EPH Controls CTR137NG Mode d'emploi

Taper
Mode d'emploi

Ce manuel convient également à

DIS. 0534026 COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.1/8
Centralina gas per centrali termiche
Gas detector for heating plants
Centrale détection de gaz pour chaufferies
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
CTR137
Caratteristiche tecniche / Technical specifications / Caractéristiques techniques
Alimentazione / Power supply / Alimentation 230Vac (-15/+10%) 50Hz / 3VA
12÷24Vac (-15/+10%) 50Hz / 3 VA
12÷24Vcc (-10/+15%) / 1,5 W
Sensore / Sensor Type / Capteur Catalitico / Catalityc / Catalytiques
Campo di misura / Standard Range / Champ de mesure 0 ÷ 20% LIE / LEL
Vita media in aria pulita / Average Life in fresh air / Vie moyenne en air pur 5 anni / years / ans
Intervento allarme
1st Alarm intervention / Seuil d'intervention de alarme
10% LIE / LEL
Intervento blocco
2nd Alarm intervention / Seuil d'intervention de blocage
20% LIE / LEL
Contatti relè / Contacts rating / Contact relais 230Vac 3A SPDT
Tempo di risposta T90 / Response Time T90 / Temps de réponse T90 < 30 secondi / seconds / secondes
Temperatura-Umidità di funzionamento
Operation Temp-Humidity / Temp. et humidité de fonctionnement
-10 ÷ +50 °C / 5 ÷ 90 % RH
non condensata / non condensed / non condensée
Temperatura-Umidità di immagazzinamento
Storage Temp-Humidity / Temp. et humidité de stockage
-25 ÷ +55°C / 5 ÷ 95 % RH
non condensata / non condensed / non condensée
Dimensioni / Size / Dimensions 160 x 125 x 80 mm / IP65
I DESCRIZIONE ............................................................................................................................ 2
FUNZIONAMENTO................................................................................................................................. 2
INSTALLAZIONE.................................................................................................................................... 2
AVVERTENZE ........................................................................................................................................ 3
VERIFICA FUNZIONAMENTO ............................................................................................................... 3
GB
DESCRIPTION............................................................................................................................. 4
OPERATIONAL DESCRIPTION............................................................................................................. 4
INSTALLATION ...................................................................................................................................... 4
WARNING............................................................................................................................................... 5
FUNTIONAL TESTING ........................................................................................................................... 5
F DESCRIPTION............................................................................................................................. 5
FONCTIONNEMENT............................................................................................................................... 6
INSTALLATION ...................................................................................................................................... 6
AVVERTISSEMENT................................................................................................................................ 7
Modello
Model / Modele
Tarato per
Calibrated for / Tarée pour
CTR137M Metano / Methane / Méthane
CTR137G GPL / LPG
DIS. 0534026 COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.2/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
I DESCRIZIONE
CTR137 è una centralina per montaggio a parete con un sensore interno di tipo catalitico per gas infiammabili. E’ ali-
mentata da rete (230Vca) e/o a 12÷24Vcc/Vac e il grado di protezione è IP65.
CTR21 è prodotto in due modelli, l'unica differenza è la taratura eseguita con specifico gas:
CTR137 va utilizzato in impianti alimentati a Metano.
CTR137 va utilizzato per quelli a GPL.
Sulla targa è visibile la barra Led che indica lo stato di funzionamento e la concentrazione di gas rilevata.
La centralina è dotata di due livelli d’allarme con uscite a relé di tipo sigillato e con contatti in scambio liberi da tensione.
E’ presente un’altra uscita relé in sicurezza positiva per le situazioni di guasto ed un ingresso ausiliario (AUX) per le no-
stre Elettrovalvole a Riarmo Manuale NC con Sensore di Posizione.
In Fig. 1 è illustrato un tipico collegamento da rete con sirena e valvola a riarmo manuale normalmente chiusa.
FUNZIONAMENTO
Preriscaldo: quando la centralina è alimentata inizia la fase di preriscaldo del sensore, segnalata dal lampeggio del Led
giallo "FAULT". Dopo circa 60 secondi, terminata questa fase il Led giallo si spegne e si accende il Led verde “ON”, che
indica il normale funzionamento.
Durante il Funzionamento Normale: la centralina legge la concentrazione di gas, tramite il sensore incorporato.
Il 1° Led Rosso si accende se la concentrazione di Gas supera il 5% LIE.
Il 2° Led Rosso si accende se la concentrazione di Gas supera il 10% LIE, se il gas non si riduce entro circa 4 secon-
di, interviene il relé "PREAL.", che normalmente è utilizzato per comandare una sirena (mod. SE301A).
Il 3° Led rosso si accende se la concentrazione di Gas supera il 20% LIE, se il gas persiste, entro circa 30 secondi, si
accende il Led rosso “STOP”e interviene il relé "ALARM", che normalmente è utilizzato per bloccare il gas tramite
elettrovalvola a riarmo manuale (NA o NC) e/o interrompere dell'energia elettrica.
Se è stata installata una ’Elettrovalvola a Riarmo Manuale NC con Sensore di posizione collegata all’ingresso “AUX”,
nel caso in cui non abbia chiuso il Gas, si accenderà il Led giallo ed interverrà il relé "FAULT" (vedi sezione Guasti
più avanti).
