Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual

Ce manuel convient également à

GHG 410 7003 P0001 D/E/F (I)
CROUSE-HINDS
SERIES
Explosionsgeschützte Steuergeräte für Schalttafeleinbau
GHG 418
Explosion-protected control units for panel mounting
GHG 418
Boites de commande pour montage sur tableau de distribution
GHG 418 pour atmospres explosives
Betriebsanleitung
Operating instructions
Mode d’emploi
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
2
Explosionsgeschützte
Steuergeräte GHG 418
Inhalt: Contents: Contenu:
Explosion-protected
control units GHG 418
Boites de commande GHG 418
pour atmosphères explosives
Inhalt ........................... ...................... 2
Maßbilder .............. ........... ................ 3
Anschlussbilder ............. ............ ....... 4
1 Technische Angaben ....... ............ ..... 3
1.1 Komplette Steuergeräte .... ........... .... 3
1.2 Drucktaster + Schalter ........ ............ . 4
1.3 Signallampe ..................... ........... ...... 4
1.4 Potentiometer ................ .......... ........ 4
2 Legende......... .............................. ..... 5
2.1 Sicherheitshinweise ......... ........... ..... 5
3 Normenkonformität ........ ........... ....... 5
4 Verwendungsbereich ... ............ ........ 5
5 Verwendung/Eigenschaften .............. 5
6 Installation ................ .......... .............. 6
6.1 Montage .................... ........... ............ 6
6.2 Öffnen des Gerätes/
Elektrischer Anschluss ...................... 7
6.3 Kabel- und Leitungseinführung;
Verschlussstopfen....................... ...... 7
6.4 Schließen des Gerätes ..... ........... .... 7
6.5 Inbetriebnahme ............. ........... ........ 7
7 Instandhaltung / Wartung ... ............ .. 7
8 Reparatur / Instandsetzung/
Änderungen ....... ........................... .... 7
9 Entsorgung / Wiederverwertung ...... . 7
Konformitätserklärung
separat beigelegt
Contents ........ ........... ........................ 2
Dimensional drawings ............ .......... 8
Contact arrangement ............ ........... 9
1 Technical Data ....................... ........... 8
1.1 Complete control units ......... ........... . 8
1.2 Push- button and switch ...... ............ 9
1.3 Signal lamp ........................... ........... . 9
1.4 Potentiometer ....................... .......... . 9
2 Principles................ .......................... 10
2.1 Safety instructions ................ ........... 10
3 Conformity with standards ... ........... 10
4 Field of application ................ .......... 10
5 Application/ Properties ......... ........... 10
6 Installation ............................ ........... 11
6.1 Mounting .............................. ......... .. 11
6.2 Opening apparatus /
Electrical connection ............ ........... 12
6.3 Cable entry (KLE);
blanking plug ........................ ........... 12
6.4 Closing apparatus ................ ............12
6.5 Putting into operation ........... ........... 12
7 Maintenance/Servicing ......... ........... 12
8 Repairs/Modifications .......... ............12
9 Disposal/Recycling ............... ...........12
Declaration of conformity,
enclosed separately.
Contenu ..... ........... ............................ 2
Plans cotés ............ .......................... 13
Schéma des conexions ..... .............. 14
1 Caractéristiques techniques............. 13
1.1 Boites de commande complètes .... 13
1.2 Bouton-poussoir et interrupteur ...... 14
1.3 Lampe de signalisation .................... 14
1.4 Potentiomètre ....................... .......... 14
2 Légende ......... .................................15
2.1 Consignes de sécurité ......... ............15
3 Conformité avec les normes ........... 15
4 Domaine d’utilisation ............. .......... 15
5 Utilisation/Propriétés ............ ........... 15
6 Installation ............................ ........... 16
6.1 Montage ............................... ........... 16
6.2 Ouverture de la boîte /
Raccordement électrique ..... ........... 17
6.3 Entrées de câble (KLE)
bouchons de fermeture ........ ........... 17
6.4 Fermeture de la boîte /
Fermeture du couvercle ....... ...........17
6.5 Mise en service .................... ...........17
7 Maintien/Entretien ................. .......... 17
8 Réparation/Remise en état ............... 17
9 Évacuation des déchets/Recyclage .. 17
Déclaration de conformité,
jointe séparément.
3
Explosionsgeschützte Steuergeräte GHG 418
D
1 Technische Angaben
1.1 Steuergeräte mit Schutzhaube
ATEX EG-Baumusterprüfbescheinigung: PTB 99 ATEX 1034
Gerätekennzeichnung nach 2014/34/EU und
Norm: EN 60079-0
D
II 2 G Ex d e IIC T6
Bemessungsspannung: bis max.500 V
Bemessungsstrom:
max. 16 A
Umgebungstemperaturbereich:
(Abweichende Temperaturen sind bei Sonderversionen möglich)
-20 °C ... +40 °C
Zul. Lagertemperatur in Originalverpackung: -20 °C ... +40 °C
Schutzart nach EN/IEC 60529: IP 66 (mit Schutzkappe)
Schutzklasse nach EN/IEC 61140: I - wird von den Geräten erfüllt.
Anschlussklemmen: siehe Einbaukomponenten
Leitungseinführung: (Ø 7 - 15 mm)
Gewicht:
Schutzkappe
ca. 0,05 kg
Prüfdrehmomente:
Anschlussklemmen: 2,50 Nm
Druckschraube der Kabeleinführung
3,50 Nm
Selbstschneidende Schrauben (Zugentlastung)
2,00 Nm
EU-Baumusterprüfbescheinigung: IBExU14ATEX1030U
Gerätekennzeichnung nach 2014/34/EU
und der Normenreihe EN 60079:
II 2 G Ex db eb IIC/IIB/IIB+H2 Gb
I M 2 Ex db eb I Mb
IECEx Konformitätsbescheinigung: IECEx IBE 14.0005U
Gerätekennzeichnung
der Normenreihe IEC 60079: Ex db eb IIC/IIB/IIB+H2 Gb
Ex db eb I Mb
Betriebstemperaturbereich:
II 2 G ... IIC
-55 °C ... +80 °C
II 2 G ... IIB
-60 °C ... +80 °C
II 2 G ... IIB+H2
-55 °C ... +80 °C
Lagertemperatur in Originalverpackung: -60 °C ... +80 °C
Bemessungsspannung: bis max. 500 V
Bemessungsstrom
maximal
Bemessungsan-
schlusssquerschnitt
Umgebungstemperatur
maximal
14 A 2,5 mm² 40 °C
16 A 4,0 mm² starr 40 °C
12 A 2,5 mm² 50 °C
15 A 4,0 mm² starr 50 °C
Schaltvermögen AC 15 (EN 60947-5-1): 250 V / 6 A 500 V / 4,0 A
Schaltvermögen DC 13 (EN 60947-5-1): 24 V / 6 A 60 V / 0,8 A 110 V / 0,5 A
mit Goldspitzkontakten: max. 400 mA
Anschlussklemmen: 2 x 1,0 - 2,5 mm²;
