Rockwell Automation 2080-LC10-12QWB Installation Instructions Manual

Taper
Installation Instructions Manual
Installation Instructions
Micro810 12 Point Programmable Controllers
Catalog Numbers 2080-LC10-12AWA, 2080-LC10-12QWB,
2080-LC10-12QBB, 2080-LC10-12DWD
http://literature.rockwellautomation.com/idc/groups/literature/documents/in/2080-in006_-mu-p.pdf
FR
Cette publication est disponible en français
sous forme électronique (fichier PDF). Pour la
télécharger, rendez-vous sur la page Internet
indiquée ci-dessus.
PT
Esta publicação está disponível em portugués
como PDF. Vá ao endereço web que aparece
acima para encontrar e fazer download da
publicação.
IT
Questa pubblicazione è disponibile in Italiano
in formato PDF. Per scaricarla collegarsi al sito
Web indicato sopra.
ZH
DE
Diese Publikation ist als PDF auf Deutsch
verfügbar. Gehen Sie auf die oben genannte
Web-Adresse, um nach der Publikation zu
suchen und sie herunterzuladen.
ZC
ES
Esta publicación está disponible en español
como PDF. Diríjase a la dirección web indicada
arriba para buscar y descarga esta publicación.
KO
Table of Contents
Topic Page
Important User Information 2
Additional Resources 6
Overview 7
Controller Description 7
Mount the Module 8
Status Indicator 7
Wire the Controller 10
Specifications 11
2 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
) describes some important differences between solid state equipment
and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that
each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the
product.
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or
death, property damage, or economic loss. Attentions help you identify a hazard, avoid a
hazard and recognize the consequences.
SHOCK HAZARD
Labels may be on or inside the equipment (for example, drive or motor) to alert people that
dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment (for example, drive or motor) to alert people that
surfaces may reach dangerous temperatures.
Micro810 12 Point Programmable Controllers 3
Publication 2080-IN006A-EN-P - September 2010
Environment and Enclosure
Preventing Electrostatic Discharge
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1),
at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there may be difficulties with
electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of flame,
complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if
non-metallic. The interior of the enclosure must be accessible only by the use of
a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply
with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1
, for additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the
degrees of protection provided by different types of enclosure.
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle
this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
4 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
North American Hazardous Location Approval
The following modules are North American Hazardous Location approved:
2080-LC10-12AWA, 2080-LC10-12QWB, 2080-LC10-12QBB, 2080-LC10-12DWD
The following information applies when
operating this equipment in hazardous
locations:
Informations sur l’utilisation de cet
équipement en environnements
dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products within
a system, the most adverse temperature code
(lowest "T" number) may be used to help determine
the overall temperature code of the system.
Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements
de Classe I Division 2 Groupes A, B, C, D dangereux et
non dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l'installation.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment
unless power has been
removed or the area is known
to be nonhazardous.
Do not disconnect connections
to this equipment unless power
has been removed or the area
is known to be nonhazardous.
Secure any external
connections that mate to this
equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.
Substitution of any component
may impair suitability for Class
I, Division 2.
If this product contains
batteries, they must only be
changed in an area known to
be nonhazardous.
AVERTISSEMENT
RISQUE D’EXPLOSION
Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher l'équipement.
Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet
équipement à l'aide de vis,
loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.
La substitution de tout
composant peut rendre cet
équipement inadapté à une
utilisation en environnement de
Classe I, Division 2.
S'assurer que l'environnement
est classé non dangereux avant
de changer les piles.
Micro810 12 Point Programmable Controllers 5
Publication 2080-IN006A-EN-P - September 2010
WARNING
If you insert or remove the module while power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
The local programming terminal port is intended for temporary use only and
must not be connected or disconnected unless the area is assured to be
nonhazardous.
When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure with proper wiring method that complies with
the governing electrical codes.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
The USB port is intended for temporary local programming purposes only and
not intended for permanent connection. If you connect or disconnect the USB
cable with power applied to this module or any device on the USB network, an
electrical arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
The USB port is a nonincendive field wiring connection for Class I, Division2
Groups A, B, C and D.
Exposure to some chemicals may degrade the sealing properties of materials
used in the Relays. It is recommended that the User periodically inspect these
devices for any degradation of properties and replace the module if
degradation is found.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this equipment must be
powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment must be powered from a source
compliant with the following:
Class 2 or Limited Voltage/Current.
