Allen-Bradley 1790-T0V16X Installation Instructions Manual

Taper
Installation Instructions Manual
Installation Instructions
Digital Expansion Terminal Block
CompactBlock LDX I/O
Catalog Numbers 1790-T16BV0X, 1790-T8BV8VX,
1790-T8BV8BX, 1790-T0B16X, 1790-T0V16X, 1790-T0W8X,
1790-T8A0X, 1790-T0A8X
Table of Contents
Topic Page
Important User Information 2
Environment and Enclosure 3
Prevent Electrostatic Discharge 3
North American Hazardous Location Approval 4
Install Your Module 5
Mount the Expansion Block 5
Connect an Expansion Block to a Base Block 8
Wire the Expansion Blocks 9
Troubleshoot with the Indicators 12
Specifications 12
2 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/
) describes some important differences between
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid-state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify
a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor)
to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
Digital Expansion Terminal Block CompactBlock LDX I/O 3
Publication 1790-IN005C-EN-P - January 2015
Environment and Enclosure
Prevent Electrostatic Discharge
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without
derating. This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate precautions, there
may be potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance. This
equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions
that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for additional
installation requirements, Allen-Bradley publication 1770-4.1
.
NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
4 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet
équipement en environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des marquages sur
sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code
de température le plus défavorable (code de température le
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection
par les autorités locales qualifiées au moment de
l'installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless
power has been removed or the area is
known to be nonhazardous.
• Do not disconnect connections to this
equipment unless power has been
removed or the area is known to be
nonhazardous. Secure any external
connections that mate to this equipment
by using screws, sliding latches, threaded
connectors, or other means provided with
this product.
• Substitution of components may impair
suitability for Class I, Division 2.
• If this product contains batteries, they
must only be changed in an area known to
be nonhazardous.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l'environnement est classé non dangereux
avant de débrancher les connecteurs.
Fixer tous les connecteurs externes reliés
à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres
moyens fournis avec ce produit.
La substitution de composants peut rendre
cet équipement inadapté à une utilisation
en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
Digital Expansion Terminal Block CompactBlock LDX I/O 5
Publication 1790-IN005C-EN-P - January 2015
Overview
This document describes how to install the expansion blocks.
Install Your Module
Follow these steps to install the block:
1. Mount the block.
2. Connect the expansion blocks.
3. Wire the expansion blocks.
These steps are explained in detail in the following sections.
Mount the Expansion Block
Mount the expansion block by connecting it to a previously-installed
CompactBlock LDX I/O base or expansion block.
Beginning with the base block, you can mount your expansion blocks either horizontally
or vertically:
horizontally (left to right)add expansion blocks in an end-to-end
configuration
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with the proper wiring
method that complies with the governing electrical codes.
6 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
vertically (up or down) – add expansion blocks either up or down in a
back-to-back configuration. In this configuration, you must use the optional
15cm ribbon cable (1790-15CMCBL) and alternately position the blocks in a
right-side up, upside-down
fashion.
You can mount your blocks on a panel or DIN rail as described in the following section.
Panel Mounting
1. Place the block against the panel where you want to mount it.
2. Gently pull and position the expansion cover to the left.
3. Place a center punch, nail or similar device through the mounting holes in the
block and make two marks on the panel (lower left and upper right corners of the
module).
4. Remove the block and drill two holes in the panel to accommodate each of the
mounting screws.
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
EXPANSION UNIT
Block LDX
PULL
PULL
UPSIDE DOWN
EXPANSION UNIT
Block LDX
PULL
PULL
RIGHT SIDE UP
Horizontal mounting
Vertical mounting
The longer
expansion cable
(1790-15CMCBL)
will allow up to
7 cm of space in
between blocks.
Digital Expansion Terminal Block CompactBlock LDX I/O 7
Publication 1790-IN005C-EN-P - January 2015
5. Replace the block on the panel and place a screw through each of the two
mounting holes. Tighten the screws until the block is firmly in place.
DIN Rail Mounting
1. On the DIN rail, position the expansion block next to your previously-installed
base block.
2. Hook the top slot of the block over the DIN Rail.
3. Pull down on the locking lever while pressing the block against the rail.
4. Push up on the locking lever to secure the block to the rail when block is flush
against the rail.
CompactBlock LDX
1790-16BVOX
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
0
7
95 mm
3.74 in
Expansion
Cover
41 mm
1.6 in
Locking Lever
8 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
Connect an Expansion Block to a Base Block
Follow these procedures when connecting the expansion block to the base block.
1. Pull and position the expansion covers inward on both the base and
expansion blocks.
2. Position the expansion block with proper spacing..
3. Mount the expansion block using panel or DIN rail mounting, as described in the
previous section.
4. Plug the expansion cable into the base and expansion blocks.
ATTENTION: Expansion blocks should not be installed when power is applied
to the base.
IMPORTANT
The expansion cable can only be connected to the modules so that the red
stripe on the cable is on the bottom as shown below.
Compact
Block LDX
1790-16BVOX
DC INPUTS
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
DC OUTPUTS
0
7
CompactBlock LDX
1790-16BVOX
DC INPUTS
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
DC OUTPUTS
0
7
Expansion cover
41 mm
1.6 in
Base block
Expansion block
95 mm
3.74 in
95 mm
3.74 in
41 mm
1.6 in
25 mm
1 in
Digital Expansion Terminal Block CompactBlock LDX I/O 9
Publication 1790-IN005C-EN-P - January 2015
5. Replace the expansion covers on all blocks.
Wire the Expansion Blocks
The following figures show the wiring information for the expansion blocks.
1790-T16BVOX Input Expansion Block Wiring Diagram
For inputs 0…7: Sinking inputs – wire COM 0 (pin 9) to Field Power (-) GND
Sourcing inputs - wire COM 0 (pin 9) to Field Power (+) 24V DC
For inputs 815: Sinking inputswire COM 1 (pin 11) to Field Power
(-) GND
Sourcing inputs – wire COM 1 (pin 11) to Field Power (+) 24V DC
Note: both COM 0 are internally connected - COM 0 is used for inputs 0…7,
COM 1 is used for inputs 8…15. Both COM 1 are internally connected.
IMPORTANT
Input and output wiring must be in accordance with Class 1, Division 2
wiring methods and in accordance with the authority having jurisdiction.
Compact
Block LDX
1790-16BVOX
DC INPUTS
EXPANSION UNIT
16 INPUTS-DCPOWER
0
7
DC OUTPUTS
0
7
CompactBlock LDX
1790-8BV8V
DC INPUTS
MOD NET
STATUS
8 INPUTS/8OUTPUTS-DC POWER
0
7
DC OUTPUTS
0
7
To install plug, gently pull
and swing cover inward
Red strip must be on bottom
of expansion cable
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
IN15
IN11
COM1
IN7
IN3
IN13
IN9
COM0
IN5
IN1
IN12
IN8
COM0
IN4
IN0
IN14
IN10
COM1
IN6
IN2
10 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
1790-T8BV8VX Input/Output Expansion Block Wiring Diagram
Sinking inputs – wire COM (pin 9) to Field Power (-) GND
Sourcing inputs – wire COM (pin 9) to Field Power (+) 24V DC
Note: both COM (pins 9 and 10) are internally connected.
Sinking outputs – wire VDC (pin 11) to Field Power (+) 24V DC, wire GND
(pin 12) to Field Power (-) GND.
1790-T8BV8BX Input/Output Expansion Block Wiring Diagram
Sinking inputs – wire COM (pin 9) to Field Power (-) GND
Sourcing inputs - wire COM (pin 9) to Field Power (+) 24V DC
Note: both COM (pins 9 and 10) are internally connected.
Sourcing outputs – wire VDC (pin 11) to Field Power (+) 24V DC, wire GND
(pin 12) to Field Power (-) GND.
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
OUT7
OUT3
GND
IN7
IN3
OUT5
OUT1
COM
IN5
IN1
OUT4
OUT0
COM
IN4
IN0
OUT6
OUT2
VDC
IN6
IN2
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
OUT7
OUT3
GND
IN7
IN3
OUT5
OUT1
COM
IN5
IN1
OUT4
OUT0
COM
IN4
IN0
OUT6
OUT2
VDC
IN6
IN2
Digital Expansion Terminal Block CompactBlock LDX I/O 11
Publication 1790-IN005C-EN-P - January 2015
1790-T0B16X Output Expansion Block Wiring Diagram
Sourcing outputs – wire VDC0 (pin 9) and VDC1 (pin 11) to Field Power (+)
24V DC, wire GND0 (pin 10) and GND1 (pin 12) to Field Power (-) GND.
