Simplicity 071019-0 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur

Ce manuel convient également à

Generator Systems
Installation & Operator’s Manual
100/200 Amp Automatic
Transfer Switch
with ACPower Control Module™
NOT
FOR
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Thank you for your purchase of this Briggs & Stratton® Power Products automatic transfer switch. This product is designed
for use with specific home standby generators and may not function with generators produced by other manufacturers.
Seek a qualified electrical professional to determine applicability of this equipment to generators manufactured by others.
When operated and maintained according to the instructions in this manual, your system will provide many years of
dependableservice.
This manual contains safety information to make you aware of the hazards and risks associated with this system and how to
avoid them. We have made every effort to provide for a safe, streamlined and cost-effective installation. As each installation
is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation might be
achieved. We do not know all possible hazards and/or the results of each possible method or procedure. It is important that
you read and understand these instructions thoroughly before attempting to install or operate this equipment. Save these
instructions for future reference.
This transfer switch requires professional installation before use. Refer to the Installation section of this manual for
instructions on installation procedures. Only licensed electrical contractors should install transfer switches. Installations must
strictly comply with all applicable federal, state and local codes, standards and regulations. Your installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your system. Consult your Yellow Pages.
There are many authorized service dealers who provide quality service. You can also contact Technical Service by phone at
(800) 743 4115 between 8:00 AM and 5:00 PM CT, or on the Internet at BRIGGSandSTRATTON.COM.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Transfer Switch
Model Number
Revision
Serial Number
Date Purchased
Briggs & Stratton Power Products Group, LLC
P.O. Box 702
Milwaukee, WI 53201-0702
Copyright © 2012. All rights reserved. No part of this material
may be reproduced or transmitted in any form without the express
written permission of Briggs & Stratton Power Products Group, LLC.
NOT
FOR
REPRODUCTION
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................5
Owner Orientation ............................................5
Installing Dealer/Contractor Responsibilities ........................5
Mounting Guidelines ..........................................6
Power Wiring Interconnections ..................................7
Supervisory Control Wiring .....................................8
System Setup...............................................11
System Test ................................................11
Controls ..................................... 11
Operation .................................... 11
Testing the Automatic Transfer Switch ...........................12
Maintenance .................................. 12
Troubleshooting................................ 13
Schematic and Wiring Diagram, Models 071018 and 071019..........14
Schematic and Wiring Diagram, Models 071020 and 071021..........15
Warranty..................................... 16
Product Specifications ........................... 17
NOT
FOR
REPRODUCTION
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the equipment.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the equipment unsafe.
Electrical Shock Read Manual
WARNING Only qualified electricians should attempt
installation of this equipment, which must strictly comply
with applicable codes, standards and regulations.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
• Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
WARNING Failure to properly ground equipment can
result in electrocution.
• Do not touch bare wires.
• Do not use equipment with worn, frayed, bare or
otherwise damaged wiring.
• Do not handle electrical cords while standing in water,
while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand
on an insulated dry surface to reduce shock hazard.
• Do not allow unqualified persons or children to operate or
service equipment.
• In case of an accident caused by electrical shock,
immediately shut down all sources of electrical power
and contact local authorities. Avoid direct contact with
the victim.
WARNING Equipment contains high voltage that can
cause personal injury or death.
• Despite the safe design of the system, operating this
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
NOTICE Improper treatment of equipment can damage it
and shorten its life.
• Use equipment only for intended uses.
• If you have questions about intended use, ask dealer or
contact Briggs & Stratton Power Products.
• Do not expose equipment to excessive moisture, dust,
dirt, or corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• If connected devices overheat, turn them off and turn off
their circuit breaker/fuse.
SAVE THESE INSTRUCTIONS
NOT
FOR
REPRODUCTION
5
Installation
We sincerely appreciate your patronage. For this reason,
we have made significant effort to provide for a safe,
streamlined and cost-effective installation. Because each
installation is unique, it is impossible to know of and advise
the trade of all conceivable procedures and methods by
which installation might be achieved. Neither could we know
of possible hazards and/or the results of each method or
procedure. For these reasons,
Only current licensed electrical should attempt system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your equipment is supplied with this combined “Installation
and Operator’s Manual”. This is an important document and
should be retained by the owner after the installation has
been completed.