1 x 4,0 mm² starr
Prüfdrehmoment Anschlussklemmen: 2,5 Nm
Gewicht: 2 polig ca. 0,15 kg
4 polig ca. 0,35 kg
1.2 Drucktaster und Schalter GHG 418 11..R....
4
Gerätekennzeichnung nach 2014/34/EU
und Norm:
D II 2 G
Ex d e IIC/IIB Gb
D I M2
Ex d e I Mb
EG-Baumusterprüfbescheinigung:
IBExU14ATEX1030U
Bemessungsspannung: bis max. 250 V
Leistung: 1 W
Drehbereich:
270°
Skalierung:
0 - 100%
Anschlussklemme:
2 x 1,0 - 2,5mm²
Gewicht:
ca. 0,15 kg
EG-Baumusterprüfbescheinigung: IBExU 12ATEX 1047 U
Gerätekennzeichnung nach 2014/34/EU
und der Normenreihe EN 60079:
II 2 G Ex db eb IIC Gb
II 2 G Ex db ia IIC Gb
IECEx Konformitätsbescheinigung: IECEx IBE 13.0031U
Gerätekennzeichnung
der Normenreihe IEC 60079: Ex db eb IIC Gb
Ex db ia IIC Gb
Einsatztemperaturbereich: -55 °C ... +80 °C
Max. Betriebstemperaturbereich: +80 °C
(Abweichende Temperaturen sind bei Sonderversionen möglich)
Lagertemperatur in Originalverpackung: -55 °C ... +80 °C
Bemessungsspannung/Bemessungsstrom:
"e" erhöhte Sicherheit (Ex db eb) 20 V ... 254 V AC/DC 4 ... 15 mA
"e" erhöhte Sicherheit (Ex db eb) 12 V ... 24 V AC/DC max. 24 mA
"i" eigensichere Ausführung (Ex db ia) 10 V ... 30 V DC max. 38,7 mA
Ex-i Daten: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Anschlussklemmen: 2 x 1,0 - 2,5 mm²; 1 x 4,0 mm² starr
Prüfdrehmoment Anschlussklemmen 2,5 Nm
Gewicht: ca. 0,15 kg
1.3 Signallampe GHG 418 1806
1.4 Potentiometer GHG 418 16..R....
Explosionsgeschützte Steuergeräte GHG 418
D
2 Legende
Achtung
Dieses Symbol warnt vor einem möglichen Ausfall. Wird diese Warnung nicht beobachtet
kann der Gesammtausfall der Vorrichtung oder des Systems oder des Betriebes erfolgen, an
die es angeschlossen wird.
X
ATEX - IEC
Besondere Bedingungen
Dieses Symbol weißt auf Hinweise zum sicheren Betrieb gemäß EU-Baumusterprüfbescheinigung /
IECEx-Konformitätsbescheinigung hin.
2.1 Sicherheitshinweise
Zielgruppe:
Elektrofachkräfte und geeignet qualifizierte, unterwiesene Personen gemäß den
nationalen Rechtsvorschriften, einschließlich der einschlägigen Normen für
elektrische Geräte in explosionsgefährdeten Bereichen (EN/IEC 60079-14).
Die Steuergeräte GHG 418 für Schalttafeleinbau sind nicht für Zone 0 geeignet.
Die auf den Steuergeräten angegebene Temperaturklasse und Explosionsgruppe ist zu
beachten.
Umbauten oder Veränderungen an den Steuergeräten sind nicht gestattet.
Sie sind bestimmungsgemäß in unbeschädigtem und einwandfreiem Zustand zu betreiben.
Vor Inbetriebnahme müssen die Steuergeräte entsprechend der im Abschnitt 6 genannten
Anweisung geprüft werden.
5
Alle Fremdkörper müssen vor der ersten Inbetriebnahme aus den
Steuergeräten entfernt werden.
Geräte ohne Schutzkappe dürfen nur in zugelassene bzw. bescheinig-
te Gehäuse, Pulte oder Schaltschränke eingebaut werden.
Beachten Sie die nationalen Sicherheits- und Unfallverhütungsvor-
schriften und die nachfolgenden Sicherheitshinweise in dieser
Betriebsanleitung, die wie dieser Text in Kursivschrift gefasst sind!
3 Normenkonformität
Das Betriebsmittel entspricht den aufgeführten Normen, in der separat
beigelegten Konformitätserklärung.
Verweise auf Normen und Richtlinien in dieser Betriebsanleitung beziehen
sich immer auf die aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die Steuergeräte sind zum Einsatz in explosionsgefährdeten Bereichen
der
Zonen 1, 2 gemäß EN/IEC 60079-10-1 geeignet!
Die eingesetzten Gehäusematerialien einschließlich der außenliegenden
Metallteile bestehen aus hochwertigen Werkstoffen, die einen anwen-
dungsgerechten Korrosionsschutz und Chemikalienresistenz in "normaler
Industrieatmosphäre" gewährleisten:
- schlagfestes Polyamid
Bei einem Einsatz in extrem aggressiver Atmosphäre, können Sie
zusätzliche Informationen über die Chemikalienbeständigkeit der
eingesetzten Kunststoffe, bei Ihrer zuständigen Cooper Crouse-Hinds
Niederlassung erfragen.
5 Verwendung/Eigenschaften
Die Steuergeräte GHG 418 dienen zur Vor-Ort-Steuerung elektrischer
Anlagen in explosionsgefährdeten Bereichen. Diese Gerätekomponenten
werden, abhängig vom Einzelfall, in Schaltschränke, Pulte und Maschinen
eingebaut.
X
ATEX - IEC
Die Einbaukomponenten müssen bei der Verwendung in explosions-
gefährdeten Bereichen in geeignete, gesondert geprüft und bescheinigtes
Ex-e Gehäuse eingebaut werden.
X
ATEX - IEC
Die Luft- und Kriechstrecken gemäß EN/IEC 60079-7, Tabelle 1 sind
einzuhalten.
X
ATEX - IEC
Der Einbau des Drucktastersockels GHG41 in Betriebsmittel der
Kategorie 2G und M2 muss gesondert geprüft und bestätigt werden.
Dabei sind unter anderem die thermische Parameter zu überprüfen.
Die Ausführung mit Goldspitzkontakten ist für die Schaltung von Klein-
spannungsstromkreisen geeignet. Maximale Strombelastung beachten,
siehe Seite 3 , technische Daten). Die Ausführung mit Goldkontakten ist
mit "G" auf den Sockeln gekennzeichnet.
Um eine sichere Trennung der Taster- und Schalterkontakte zu gewährleis-
ten, sind die Öffnerkontakte als Zwangsöffner ausgeführt.
Die Sockel sind je nach Bedarf auch mit 0,6 W Widerständen, Feinsiche-
rungen und Dioden bestückt (max. Verlustleistung 1W).
Die Kleinsteuerschalter können durch Ausschneiden des Schaltkragens an
der jeweiligen Abschließposition über ein Vorhängeschloss abgeschlossen
werden ( Ø Schlossbügel bis 5 mm).
X
ATEX - IEC
Der Einbau der Signalleuchte GHG417 1805 in Betriebsmittel der
Kategorie 2G muss gesondert geprüft und bestätigt werden. Dabei sind
unter anderem die thermische Parameter zu überprüfen. Die Betriebstem-
peratur darf 68 °C nicht übersteigen.
Die Geräteausführung ohne Schutzkappe ist "teilbescheinigt" und
darf nur in dafür bescheinigten Ex-e Schutzgehäusen eingebaut und
betrieben werden.
Die Geräteausführung mit Schutzkappe ist komplett bescheinigt und kann
somit direkt betrieben werden.
Unzulässig hohe mechanische Beanspruchung der Schutzkappe
vermeiden - Gefährdung des Explosionsschutzes.
Angaben aus Punkt 3 und 4 sind bei der Verwendung zu
berücksichtigen.
Andere als die beschriebenen Anwendungen sind ohne schriftliche
Erklärung der Fa. COOPER CROUSE-HINDS / EATONnicht zulässig.