1790-T0V16X Output Expansion Block Wiring Diagram
Sinking outputs – wire VDC0 (pin 9) and VDC1 (pin 11) to Field Power (+)
24V DC, wire GND0 (pin 10) and GND1 (pin 12) to Field Power (-) GND
1790-T0W8X Relay Output Expansion Block Wiring Diagram
Wire VDC (pin 1) to Field Power (+) 24V DC
Wire GND (pin 2) to Field Power (-) GND
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
OUT15
OUT11
GND1
OUT7
OUT3
OUT13
OUT9
GND0
OUT5
OUT1
OUT12
OUT8
VDC0
OUT4
OUT0
OUT14
OUT10
VDC1
OUT6
OUT2
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
OUT15
OUT11
GND1
OUT7
OUT3
OUT13
OUT9
GND0
OUT5
OUT1
OUT12
OUT8
VDC0
OUT4
OUT0
OUT14
OUT10
VDC1
OUT6
OUT2
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
OUT15
OUT11
GND1
OUT7
OUT3
OUT13
OUT9
GND0
OUT5
OUT1
OUT12
OUT8
VDC0
OUT4
OUT0
OUT14
OUT10
VDC1
OUT6
OUT2
12 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
Troubleshoot with the Indicators
Use the I/O status indicators to troubleshoot your expansion blocks:
Specifications
The following table contains specifications that are common to all of the blocks in this
document. Individual base block specifications are detailed after this table.
Universal DC Input Expansion Block – 1790-T16BVOX
I/O Status Indicators
Indicator Status Description
Output
status
Off Output not energized
Solid green Output energized
Input
status
Off No valid input
Solid green Valid input
Attribute Value
Number of inputs per
expansion block
16 points, sinking or sourcing
Indicators 16 green – Input status
Common type 8 points/2COM (non-polarity)
On-state voltage 9.6V DC min
24V DC nom
28.8V DC max
Off-state voltage, max 5.0V DC
On-state current, max 8 mA per channel @ 28.8V DC
Input signal delay, max
OFF to ON
ON to OFF
10 ms
10 ms
Digital Expansion Terminal Block CompactBlock LDX I/O 13
Publication 1790-IN005C-EN-P - January 2015
DC Input/Output Combination Expansion Block –
1790-T8BV8VX, 1790-T8BV8BX
Attribute 1790-T8BV8VX 1790-T8BV8BX
Input Specifications
Number of inputs per
expansion block
8 points, non-isolated, sinking or sourcing
Indicators 8 green status
Common type 8 points/2COM (non-polarity)
On-state voltage 9.6V DC min
24V DC nom
28.8V DC max
Off-state voltage, max 5.0V DC
On-state current, max 8 mA per point @ 28.8V DC
Nominal input impedance 4.8 K
Input signal delay, max
OFF to ON
ON to OFF
10 ms
10 ms
Output Specifications
Number of outputs per
expansion block
8 points, non-isolated, sinking 8 points, non-isolated, sourcing
Indicators 8 green status
Common type 8 points/2COM (non-polarity)
On-state voltage 10V DC min
24V DC nom
28.8V DC max
On-state voltage drop,
max
0.5V DC
On-state current, min 1 mA per channel
Off-state leakage, max 0.5 mA
14 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
DC Output Expansion Block – 1790-TOV16X, 1790-TOB16X
Output signal delay, max
OFF to ON
ON to OFF
0.5 ms
1.0 ms
Output current rating, max 0.5 A per output
4.0 A per common
Field power dissipation 3.22 W @ 28.8V DC
Attribute 1790-TOV16X 1790-TOB16X
Number of inputs per
expansion block
16 points, non-isolated, sinking 16 points, non-isolated, sourcing
Indicators 16 green status
Common type 8 points/2COM 8 points/8COM
Off-state voltage, max 28.8V DC
On-state current, min 1 mA per channel
Off-state leakage, max 0.5 mA
Nominal input impedance 4.8 K
Output signal delay, max
OFF to ON
ON to OFF
0.5 ms
1.0 ms
On-state voltage 10V DC min
24V DC nom
28.8V DC max
On-state voltage drop,
max
0.5V DC
On-state current, min 1 mA per channel
Output current rating, max 0.5 A per output
4.0 A per common
Field power dissipation 2.76 W @ 28.8V DC
Attribute 1790-T8BV8VX 1790-T8BV8BX
Digital Expansion Terminal Block CompactBlock LDX I/O 15
Publication 1790-IN005C-EN-P - January 2015
AC/DC Relay Output Expansion Block – 1790-TOW8X
AC Input Expansion Block – 1790-T8AOX
Attribute Value
Relay type Form A, normally open
Single pole, single throw
Indicators 8 green status
Common type 1 point/1COM
Output voltage range,
load dependent
5…28V DC @ 2.0 A resistive
48V DC @ 0.8 A resistive
125V AC @ 2.0 A resistive
250V AC @ 2.0 A resistive
Minimum load, per point 100 A, 100 mV DC
Off-state leakage, max 1.5 mA
On-state voltage drop,
max
0.5V DC @ 2.0 A, resistive load, 24V DC
Initial contact resistance 30 m
Expected contact life 300K cycles resistive
100K cycles inductive
Output delay time, max
OFF to ON
ON to OFF
10 ms
10 ms
Field power voltage range 19.2…28.8V DC
Field power dissipation 2.3 W @ 28.8V DC
Attribute Value
Inputs per expansion block 8 points non-isolated
Indicators 8 green – input status
Common type 8 points/8COM
On-state voltage range 79V AC min
110V AC nom
132V AC max
Input impedance 18 K
On-state current, max 9 mA @ 132V AC
16 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
110V AC Output Expansion Block – 1790-T0A8X
Off-state voltage, max 45V AC
Input signal delay, max
OFF to ON
ON to OFF
10 ms
30 ms
External AC power supply
voltage
110V rms, 60 Hz
External AC power supply
voltage range
85…132V rms, 47…63 Hz
External AC power supply
power dissipation
3 W @ 132V AC
Attribute Value
Outputs per expansion block 8 points non-isolated
Indicators 8 green – input status
Common type 8 points/8COM
Load voltage range 15…132V rms
Load current, max 0.5 A rms
Load current, min 10 mA rms
Off-state leakage current,
max
1.0 mA rms @ 100V rms, 60 Hz
On-state voltage drop, max 1.3V rms @ max load
Operate time, max 1 ms
Release, max 1/2 cycle + 1 ms
Input signal delay, max
OFF to ON
ON to OFF
10 ms
30 ms
Insulation resistance, min 1,000 M (for input-output)
Dielectric strength 2500V rms, 1 minute (for input-output)
External AC power supply
voltage
110V rms, 60 Hz
Attribute Value
Digital Expansion Terminal Block CompactBlock LDX I/O 17
Publication 1790-IN005C-EN-P - January 2015
General Specifications
External AC power supply
voltage range
15…132V rms, 60 Hz
External AC power supply
power dissipation
5.2 W @ rated current
Attribute Value
Mounting DIN rail or screw
Dimensions 52H x 104W x 42D mm (2.03H x 4.07W x 1.64D inches)
Weight 100 g (3.53 oz)
Number of nodes, max 64 – rotary switch type node address setting
Indicators 1 red/green – module status
1 red/green – network status
Isolation voltage I/O to logic: photocoupler isolation
Type tested at 1250V AC for 60 s, between field power and DeviceNet (I/O
to logic)
DeviceNet to logic: non-isolated
DeviceNet power: non-isolated
Field Power,
Voltage range
10.…28.8V DC
Field Power,
Supply voltage
24V DC nom
Field power dissipation 3.68 W max @ 28.8V DC
Network protocol I/O Slave messaging:
- Poll command
- Bit Strobe command
- Cyclic command
- COS command
Network length, max 500 m @ 125 Kbps
100 m @ 500 Kbps
Communication rate 125 Kbps, 250 Kbps, 500 Kbps – auto baud rate selection
Enclosure type rating None (open-style)
Wiring Category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
2
Wiring copper or copper-clad aluminum conductors
Wiring terminal screw
torque, max
0.6 Nm (5.2 lb-in.)
Removable terminal block
screw torque, max
0.56 Nm (5.0 lb-in.)
Attribute Value
18 Digital Expansion Terminal Block CompactBlock LDX I/O
Publication 1790-IN005C-EN-P - January 2015
Environmental Specifications
Attribute Value
Operating
temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Non-operating
temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…90% noncondensing
Operating altitude 2000 m
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
10 g
Non-operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
EFT/B immunity IEC 61000-4-4:
1 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Digital Expansion Terminal Block CompactBlock LDX I/O 19
Publication 1790-IN005C-EN-P - January 2015
Certification (when product is marked)
Certification (when
product is
marked)
(1)
(1)
See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for Declaration of
Conformity, Certificates, and other certification details.
Value
c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ODVA ODVA conformance tested to DeviceNet specifications
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
technical and application notes, sample code and links to software service packs, and a MySupport feature
that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be returned, follow
these procedures.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002
, available at
http://www.rockwellautomation.com/literature/
.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator
at
http://www.rockwellautomation.com/support/americas/phone_en.html
, or
contact your local Rockwell Automation representative.
United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete the
return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
Publication 1790-IN005C-EN-P - January 2015 PN-297585
Supersedes Publication 1790-IN005B-EN-P - March 2003 Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in Korea.
Allen-Bradley, Rockwell Automation, CompactBlock LDX and RSNetWorx for DeviceNet, are trademarks of Rockwell Automation, Inc.
DeviceNet is a trademark of Open DeviceNet Vendor Association.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Allen-Bradley 1790-T0V16X Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues