buzzer is active during this time
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40026
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
Programming Section Accessing Password
. If password selected ‘12’, only , and
parameters will be accessible.
( Default = 0 ) MODBUS ADDRESS:40031
It is used for accessing to the programming section. It can be adjusted from 0 to 999. If it is
selected 0, password will not be asked
Defrost time value can not be changed, manual defrost is available..
PROKEY communication selected.
Communication Mode Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40028
Rs485 communication selected.
Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40029
Device communication address parameter (1 to 247).
MODBUS ADDRESS:30001 Temperature Value
MODBUS ADDRESS:30002 Reserved
o
MODBUS ADDRESS:30003 Led Status : 0.bit C Led, 5.bit Defrost Led,
6.bit Compressor Led, 7.bit Alarm Led
13.bit Program Led, 14.bit Set Led
MODBUS ADDRESS:30004 Device Status : 0.bit Alarm Status
1.bit Buzzer Status
2.bit Sensor Lost Status
7.bit Defrost Status
MODBUS ADDRESS:30005 Output Status
MODBUS ADDRESS:30006 Device Type and Device Version
A
A
A
A
A
6.3 Modbus Adresses of Device Status Parameters (Read Input Register)
12
ENGLISH
ENGLISH
13
6.4 Operation Graphics of ESM-3711-CN Cooling Controller
Power
Time
Time
Time
Time
Time
1-If defrost time parameter 1 ,
Defrosting repeat cycle 1 ,
Defrost at Power On Parameter = 1 and
Defrost Delay at Power On Parameter 1;
Defrost
Led
Output
Defrost time
starts with
button.
2- If is 1 ,
1 and
Compressor Start-Start Delay Parameter is 1 then ;
Compressor Start Delay at Power On Parameter
Compressor Stop-Start Delay Parameter is
Power
Time
Time
Time
Time
Output
Output
Led
ENGLISH
14
When SET button is pressed for 5
seconds, “PR” led starts to blink. If
programming mode entering
password is different from 0,
programming mode entering screen
will be observed.
Main Operation Screen
Programming Screen
Change the value with increment
and decrement buttons.
Hysteresis Value for
Compressor Output
Press SET button for accessing to the parameter
value. Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter.
Press set button for saving the
parameter.
Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter
Password Entering Screen
Programming Mode
Entering Screen
Press SET button for
accessing to the
password entering
screen.
Password Entering Screen
Enter programming mode accessing password
with increment and decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters
are accessible, and the parameter values can be changed.
Press SET/OK button for
entering the password.
Note1: If programming
mode accessing password
is 0, Temperature Unit
Selection parameter is
observed instead of
programming screen
Hysteresis Value for
Compressor Output
If no operation is performed in programming mode for 20 seconds, device turns to main
operation screen automatically..
i
Hysteresis Parameter
for Compressor
6.5 Entering To The Programming Mode, Changing and Saving Parameter
O
F
O
C
P
S
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
O
F
O
C
S
P
ü
ESM-3711CN
ENGLISH
Example-1 : If alarm function selection parameter In programming section is 1(Absolute
alarm) and minimum alarm parameter is 20 ;
When temperature is less than 20°C, value on the screen starts to blink. Also if buzzer function
selection parameter is 2 or 4 , then internal buzzer is on.
1. Screen Blinking
Sensor failure . Sensor connection is wrong or there is no sensor connection. If buzzer function
selection parameter is 3 or 4, internal buzzer starts to operate.
15
Device Type : Cooling Controller
Housing&Mounting : 76mm x 34.5mm x 71mm plastic housing for panel
Mounting. Panel cut-out is 71x29mm.
Protection Class : NEMA 4X (Ip65 at front, Ip20 at rear).
Weight : Approximately 0.20 Kg.
Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
o o o o
Storage / Operating Temperature: -40 C to +80 C / -30 C to +80 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24 ,10-30
Temperature Sensor Input : NTC or PTC
NTC input type : NTC (10 kW @25 °C )
PTC input type : PTC (1000 W @25 °C )
Accuracy : ± 1 % of full scale for thermoresistance
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Outputs : 16(8) A@250 V V for Resistive load (Compressor
output)
(Electrical life : 100.000 switching at full load)
Display : 14 mm Red 4 digits LED Display
o o
LED : S (Green), P (Green), C (Yellow), F(Yellow), Alarm (Red),
Defrost (Red), Compressor Output (Red)
Internal Buzzer : 83dB
Approvals :
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA VZ 1.5W
V ±
V ±
V ±
9. Specifications
3 sn.
While defrost time parameter value 1, button protection
parameter value = 0 or 2 and defrost output is inactive,
in main operation screen if defrost button is pressed for
3 seconds defrost operation starts and defrost led becomes
active.If defrost button pressed for 3 seconds while defrost
continues,defrost is finished and defrost led becomes inactive.
8. Manual Defrost Operation with Defrost Button
O
F
O
C
P
S
7. Failure Messages in ESM-3711-CN Cooling Controller
2- Blinking the Screen Value
If temperature higher than the alarm parameters limit, value on the screen starts to blink.
Example-2 : If alarm function selection parameter in programming section is 1 (Absolute
Alarm) and maximum alarm parameter is 50
When temperature is above 50 °C, value on the screen starts to blink. Also buzzer function
selection parameter is 2 or 4, then internal buzzer is on.
ü
ESM-3711CN
,
ENGLISH
16
All order information of ESM-3711-CN Cooling Controller are given on the table at left. User may form
appropriate device configuration from information and codes that at the table and convert it to the
ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order
code blanks according to your needs.
Please contact us, if your needs are out of the standards.
V Ş Vac,
Z Ş Vdc
Ş Vdc or Vac can be appliedW
c
10.Ordering Information
A BC D E FG HI /
/
U
V W Z/
/
0 1 0 0
1
Relay Output ( 16(8) A@250 V V at resistive load, 1 NO )
Compressor Output
E
Supply VoltageA
Input Type
BC
Scale(°C)
ESM-3711-CN
4
-50°C/-58°F ; 100°C/212°F
18
NTC (Note-1)
Temp. Sensor which is given with ESM-3711-CN
V
0
None
3
NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with
1.5 m cable for cooling application)
4
NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with
1.5 m cable for cooling application)
9
Customer
115V ( %15) 50/60Hz - 1.5VAV ±
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
8
10 - 30 V Z
00 00
(77x35 DIN Size)
11.Optional Accessories
3
24V ( %15) 50/60Hz - 1.5VAV ±
5
230V ( %15) 50/60Hz - 1.5VAV ±
-50°C/-58°F ; 150°C/302°F
12
PTC (Note-1)
1
2
PTC-M6L40.K1.5 (PTC Air Probe with 1.5 mt silicon cable)
PTCS-M6L30.K1.5.1/8” (PTC Liquid Probe with1.5 mt silicon cable)
Your Technology Partner
www.emkoelektronik.com.tr
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
RS-485 Communication Interface
1.RS-485 Module 2.PROKEY Programming Module
The device is programmed(Upload or
Download) by using the parameters.
ESM-3711-CN 77x35 DIN Maß Kühlregler
Bedienungsanleitung: DE ESM-3711-CN 02 V02 09/12
- 4-stellige Anzeige
- NTC Eingang oder PTC Eingang (Muss vorher festgelegt werden)
- Einstellbare Temperaturabweichung
- Begrenzte einstellbare Werte
- Bei Sensorschaden Wahl zwischen Dauerbetrieb, Stopp oder
periodischem Betrieb des Kompressors.
- Verzögerter Überstromschutz des Kompressors
- Von der Vorderseite aus einstellbare Abtauzeit
- Manuellles Abtauen von der Vorderseite aus
- Parameter für den Abtauvorgang
- Parameter für den Alarm
- Eingebauter einstellbarer Summer gesteuert vom Kühlfachsensor
Schadens- und Alarmstatus
- Schutz der eingestellten Werte für manuell eingestellte Abtauzeit
und/oder eingestellte Temperaturwerte
- Passwortschutz für den Programmierbereich
- Parameter werden mit Prokey installiert
- Fernregelung,Datenkontrolle und Regelung mit Modbus RTU
- Mit EU Kennzeichnung gebaut nach den europäischen Normen
ESM-3711-CN 77 x 35 DIN Maß
Digitaler , EIN / AUS Kühlregler
DEUTCH
DEUTCH
Betriebstemperatur : 0 bis 50 °C
Max.Feuchtigkeit: : 90% r.L. (kein Kondenswasser)
Höhe: : Bis zu 2000 m.
Unzulässig
Korrosive Umgebung
Explosive Atmosphäre
Verwendung im Heimbereich (Gerät ist für industrielle Anwendung gedacht)
c
1.2 Allgemeine Daten
1.Vorwort:
Die Kühlregler der Serie ESM-3711-CN sind für die Regelung von Kühlprozessen gedacht.
Durch ihren einfachen Gebrauch sind sie vielfältig einsetzbar, auch wegen ihrer EIN/AUS-
Regelung und ihrer Abtaufunktion. Einige Anwendungen sind in der Liste unten aufgeführt:
Einsatzbereiche:
Lebensmittel
Maschinen, Produktion, Industrie
usw....
ESM-3711-CN
Anwendungen:
Kühlschränke
Klimaanlagen
Lagerung
Kühlräume
usw...
2
Kühlfunkion
EIN/AUS-Regelung
1.1 Umweltfreundlichkeit
Kompressorausgang
Anschluss
Stromversorgung
Sensoreingang
NTC,PTC
230V ( %15) 50/60HzV ±
Wahlweise auch:
115 V (±%15) 50/60Hz,
10 - 30 V Z
V
Standard
3
DEUTCH
3
2 Jahre Garantieschutz gegen Material- und Verarbeitungsfehler.
Diese Garantie wird mit dem Vorbehalt gewährleistet, dass der Kunde
den in Garantieschein und
Bedienungsanleitung erwähnten Pflichten nachkommt.
Das Gerät muss durch geschultes Personal gewartet werden. Vor dem Zugriff auf
Innenteile, alle stromführenden Leitungen trennen. Gerät nicht mit auf Kohlenwasserstoff
basierenden Lösungsmitteln (wie Benzin, Trichlorethylen etc.) reinigen. Das Reinigen mit
diesen Lösungen kann die mechanische Sicherheit des Geräts vermindern. Verwenden Sie
ein mit Ethylalkohol oder Wasser benetztes Tuch um das Plastikgehäuse außen zu reinigen.
Information des Herstellers:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
Tel : +90 224 261 1900
Fax : +90 224 261 1912
Information über Reparatur und Wartungsdienst
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
Tel : +90 224 261 1900
Fax : +90 224 261 1912
Vor Montage das Gerät visuell prüfen, ob das Gerät während der Beförderung beschädigt
wurde. Die Montage und Inbetriebnahme muss durch geschultes Personal ausgeführt werden.
Dies steht unter der Verantwortung des Käufers.
Falls aufgrund eines Fehlers oder einer Störung des Geräts eine Gefahr bestehen sollte,
Spannungsversorgung abschalten und alle elektrischen Verbindungen zum Geräts entfernen.
Standardmäßig wird das Gerät ohne Netzschalter und ohne Sicherung ausgeliefert.
Bei Bedarf müssen diese vom Anwender selbst angebracht werden.
Es muss eine zum Gerät passende Versorgungsspannung verwendet werden, um
Fehlfunktionen und Schäden zu vermeiden.
Um einen elektrischen Schock und ähnliche Unfälle zu vermeiden, darf das Gerät vor
Abschluss der Verkabelung nicht mit Spannung versorgt werden.
An dem Gerät keine Veränderungen vornehmen, und das Gerät nicht reparieren.
Eingriffe am Gerät können fehlerhafte Funktion, Beschädigung des Geräts oder
angeschlossener Geräte, elektrischen Schocks und Feuer auslösen.
Das Gerät darf unter keinen Umständen in der Nähe von brennbaren und explosiven Gasen
verwendet werden.
Die Schalttafelausschnitte können scharfe Kanten aufweisen, welche bei der Montage des
Geräts Schnittverletzungen verursachen können. Bitte treffen Sie die erforderlichen
Vorsichtsmaßnahmen.
Es ist wichtig, dass das Gerät mit den mitgelieferten Befestigungsteilen montiertwird.
Das Gerät nicht mit ungeeigneten montieren. Achten Siedarauf, dass das Gerät während der
Montage nicht herunterfällt.
Es unterliegt Ihrer Verantwortung, wenn das Gerät nicht wie in dieser Anleitung beschrieben,
verwendet wird.
1.3 Installation
1.6 Sonstige Angaben
1.4 Garantie
1.5 Instandhaltung
2.2 Ausschnitt in der Schalttafel
2. Allgemeine Beschreibung:
2.1 Vorderansicht und Abmessungen des ESM-3711-CN Kühlreglers
Halteklammern
Frontplatte
(maximale Dicke 15 mm / 0.59 Zoll)
Vorderseite
Schutzklasse IP65
NEMA 4X
4
76 mm / 3 Zoll
O
F
O
C
S
P
ü
6 mm / 0.24 Zoll
34,5 mm / 1.36 Zoll
65 mm / 2.56 Zoll
Maximal 15 mm / 0.59 Zoll
110 mm / 4.33 Zoll (min)
71 mm / 2.79 Zoll
29 mm / 1.14 Zoll
50 mm / 1.97 Zoll (min)
DEUTCH
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

EMKO ESM-3711-CN Manuel utilisateur

Taper
Manuel utilisateur