Do not wire more than 2 conductors on any single terminal.
Be careful when stripping wires. Wire fragments that fall into the controller
could cause damage. Once wiring is complete, make sure the controller is free
of all metal fragments.
6 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Additional Resources
If you would like a manual, you can:
download a free electronic version from the Internet:
http://literature.rockwellautomation.com
purchase a printed manual by contacting your local Allen-Bradley distributor or
Rockwell Automation representative
ATTENTION
Do not remove the protective debris strips until after the controller and all other
equipment in the panel near the module are mounted and wired. Remove strips
before operating the controller. Failure to remove strips before operating can
cause overheating.
Electrostatic discharge can damage semiconductor devices inside the module.
Do not touch the connector pins or other sensitive areas.
This product is intended to be mounted to a well-grounded mounting surface
such as a metal panel. Additional grounding connections from the power
supply's mounting tabs or DIN rail (if used) are not required unless the mounting
surface cannot be grounded. Refer to Industrial Automation Wiring and
Grounding Guidelines, Allen-Bradley publication 1770-4.1
, for additional
information.
The USB cable is not to exceed 3.0 m (9.84 ft).
Resource Description
Micro810 Programmable Controllers User
Manual, publication 2080-UM001
A more detailed description of how to install and use your
Micro810 programmable controller and expansion I/O system.
Micro810 AC Power Supply Installation
Instruction, publication 2080-IN001
Information on wiring and installing the optional AC power supply.
Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
More information on proper wiring and grounding techniques.
Micro810 12 Point Programmable Controllers 7
Publication 2080-IN006A-EN-P - September 2010
Overview
The Micro810 12 Point controller is an economical brick-style controller with embedded
inputs and outputs. It can accomodate a USB adapter, and an LCD module. It can also
accomodate any 24V DC output power supply that meets minimum specifications such as the
optional Micro800 power supply.
Controller Overview
Status Indicator
Controller Description
Description Description
1 Status indicator 4 USB port (for use with USB Adapter only)
2 Input terminal block 5 DIN rail mounting latch
3 Mounting screw hole/ mounting foot 6 Output connectors
State During Normal Operation During Firmware Update or
Program/Data Transfer
Off No power applied to device, or in Fault mode No power applied to device, or in Fault mode
Solid green Device operating normally Program transfer successful
Flashing green Operating System error Firmare update in progress
1
2
4
56
45052
3
3
8 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Mount the Module
Most applications require installation in an industrial enclosure to reduce the effects of
electrical interference and environmental exposure. Locate your controller as far as possible
from power lines, load lines, and other sources of electrical noise such as hard-contact
switches, relays, and AC motor drives. For more information on proper grounding guidelines,
see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
Mounting Dimensions and DIN Rail Mounting
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment.
Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 x 1 mm
(EN 50 022 - 35 x 7.5) .
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the DIN rail latch
and pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the controller onto the DIN rail, and
then press the bottom until the controller snaps onto the DIN rail.
2. Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAHJ35)
for vibration or shock environments.
45054
Mounting dimensions do not include
mounting feet or DIN rail latches.
75 mm (2.95 in.)
59 mm (2.32 in.)
91 mm (3.58 in.)
Micro810 12 Point Programmable Controllers 9
Publication 2080-IN006A-EN-P - September 2010
To remove your controller from the DIN rail, pry the DIN rail latch downwards until it is in
the unlatched position.
Panel Mounting
The preferred mounting method is to use four M4 (#8) screws per module. Hole spacing
tolerance: ±0.4 mm (0.016 in.).
Follow these steps to install your controller using mounting screws.
1. Place the controller against the panel where you are mounting it. Make sure the
controller is spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet then remove
the controller.
3. Drill the holes at the markings, then replace the controller and mount it.
Leave the protective debris strip in place until you are finished wiring the controller
and any other devices.
Panel Mounting Dimensions
TIP
For environments with greater vibration and shock concerns, use the panel
mounting method, instead of DIN rail mounting.
