MAIN DEVICE
MOUNTING FEET
MOUNTING RAIL(S)
“X”
“Z”
MOUNTING FEET
Fig. 1 Locations of Mounting Feet, Rails, and Modules
Fig. 2 Ring Type and Ringless Covers
METER COVER
SCREWS
MOVABLE LATCH
RING STYLE
COVER
RINGLESS STYLE
COVER
35SS, 37SS - 2,3 METER
35SS, 37SS - 1 METER
1MM, 3MM - 200 AMP
1MM, 3MM - 125 AMP
TYPE OF METER MODULE
35-3/16 (893.76)
17-1/16 (433.39)
34-7/32 (869.16)
34-7/32 (869.16)
“X” in.(mm)
18-1/2 (469.90)
19-27/32 (504.03)
18-15/32 (469.11)
12-19/32 (319.88)
“Z” in.(mm)
35MM, 37MM - 2 METER
35MM, 37MM - 1,3,4 METER
30-11/16 (779.46)
30-11/16 (779.46)
27 (685.80)
13 (330.20)
Installation Instructions for Type 1MM, 3MM, 35MM, 37MM,
35SS, and 37SS Modular Metering Centers
H A Z A R D O U S VO LTAG E . W I L L CAU S E
SEVERE INJURY OR DEATH.
VOLTA JE P ELIGROSO. CAUSA HERI DAS
SEVERAS O MUERTE.
Tur n OFF power suppl ying this equ ipme nt befor e worki ng
inside.
INTERRUMPA el suministro de energia que alimen ta este
e qu i p o a nt e s d e tr ab a j a r en e l i n te r i o r del m i s m o.
PELIGRO
DANGER
MOUNTING FEET:
Swivel the mounting feet at the top and bottom of the en-
closures as shown (meter modules have two mounting feet
and main devices have four mounting feet). After marking
holes on the wall, the mounting feet may be moved away
for drilling of the holes. (See Fig. 1 below).
Please read these instructions completely before installing
or removing device. Improper installation could be
hazardous to personnel and/or equipment.
Por favor lea estas instrucciones en su totalidad antes de
instalar o mover el aparato. Una instalacion inapropiada
puede ser peligrosa para el personal y/o el equipo.
Veuillez lire les présentes directives au complet avant
d’installer ou de retirer le dispositif. Une mauvaise installation
pourait causer des blessures au personnel et/ou
endommager l’equipement.
INSTALL MOUNTING RAILS ON WALL:
Establish the required height of the centerline of the bottom
meter socket, per the utility company specifications.
Determine the bottom line of the meter modules and main
devices. Use a “Z” dimension per the table below. That
is the distance from the bottom meter socket line to the
bottom of a meter module.
Measure up a distance “X” (see table) inches from the
bottom line of the meter modules to mounting holes for the
mounting rail. Strike a level line for the fasteners and attach
the mounting rails. (See Fig. 1 below).
METER SOCKET COVERS:
Remove all the meter socket covers which are over the
horizontal main bus. Ring style covers are attached with
two screws inside the socket rim. Ringless style covers
are attached with an external movable latch. (See Fig. 2).
Ringless style covers have barrel lock provision K.O. To
use, remove knockout and apply kit 3MMBLKIT or 37MMBLK.
METER MODULES:
Hang meter modules on the mounting rails, loosen all of
the main bus joint bolts, and slide the meter modules
together.
Fasten the enclosures together, in order to bond devices
together and provide suitable ground path, with the (2) # -
20 screws supplied with each module.
Torque to 26 lb-in (2.94 N-m).
Torque each main bus joint bolt to 300 lb-in (33.90 N-m).
Secure mounting feet to the wall. (See Fig. 3 on Page 2).
TENSION DA N G E R E U S E . PEUT CAUS E R
DES BLESSURES GRAVES O U LA MORT.
Coup er l’alimen tatio n élect riqu e d e c et éq uipem ent avant
d’y effectuer des travaux.
)
I.L. 70-8306
1