Every effort has been made to make sure that the information
in this manual is both accurate and current. However, the
manufacturer reserves the right to change, alter or otherwise
improve the system at any time without prior notice.
Home Owner Responsibilities
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation before contracting
or starting your equipment installation.
To arrange for proper installation, contact the store at which
you purchased your equipment, your dealer, or your utility
power provider.
The equipment warranty is VOID unless the system is
installed by licensed electrical professionals.
Owner Orientation
The illustrations provided are for typical circumstances and
are meant to familiarize you with the installation options
available with your system.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional. As the distance from the existing electrical
service increases, compensation in wiring materials must
be allowed for. This is necessary to comply with local codes
and overcome electrical voltage drops.
These factors will have a direct effect on the overall price
of your equipment installation.
NOTE: Your installer must check local codes AND obtain
permits before installing the system.
 • Readandfollowtheinstructionsgiveninthismanual.
 • Followaregularscheduleincaringforandusingyour
equipment, as specified in this manual.
Installing Dealer/Contractor Responsibilities
 • Readandobservethesafetyrules.
 • Readandfollowtheinstructionsgiveninthismanual.
 • Theinstallermayneedtoprovideappropriaterated
contactors based on loads to be controlled.
 • Checkfederal,stateandlocalcodesandauthority
having jurisdiction, for questions on installation.
 • Ensuregeneratorisnotoverloadedwithselectedloads.
If you need more information about the transfer switch, call
(800) 743-4115, between 8:00 AM and 5:00 PM CT.
Equipment Description
The transfer switch is designed to transfer the selected
loads found in normal residential installations to generator
power in the event of a utility power failure. The load is
connected either to utility power (normal) or home standby
power (generator). The transfer switch monitors utility and
generator voltages and will automatically connect to the
appropriate source of power.
These switches make it easy for a licensed electrician to
complete a home standby installation. Depending on the
specific model purchased, service conduit and conductors
can be wired directly from the hour-meter to the transfer
switche a separate disconnect and associated wiring are not
required when installed per applicable federal, state and local
codes, standards and regulations.
Major components of the transfer switch are a 2 pole utility
disconnect circuit breaker, a 2 pole generator disconnect
circuit breaker, a 2 pole double throw transfer switch, control
circuit board, fused utility terminals and interconnecting
wiring. The control board also has two inputs for current
transformers that sense generator current. These
components are housed in a NEMA 3R enclosure that is
suitable for both indoor and outdoor installations.
The transfer switch is solenoid-operated from utility or
generator inputs and contain suitable mechanical and
electrical interlock switches to eliminate the possibility of
connecting the utility service to the generator output. It
has ratings capable of switching full utility power into the
residence. In addition, a manual override lever is provided
for the transfer function.
The control board has active circuits sensing utility and
generator voltages. It creates a signal for the generator
start-up, switch transfer and retransfer when utility is
restored. The control board also contains red and green
LED’s indicating the power sources available and two
relay operated contacts that provide supervisory control of
external loads.
NOT
FOR
REPRODUCTION
6 BRIGGSandSTRATTON.COM
Delivery Inspection
After opening the carton, carefully inspect the transfer
switch components for any damage that may have occurred
duringshipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor’s
memo of loss or damage. If loss or damage is noted after
delivery, contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment contents
 • Automatictransferswitch(1)
 • Installationandoperator’smanual(1)
 • Currenttransformers(2)
To be supplied by installer:
 • Connectingwireandconduit
 • Variousspecialtytools/equipment
Mounting Guidelines
The system circuitry is enclosed in a NEMA Type 3R
enclosure suitable for indoor/outdoor use. Guidelines for
mounting the enclosure include:
 • Installenclosureonafirm,sturdysupportingstructure.
 • TheenclosuremustbeinstalledwithminimumNEMA
3R hardware for conduit connections.
 • Levelandplumbtheenclosure.Thiscanbedone
by placing washers between the enclosure and the
mounting surface.
 • NEVERinstalltheswitchwhereanycorrosive
substance might drip onto the enclosure.
 • Protecttheswitchatalltimesagainstexcessive
moisture, dust, dirt, lint, construction grit and corrosive
vapors.
Typical automatic transfer switch installations are depicted
below. It is best if the transfer switch is mounted near
the utility meter, either inside or outside. Discuss layout
suggestions/ changes with the owner before beginning the
system installation process.
Main
Distribution
Panel
Transfer
Switch
Hot Water
Heater
Air
Conditioner
Contactor
Disconnect Switch
Generator
Watt -
Hourmeter
Branch
Circuits
Emergency Branch
Circuits
— — — — — — Control Wiring
Emergency
Load
Center
071018 &071019
071020 & 071022
Main
Distribution
Panel
Transfer Switch
w/ Service
and Generator
Disconnect
Hot Water
Heater
Air
Conditioner
Generator
Watt -
Hourmeter
— — — — — — Control Wiring
Disconnect Switch
Contactor
Branch Circuits
NOT
FOR
REPRODUCTION
7
Power Wiring Interconnections
All wiring must be the proper size, properly supported
and protected by conduit. All wiring should be done per
applicable federal, state and local codes, standards and
regulations. Obey wire type and torque specifications printed
on the terminal blocks and neutral/ground connector.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator.
Useunstaller-supplied300VACorgreaterwirethatcomplies
with Table 310.16 in the National Electric Code. Apply the
necessary correction factors and wire size calculations.
1. Set generator’s system switch to OFF position.
2. Set generator’s circuit breaker to OFF (open) position.
3. Turn off utility power to the standby generator and
transfer switch.
4. Connect transfer switch to utility power:
To connect models 071018 and 071019 to utility:
 • Connectcopperfeederconductorsfrommain
distribution panel two-pole breaker to transfer switch
terminals marked “UTILITY CONNECTION”.
 • Connectcopperconductorfrommaindistributionpanel
neutral bus to transfer switch neutral terminal.
 • Connectcopperconductorfrommaindistributionpanel
ground bus to transfer switch “GND” terminal.
NOTE: Assure grounding electrode conductor is
connected and bonded per applicable federal, state and
local codes, standards and regulations.
To connect models 071020 and 071021 to utility:
 • Connectutilityservicetotransferswitchservice
disconnect circuit breaker terminals marked
“UTILITYCONNECTION”.
 • Connectutilityserviceneutraltotransferswitch
neutralterminal.
5. Connect copper feeder conductors from transfer
switch breaker “GENERATOR CONNECTION” terminals
to generator control panel breaker LINE1 and LINE2
terminals. Each conductor must pass through hole of
current transformer before makingconnection.
6. Plug current transformer leads into “CT1” and “CT2”
terminals on control module.
7. Connect copper conductor from transfer switch
neutral terminal to generator control panel NEUTRAL
terminal. Observe control panel labeling for
terminalidentification.
8. Connect copper conductor from transfer switch “GND”
terminal to generator control panel GROUND terminal.
NOTE: Assure generator equipment grounding conductor
is connected per applicable federal, state and local codes,
standards and regulations.
WARNING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
• Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
NOTICE Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit
boards in live circuits will damage the board and is not
covered by warranty. ALWAYS disconnect ALL sources of
power prior to servicing.
• Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the board
when making electrical connections.
• Turn generator to OFF position.
• Turn off utility power to the standby generator and
transfer switch.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
33
240V
11
22
44
11
22
44
120V
120V
0
Neutral
Ground
To Transfer Switch
Line 1 Neutral
Ground
Line 2
Circuit
Breaker
NOT
FOR
REPRODUCTION
8 BRIGGSandSTRATTON.COM
9. Connectthetransferswitch“UTILITY240VAC”
terminalstogenerator’s“240VAC”terminals
usinginstallersupplied300VACorgreatercopper
wire, minimum #14 AWG conductors via supplied
two-poleconnector.
10. Connect “T/R” and “GND” terminals on transfer
switch control board (B) to the generator’s control
panel (A) “TxRx” and “TxRx GND” terminals using
#18 AWG twisted pair copper conductors, no greater
than 200 ft in length, 300 volt 75°C-90°C via supplied
ten-poleconnector.
11. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torque values.
• Whenconnectingtocircuitboardterminalblocks,
fasten only one wire to each connector screw.
Connector tightening torques shall be asfollows:
Utility - 50 in-lb (5.5 Nm) Ground - 50 in-lb (5.5 Nm)
Generator - 50 in-lb (5.5 Nm)
Control - 12 in-lb (1.4 Nm)
Neutral - 110 in-lb (12.5Nm)
Fuseblocks - 12 in-lb (1.4Nm)
Use oxide inhibitor on all aluminum terminations.
All terminal and bus lugs are suitable for copper wire of
60°/75°C rating.
The illustrations on the following pages show typical
completed installations. Your actual installation will vary.
Supervisory Control Wiring
An air conditioner can be used with the supervisory contacts
on either terminals A-A or B-B. Terminals A-A can only be
used with supervisory control. Large loads can only be used
with contactor control on terminals B-B. Examples of each
system are described below.
1. The terminal strip on the control module in transfer
switch has four connections for customer use. There
are two sets of “Normally Closed” contacts available.
They will be activated when generator power is
required. These can be used for supervisory control
of large connected loads on generator. Loads will
be allowed to operate if there is enough generator
poweravailable.
NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.
2. Terminals “A-A” on control module are rated for
24VACandairconditionercontactorcontrol.Contacts
are connected in series with the air conditioner
contactor control circuit.
3. Terminals “B-B” on control module are rated for 1 Amp
125VACandinstallersuppliedcontactortocontrol
a large load, such as an electric hot water heater.
Contacts are connected in series with the contactor
control circuit.
4. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torque values.
A
B
A
A
Air Conditioner Contactor
24VAC
B
B
Contactor
Neutral
120VAC
NOT
FOR
REPRODUCTION
9
Essential Circuit
Sub Panel
Ground
Terminal
Load
Connection
Generator
Connection
Utility
Connection
Supervisory
Contacts
Neutral
Terminal
UTILITY 240VAC to Generator
T/R and GND
to Generator
T
XRX
TXRX Gnd
Two Pole
Breaker
Neutral
Bus
Ground
Bus
To Utility
Main
Distribution
Panel
Automatic
Transfer
Switch
B&S Generator
G
CT’s
240VAC
L1
L2
N
Neutral
Bus
Ground
Bus
G
E1
E2
N
240
VAC
L1
L2
N
L1
L2
N
G
G
E1
E2
N
Models 071018 & 071019
NOT
FOR
REPRODUCTION
10 BRIGGSandSTRATTON.COM
Ground
Terminal
Load
Connection
Generator
Connection
Utility
Connection
Supervisory
Contacts
Neutral
Terminal
UTILITY 240VAC
to Generator
T/R and Gnd
to Generator
T
XRX
TXRX Gnd
To Utility
Main
Distribution
Panel
Automatic
Transfer
Switch
B&S Generator
G
CT’s
240VAC
Neutral
Bus
Ground
Bus
E1
E2
N
240
VAC
L
1
L
2
N
G
G
E1
E2
N
L
1
L
2
N
Models 071020 & 071021
NOT
FOR
REPRODUCTION
11
System Setup
You must perform the following before operating the system:
 • Ifgeneratorisinstalledinanarearegularlysubjected
to temperatures below 40°F (4°C), select a 50 second
warm up time by moving jumper installed on JP2 from
‘20’ position to ‘50’ position.
 • Settwo-positionSW1onthecontrolmoduletomatch
the fuel supplied to the home standby generator, either
NG or LP.
 • Setthree-positionSW2onthecontrolmoduleto
match the KW rating of the home standby generator:
12,15or20.
System Test
With the generator system switch in AUTO, turn the service
disconnect feeding the transfer switch to the OFF position.
After a few minutes the generator will start and the transfer
switch will transfer to generator power.
To return to utility power, turn the service disconnect feeding
the transfer switch to the ON position.
Controls
Other than a Manual Override lever, there are no operator
controls because this is an automatic transfer switch. The
manual override is to be used only by licensed professionals.
Operation
To select automatic transfer operation, do the following:
1. Set service disconnect switch that sends utility power
to transfer switch contactor to “ON” position.
2. Install 15 Amp fuse in generator’s control panel.
3. Set generator’s circuit breaker to “ON” position.
4. Set generator’s system switch to “AUTO” position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the control module is constantly monitoring
generator power. If the air conditioner is called to run, and
there is sufficient generator power available, the controller
will close contacts “A-A” to air conditioner contactor.
Contacts “B B” will open before contacts A-A close. If loads
are too great for the generator, contacts A-A and/or B-B will
open. When air conditioning is not needed, A-A will open. If
enough power is available, B-B will close.
Enclosure Door
To open door, press the spring-load door lock to the right
and pull down on the door.
To close and latch door, push door closed against enclosure.
While in this position, push door upwards. This will cause
spring-load door lock to engage and latch door in place.
NOTE: Enclosure door MUST be closed and latched at all
times except when system is being serviced.
2 Position
Switch SW1
3 Position
Switch SW2
JP2
CT1 & CT2
Connectors
Supervisory
Contacts
NOT
FOR
REPRODUCTION
12 BRIGGSandSTRATTON.COM
Testing the Automatic Transfer Switch
Turn the main distribution panel breaker or service
disconnect feeding the transfer switch contactor to the “Off”
position. The system’s automatic sequence will initiate.
To return to utility power, turn the main distribution panel
breaker or service disconnect to the “On” position.
Utility Fail
The generator senses when utility voltage is below
70percent of nominal. Engine start sequence is initiated
after 6second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer. Use
jumper on control board to select delay of 20 seconds or
50seconds.
Transfer
Transfer from utility to generator supply occurs after voltage
is above set levels. Minimum engine run time is 5 minutes
after transfer.
Utility Pickup
Voltagepickuplevelis80percentofnominalvoltage.
Retransfer
Retransfer from generator to utility power is approximately
10 seconds after utility voltage supply is above pickup level
and minimum run time is completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visualinspectionsshouldbedoneatleastonceamonth.
Access to transfer switch must not be obstructed. Keep
3feet (92 cm) clearance around transfer switch. Check
for an accumulation of dirt, moisture and/or corrosion
on and around the enclosure, loose parts/hardware,
cracks and/or discoloration to insulation, and damaged or
discoloredcomponents.
Exercise the transfer switch at least once every three months
as described in Testing the Automatic Transfer Switch unless
a power outage occurs and home generator system has gone
through an automatic sequence. Allow generator to run for at
least 30minutes.
Contact a licensed electrical professional to inspect and clean
the inside of the enclosure and other components of your
home generator system at least once a year.
When Calling for Assistance
You must have the Model Number and Serial Number from
the unit ID label at hand if it is necessary to contact a local
service center regarding service or repair of this unit. Obtain
this information from the unit ID label located on or inside
the enclosure.
To contact Briggs & Stratton call (800) 743 4115, between
8:00 AM and 5:00 PM CT.
Installation Inspection
Before placing the generator system into service, inspect the
entire installation carefully.
Complete the ”Installation Checklist” supplied with the
generator as you make the inspection. Ensure all items have
been filled-in and all signatures have been obtained. Instruct
the owner to mail the white copy to:
Warranty Registration
P. O. Box 239
Jefferson, WI 53549
NOT
FOR
REPRODUCTION
13
Troubleshooting
Problem Cause Correction
Automatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Automatic transfer switch does not
transfer to utility
1. Main distribution panel breaker open
(Models 071018 & 071019 only).
2. Service disconnect breaker open
(Models 071020 & 071021 only).
3. Utility voltage not acceptable.
1. Reset main distribution panel breaker
(Models 071018 & 071019 only).
2. Reset service disconnect breaker
(Models 071020 & 071021 only).
3. Wait for utility voltage to return
tonormal.
Generator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power
1. A-A or B-B contacts not
operatingcorrectly.
2. Too much load on generator.
3. Current transformer not connected.
4. Broken current transformer.
1. Check A-A or B-B contacts for proper
operation and/or check control wiring
to external load.
2. Decrease load to generator.
3. Plug CT connectors into
controlboard.
4. Contact local service center.
Generator is still running after utility
power is restored
1. Minimum engine run time has
notelapsed.
2. Fuse(s) in transfer switch is defective.
1. Wait five minutes for transfer switch
to retransfer to utility power.
2. Check fuse(s) and replace
ifnecessary
NOT
FOR
REPRODUCTION
14 BRIGGSandSTRATTON.COM
Schematic and Wiring Diagram, Models 071018 and 071019
NOT
FOR
REPRODUCTION
15
Schematic and Wiring Diagram, Models 071020 and 071021
NOT
FOR
REPRODUCTION
16 BRIGGSandSTRATTON.COM
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty
repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if
equipment damage occurred because of misuse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the
warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During
the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal
use and service. This warranty will not cover the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover
repair when normal use has exhausted the life of a part or the equipment.
• Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation
or alteration and modification, misuse, negligence, accident, overloading, improper maintenance, repair or storage so as, in our judgment, to adversely
affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, cleaning and fuse replacement.
• Other Exclusions: This warranty excludes wear items or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or
improper servicing. Accessory parts are excluded from the product warranty. This warranty excludes failures due to acts of God and other force
majeure events beyond the manufacturers control. Also excluded is used, reconditioned, and demonstration equipment. 198180E, Rev. C, 12/31/2006
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON, WI, USA
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated in the
table above. “Consumer use” means personal residential household use by a retail consumer. “Commercial use” means all other uses, including use for
commercial, income producing or rental purposes. Once equipment has experienced commercial use, it shall thereafter be considered as commercial use for
purposes of this warranty. Equipment used for prime power in place of utility are not applicable to this warranty.
NOWARRANTYREGISTRATIONISNECESSARYTOOBTAINWARRANTYONBRIGGS&STRATTONPRODUCTS.SAVEYOURPROOFOFPURCHASE
RECEIPT.IFYOUDONOTPROVIDEPROOFOFTHEINITIALPURCHASEDATEATTHETIMEWARRANTYSERVICEISREQUESTED,THEMANUFACTURING
DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
3 years
None
Consumer Use
Commercial Use
WARRANTY PERIOD
Warranty
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC TRANSFER SWITCH OWNER WARRANTY POLICY
Effective November 1, 2005 replaces all undated Warranties and all Warranties dated before November 1, 2005
LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or
workmanship or both. Transportation charges on product submitted for repair or replacement under this warranty must be borne by purchaser. This
warranty is effective for the time periods and subject to the conditions stated below. For warranty service, find the nearest Authorized Service Dealer in
our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE
EXCLUDED.LIABILITYFORINCIDENTALORCONSEQUENTIALDAMAGESAREEXCLUDEDTOTHEEXTENTEXCLUSIONISPERMITTEDBYLAW.Some
states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and you
may also have other rights which vary from state to state or country to country.
NOT
FOR
REPRODUCTION
17
Product Specifications
Model 071018
Rated Maximum Load Current*
(at 25°C/77°F) ......................................................100 Amps
RatedACVoltage .................................................... 250Volts
Poles .................................................................................... 2
Frequency ..................................................................... 60 Hz
Fault Current Rating ....... 22,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals.................................................... 24VoltAC
B-B Terminals.................... 1Amp,125VoltAC,PilotDuty
Normal Operating Range .... -20°F (-28.8°C) to 104°F (40°C)
Weight ............................................................25 lbs. (11 kg)
Model 071019
Rated Maximum Load Current*
(at 25°C/77°F) ......................................................200 Amps
RatedACVoltage .................................................... 250Volts
Poles .................................................................................... 2
Frequency ..................................................................... 60 Hz
Fault Current Rating ....... 25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals.................................................... 24VoltAC
B-B Terminals.................... 1Amp,125VoltAC,PilotDuty
Normal Operating Range .... -20°F (-28.8°C) to 104°F (40°C)
Weight ............................................................38 lbs. (17 kg)
Model 071020
Rated Maximum Load Current*
(at 25°C/77°F) ......................................................100 Amps
RatedACVoltage .................................................... 250Volts
Poles .................................................................................... 2
Frequency ..................................................................... 60 Hz
Fault Current Rating ....... 22,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals.................................................... 24VoltAC
B-B Terminals.................... 1Amp,125VoltAC,PilotDuty
Normal Operating Range .... -20°F (-28.8°C) to 104°F (40°C)
Weight ............................................................40 lbs. (18 kg)
Model 071021
Rated Maximum Load Current*
(at 25°C/77°F) ......................................................200 Amps
RatedACVoltage .................................................... 250Volts
Poles .................................................................................... 2
Frequency ..................................................................... 60 Hz
Fault Current Rating ....... 25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals.................................................... 24VoltAC
B-B Terminals.................... 1Amp,125VoltAC,PilotDuty
Normal Operating Range .... -20°F (-28.8°C) to 104°F (40°C)
Weight ............................................................63 lbs. (29 kg)
Automatic Transfer Switch
Briggs & Stratton Power Products Group, LLC
900 N. Parkway
Jefferson, Wisconsin, 53549 U.S.A.
*This transfer switch is certified in accordance with UL (Underwriters Laboratories) 1008 (transfer switch equipment).
NOT
FOR
REPRODUCTION
18 BRIGGSandSTRATTON.COM
Reserved
NOT
FOR
REPRODUCTION
Generator Systems
Manual de Instalación y del Operario
100/200 Amperios
Interruptor de
transferencia automática
NOT
FOR
REPRODUCTION
2 BRIGGSandSTRATTON.COM
Gracias por comprar este conectador automático de Briggs & Stratton® Power Products. Este producto está diseñado para
utilizarse con generadores de reserva domésticos específicos y puede no funcionar con generadores producidos por otros
fabricantes. Recurra a un electricista profesional cualificado para determinar la aplicabilidad de este equipo en generadores
fabricados por terceros. Si se utiliza y mantiene de acuerdo con las instrucciones de este manual, su sistema le proporcionará
muchos años de funcionamiento fiable.
Este manual contiene información de seguridad para que usted conozca los peligros y riesgos propios de este sistema y
cómo evitarlos. Se ha realizado el máximo esfuerzo para que la instalación resulte segura, sencilla y económica. Debido a que
cada instalación es única, es imposible conocer y recomendar todos los procedimientos y métodos posibles para efectuarla.
No conocemos todos los riesgos y/o resultados posibles de cada método o procedimiento existente. Es importante que lea
y comprenda perfectamente estas instrucciones antes de intentar instalar o utilizar este equipo. Guarde estas instrucciones
para futuras consultas.
Este el conectador requiere instalación profesional antes de utilizarse. Consulte las instrucciones sobre los procedimientos
de instalación en la sección Instalación del presente manual. Los conectador sólo deben ser instalados por electricistas con
licencia. Las instalaciones deben cumplir estrictamente la totalidad de los códigos, estándares y regulaciones federales,
estatales y locales vigentes. El instalador debe seguir las instrucciones detalladamente.
Ubicación
Nunca debe ir demasiado lejos para encontrar el soporte y servicio de Briggs & Stratton para su sistema. Consulte las
Páginas Amarillas. Existen múltiples distribuidores de servicio autorizados que ofrecen un servicio de calidad. También puede
comunicarse con el Servicio técnico por teléfono al (800) 743 4115 de 8:00 a. m. a 5:00 p. m. Hora del Centro, o a través de
Internet en BRIGGSandSTRATTON.COM.
Para futuras consultas
Llene la siguiente información y conserve su factura para facilitar la identificación de la unidad en caso de que surjan
problemas relacionados con la compra en el futuro.
Conectador automático
Número de modelo
Revisión
Número de serie
Fecha de compra
Briggs & Stratton Power Products Group, LLC.
P.O. Box 702
Milwaukee, WI 53201-0702
Copyright©2012.Reservadostodoslosderechos.Quedaprohibidala
reproducción o transmisión total o parcial de este material, sin el permiso
previo y por escrito de Briggs & Stratton Power Products Group, LLC.
NOT
FOR
REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Simplicity 071019-0 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
Ce manuel convient également à