10 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Wire the Controller
L2/N VAC
L1 VAC L2/N VAC
NC
I-00
I-01
I-02
12345678 9101112
I-05 I-07I-03
I-04 I-06
45055
Input Terminal Block
Output Terminal Block
45056
Input Terminal Block
Output Terminal Block
2080-LC10-12AWA
2080-LC10-12QWB
2080-LC10-12DWD
45057
45058
CM0 CM1
O-03O-01O-00
CM2
O-02
12345678
CM3
45059
+DC24 COM0
-DC24I-00-DC24
I-01
I-02
12345678 9101112
I-03 I-04 I-06
I-05 I-07
CM0 CM1
O-03O-01O-00
CM2
O-02
12345678
CM3
45059
Input Terminal Block
Output Terminal Block
CM0 CM1
O-03O-01O-00
CM2
O-02
12345678
CM3
45059
2080-LC10-12QBB
Input Terminal Block
Output Terminal Block
45056
+DC24 COM0
-DC24I-00-DC24
I-01
I-02
12345678 9101112
I-03 I-04 I-06
I-05 I-07
COM0+DC12
-DC12I-00-DC12
I-01
I-02
12345678 9101112
I-03 I-04 I-06
I-05 I-07
+CM0 O-00
-CM0O-01 O-03+CM0
O-02
12345678
-CM0
Micro810 12 Point Programmable Controllers 11
Publication 2080-IN006A-EN-P - September 2010
Specifications
General (2080-LC10-12AWA, 2080-LC10-12QWB, 2080-LC10-12QBB,
2080-LC10-12DWD )
Attribute 2080-LC10-12AWA 2080-LC10-12QWB 2080-LC1012DWD 2080-LC10-12QBB
Number of I/O 8 Input (4 digital, 4 analog/digital, configurable)
4 Output
Dimensions
HxWxD
91 x 75 x 59 mm
(3.58 x 2.95 x 2.32 in.)
Supply voltage range 85V…263V 20.426.4V DC 10.8V…13.2V DC 11.4V..26.4V DC
Supply frequency
range (AC supply)
47…63 Hz N.A.
Voltage range 100…240V AC,
50/60 Hz
24V DC
Class 2
12V DC
Class 2
12/24V DC
Class 2
Power consumption 5V A 5 W
I/O rating Input: 120…240V
AC, 8.4V A
Output: C300 R150,
8A 250V AC
General Use
Input: 24V DC, 8 mA
Output: C300 R150,
8A 250V AC General
Use
Input: 12V DC,
8mA
Output: C300 R150,
8A 250V AC
General Use
Input: 24V DC, 8 mA
Output: 24V DC 1A,
25 °C, 24V DC 0.5A
55°C
Shipping weight,
approx.
0.203 kg (0.448 lb)
Wire size 0.32... 2.1 mm² (22...14 AWG) solid copper wire or
0.32... 1.3 mm² (22...16 AWG) stranded copper wire
rated at 90 °C (194 °F ) insulation max.
Wiring category
(1)
2 - on signal ports
2 - on power ports
Wiring torque 1.085 Nm (8 in-lb)
Wire type use Copper Conductors only
Fuse, type Rated 250V 3.15 A-RADIAL
Enclosure type rating None (open-style)
North American temp
code
T5
Insulation stripping
length
7 mm (0.28 in)
12 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Isolation voltage 250V (continuous),
Reinforced
Insulation Type, I/O
to Aux and
Network, Inputs to
Outputs.
Type tested for 60 s
3250V DC, I/O to
Aux and Network,
Inputs to Outputs
250V (continuous), Reinforced Insulation
Type, I/O to Aux and Network, Inputs to
Outputs
Type tested for 60 s at 720V DC, Inputs to
Aux and Network, 3250V DC Outputs to
Aux and Network, Inputs to Outputs
50V (continuous),
Reinforced
Insulation Type, I/O
to Aux and
Network, Inputs to
Outputs
Type tested for 60 s
at 720V DC, I/O to
Aux and Network,
Inputs to Outputs
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1
.