Pulsante "RESET": la condizione d’allarme rimane memorizzata, Led e relé restano attivati, anche se la concentrazione
di gas diminuisce (dato che si è chiusa la valvola, se installata). Per ripristinare le condizioni di funzionamento normali
e/o per tacitare la sirena è utilizzato il Pulsante “RESET”.
Tacitazione Sirena: solo se la concentrazione di gas è superiore al 10% del LIE il relé "PREAL." sadisattivato ed il
Led rosso lampeggerà. Dopo circa 20 secondi entrambi torneranno in preallarme (suona la Sirena).
Se fosse stata utilizzata l’Elettrovalvola a Riarmo Manuale NC con Sensore di posizione, e nel caso in cui essa sia
scattata, si spegnerà il Led giallo e si disattiverà il relé "FAULT" (vedi sezione ‘Guastipiù avanti).
Ripristino dopo un Allarme: la centralina tornerà al funzionamento normale solo se la concentrazione di gas è infe-
riore al 10% del LIE il relè "ALARM" sarà disattivato, il e Led rosso si spegneranno. Se attivato, sarà disattivato il
relé "FAULT" e si spegnerà il Led giallo (vedi sezione ‘Guasti’ più avanti).
AVVERTENZA: dopo aver premuto il RESET, può accadere che se la concentrazione di gas è superiore al F.S. il
relé "PREAL." sarà disattivato ed i primi tre Led rossi si spegneranno. Si accenderà il Led giallo ed interverrà il relé
"FAULT". In questo caso è molto probabile un guasto nel sensore. Se, eliminata la causa dell’allarme, premendo il pul-
sante "RESET" la condizione persiste, consultare la sezione ‘Guasti’ più avanti.
Guasti: La centralina segnala diversi tipi di guasti con l’accensione del Led giallo e attivazione del relé "FAULT" che è
normalmente eccitato con contatti in scambio liberi da tensione. Se richiesto, può essere utilizzato per segnalare a di-
stanza la condizione di guasto e/o la mancanza d’alimentazione.
Led Giallo e Verde accesi e relé "FAULT" attivato: questo avviene in caso di guasto del sensore catalitico. Se la
condizione persiste, sarà necessario sostituire la centralina o inviarla al fornitore per la riparazione.
Led Giallo, Verde e 4° Rosso accesi e relé "FAULT" e “ALARM” attivati: (solo dopo aver premuto il tasto “RESET)
questo avviene verifica sia per guasto del sensore catalitico, sia, in rari casi, per presenza di un elevatissima concentra-
zione di gas. In questo caso la centralina rimarrà in allarme come descritto nella sezione ‘FUNZIONAMENTO >
AVVERTENZA. Se non è presente alcuna fuga di gas e la condizione persiste, sarà necessario sostituire la centralina
e/o inviarla al fornitore per la riparazione.
Guasto Elettrovalvola a Riarmo Manuale NC con Sensore di posizione: questa situazione avviene SOLO se è in-
stallata un’Elettrovalvola con sensore di Posizione; se non chiude il gas, all’attivazione del relé "ALARM" (concentrazione
di Gas altre il 20% LIE), il sensore di posizione segnala alla centralina l’avvenuto malfunzionamento. In questo caso si
avranno tutti i Led accesi e tutti i reattivi. La condizione di guasto (Led giallo "FAULT" acceso e re"FAULT" attivo)
sarà annullata se, premendo il tasto “RESET”, sarà riscontrata l’effettiva risoluzione del problema (l’elettrovalvola si è
chiusa). Se invece, premendo il tasto RESET”, l’allarme rientra (concentrazione di Gas inferiore al 10% LIE), la condi-
zione di guasto, sarà annullata in ogni caso. Si consiglia pertanto di controllare che l’elettrovalvola non sia bloccata e che
i cavi di collegamento con l’elettrovalvola non siano interrotti.
INSTALLAZIONE
CTR137 va installato seguendo tutte le normative vigenti in materia.
Posizionamento del Mod. CTR137M: il Metano (CH4) è un gas più leggero dell'aria, la sua densità relativa all'aria è
0,55, il suo LIE (Limite Inferiore d’Esplosività) è 5%v/v (Volume). Il rivelatore va posto a 30 cm. dal soffitto, ad una di-
stanza di 1-1,5 metri dall'utilizzatore, lontano dagli angoli del locale o da prese di ventilazione.
DIS. 0534009a COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.3/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
Posizionamento del Mod. CTR137G: il GPL è una miscela composta dal 20-30% di Propano (C3H8) e dal 80-70% di
Butano (C4H10). La taratura per GPL è eseguita con iso-Butano che è un gas combustibile più pesante dell'aria, la sua
densità relativa all'aria è 2, il suo LIE (Livello Inferiore d’Esplosività) è 1,8%v/v (Volume).
Il rivelatore va posto a 30 cm. dal pavimento, ad una distanza di 1-1,5 metri dall'utilizzatore, lontano dagli angoli del loca-
le o da prese di ventilazione.
Montaggio: In Fig. 2 sono indicate le dimensioni della centralina che va montata a parete con tre tasselli. La valvola di
blocco gas, a riarmo manuale, va installata all'esterno del locale, in posizione chiaramente segnalata e protetta dalla
pioggia diretta.
Collegamenti elettrici: I morsetti sono di tipo ad innesto polarizzati, si consiglia, di ancorare i cavi nella custodia per evi-
tare eccessive sollecitazioni ai morsetti e utilizzare un pressacavo adeguato al tipo di cavo utilizzato. Il collegamento da
rete della centralina non necessita di conduttore di terra.
In Fig. 3 è illustrato un esempio di collegamento da rete 230Vac con la sirena ed elettrovalvola a riarmo manuale nor-
malmente chiusa.
In Fig. 4 è illustrato lo schema di collegamento da rete 230Vac con sirena ed elettrovalvola normalmente aperta.
In Fig. 5 è illustrato lo schema con la sirena ed Elettrovalvola a Riarmo Manuale Normalmente Chiusa con Sensore di
posizione per verificare sulla Centralina se la Valvola si è effettivamente chiusa.
In Fig. 6 è illustrato lo schema di collegamento con centralina, sirena ed elettrovalvola normalmente chiusa con ali-
mentazione a 12Vcc. (Utilizzando ad esempio un alimentatore esterno con batteria tampone tipo nostro PS180, in que-
sto caso è possibile collegare anche l’alimentazione da rete).
AVVERTENZE
La centralina non necessita di regolazioni dopo l'installazione.
La vita utile del sensore in aria pulita è mediamente 5 anni. Al termine di questo periodo è possibile sostituire il senso-
re e tarare lo strumento con gas campione presso il nostro laboratorio.
Importante: Il sensore catalitico funziona solo alla presenza d’Ossigeno. Non usare gas puri o l'accendino direttamente
sul sensore che potrebbe essere irrimediabilmente danneggiato.
Il segnalatore non è in grado di rivelare perdite che avvengono fuori del locale in cui è installato o all'interno dei muri o
sotto il pavimento.
ATTENZIONE: Considerare che in ambienti particolarmente inquinati o con vapori di sostanze infiammabili (in particolare
solventi), la vita utile del sensore può ridursi notevolmente. Alcune sostanze causano una riduzione permanente di sen-
sibilità. Evitare che il sensore venga a contatto con vapori di Silicone (presente in vernici e sigillanti), Tetraetile di Piombo
o Esteri fosfati. Altre sostanze causano una temporanea perdita di sensibilità. Questi “inibitori” sono gli Alogeni,
l’Idrogeno solforato, il Cloro, gli Idrocarburi clorurati (Trielina o Tetracloruro di carbonio). Dopo un breve tempo in aria pu-
lita, il sensore riprende il proprio funzionamento normale.
VERIFICA FUNZIONAMENTO
Verifiche Periodiche: Si consiglia di eseguire la verifica di funzionamento ogni 6-12 mesi in base all’utilizzo.
IMPORTANTE: La prova, deve essere eseguita con estrema attenzione e da personale autorizzato e addestrato, in
quanto vengono attivate le uscite (relè) provocando l’attivazione dei dispositivi d’allarme collegati. Durante il funziona-
mento normale, il pulsante "TEST" è sempre disattivato se è presente gas o se sono attivati il 1° e/o il 2° relé.
Verifica funzionamento elettrico della centralina, tenere premuto il pulsante "TEST" per circa 3 secondi, finchè non si
spengono tutti Led e si disattivano tutti i relé. A questo punto la barra Led si accenderà in sequenza, dal Led giallo al
quarto Led rosso. All’accensione dei vari Led corrisponde l’attivazione dei relativi relé (relé "FAULT" con il Led giallo, relé
"PREAL." con il secondo Led rosso, relé "ALARM" con il terzo Led rosso). Alla fine tutta la barra Led rimarrà accesa per
circa 5 secondi poi la centralina torna nelle condizioni di funzionamento normale. NOTA: durante il Test si possono veri-
ficare alcune condizioni:
Tutti i 5 Led sono accesi: SOLO quando alla centralina è collegato il filo di controllo presente in alcuni tipi d’elet-
trovalvole. In questo caso il test è riuscito correttamente.
Se il Led giallo si spegne (dopo i Led rossi): questo indica l’assenza del filo di controllo dell’elettrovalvola o che
l’elettrovalvola è chiusa. Se questo filo non è collegato alla centralina, il test è riuscito correttamente. In caso contrario
bisogna controllare lo stato dell’elettrovalvola e ripetere il test. Se il risultato del test non cambia, significa che ci sono dei
problemi elettrici. In tal caso, contattare il fornitore.
Se il terzo Led rosso si è spento: avviene SOLO quando alla centralina è collegato il filo di controllo presente in al-
cuni tipi di elettrovalvole. Il filo di controllo dell’elettrovalvola è interrotto o l’elettrovalvola è aperta. In questo caso control-
lare sia lo stato dell’elettrovalvola, sia il collegamento del filo di controllo e ripetere il test. Se questo filo non è collegato
alla centralina, controllare che il ponticello presente sul morsetto ‘AUX’ sia ben collegato e ripetere il test. Se la condizio-
ne persiste, significa che ci sono dei problemi elettrici. In tal caso, contattare il fornitore.
In tutti gli altri casi: Se ci sono dei Led che non si accendono o dei relé che non scattano, significa che la centralina è
guasta. In tal caso, sostituirla e/o inviarla al fornitore per la riparazione.
Verifica Funzionamento Sensore con Miscela di Gas Calibrato, le centraline sono tarate nel nostro laboratorio con
Gas Campioni, normalmente è sufficiente eseguire una verifica della taratura utilizzando bombole con miscela di Gas
al 25%LIE (Metano per la CTR137M e Butano per la CTR137G) e resto aria (20,9% O2), in quanto i sensori Catali-
tici non possono funzionare in assenza d’ossigeno.
DIS. 0534026 COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.4/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
Nota: La verifica della taratura va effettuata solo da personale addestrato e autorizzato. Nel caso i valori non siano quelli
richiesti contattare il nostro laboratorio.
La verifica della Taratura può essere fatta utilizzando il nostro kit TC011 (Vedi istruzioni fornite con il Kit), collegare la
bombola al portagomma del Flussometro, far affluire il gas (a circa 0,3 l/min), attendere circa 3 minuti e verificare che la
centralina sia in allarme come decritto nel capitolo “FUNZIONAMENTO”
GB
DESCRIPTION
The CTR137 is a central unit for wall installation, IP65, with a catalytic sensor for flammable gas. It is normally powered
at 230 AC and/or 12÷24Vdc/ac.
Two different models are available and the only difference is the calibration carried out with specific gas:
the CTR137M should be used with Methane plants.
the CTR137G should be used with LPG plants.
On the front plate the LED bar shows both the working condition and the gas concentration detected by the sensor. The
instrument is supplied with two alarm levels with sealed-type outputs relays and with tension-free change over contacts.
Furthermore it has an auxiliary outputs relays in positive security for FAULT situation and an auxiliary input (AUX) con-
nectable to our Manual NC Resetting valve with Positioning Sensor.
Fig. 1 shows a typical mains supply wiring diagram with alarm siren and normally closed solenoid valve.
OPERATIONAL DESCRIPTION
PREHEATING: when the central unit is supplied, the “yellow” LED starts to flash and it means the sensor is heating. Af-
ter 60 seconds, the “Green” Led switches on and it means the normal working.
NORMAL OPERATING: the central unit reads the gas concentration through the internal sensor
1st Red LED: it switch on if the gas concentration is higher than 5% LIE.
2nd Red LED: it switch on if the gas concentration is higher than 10% LEL; if within 4 seconds the gas is not reduced,
the “PREAL.”relay will activate.
This relay is normally used as a prealarm for the controlling of a siren
(SE301A).
3rd Red LED: it switch on if the gas concentration is higher than 20% LIE; if the gas persists, the 4th Red LED “STOP”
switches on within 30 seconds and the “ALARM” relay will activate. It is normally used to stop the gas through the man-
ual reset solenoid valve (NO or NC) and/or the interruption of the electrical energy.
If it has been installed a manual reset solenoid valve N.C. with magnetic sensor connected to “AUX” input, in the case that the
gas is still open, the yellow LED and the “FAULT “ Relay will activate (
see “FAULTS” section
).
RESET KEY: The alarm condition remains latched, LEDs and relays remain activated, even if the gas concentration is
reduced, because the mounted valve is closed. To reset the normal working conditions and/or switch off the siren push
the "RESET" button.
Buzzer the “PREAL.” relay will be deactivated and the Red Led flashes, only if the gas concentration is higher than
10% of LIE. After 20 seconds, both of them will return in preallarm. (the siren rings)
If it has been used a manual reset solenoid valve NC with the magnetic sensor and in the case that it is snapped, the
Yellow led will switch off and the “FAULT” relay will be deactivated. (See FAULTS section).
Alarm Reset The central unit will begin to the normal working, only if the gas concentration is lower than 10% LIE, the
“ALARM” relay will be deactivated and the 3rd and 4th Red LED will switch off. If activated, the “FAULTrelay will be de-
activated and the “Yellow” LED will switch off. (see FAULTS sections).
Warning: Pushing the RESET button, if the gas concentration is higher than F.S., it can happen that the first “PREAL.”
relay will be deactivated and the first three Red LEDs will switch off. The Yellow LED will illuminate and the “FAULT” re-
lay will activate. A fault on the sensor is most probable in this case. Eliminate the alarm’s cause, if the condition persist
pushing the RESET button, please consult the FAULTS section.
FAULTS: The central unit signal different kind of failures activating the Yellow LED and the FAULT relay. That is nor-
mally activated. The "FAULT" relay, if necessary, can be used both to signal remotely an occurred damage and to signal
the absence of power to the instrument.
Yellow and Green LEDs and FAULT relay activate: this happens when the catalytic sensor is not working. If this
condition do not change, it will be necessary to replace the unit or to send it to the supplier back to repair.
Yellow, Green, 4th Red LEDs and FAULT and ALARM relays activate: (only after press RESET key) this happens
when the catalytic sensor is not working or in few cases when there is a higher gas concentration. In this case the central
unit will remain in alarm, as described in the OPERATING>WARNING Section. If there are not any gas leaks and the condition
is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair.
Manual reset solenoid valve NC with magnetic sensor failure: this situation appears ONLY when is installed an
electro valve with magnetic sensor; if it not close the gas, the ALARM relay will activate (gas concentration higher than
20% LIE) and the magnetic sensor signals to the central unit the this bad working. In this case all led will be lighted and
relays will be activated. The failure condition (yellow led lighted and FAULT relay activated) will be cancelled if pressing
the RESET key, the solution of the problem will be visualized.
INSTALLATION
The CTR137 should be installed according to the national disposition in force on the matter.
Model CTR137M positioning: Methane (CH4) is a combustible gas lighter than air. Its density related to air is 0.55; its
LEL (Lower Explosion Limit) is 5% v/v (Volume). The instrument should be fixed at 30 cm from the ceiling and be placed
at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes.
DIS. 0534009a COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.5/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
Model CTR137G positioning: LPG is a gas mixture composed by 20-30% Propane (C3H8) and by 70-80% Butane
(C4H10). LPG calibration must be carried out with Butane which is a combustible gas heavier than air. Its density related
to air is 2; its LEL (Lower Explosion Limit) is 1.5%v/v (Volume). The instrument should be fixed at 30 cm. from the floor
and be placed at 1-1.5 meter from the gas appliance, far from the room corners or from ventilation intakes
Mounting: The Fig. 2 shows the instrument size. It should be wall-mounted by three screw anchors. The normally
closed manually resetting valve for the gas cut-off should be installed outside the room in a clearly indicated position
and should be protected from rain.
Electrical Connection: the instrument is supply with non reversible and plug-in terminals. Therefore the cables should
be anchored to the case in order to avoid terminal overstress. The connection to the central unit does not need any
hearting.
Fig. 3 shows the AC powering connection with alarm siren and normally closed manual resetting valve.
Fig. 4 shows the AC powering connection with alarm siren and normally open manual resetting valve.
Fig. 5 shows the AC powering connection with alarm siren and our normally closed manual resetting valve with posi-
tioning sensor to verify, if an alarm occurs, the really gas cut-off.
Fig. 5 shows the 12Vdc powering connection with both 12Vdc alarm siren and normally closed manual resetting valve
with, for example, our power supply unit PS175 with internal 12Vcc-7Ah battery to maintain the system powered on in
absence of Main power supply.
WARNING
The detector doesn't need adjustments after being installed.
Average life: the sensitive element used in this detector has an excellent stability in time. In fresh air and in normal
working condition the sensor's life is more than 5 years from the date of installation.
Important: Catalytic sensors can operate only in presence of Oxygen. Do not use pure gases or a lighter directly on the
sensor since they could damage it irremediably. The detector is not able to detect gas leaks occurring outside the room
where it is installed, neither inside walls nor under the floor.
Attention: please note that in polluted environments, where vapours of flammable agents, especially solvents, might be
present, the sensor's life can be reduced. Some substances cause a permanent reduction in sensitivity. Avoid contacts
of the sensor with vapours of Silicone compounds (paintings and sealing paste), Tetra-ethyl Lead and Phosphate esters.
Some other substances produce a temporary loss of sensitivity. These “inhibitors” include Hydrogen sulphide, Chlorine,
Chlorinated hydrocarbons and halogenated compounds. The sensitivity is recovered after a short period of running in
clear air.
FUNTIONAL TESTING
Periodical testing: we advise to carry out working tests every 6-12 months.
PAY ATTENTION: This procedure has to be made with extreme attention and by authorized and trained people; be-
cause starting this procedure it will start both Outputs (relays) causing the activation of connected alarm devices. The
“TEST” key is deactivating when an alarm condition occurs.
Instrument operation check: push the "TEST" button for 3 seconds until all Led and relays deactivates.
Then the LED will illuminate in sequence. With the LEDs the corresponding relays will activate (Yellow LED - FAULT re-
lay, 2nd red LED - PREAL. Relay and 3rd red LED - ALARM relay). After 5 seconds the instrument returns to normal
working condition. NOTE: during the Test some conditions occur:
All 5 LEDs illuminates: ONLY when the central unit is connected with a control wire for certain types of valves. In this
case the test results correct
Yellow LED off (after red LEDs): indicates the lack of control wire of the valve or that the valve is closed. If this wire is
disconnected from the central unit the test results correct, if not please check the valve and repeat test. If test result is
unchanged, electrical problems are in place, please contact the supplier.
The 3rd Red LED off: ONLY when the central unit is connected with a control wire for certain types of valves. The con-
trol wire is disconnected or the valve is open. In this case please check both the valve status and the wire connection
and repeat the test. If wire is disconnected, check the bridge on the terminal “AUX” that has to be connected and repeat
the test.
All other cases: If some leds do not light on or some relays do not switch, the central unit is damaged. In this case
please replace it or send it back to the supplier.
Calibration testing with gas mixture: the calibration is carried out with specific gas in our laboratory. We advise to
check the calibration only using sample gas bottles with a mixture abut 25%LEL Gas in Air (20.9% Oxygen) (Gas
Methane for CTR137M and Butane for CTR137G). Catalytic sensors cannot work without Oxygen.
Note: The calibration routine is to be carried out by trained or authorised personnel only. In case the values are not the
required ones please apply to our Laboratory.
The calibration testing should be done with Calibration Kit model TC011 (See specific user’s manual). Connect the sam-
ple gas bottle to the flow meter, open Gas (0,3 l/min flow rate), wait for 3 minutes and check that the instrument activate
Alarms as shown in chapter “OPERATIONAL DESCRIPTION”.
F DESCRIPTION
Le CTR137 est une centrale de détection de gaz pour montage aux murs. Utilise un capteur de type catalytique pour gaz
inflammables. Elle est alimentée en 230Vca ou 12÷24Vcc/ca et l'indice de protection de la centrale est IP65. Le CTR137
DIS. 0534026 COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.6/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
est fabriqué en deux versions que présentent les mêmes caractéristiques; la seule différence est constituée par
l’étalonnage qui est effectué avec du gaz spécifique.
la version CTR137M qui doit être utilisée avec des installations alimentée en gaz méthane.
la version CTR137G qui doit être utilisée avec des installations alimentée en GPL.
Sur la face avant de la centrale l'on distingue le barregraphe indiquant l'état de fonctionnement ainsi que la concentration
de gaz détectée par le capteur. L'appareil est doté de 2 seuils d'alarme avec sorties sur relais de type étanche avec
contacts inverseurs libres de tension et une sortie sur relais pou dérangement functionnant normalement excités (sécuri-
positive) et une entrée auxiliaire (AUX)pour nos vannes de sécurité NF à réarmement manuel avec senseur de fin de
course.
En figure1, un exemple de raccordement sur secteur avec sirène d'alarme et électrovanne normalement fermée.
FONCTIONNEMENT
Préchauffage: Lorsque la centrale est alimentée, le capteur a besoin d’un temps de préchauffage d’environ 60 se-
condes pour être opérationnel signalé par le led jaune clignotant. Après ce temps le led s’étende et le led vert “ON”
s’allume pour indiquer le fonctionnement.
Fonctionnement normale: l’appareil lit la concentration de gaz par le capteur incorporé.
La 1ème LED rouge s’allume lorsque la concentration de gaz rejoint 5% de la LIE.
La 2ème LED rouge s’allume lorsque la concentration de gaz rejoint 10% de la LIE, si la concentration de gaz ne basse
pas dans 4 seconds, le 1er relais PREAL intervient en se excitant. Ce seuil est habituellement utilisé comme pré alarme
pour commander une sirène (SE301A).
La 3ème LED rouge s’allume si la concentration augmente jusqu'à rejoindre 20% de la LIE, et après une temporisation
de 30 secondes la 4éme LED rouge STOP s'allume et le relais ALARM intervient en se excitant. Ce seuil commande la
coupure du Gaz avec l'électrovanne normalement fermée et/ou la coupure de l'énergie électrique. Si une vanne NF avec
senseur de fin de course est installé sue l’entrée “AUX”, dans le cas de fuite de gaz, la LED jaune, s’allume et le relais
“ Dérangement ” interviens. (voir sect. “ Dérangement ”)
Le bouton RESET:
Dans les conditions d’alarme, le barregraphe restera illuminé et les relais intervient en se désexcitant
jusqu'à ce que l'on ait remédié aux causes de l'alarme et armé ensuite le dispositif par action manuelle sur le bouton
“RESET”
Cette action ne sera possible que si la centrale à ce moment ne détecte pas de présence gazeuse.
Arrêt de la Sirène d'alarme: si la concentration de gaz est supérieure 10% de la LIE la relais “PREAL”, serait désac-
tivée et le deuxième Led rouge clignote. Apres 20 seconds les deux revient in prealarme (la sirène sonne). Si la vanne
NF à réarmement manuel avec senseur de fin de course a été utilisée et dans ce cas elle est activée, la led jaune
s’étende et le relais Dérangement ” se désactive. (voir section relais “ Dérangement ”).
Réarmement après une d’alarme: La centrale revient au fonctionnement normal si la concentration de gaz est infé-
rieure 10% de la LIE . Le relais “ALARME” sera désactivé le et led rouge s’étendent. Si le relais Dérangement
est activé, il vient désactivé et le led jaune s’étende. (voir section relais “ Dérangement ”).
Attention: Apres avoir appuyé le bouton “RESET” dans le cas que la concentration de gaz est supérieur au F.S., le 1°
relais “PREAL” sera désactivé et les premiers trois led rouge s’étendent. La led jaune s’allume et le relais Dérange-
ment intervient. Dans ce cas c’est probable que le détecteur est en panne. Si en éliminant la cause d’alarme et ap-
puyant le bouton “RESET”, la condition persiste, consultez la section “Dérangement ”.
Dérangement: la centrale signale divers tipes des rangements avec l’allumage de la led jaune et l’activation du relais
Dérangement qui est normalement excité avec contacts en échange sans tension. Sur demande il peut être utilisé
pour signaler à distance la condition de dérangement et/ou la manque de alimentation.
Les LED jaune, verte allumé et le relais “Dérangementactivé : en cas de détérioration du capteur, si la situation
continue, il faut remplacer la centrale et la renvoyer au producteur pour réparation.
Les LED jaune, verte et le 4éme rouge allumés et les relais “Dérangement” et ALARM activé: (seulement après
avoir appuyé le bouton “RESET”) en cas de détérioration du capteur ou bien dans de rares cas de haute concentration
de gaz. La centrale reste en alarme comme décrite dans la partie FONCTIONNEMENT ATTENTION: Si la situation
continue sans fuites de gaz, il faut remplacer la centrale et la renvoyer au producteur pour réparation.
Dérangement de l’électrovanne de sécurité à réarmement manuel N.F. avec senseur de fin de course: Cette
peut ce vérifier SEULEMENT si une vanne avec senseur de fin de course est installé. Si elle ne ferme pas le gaz à
l’activation du relais ALARM (concentration de gaz plus de 20% de LIE) le senseur de fin de course signale à la cen-
trale le dérangement Dans ce cas tous les led seront allumés et actifs. La condition de dérangement (led jaune “Déran-
gement” allumé et relais “Dérangementactive) sera annulée si, en appuyant le bouton “RESET”, le problème est réso-
lue (électrovanne fermée). Si, par contre, en appuyant le bouton “RESET”, l’alarme rentre (concentration de gaz moins
que 10% du LIE) La condition de dérangement sera annulée dans tous les cas. Nous conseillons de vérifier le blocage
de l’électrovanne et que les câbles de connexion ne soit interrompues.
INSTALLATION
La centrale doit être installée dans le respect des normes particulières à chaque pays.
Positionnement du modèle CTR137M: le méthane (CH4) est un gaz plus léger que l’air. Sa densité par rapport à l’air
est 0,55, sa LIE (limite inférieure d’explosivité) est de 5% v/v (%volume).
Le détecteur doit être installé à une hauteur de 30 centimètres du plafond et à la distance de 1÷1,5 mètres de l’appareil
alimenté en, à l’écart des angles de la pièce et des prises de ventilation.
Positionnement du modèle CTR137G: le GPL est formé d’un mélange composé de 20 à 30 % pour le propane et de
80 à 70 % de butane (C4H10). L’étalonnage est effectué avec du isobutane, qui est un gaz combustible plus lourd que
l’air. Sa densité par rapport à l’air est 2, sa LIE (limite inférieure d’explosivité) est de 1,8%v/v (%volume). Le détecteur
DIS. 0534009a COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.7/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
doit être installé à une hauteur de 30 centimètres du plafond et à la distance de 1÷1,5 mètres de l’appareil alimenté en, à
l’écart des angles de la pièce et des prises de ventilation.
Fixation: En figure 2 sont indiquées les dimensions de la centrale. La fixation s'effectue par des 3 vis et chevilles.
Raccordements électriques: Les bornes sont de type débrochage et il est conseillé de fixer les câbles dans le boîtier
afin d'éviter une excessive tension mécanique sur les bornes. L'électrovanne à réarmement manuel n.f. doit être instal-
lée à l'extérieur du local, clairement signalé et protégé de la pluie et des projections de liquide.
En figure 3 est illustré le schéma de raccordement sur secteur 230Vca, d'un dispositif avec sirène et électrovanne
normalement fermée.
En figure 4 est illustré le schéma de raccordement sur secteur 230Vca, d'un dispositif avec sirène et électrovanne
normalement ouverte.
En figure 5 est illustré le schéma de raccordement sur secteur 230Vca, d'un dispositif avec sirène et de sécurité à ré-
armement manuel normalement fermée avec senseur de positionne pour vérifier à la centrale si l’électrovanne est effec-
tivement fermée.
En figure 6 est illustré le schéma de raccordement sur 12Vcc, d'un dispositif avec sirène et électrovanne normalement
fermée (en utilisant par exemple un module d’alimentation extérieur comme le notre PS180). Dans ce cas on peut
connecter l’alimentation du réseau électrique.
AVVERTISSEMENT
La centrale ne nécessite aucun réglage après son installation
Vie moyenne: ce capteur a une excellente stabilité dans le temps. En condition de fonctionnement normale, en air non
pollué la vie utile du capteur est supérieure de 5 ans à partir de la date de mise sous tension.
Attention: Les capteurs à combustion catalytique fonctionnent seulement en présence d’Oxygène. Eviter l'usage de gaz
pur ou du briquet sur le capteur, qui pourrait être irrémédiablement endommagé.
L’appareil n’est pas en mesure d’identifier des fuites qui se vérifient au dehors de la pièce il a été installé ainsi que
des fuites qui se vérifient dans les murs ou bien au-dessous du sol.
Attention: Eviter que le capteur vienne au contact de vapeurs de silicone, plomb tétraéthyle ou hydrocarbures chlorés,
ces substances pouvant en réduire irréversiblement la sensibilité. Le contact occasionnel avec des solvants type trichlo-
réthylène ou tétrachlorure de carbone peuvent inhiber temporairement le capteur. Après un bref temps en air pur le cap-
teur reprend son fonctionnement normal.
VERIFICATIONS PERIODIQUES
Vérification périodique: il est conseillé d'effectuer une vérification de fonctionnement tous les 6/12 mois.
ATTENTION : cette procédure doit être exécutée avec une extrême attention, par un personnel autorisé et compétent,
car elle entraîne l’activation des sorties à relais et des asservissements en dépendant. Pendant le functionement normal
le bouton “TEST” est désactivé en présence de gaz ou si les relais 1er o 2nd sont activés.
Pour vérifier le fonctionnement de la centrale: appuyer sur le bouton “TEST” pour 3 seconds, jusqu’à tous les Led
s’éteint et tous les relais se désactivent, la barre graphe s'illuminera en séquence à partir de led jaune jusqu’a quatrième
led rouge. L’allumage des led corresponde à l’activation des relais (relais “Dérangement” avec led jaune, relais PREAL
avec 2nd led rouge, relais ALARMavec troisième led rouge). Enfin toute la barre graphe restera allumée pour 5 se-
condes a pue prêt, après ce la centrale reviens dans le conditions de fonctionnement normal. NOTA pendant le test
nous pouvons avoir les conditions suivantes :
Tous les 5 Led sont allumés: seulement quand à la centrale est connecté le fil de contrôle de certains typologies
d’électrovannes. Dans ce cas le test est réussit correctement.
Si le Led jaune s’éteint (après les led rouge): Indique l’absence du fil de contrôle de l’électrovanne ou bien que
l’électrovanne est fermé. Si ce fil n’est pas connecté à la centrale le test est réussit correctement. Dans le cas contraire il
faut contrôler la condition de l’électrovanne et répéter le test. Si le résultat ne change pas, il y a des problèmes électri-
ques. Dans ce cas contacter le fournisseur.
Si le troisième led rouge s’éteint: ceci est seulement dans le cas de la centrale avec le fil de contrôle de certains ty-
pologies d’électrovannes. Le fil de contrôle le l’électrovanne est coupé ou l’électrovanne est ouverte. Dans ce cas vérifier
l’état de l’électrovanne et la connexion du fil de contrôle et répétez le test. Si le fil n’est pas connecté, vérifier que le pont
de la connexion AUX” soit bien connecté et répéter le test.
Dans tous les autres cas: Si il y a des Led qui ne s’allument pas ou des relais qui ne s’activent pas, la centrale est en
panne, la remplacer ou la renvoyer au fournisseur.
Pour vérifier l’étalonnage de la centrale: toutes les centrales sont étalonnées dans nos laboratoires avec Gaz Echan-
tillons, normalement ce suffit de vérifier l’étalonnage avec de bouteilles de mixture de gaz à 25% du LIE (Gaz naturel
pour le CTR137M e LPG pour le CTR137G) et le reste air (20.9% O2) vue que le senseurs catalytiques ne mar-
chent pas sans la présence d’oxygène.
Attention: L'étalonnage doit être effectué seulement par le personnel autorisé. Dans le cas les valeurs ne sont pas
correctes, veuillez prendre contacts avec notre Laboratoire.
Raccorder la bouteille au débitmètre faire débiter le gaz (0,3 l/min), attendre 3 minutes et vérifier que la centrale soit en
Alarme comme décrit dans le chapitre FONCIONNEMENT”
DIS. 0534026 COD. 27102280 Istruzione / User’s Manual / Manuel d’utilisation Pag.8/8
GECA Srl Via E. Fermi 98, 25064 Gussago (Brescia) Italy http://www.gecasrl.it Tel:+39 030/3730218 Fax: +39 030/3730228
VALVOLA
VALVE
230Vac
GUASTO
FAULT / DE RANGE ME NT
SE301A
SIRENA
/
Fig.1 Esempio di inst allazione della centralina CTR137
CTR1 37 installation diagram / Schéma dinstallation du détecteur CTR137
AUSILIARIO
/ AUX / AUXILIAIRE
SEGNALATORE GAS
GAS DE TECTOR
DETECTEUR DE GAZ
SENSORE
SE NSOR / CA PTEUR
160
115
80
Fig. 2 Dimensioni / Size / Dimensions
Fig. 3 Collegamento con valvola a riarmo manuale Norm.Chiusa
Wiring diagram with a normally closed manual resetting valve
Schéma avec vanne à réarmement manuel norm.fermée
230Vca
NC
C NA
NC
C NA
NC
C NA
L
N
SE301A
PREAL.
ALARM
Valvola NC
FAULT
AUX
Fig.
4
Collegamento con valvola a riarmo manuale Norm.
Aperta
Wiring diagram with a normally open manual resetting valve
Schéma avec vanne à réarmement manuel norm.ouverte
230Vca
NC
C NA
NC
C NA
NC
C NA
L
N
SE301A
PREAL.
ALARM
Valvola NA
FAULT
AUX
Fig. 5 Collegamento con valvola a riarmo manuale Norm.Chiusa
Wiring diagram with a normally closed manual resetting valve
Schéma avec vanne à réarmement manuel norm.fermée
230Vca
NC
C NA
NC
C NA
NC
C NA
L
N
SE301A
PREAL.
ALARM
EV GAS GAS N.C.
FAULT
AUX
+
++
+
-
--
-
Fig. 6 Collegamento 12Vcc con valvola a riarmo man. Norm.Chiusa
12Vdc Wiring diagram with a normally closed manual resetting
valve
Sch
éma à 12Vcc avec vanne à réarmement manuel norm.
fermée
NC
C NA
NC
C NA
NC
C NA
L
N
- +
SE301B (12Vdc)
PREAL.
ALARM
EV GAS GAS N.C. (12Vdc)
FAULT
AUX
230Vca
PS180
2,5A / 7Ah
12Vdc
230Vca
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

EPH Controls CTR137NG Mode d'emploi

Taper
Mode d'emploi
Ce manuel convient également à