Beim Betrieb sind die in der Betriebsanleitung unter Punkt 7 genannten
Anweisungen zu beachten.
Die Verantwortung hinsichtlich bestimmungsgemäßer Verwendung
dieser Steuergeräte unter Bezugnahme der in dieser Anleitung
vorhandenen Rahmenbedingungen (siehe technische Daten) liegt
allein beim Betreiber.
6 Installation
Für das Errichten / Betreiben sind die relevanten nationalen Vorschriften
sowie die allgemein anerkannten Regeln der Technik maßgebend
(IEC/EN 600079-14).
Unsachgemäße Installation der Steuergeräte können zum Verlust
der Garantie führen.
6.1 Montage / Demontage
Die Montage der Schalttafeleinbaukomponenten erfolgt gemäß den
Bildern 1 - 4, Seite 13, wie nachfolgend beschrieben:
1 Das Bedien- oder Anzeigeelement Pos. 4, wird von vorne in die
Bohrung (Ø 30,3mm) der Schalttafel oder des Gehäuses mit einer
Maximalwandstärke von 5mm, eingesetzt.
Dabei ist auf den korrekten Sitz der Dichtung Pos. 5, und des
Elementes zu achten (Positioniernase am Element muss in die
Aussparung passen, siehe Maßbild Seite 12).
2 Die Kontermutter Pos. 3, ist mit dem Montagewerkzeug Pos. 12
(Zubehör Bestellnummer GHG4101914R0001), fest anzuziehen.
Bei übermäßigem Anziehen können die Bedienelemente beschädigt
werden.
3 Die Ex-d Komponente Pos. 1, wird auf das Bedienelement Pos. 4,
aufgesteckt und mit dem Haltebügel Pos. 2, verriegelt.
Die minimalen Abstände der Bedienelemente sind zu beachten
(siehe Maßbild).
Die teilbescheinigten Einbaukomponenten können durch nachrüsten mit
der Schutzkappe Pos. 7, optional wie unter Punkt 5 beschrieben, zu
komplett bescheinigten Einbaugeräten vervollständigt werden.
Hierzu muss zuvor der Berührungsschutz der Anschlussklemmen entfernt
werden.
Die Montage der Schutzkappe erfolgt wie nachfolgend beschrieben:
4 Die Druckschraube mit der Dichtung Pos. 8, von der Schutzkappe
Pos. 7, entfernen und die Dichtringe entsprechend dem Kabelquer-
schnitt anpassen.
5 Das Kabel Pos. 9, durch die Druckschraube mit Kabeldichtung Pos. 8,
der Dichtung Pos. 6, und der Schutzkappe Pos. 7, schieben.
6 Das Kabel anschließen.
Die Zugentlastung Pos. 1, mit den Schrauben Pos. 11, am Kabel
befestigen und in die Führungsnuten Pos. 15a und 15b, der Kompo-
nente Pos. 1, einrasten (siehe Bild 3).
Explosionsgeschützte Steuergeräte GHG 418
D
6
7 Instandhaltung / Wartung
Die für die Wartung / Instandhaltung von elektrischen Betriebsmitteln
in explosionsgefährdeten Bereichen geltenden nationalen Bestim-
mungen sind einzuhalten
(EN/IEC 60 079-17).
Vor Öffnen des Gehäuses Spannungsfreiheit sicherstellen bzw.
geeignete Schutzmaßnahmen ergreifen.
Die erforderlichen Wartungsintervalle sind anwendungsspezifisch und
daher in Abhängigkeit von den Einsatzbedingungen vom Betreiber
festzulegen.Im Rahmen der Wartung sind vor allem die Teile, von denen
die Zündschutzart abhängt, zu prüfen (z.B. Unversehrtheit der druckfesten
Komponenten, des Gehäuses, der Dichtungen und der Kabeleinführung),
sowie die Schaltwerksfunktion.
Sollte bei einer Wartung festgestellt werden, dass Instandsetzungsarbei-
ten erforderlich sind, ist Abschnitt 8 dieser Betriebsanleitung zu beachten.
8 Reparatur / Instandsetzung / Änderung
Instandsetzungsarbeiten / Reparaturen dürfen nur mit COOPER CROUSE-
HINDS / EATONOriginalersatzteilen vorgenommen werden.
Bei Schäden an der druckfesten Kapselung ist nur ein Austausch
zulässig. Im Zweifelsfalle ist das betroffene Betriebsmittel an
COOPER CROUSE-HINDS / EATONzur Reparatur zurückzugeben.
Reparaturen, die den Explosionsschutz betreffen, dürfen nur von
COOPER CROUSE-HINDS / EATONoder einer qualifizierten Elektro-
fachkraft in Übereinstimmung mit national geltenden Regeln
durchgeführt werden (EN/IEC 60 079-19).
Umbauten oder Änderungen am Betriebsmittel sind nicht gestattet.
Bei Austausch einzelner Einbaukomponenten (Taster usw.) ist Pkt. 6.2
"Öffnen des Gerätes /Elektrischer Anschluss" zu beachten.
9 Entsorgung / Wiederverwertung
Bei der Entsorgung des Betriebsmittels und der Einbaukomponenten
(Messinstrument, Signalleuchte, Taster usw.) sind die jeweils geltenden
nationalen Abfallbeseitigungsvorschriften zu beachten.
Zur Erleichterung der Wiederverwertbarkeit von Einzelteilen sind
Kunststoffteile mit dem Kennzeichen des verwendeten Kunststoffes
versehen.
Programmänderungen und -ergänzungen sind vorbehalten.
Explosionsgeschützte Steuergeräte GHG 418
D
7 Die Schutzkappe über die Anschluss- klemmen schieben, bis die
Rastflügel Pos. 14, in die Nuten der Komponente Pos. 1, einrasten
(siehe Bild 3). Dabei ist auf den korrekten Sitz der Dichtung Pos. 6, zu
achten.
8 Das Anschlusskabel mit der Druck- schraube Pos. 8, in der
Schutzkappe festdrehen (siehe Punkt 6.3).
Die Demontage erfolgt in umgekehrter Reihenfolge. Um die Schutzkappe
wieder zu lösen werden mit dem Demontagewerkzeug Pos. 13, die
Rastflügel, wie in Bild 4 dargestellt aus der Nut der Komponente Pos. 1,
heraus gedrückt und die Schutzkappe abgezogen.
6.2 Öffnen des Gerätes / Elektrischer Anschluss
Vor Öffnen der Geräte (abziehen der Schutzkappe) ist die Spannungs-
freiheit sicherzustellen bzw. sind geeignete Schutzmaßnahmen zu
ergreifen.
Der elektrische Anschluss des Betriebsmittels darf nur durch
Fachpersonal erfolgen (EN/IEC 60079-14).
Die ordnungsgemäß abisolierten Anschlussleitungen der Kabel sind unter
Berücksichtigung einschlägiger Vorschriften anzuschließen.
Zur Aufrechterhaltung der Zündschutzart ist der Leiteranschluss mit
besonderer Sorgfalt durchzuführen.
Die Isolation der Anschlussleitungen muss bis an die Klemme
heranreichen. Der Leiter selbst darf nicht beschädigt sein.
Die minimal und maximal anschließbaren Leiterquerschnitte sind zu
beachten (siehe technische Daten).
Alle Schrauben und / oder Muttern der Anschlussklemmen, auch die der
nicht benutzten, sind fest anzuziehen.
Die Standardklemmen sind zum Direktanschluss von Leitern mit
Kupferadern ausgelegt.
Das Schaltbild der Einbaukomponenten ist auf den Komponenten oder in
der Betriebsanleitung angegeben.
6.3 Kabel-und Leitungseinführungen (KLE); Verschlussstopfen
Es ist darauf zu achten, dass bei der Installation der Kabel, die für den
Leitungsdurchmesser geeigneten Dichtungseinsätze der Kabeleinführung
der Schutzkappe verwendet werden.
Zur Sicherstellung der erforderlichen Mindestschutzart sind die Druck-
schraube der Kabeleinführung fest anzuziehen.
Bei übermäßigem Anziehen kann die Schutzart beeinträchtigt
werden.
6.4 Schließen des Gerätes
Alle Fremdkörper sind aus dem Gerät zu entfernen.
Zur Sicherstellung der erforderlichen Mindestschutzart ist die Schutzkappe
und das Bedienelement korrekt gemäß den Anweisungen unter Punkt 6.1
(Montage), zu montieren.
Bei übermäßigem Anziehen kann die Schutzart beeinträchtigt
werden.
6.5 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind die in den einzelnen
nationalen Bestimmungen genannten Prüfungen durchzuführen.
Außerdem ist vor der Inbetriebnahme die korrekte Funktion und Installati-
on des Betriebsmittels und der Einbaukomponenten (Signalleuchte, Taster
usw.) in Übereinstimmung mit dieser Betriebsanleitung und anderen
anwendbaren Bestimmungen zu überprüfen.
Unsachgemäßer Betrieb der Steuergeräte kann zum Verlust der
Garantie führen.
7
1 Technical data
1.1 Control unit assemblies with protective cap
ATEX type examination certificate: PTB 99 ATEX 1034
Marking acc. to 2014/34/EU and standard:
EN 60079-0
D
II 2 G Ex d e IIC T6
Rated voltage: up to max.500 V
Rated current:
max. 16 A
Ambient temperature range:
(Special versions permit deviating temperature ranges)
-20 °C to +40 °C
Perm.storage temperature in original packing: -20 °C to +40 °C
Degree of protection to EN/IEC 60529: IP 66 (with protective cap)
Insulation class acc. to EN/IEC 61140: I - the apparatus fulfil this requirement
Supply terminal:
see built-in components
Cable entry: (Ø 7 - 15 mm)
Gewicht:
Schutzkappe
approx. 0.05 kg
Test torques:
Terminal: 2,50 Nm
Cap nut of the plastic cable entry
3,50 Nm
Self cutting screw (strain relief)
2,00 Nm
Explosion-protected control units GHG 418
GB
EU-Type Examination Certificate: IBExU14ATEX1030U
Marking acc. to 2014/34/EU
and standard of series EN 60079:
II 2 G
Ex db eb IIC/IIB/IIB+H2 Gb
I M 2
Ex db eb I Mb
IECEx type examination certificate: IECEx IBE 14.0005U
Category of application
standard of series IEC 60079: Ex db eb IIC/IIB/IIB+H2 Gb
Ex db eb I Mb
Operating temperature:
II 2 G ... IIC
-55 °C ... +80 °C
II 2 G ... IIB
-60 °C ... +80 °C
II 2 G ... IIB+H2
-55 °C ... +80 °C
Perm.ambient temperature in original packing: -60 °C ... +80 °C
Rated voltage:
up to
500 V
Rated current Rated supply terminal
Permissible ambient
temperature max.
14 A 2.5 mm² 40 °C
16 A 4.0 mm² single wire 40 °C
12 A 2.5 mm² 50 °C
15 A 4.0 mm² single wire 50 °C
Switching capacity acc. to
AC 15
(EN 60947-5-1): 250 V / 6 A 500 V / 4,0 A
Switching capacity acc. to
DC 13
(EN 60947-5-1): 24 V / 6 A 60 V / 0,8 A 110 V / 0,5 A
with gold-tipped contacts: max. 400 mA
Supply terminal: 2 x 1.0 - 2.5 mm²
1 x 4.0 mm² single wire
Test torques: 2.5 Nm
Weight: 2 pole approx. 0.15 kg
4 pole approx. 0.35 kg
1.2 Pushbutton and switch GHG 418 11..R....
8
Explosion-protected control units GHG 418
GB
1.4 Potentiometer GHG 418 16..R....
Marking acc. to 2014/34/EU and directive:
D II 2 G
Ex d e IIC/IIB Gb
D I M2
Ex d e I Mb
EC type examination certificate:
IBExU14ATEX1030U
Rated voltage: up to 250 V
Rating:
1 W
Turning range:
270°
Scale:
0 - 100%
Supply terminal:
2 x 1,0 - 2,5mm²
Weight:
approx. 0,15 kg
EC-Type Examination Certificate: IBExU 12ATEX 1047 U
Marking acc. to 2014/34/EU
and standard of series EN 60079:
II 2 G Ex db eb IIC Gb
II 2 G Ex db ia IIC Gb
IECEx type examination certificate:
IECEx IBE 13.0031U
Category of application
standard of series IEC 60079: Ex db eb IIC Gb
Ex db ia IIC Gb
Permissible operating temperature range: -55 °C ... +80 °C
Max. service temperature +80 °C
(Other temperatures possible with special versions)
Perm.ambient temperature in original packing: -55 °C ... +80 °C
Rated voltage /Rated current:
"e" increased safety (Ex db eb) 20 V ... 254 V AC/DC 4 ...15 mA
"e" increased safety (Ex db eb) 12 V ... 24 V AC/DC max. 24 mA
"i" intrinsically safe version (Ex db ia) 10 V ... 30 V DC max. 38.7 mA
Ex-i Datas: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Supply terminal: 2 x 1.0 - 2.5 mm²; 1 x 4.0 mm² single wire
Test torques: 2.5 Nm
Weight: approx. 0.15 kg
1.3 Signal lamp GHG 418 1806R....
2 Principles
Caution
This symbol warns of a possible failure. Failure to observe this caution may result in the total
failure of the device or the system or plant to which it is connected.
X
ATEX - IEC
Special conditions
This symbol shows Highlights for safe use in accordance to EU-Type-Examination Certificate/ IEC
Ex-Certificate of Conformity.
2
Safety instructions
Target group:
For skilled electricians and suitable qualified, instructed personnel in accordance
with national legislation, including the relevant standards and, where applicable, in
acc. with
IEC/EN 60079-14 on electrical apparatus for explosive atmospheres.
The control units GHG 418 .. are not suited for use in Zone 0.
The temperature class and type of protection stated on the apparatus shall be observed.
Modifications or changes to the control units are not permitted.
They shall be used for their intended purpose and shall be in a perfect and clean state.
Prior to being put into operation, the control units shall be checked in accordance with the
instructions as per section 6.
9
Before initial operation, any foreign matter shall be removed from the
apparatus.
Apparatus without a protective cap may only be built into approved
or certified enclosures, operating panels or switch cabinets.
The national safety rules and regulations for the prevention of
accidents, as well as the safety instructions included in these
operating instructions, that, like this text, are set in italics, shall be
observed!
3 Conformity with standards
The apparatus is conform to the standards specified in the EU-Declaration
of conformity, enclosed separately.
References to standards and directives in these operating instructions
always relate to the latest version. Other additions (e.g. details relating to
the year) shall be observed.
4
Field of application
The control units are intended for use in potentially explosive atmospheres
in zones 1,2 in accordance with IEC/EN 60079-10-1.
The enclosure materials used, including any external metal parts, are high
quality materials that ensure a corrosion resistance and resistance to
chemical substances according to the requirements for use in a ”normal
industrial atmosphere”:
- impact resistant polyamide
When used in extremely aggressive atmospheres, the additional data
relating to the chemical resistance of the plastics being used shall be
taken from the data sheet
GHG 902 4001 P0001.
5
Application / Properties
The control units GHG 418 .. are intended for the local control of electrical
installations in potentially explosive atmospheres. These apparatus
components are built into switch cabinets, operating panels or machinery
according to the individual requirements.
X
ATEX - IEC
For this purpose, they must be installed in suitable Ex-e enclosures
when used in explosive atmospheres.
X
ATEX - IEC
The installation of the actuator GHG41 in equipment of 2G and M2
must be tested and certified separately. At this, the thermal parameters
have to be verified among others.
X
ATEX - IEC
The creepage and clearance distance have to be fulfil the
EN/IEC 60079-7, table 1.
The version with gold-tipped contacts is suited for switching extra-low
voltage circuits. Special attention shall be paid to the maximum current
load (see technical data, page 6). The contact chamber of the gold-tipped
version is marked with the letter ”G” or colour-coded.
To ensure a safe and reliable disconnection, the normally closed contacts
are designed as compulsory opening contacts.
Where required, the bases are fitted with 0.6 W resistors, fine-wire fuses and
diodes (max. power dissipation 1 W).
When the switch collar of small control switches is cut out at the
respective locking position, they can be padlocked
(padlock shackle Ø up to 5 mm).
X
ATEX - IEC
The installation of the signal lamp GHG417 1805 in equipment of 2G
must be tested and certified separately. At this, the thermal parameters
have to be verified among others.
Apparatus versions without a protective cap are only issued with a
”Component Certificate” and may only be used if built into certified
Ex-e protective enclosures.
The apparatus versions with a protective cap are fully certified and can,
therefore, be operated directly.
Any admissibly high mechanical stress of the protective cap that
might impair the explosion protection shall be avoided.
The data according to sections 3 and 4 shall be taken into account
during use.
Applications other than those described are not permissible without
a written declaration of consent from Messrs. COOPER CROUSE-
HINDS / CEAG.
During operation the instructions stated in section 7 of the operating
instructions shall be observed.
The sole responsibility with respect to the suitability and proper use
of the control switches with regard to the basic requirements of
these instructions (see technical data) lies with the operator.
6 Installation
The relevant national regulations(e.g. Betr.Si.V, the equipment safety law
for Germany) and the generally recognized rules of engineering apply for
the installation and operation (IEC/EN 600079-14).
The improper installation and operation of control switches may
result in the invalidation of the guarantee.
6.1 Mounting / Dismantling
Components for panel mounting are mounted in accordance with Figs. 1
– 4, page13 and according to the following:
1. The operating and indicating element, item 4, is inserted from the
front into the bore hole ( Ø 30.3 mm) of the switch panel or enclosure,
maximum wall thickness 5 mm.
Here special attention shall be paid to the correct fit of the seal, item
5, and of the element (positioning lug on element shall fit into the
recess, see dimensions drawing on page 12.)
2. Tighten the counter-nut, item 3, using the mounting tool, item 12
(Accessory Order No. GHG4101914R0001).
Excessive tightening can result in damage to the actuator elements.
3. The Ex-d components, item 1, can be completed by adding a
protective cap, item 7, an optional item – see section 5 –to form fully
certified built-in apparatus.
The minimum distances of the operating elements have to be
observed (see Dimension drawing page).
The partially certified built-in components can be retrofitted with the
protective cap Pos. 7, optionally as described under point 5, can be
completed to fully certified built-in devices.
To do this, the contact protection of the terminals must first be removed.
The protective cap is mounted as follows:
4. Remove the pressure screw with seal, item 8, from the protective
cap, item 7, and adapt the sealing rings to suit the cable cross
section.
5. Push the cable, item 9, through the pressure screw with cable seal,
item 8, of the seal, item 6, and the protective cap, item 7.
6. Connect the cable. Fix the strain-relief, item 1, with the screws, item
11, to the cable and engage in the guide grooves, items 15a and 15b,
of the component, item 1 (see Fig. 3).
Explosion-protected control units GHG 418
GB
10
7. Push the protective cap over the connection terminals until the clips,
item 14, engage in the grooves of the component, item 1 (see Fig. 3).
Special attention shall be piad to the correct fit of the seal, item 6.
8. Tighten the connection cable in the protective cap with the pressure
screw, item 8 (see Section 6.3).
To dismantle, proceed in the reverse order. To release the protective cap,
the clips are pushed out of the grooves in the component, item 1, using
the dismantling tool (item 13) and the protective cap removed (see Fig. 4).
6.2 Opening apparatus / Electrical connection
Before opening the apparatus (pulling off protective cap), it is
necessary to ensure that there is no voltage or to take suitable
protective measures.
The electrical connection of the may only be carried out by special-
ists (IEC/EN 60079-14).
The properly bared conductors of cables shall be connected with due
regard to the respective regulations.
To maintain the explosion protection, conductors shall be connected
with special care.
The insulation shall reach up to the terminal. The conductor itself
shall not be damaged.
The minimum and maximum conductor cross sections that can be
connected shall be observed (see technical data).
All screws and/or nuts of connection terminals, including those not in use,
shall be tightened down securely.
The standard terminals are designed for the direct connection of
conductors with copper wires.
The circuit diagram of the built-in components is shown on the compo-
nents or in the operating instructions.
6.3 Cable entries (KLE); blanking plugs
When fitting cables, care shall be taken to use sealing inserts of the cable
entry of the protective cap that are suited for the respective cable
diameter.
In order to ensure the required minimum degree of protection, the
pressure screws shall be tightened down securely.
Overtightening can impair the degree of protection.
6.4 Closing apparatus
Any foreign matter shall be removed from the apparatus.
In order to ensure the required minimum degree of protection, the
protective cap and the actuating element shall be mounted correctly in
accordance with the instructions (see 6.1).
Overtightening can impair the degree of protection.
6.5 Putting into operation
Before putting the apparatus into operation, the tests specified in the
individual national regulations shall be performed.
In addition to this, before being put into operation, the correct functioning
and installation of the apparatus and built-in components (signal lamps,
pushbuttons, etc.) shall be checked in accordance with these operating
instructions and other applicable regulations.
The improper operation of control units may result in the invalida-
tion of the guarantee.
Explosion-protected control units GHG 418
GB
7 Maintenance / Servicing
The valid national regulations for the servicing / maintenance of
electrical apparatus for use in potentially explosive atmospheres
shall be observed (IEC/EN 60 079-17).
Prior to opening the enclosure, it is necessary to ensure that the
voltage supply has been isolated or to take suitable protective
measures.
The necessary intervals between servicing depend upon the specific
application and shall be stipulated by the operator according to the
respective operating conditions.
During servicing, above all, the parts on which the explosion protection
depend, (e.g. intactness of the flameproof components, the enclosure,
the seals and cable entries), and the switch mechanism function of the
control switch shall be checked.
If, in the course of servicing, it is ascertained, that repairs are necessary,
section 8 of these operating instructions shall be observed.
8 Repairs / Overhaul / Modifications
Only original COOPER CROUSE-HINDS / EATONparts shall be used for
carrying out repairs.
In the event of damage to the flameproof encapsulation, replacement
of these components is mandatory. In case of doubt, the respective
apparatus shall be sent to COOPER CROUSE-HINDS / EATONfor
repair.
Repairs that affect the explosion protection may only be carried out
by COOPER CROUSE-HINDS / EATONor by a qualified electrician in
compliance with the respective national regulations
(IEC/EN 60 079-19).
Apparatus modifications or design changes are not permitted.
When replacing individual built-in components (pushbuttons, etc.) section
6.2 ”Opening apparatus / Electrical connection” shall be observed.
9 Disposal / Recycling
The respective valid national regulations for waste disposal shall be
observed when disposing of apparatus and built-in components (measur-
ing instruments, signal lamps, pushbuttons, etc.).
To facilitate the recycling of individual parts, parts made of moulded plastic
shall bear the marking for the type of plastic used.
The product range is subject to changes and additions.
11
Boites de commande GHG 418 pour atmosphères explosives
F
1 Caractéristiques techniques
1.1 Boites de commande complete avec capot de protection
ATEX Certificat de Conformité: PTB 99 ATEX 1034
Marquage selon 2014/34/UE et directive:
EN 60079-0
D
II 2 G Ex d e IIC T6
Tension nominale: jusqu’à 500 V
Courant nominal:
16 A au maxi
Gamma température ambient:
(Variations de température possibles sur les versins spéciales)
-20 °C à +40 °C
Temp. de stockage dans l’emballage original: -20 °C à +40 °C
Degree of protection to EN/IEC 60529: IP 66 (avec capot de protection)
Classe d’isolation selon CEI/EN 61140: I - est remplie par les appareils d'éclairage
Bornes de connexion:protctive cap voir composants
Entrées de câble: (Ø 7 - 15 mm)
Poids:
Capot de protection
env. 0,05 kg
Couples de serrage testés:
Borne de connexion: 2,50 Nm
Ecrou borgne bas de l’entrée plastique
3,50 Nm
Vis auto-taraudeuse (décharge)
2,00 Nm
1.2 Bouton-poussoir et interrupteur GHG 418 11..R....
Attestation d’examen CE de type: IBExU14ATEX1030U
Marquage selon 2014/34/UE et directive:
EN 60079-0
II 2 G
Ex db eb IIC/IIB/IIB+H2 Gb
I M 2
Ex db eb I Mb
IECEx Certificat de Conformité: IECEx IBE 14.0005U
Marquage selon:
IEC 60079-0 Ex db eb IIC/IIB/IIB+H2 Gb
Ex db eb I Mb
Température de fonctionnement:
II 2 G ... IIC
-55 °C ... +80 °C
II 2 G ... IIB
-60 °C ... +80 °C
II 2 G ... IIB+H2
-55 °C ... +80 °C
Température de stockage dans l’emballage d’orgine: -60 °C ... +80 °C
Tension nominale: jusqu’à
500 V
Courant nominal
maxi
Borne de
connexion
Température ambiante
admissible maxi
14 A 2,5 mm² 40 °C
16 A 4,0 mm²
rigide
40 °C
12 A 2,5 mm² 50 °C
15 A 4,0 mm²
rigide
50 °C
Puissance de coupure
AC15
(EN 60947-5-1): 250 V / 6 A 500 V / 4,0 A
Puissance de coupure
DC13
(EN 60947-5-1): 24 V / 6 A 60 V / 0,8 A 110 V / 0,5 A
Modèle à pointes de contact d’or:
400 mA au maxi
Borne de raccordement:
2 x 1,0 - 2,5 mm²;
1 x 4,0 mm²
rigide
Couples de serrage testés bornes de connexion:
2,5 Nm
Poids: 2 pole env. 0,15 kg
4 pole env. 0,35 kg
12
Boites de commande GHG 418 pour atmosphères explosives
F
Marquage selon 2014/34/UE :
D II 2 G
Ex d e IIC/IIB Gb
D I M2
Ex d e I Mb
Attestation d’examen CE de type:
IBExU14ATEX1030U
Tension nominale: jusqu’à 250 V
Puissance:
1 W
Domaine de rotation:
270°
Echelle:
0 - 100%
Borne de raccordement:
2 x 1,0 - 2,5mm²
Poids:
env. 0,15 kg
1.3 Signallamp GHG418 1806 R...
1.4 Potentiomètre GHG 418 16..R....
2 Légende
Attention
Ce symbole met en garde contre un éventuel défaut. Le non-respect de cette consigne peut
entrainer une panne totale de l’appareil ou du système ou de l’installation à laquelle il est
connecté.
X
ATEX - IEC
Conditions particulières:
Ce symbole indique la présence de conditions particulières d’utilisation à respecter, en lien avec
l’attestation d’examen UE de type et le certificat IEC Ex.
2 Consignes de sécurité
Groupe cible:
Pour les électriciens qualifiés et les personnels ayant reçu les formations adéquates, confor-
mément à la législation nationale en vigueur et, si applicable, à la norme CEI/EN 60079-14 sur
les installations électriques pour les atmosphères explosives.
Les boites de commande GHG 418 encastrables ne conviennent pas à un emploi
en zone 0.
Le groupe d’explosion et la classe de température marqués sur les appareils
devront être respectés.
Il n’est pas permis de transformer ou de modifier les boites de commande.
Seuls des boites de commande intactes et parfaites devront être employées pour la fonction
qui leur est dévolue.
Avant la mise en service, les boites de commande doivent être vérifiées selon l’instruction
donnée dans la section 6.
1.3 Lampe de signalisation GHG418 1806 R......
Attestation d’examen CE de type: IBExU 12ATEX 1047 U
Marquage selon 2014/34/UE
et normes de la série EN 60079:
II 2 G Ex db eb IIC Gb
II 2 G Ex db ia IIC Gb
IECEx Certificat de Conformité: IECEx IBE 13.0031U
Marquage selon
normes de la série IEC 60079: Ex db eb IIC Gb
Ex db ia IIC Gb
Température ambiante admissible en fonctionnement: -55 °C ... +80 °C
Max. température de service: +80 °C
(d’autres valeurs sont possibles avec des modèles spéciaux.)
Temp. de stockage dans l’emballage original: -55 °C ... +80 °C
Tension nominale / courant nominal:
"e" une sécurité accrue (Ex db eb) 20 V ... 254 V AC/DC 4 ... 15 mA
"e" une sécurité accrue (Ex db eb) 12 V ... 24 V AC/DC max. 24 mA
"i" version à sécurité intrinsèque
(Ex db ia)
10 V ... 30 V DC max. 38,7mA
Données de Ex-i: U i 30 V
I i 100 mA
Ci 0
Li 0
Pi 750 mW
Borne de connexion: 2 x 1,0 - 2,5 mm²; 1 x 4,0 mm² rigide
Couples de serrage testés bornes de connexion: 2,5 Nm
Poids: env. 0,15 kg
13
Le modèle sans capot protecteur est certifié selon un "certificat de
composant" et ne doit être encastré que dans des coffrets de
protection "certifiés Ex-e".
Le modèle avec capot protecteur est certifié comme élément peut donc
être installé directement.
Eviter une sollicitation mécanique excessive du capot protec-
teur-risque du mode de protection contre l'explosion.
Pour l’emploi, les consignes des sections 3 et 4 devront être
respectées.
Des emplois autres que ceux décrits ne sont admis qu’avec le
consentement écrit de COOPER CROUSE-HINDS / CEAG.
Lors de l’exploitation, les instructions du point 7 de ce mode
d’emploi doivent être respectées.
Seul l’utilisateur est responsable de l’utilisation conforme de ces
boites de commande, en tenant compte des conditions générales
existant dans l’usine
6 Installation
Pour l’installation et l’exploitation de ces appareils, laglementation
nationale en vigueur (en Allemagne par ex. BetrSiV, loi de sécurides
appareils) ainsi que les règles de la technique géralement reconnues
devront être respectées (CEI/EN 600079-14).
L’installation incorrecte de ces boites à commande peut annuler la
garantie.
6.1 Montage / Demontage
Pour le montage des composants encastrables, on se référera aux figures
1 à 4, page 13 et aux instructions ci-dessous:
1. L’élément de commande ou d’affichage (Pos. 4) entre par la face
externe du tableau, dans le percage (ø 30,3 mm) prévu à cet effet
(max. epaisseur de l'enveloppe 5 mm).
Ce faisant, on veillera au bon positionnement du joint (Pos. 5) et de
l’élément (le cran de positionnement de l’élément doit entrer dans
l’évidement (voir schéma page 12).
2. Le contre-écrou (Pos. 3) se serre à fond à l’aide de l’outil de montage
(Pos. 12- Ref. de commande de cet accessoire:
GHG410 1914 R0001.
Un serrage excessif peut endommager les éléments de commande.
3. Le composant Ex-d (Pos. 1) est enclipsé sur l’élément de commande
(Pos. 4) et maintenu par l’étrier de fixation (Pos. 2).
Un espacement minimum doit être prévu entre chaque organe de
commande (voir plan de perçage).
Les organes de commande certifiés en tant que composants peuvent
évoluer vers des composants complètement certifiés, en leur ajoutant un
capot de protection (pos. 7, fig. 1).
Pour ce faire il faudra d’abord retirer le cache bornes.
Le montage du capot de protection s’effectue comme suit:
4. Séparer l’écrou borgne et le joint
(Pos. 8) du capot de protection (Pos. 7) et adapter le joint au diamètre
du câble.
5. Insérer le câble (Pos. 9) par l’écrou borgne arrière, ajuster le joint (Pos.
8). Enclencher l’autre joint (Pos. 6) et le capot de protection.
6. Connecter le câble. Assurer la décharge de traction (Pos. 10) au câble
avec les vis et enclencher les éléments (Pos. 1) dans les encoches
(Pos. 15a et 15b). Voir Fig. 3.
Boites de commande GHG 418 pour atmosphères explosives
F
Avant la première mise en service, tout corps étranger doit être ôté
de la boite de commande.
Des unités sans capot protecteur ne doivent être installées que dans
des enveloppes, des tableaux ou des armoires de commande
certifiés.
Respectez les prescriptions nationales de sécurité et de prévoyance
contre les accidents ainsi que les consignes de sécurité figurant en
italique dans ce mode d’emploi.
3 Conformité avec les normes
Les Appareils sont conformes aux normes reprises dans la déclaration de
conformité, jointe séparément.
Les références aux normes et directives dans cette notice se réfèrent
toujours à la dernière version. Les suppléments éventuels doivent
également être respectés.
4 Domaine d’utilisation
Les boites de commande répondent aux exigences d’une utilisation en
atmosphère explosible, zones 1, 2 selon la norme CEI/EN 60079-10-1.
Pour l’enveloppe, y compris les pièces métalliques extérieures, des
matières de qualité supérieure (polyamide anti-choc) qui assurent une
protection appropriée contre la corrosion et une résistance aux agents
chimiques en ”atmosphère normale” ont été employées.
- polyamide anti-choc
En cas d‘utilisation en atmosphère extrèmement corrosive, vous pouvez
obtenir des informations complémentaires sur la résistance chimique des
plastiques utilisés chez la succursale Cooper Crouse-Hinds de votre
région.
5 Utilisation / Propriétés
Les boites de commande GHG 418 pour montage sur tableau de
distribution servent à la commande sur place d’installations électriques en
atmosphère explosive.
Selon de l’application spécifique et suivant le cas, les appareils sont
encastrés dans des armoires de commande et des machines.
X
ATEX - IEC
À cet effet, elles doivent être installées dans des enceintes Ex-e
appropriées lorsqu'elles sont utilisées dans des atmosphères explosives.
X
ATEX - IEC
L'installation de l'actionneur GHG41 dans les équipements 2G et M2
doit être testée et certifiée séparément. Pour cela, les paramètres
thermiques doivent être vérifiés entre autres.
X
ATEX - IEC
La distance de fuite et de jeu doit être conforme à la norme
EN / IEC 60079-7, tableau 1.
Le modèle à pointes de contact or est employé pour la coupure de valeurs
de tension peu élevées. La tension maximale admise doit être observée
(voir page 9, Caractéristiques techniques). Ce modèle est reconnaissable
au marquage ”G” sur le socle.
Afin d’obtenir une déconnexion fiable, des contacts de rupture forcée ont
été montés comme contacts normaux.
Suivant le cas, les socles sont aussi dotés de résistances de 0,6 W, de
fusibles pour faible intensité et de diodes
(puissance dissipée de 1 W maxi).
Si le collet de commutation des manipulateurs est découpé en position de
verrouillage respective, il est possible de cadenasser ceuxcidans cette
position (Ø de l’étrier jusqu’à 5 mm).
X
ATEX - IEC
L'installation de la lampe témoin
GHG417 1805 en équipement de 2G doit être testé et certifié séparément.
Pour cela, les paramètres thermiques doivent être vérifiés entre autres.
14
Boites de commande GHG 418 pour atmosphères explosives
F
7. Insérer le capot de protection sur les bornes de connexion de telle
façon que les crans (Pos. 14) atteignent les encoches des éléments
(Pos. 1). Voir Fig. 3. Ce faisant, on veillera au bon positionnement des
joints.
8. Le câble de connexion doit être serré dans le capot de protection à
l’aide de l’écrou borgne (Pos. 8). Voir chapitre 6.3.
Le démontage s’effectue dans l’ordre inverse. Pour retirer le capot de
protection (Pos. 13), les crans seront séparés de l’encoche des éléments
(Pos. 1) avec l’outil de démontage (Pos. 13), comme représenté par la Fig. 4.
6.2 Ouverture de l’appareil / Raccordement électrique
Avant ouverture des composants (séparation du capot de protection),
on s’assurera de la mise hors tension et de la prise de mesures de
sécurité.
Le raccordement électrique de l’appareil ne doit se faire que par un
personnel qualifié (CEI/EN 60079-14).
En tenant compte des règlements respectifs, les conducteurs dûment
dénudés des câbles sont raccordés.
Afin de maintenir le mode de protection, la connexion des conduc-
teurs doit se faire très soigneusement.
L’isolation doit couvrir le conducteur jusqu’à la borne. Le conducteur
lui-même ne doit pas être endommagé.
Les sections minimales et maximales admissibles des conducteurs
doivent être respectées (voir caractéristiques techniques).
Toutes les vis et/ou écrous des bornes de connexion, aussi celles des
bornes non utilisées, doivent être serrées à fond.
La borne standard installée au choix est prévue pour raccordement direct
des conducteurs en cuivre.
Le schéma des connexions des composants encastrés est soit indiqué sur
ceux-ci, soit joint à l’appareil. Il peut encore être exposé dans la notice
d’utilisation.
6.3 Entrées de câble (KLE) / Bouchons de fermeture
On veillera à ce que lors de l’insertion du câble, des joints conformes au
diamètre de celui-ci sont employés
Afin de maintenir le degré de protection requis, l’écrou borgne bas de
l’entrée doit serrer le câble à fond.
Au cas où elle serait forcée cela pourrait être nuisible à l’indice de
protection.
6.4 Fermeture de l’appareil
Tout corps étranger doit être ôté de l’appareil.
Afin de maintenir le degré de protection requis, le capot de protection et
l’élément de commande doivent être montés correctement en suivant les
instructions du chapitre 6.1. de ce mode d’emploi.
Si les vis sont forcées, cela peut être nuisible à l’indice de protection.
6.5 Mise en service
Avant la mise en service de l’appareil, les vérifications spécifiées dans les
règlements nationaux individuels devront être exécutées.
De plus, on vérifiera que son fonctionnement et son installation sont
correcte de telle sorte à respecter les instructions de ce mode d’emploi et
des autres règlements applicables
L’utilisation incorrecte de ces boites à bornes peut annuler la
garantie.
7 Maintien/Entretien
La règlementation nationale en vigueur pour le maintien et l’entre-
tien du matériel électrique pour atmosphère explosive doit être
respectée (CEI/EN 60079-17).
Avant d’ouvrir l’enveloppe, débrancher l’appareil de la tension ou
prendre des mesures préventives appropriées.
Les intervalles de service requis dépendent de l’emploi spécifique et
devront donc être fixés par l’utilisateur en tenant compte des conditions
d’utilisation.
Lors de l’entretien des commutateurs, surtout les composants qui sont
essentiels à leur mode de protection contre l’explosion, doivent être
vérifiés (par ex. intégrité des composants antidéflagrants et du boitier,
efficacité des joints de couvercle et resserrement des entrées de câble)
ainsi que le fonctionnement du mécanisme de commutation.
Si, lors d’un entretien, on constate que des travaux d’entretien sont
nécessaires, il faudra suivre le point 8 de ce mode d’emploi.
8 Réparations/Remise en état
Des réparations ne doivent être exécutées qu’à l’aide des pièces de
rechange d’origine COOPER CROUSE-HINDS / CEAG.
En cas de défauts sur l’enveloppe antidéfla-grante, seul un remplace-
ment est admissible. Dans le doute, l’appareil défectueux devra être
renvoyé à COOPER CROUSE-HINDS / EATONpour être réparé
(CEI/EN 60079-19).
Des réparations qui portent sur la protection contre l’explosion, ne
devront être exécutées que par COOPER CROUSE-HINDS / EATONou
par un électricien qualifié en conformité avec la règlementation
nationale en vigueur.
Il n’est pas permis de transformer ou de modifier ces appareils.
En cas de remplacer des composants encastrés individuels ( bouton-pous-
soir etc.), l’alinéa 6.2 „Ouverture de l’appareil/Raccordement électrique
devra être respecté.
9 Évacuation des déchets / Recyclage
Lors de l’évacuation de ce matériel électrique, la règlementation nationale
respective en vigueur devra être respectée.
Pour faciliter la réutilisation des composants individuels, des pièces en
matière plastique ont été repérées de la marque distinctive de la matière
plastique employée.
Sous réserve de modification ou d’informations supplémentaires.
15
Maßbilder in mm
X = Befestigungsmaße
Dimensions in mm
X = Fixing dimensions
Dimensions en mm
X =dimensions de fixation
Steuergerät ohne Schutzkappe
Control unit without protective cap
Boite de commande sans capot de protection
Steuergerät mit Schutzkappe
Control unit with protective cap
Boite de commande avec capot de protection
Bohrung für Minimale Abstände
Bedienelemente der Bohrungen
Drilling for Minimum clearances
actuator elements between drillings
Perçage pour éléments Distance minimale
de commande des perçages
Maßbilder Bedienelemente
Dimensions of the actuator elements
Dimensions des éléments de commande
Drucktaster Signalleuchte Doppeldrucktaster
Pushbutton Signall lamp Double pushbutton
Bouton-poussoir Voyant lumineux Bouton-poussoir
double
Schlagtaster Schalter Schlagtaster
"NOT-AUS" Potentiometer
Mushroom-head Switch Mushroom-head
EMERGENCY STOP"
Potentiometer
Bouton-poussoir Interrupteur Bouton-poussoir
"ARRET D'URGENCE"
Potentiomètre coup de poing
Schlagtaster "NOT-AUS" Schlüsseltaster
mit Schlüsselentriegelung
Mushroom-head pushbutton Key-operated
"EMERG. STOP" pushbutton
with key release
Bouton-poussoir coup de poing Bouton-poussoir
"ARRET D'URGENCE" à clé
avec serrure
Schaltabwicklungen
Contact arrangements
Schémas des connexions
Drucktaster
Pushbutton
Bouton-poussoir
Doppeldrucktaster
Double-pushbutton
Bouton-poussoir double
Schlagtastertaster
Mushroom head pushbutton
Bouton-poussoir à frepper
Schlagtastertaster mit Schlüssel
Mushroom head pushbutton with key
Bouton-poussoir avec clé à frapper
Schlüsseltaster
Key-operated pushbutton
Bouton-poussoir à clé amovible
Potentiometer
Potentiomètre
Steuerschalter R6201
Control switch R6201
Commutateur de commande R6201
Steuerschalter R6102
Control switch R6102
Commutateur de commande R6102
Steuerschalter R6002
Control switch R6002
Commutateur de commande R6002
Steuerschalter R5307
Control switch R5307
Commutateur de commande R5307
Steuerschalter R5507
Control switch R5507
Commutateur de commande R5507
Steuerschalter R8701
Control switch R8701
Commutateur de commande R8701
1 2
3 4
1
2
3
4
1211
21 22
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1 Druckfeste Komponente
Flameproof components
Composants antidéflagrants
2 Haltebügel
Fixing bow
Étrier de fixation
3 Kontermutter
Counter-nut
Contre-écrou
4 Bedienelement
Actuator elements
Tête de commande
5 Dichtung für Bedienelement
Seal for actuator elements
Joint pour tête de commande
6 Dichtung für Schutzkappe
Seal for protective cap
Joint pour capot de protection
7 Schutzkappe
Protective cap
Capot de protection
8 Druckschraube der Kabeleinführung
Cap nut of the cable entry
Ecrou borgne bas de l’entrée
9 Anschlusskabel
Cable
Câble
10 Zugentlastung
Strain-relief
Décharge de traction
11 Selbstschneidente Schraube
Self-cutting screw
Vis auto-taraudeuse
12 Montagewerkzeug
Mounting tool
Outil de montage
13 Demontagewerkzeug
Dismantling tool
Outil de démontage
14 Rastflügel
Clips
Cran
Bild/ Fig. 1
Bild/ Fig. 2
Bild/ Fig. 4
Bild/ Fig. 3
4 5 3 2 1 6 14 7
10 11 8 9
4 5 3 12
13 14 7
2 1 6 10 11 9
2 1 14 15b 7 8
15a
Komponenten
Components
Composants
Publication No.
GHG 410 7003 P0001 D/E/F (i)
Auflage 0.000 · 49.2017 · MS
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Eaton is dedicated to ensuring that reliable, efficient
and safe power is available when it’s needed most. With
unparalleled knowledge of electrical power management
across industries, experts at Eaton deliver customized,
integrated solutions to solve our customers’ most critical
challenges.
Our focus is on delivering the right solution for the appli-
cation. But, decision makers demand more than just
innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer
success a top priority. For more information, visit
www.eaton.com/electrical.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual
Ce manuel convient également à

dans d''autres langues