Non-isolated AC Inputs (2080-LC10-12AWA)
Attribute Value
On-state voltage, nom 120/240 V AC
On-state voltage, min 79 V AC
On-state voltage, max 265 V AC
Off-state voltage, max 40 V AC
Operating frequency, nom 50/60 Hz
Input impedence 423.7 kΩ
Operating frequency 47…63 Hz
DC Inputs (2080-LC10-12QWB, -12QBB, -12DWD) (Inputs 0 through 3)
Attribute Non-isolated, shared with analog inputs Isolated
Voltage category 24V DC sink/source
On-state voltage, nom 12/24V DC
On-state voltage, min 9.8V DC
On-state voltage, max 28.8V AC
Off-state voltage, max 5V DC
Off-state current, max 0.5 mA 1.5 mA
On-state current, min 0.75 mA @ 10.8V DC
1.0 mA @ 15 V DC
1.8 mA @ 10.8V DC
2.7 mA @ 15 V DC
On-state current, nom 1.7 mA @ 24V DC 6 mA @ 24V DC
On-state current, max 2.1 mA @ 28.8 V DC 7.5 mA @ 28.8 V DC
General (2080-LC10-12AWA, 2080-LC10-12QWB, 2080-LC10-12QBB,
2080-LC10-12DWD )
Attribute 2080-LC10-12AWA 2080-LC10-12QWB 2080-LC1012DWD 2080-LC10-12QBB
Micro810 12 Point Programmable Controllers 13
Publication 2080-IN006A-EN-P - September 2010
Nominal impedance 14.1 kΩ 3.74 kΩ (isolated)
IEC input compatibility Type 1 Type 3
Analog Inputs (2080-LC10-12QWB, -12QBB, -12DWD) (Inputs 4 through 7)
Attribute Value
Input type DC voltage
Input voltage range 0…10V DC
Input voltage, max 26.4V DC
Value of LSB 2.5 mV
Input resolution 10-bit
Smoothing None, smoothing
Overall accuracy 5% of full-scale (2% with calibration)
(25…55 °C)
(77…131 °F)
Noise rejection 50/60 Hz
Common mode rejection 40 dB, DC to 60 Hz with Smoothing filter
Nominal impedance 14.1 kΩ (non-isolated)
DC Output (2080-LC10-12QBB)
Attribute Value
User supply voltage, min 10 V DC
User supply voltage, max 26.4V DC
On-state voltage drop 1V @ max load current
2.5V @ max surge current
Current ratings 0.5A @ 55 °C max
1.0A @ 30 °C max
1.0 mA min
Surge current, peak 4.0 A
Surge current, max duration 10 ms
Turn-on- time, max 0.1 ms
Turn-off time, max 0.1 ms
DC Inputs (2080-LC10-12QWB, -12QBB, -12DWD) (Inputs 0 through 3)
Attribute Non-isolated, shared with analog inputs Isolated
14 Micro810 12 Point Programmable Controllers
Publication 2080-IN006A-EN-P - September 2010
Relay Outputs (2080-LC10-12AWA, -12QWB, -12DWD)
Attribute Value
Output rating Relay 00 & 01: 8 A @ 240V AC, 5A @ 24V DC, B300
Relay 02 & 03: 4 A @ 240V AC, 2A @ 24V DC, C300, R150
For more specifications, refer to the Micro810 Programmable Controllers User Manual, publication
2080-UM001
.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Temperature,
surrounding air, max
55 °C (131 °F)
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g (DIN Rail Mounted)
30 g (Panel Mounted)
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
Micro810 12 Point Programmable Controllers 15
Publication 2080-IN006A-EN-P - September 2010
Surge transient
immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on shielded ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Voltage variation IEC 61000-4-11:
60% dip for 5 and 50 periods on AC supply ports
30% dip for 0.5 period at 0° and 180° on AC supply ports
100% dip for 0.5 period at 0° and 180° on AC supply ports
±10% fluctuations for 15 min on AC supply ports
>95% interruptions for 250 periods on AC supply ports
Certifications
Certification (when
product is marked)
(1)
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other
certification details.
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E334470.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Environmental Specifications
Attribute Value
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its
products. At http://support.rockwellautomation.com
, you can find technical manuals, a
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect support programs. For more information, contact
your local distributor or Rockwell Automation representative, or visit
h
ttp://support.rockwellautomation.com.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer Support
number for initial help in getting your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when
shipped from the manufacturing facility. However, if your product is not functioning and
needs to be returned, follow these procedures.
Allen-Bradley, Rockwell Automation, Micro810, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
United States 1.440.646.3434
Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United States Please contact your local Rockwell Automation representative for any technical
support issues.
United States Contact your distributor. You must provide a Customer Support case number (call the
phone number above to obtain one) to your distributor in order to complete the return
process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
Publication 2080-IN006A-EN-P - September 2010 PN 953203-31
Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Rockwell Automation 2080-LC10-12QWB Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues