– ECO-i System Air Conditioner –
INSTALLATION AND OPERATION MANUAL
R410A Models
Indoor Units
Outdoor Units
SPW-UMR74EXH56
SPW-UMR94EXH56
SPW-UMR124EXH56
SPW-UMR164EXH56
SPW-UMR184EXH56
SPW-UMR224EXH56
* Refrigerant R410A is used in the outdoor units.
C
DC Inverter Main Unit SPW-CR604GDXH8, SPW-CR704GDXH8, SPW-CR904GDXH8, SPW-CR1154GDXH8
Constant Speed (Sub) Unit SPW-CR704GDCH8, SPW-CR904GDCH8, SPW-CR1154GDCH8
Optional Controllers
Remote Controller RCS-SH80AG
RC Wireless Remote Controller RCS-BH80AG.WL
Simplified Remote Controller RCS-KR1AG
for Refrigerant R410A
SANYO Airconditioners Europe S.r.l.
Via Bisceglie, No. 76
20152 Milano, Italy
37.4196.054.0 ©SANYO 2005
2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operat-
ing standards. As the installer or service person, it is an
important part of your job to install or service the system so it
operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
This product is intended for professional use.
Permission from the power supplier is required when
installing an outdoor unit that is connected to a 16 A
distribution network.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including fail-
ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this sys-
tem. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inad-
equate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
When Installing
In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
In an area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free con-
nection.
Check carefully for leaks before starting the test run.
Depending on the system type, liquid and gas lines may
be either narrow or wide. Therefore, to avoid confusion
the refrigerant tubing for your particular model is speci-
fied as either “narrow” or “wide” than as “liquid” or “gas.”
When Servicing
Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical parts
and wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
Ventilate any enclosed areas when installing or testing the
refrigeration system. Escaped refrigerant gas, on contact
with fire or heat, can produce dangerously toxic gas.
Confirm after installation that no refrigerant gas is leak-
ing. If the gas comes in contact with a burning stove, gas
water heater, electric room heater or other heat source, it
can cause the generation of poisonous gas.
NOTE
WARNING
WARNING
CAUTION
CAUTION
3
2. The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top
or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when mechanical ventilation is installed inter-
locked with a gas leakage detector in the smallest
room where the density limit is exceeded, the vol-
ume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows: (When
the ceiling is 2.7 m high)
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air condi-
tioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to pro-
tect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent. With the recent
increase in the number of high density buildings, how-
ever, the installation of multi air conditioner systems is
on the increase because of the need for effective use
of floor space, individual control, energy conservation
by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is
able to replenish a large amount of refrigerant com-
pared to conventional individual air conditioners. If a
single unit of the multi air conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant acci-
dentally leaks out, its density does not reach the limit
(and in the event of an emergency, measures can be
made before injury can occur).
In a room where the density may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device. The density is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
3
)
Density limit (kg/m
3
)
The density limit of refrigerant which is used in multi air con-
ditioners is 0.3 kg/m
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a sin-
gle refrigerating device, the amount of refrigerant
should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15 kg.
NOTE
Outdoor unit
Refrigerant tubing
Indoor unit
e.g., charged
amount (10 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
e.g., charged
amount (15 kg)
Refrigerant tubing
Outdoor unit
Very
small
room
Indoor unit
Small
room
Medium
room
Large room
Mechanical ventilation device Gas leak detector
40
35
30
25
20
15
10
5
0
10 20 30
Total amount of refrigerant
Min. indoor floor space
m
2
kg
Range below the
density limit
of 0.3 kg/m
3
(countermeasures
not needed)
Range above
the density limit
of 0.3 kg/m
3
(countermeasures
needed)
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of
instructions for the indoor unit and make sure all accessory parts listed are with the system before beginning.
1-2. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately
from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness
of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire
size varies with the total length of wiring. Refer to
4. Electrical Wiring for details.
1-3. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
CAUTION
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions
or limitations.
4
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Read Before Starting
Check of Density Limit
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-1. Tools Required for Installation (not supplied)
1-2. Type of Copper Tube and Insulation Material
1-3. Additional Materials Required for Installation
2. HOW TO INSTALL THE UNIT . . . . . . . . . . . . . .5
2-1. Duct for fresh air
3. TEST OF THE SYSTEM AND CONTROL OF THE
AIR VOLUME TO THE OUTLET GRILLES . . . .7
CONTENTS
Page
Page
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenters level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
4. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . .8
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire Diame-
ter for Power Supply System
4-3. Wiring System Diagrams
5. HOW TO PROCESS TUBING . . . . . . . . . . . . . .12
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing between Indoor and Out-
door Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
6 APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5
2. HOW TO INSTALL THE UNIT
Fig. 2-1
Minimum operation and maintenance area. (fig. 2-1)
Fig. 2-2
Fig. 2-4
Find the space for the installation of the return air grille and
mark the opening to do. Cut the falseceiling. (fig. 2-2)
Use rawl plug suitable to the ceiling consistence and four
M10 threaded bars of suitable length (not supplied). (fig. 2-
3)
Mark on the ceiling the holes for the hanging rods, verify the
distance of the centres. The value included in the brackets
is referred to the model X18. (fig. 2-4)
Drill a 80 mm diameter hole, for the passage of refrigeration
pipework, condensate pipework and electrical cable. Insert
a PVC pipe in the wall. (fig. 2-5)
Secure the unit in position with locknuts and washers, level
the unit, keeping the right distance from the falseceiling for
the installation of return air grille. (fig. 2-6)
Foresee a removable panel of the falseceiling for servicing.
(fig. 2-7)
The unit is supplied with PVC hose from the condensate
pump. Maximum pump lift is 250 mm over the unit. Convoy
the condensate with a positive slope (min. 1:100) to the out-
side. The highest point in the condensate pipework should
be as close to the unit as possible. This prevents a large
volume of water draining back into the unit when it is
switched off. (fig. 2-8)
Convoy the condensate to the outside with a positive slope,
from a trap at the end if necessary. (fig. 2-9)
300
Fig. 2-3
Fig. 2-5
Fig. 2-6
Fig. 2-7
Fig. 2-8
Fig. 2-9
7/9/12 1500 1100
16/18/22 1700 1100
AB
6
Intake coduct
False ceiling
Air intake
Outlet conduct
On the front and rear side of the unit a rectangular port
(with flange) helps during duct mounting. (fig. 2-10)
Rear and front flange for the air intake. The value included
in the brackets is referred to the model X18. (fig. 2-11)
Discarge air duct (optional accessory).
Contact the After Sale Service. (fig. 2-12)
Remove the filter and pour, inside the condensate drain
pan, 0.5 liter of water. Start the unit checking for proper
drain pump operation. (fig. 2-13)
Fig. 2-10
Fig. 2-11
Fig. 2-12
Fig. 2-13
2
1
There is a duct connection port for drawing in fresh air.
The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON-OFF switch
with safety fuses.
Fresh air flow must be about 10% of the total air flow to avoid operating problems and noise.
Open the knock-out hole , fix a 120 mm flange on the unit and connect the thermically insulated duct.
Install an outside grille with filter inspection port to prevent dust and leaves from entering and fouling the indoor unit heat
exchanger.
2-1 Duct for fresh air
7
3. TEST OF THE SYSTEM AND CONTROL OF THE AIR VOLUME TO THE OUTLET GRILLES
The unit is prearranged to supply an external static pressure
of about 5 mm. Too high resistances in the air distribution
system can cause an exceedingly small air volume to the
outlet grilles.
This trouble can be solved by increasing the fan speed as
follows:
Open the cover of the electrical junction box. Take out the
booster cable clamped in the box. (fig. 3-1)
Disconnect the fan motor plug in the electrical box and insert
the booster cable as a cable extension between the motor
plug and the socket from the PCB. The external static pres-
sure will increase to 7 mm w.g. Check static pressure and air
flow rate on the fan performance graph. (fig. 3-2)
Fan motor
Fan motor
Booster cable
Booster cable
Connector motor cable (at the supply)
Fig. 3-1
Fig. 3-2
0
2
4
6
8
10
200 400 600 800 1000
H
HH
M
L
0
2
4
6
8
10
300 500 700 900 1100 1300 1500
L
M
H
HH
7/9/12
16/18/22
m
3
/h
m
3
/h
EXTERNAL STATIC PRESSURE (mmW.G.)
EXTERNAL STATIC PRESSURE (mmW.G.)
H = High fan speed
L = Low fan speed
HH = Very high fan speed
M = Middle fan speed
H: Standard supplied unit. Available fan speeds: Low-Midd-
le-High (L - M - H). Max. static pressure: about 5 mm
HH: Unit with cable extension of the fan motor (booster
cable). Available fan speeds: Middle-High-Very high (M -
H - HH). Max. static pressure: about 7 mm
8
Control wiring
(C) Inter-unit (between outdoor and
indoor units) control wiring
(D) Remote control wiring (E) Control wiring for group control
(F) Inter-outdoor unit control wiring
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring* Use shielded wiring Use shielded wiring
0.75 mm
2
(AWG #18)
Use shielded wiring
Max. 1,000 m
Max. 500 m
Max. 500 m (Total)
Max. 500 m
4. ELECTRICAL WIRING
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and cir-
cuit breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES before begin-
ning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit
power wiring.
Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop
appointed by the manufacture, because special
purpose tools are required.
4-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power supply
(A) Power supply
Wire size Max. length
Wire size Max. length
SPW-CR604GDXH8 113 m 15 A
SPW-CR704GDXH8 74 m 30 A
SPW-CR904GDXH8 60 m 35 A
SPW-CR1154GDXH8 55 m 40 A
SPW-CR704GDCH8 47 m 35 A
SPW-CR904GDCH8 46 m 40 A
SPW-CR1154GDCH8
4 mm
6 mm
6 mm
6 mm
6 mm
6 mm
6 mm
2.5 mm
2
6 mm
2
6 mm
2
10 mm
2
6 mm
2
10 mm
2
10 mm
2
2
2
2
2
2
2
2
39 m 50 A
Time delay fuse or
circuit capacity
Time delay fuse or
circuit capacity
or
70 m
74 m
60 m
91 m
47 m
77 m
65 m
16A
35A
35A
50A
35A
50A
50A
Indoor unit
Time delay fuse or
circuit capacity
(B) Power supply
2.5 mm
2
Max. 130 m
10 ~ 16A
NOTE
* With ring-type wire terminal.
9
4-3. Wiring System Diagrams
U2
U1
1
2
2
1
U2
U1
4
3
3
4
5
2
1
WHT
Remote
controller
BLK
2
1
U2
U1
1
2
U2
U1
1
2
U2
U1
1
2
2
1
WHT
Remote
controller
Group control:
BLK
2
1
2
1
WHT
Remote
controller
D
A
E
Indoor
unit (No. n)
Indoor
unit (No. 1)
Indoor
unit (No. 2)
Indoor
unit (No. 3)
C
B
Outdoor unit
INV unit
L1
Power supply
L2
L3
380-415V-3N 50Hz
N
Ground
Ground
L
N
L
N
L
N
L
N
BLK
2
1
2
1
4
3
3
4
5
Outdoor unit
CS unit
Power supply
220-240V 50Hz
B
B
B
Ground
Ground
Ground
Ground
A
L1
Power supply
L2
L3
N
Ground
380-415V-3N 50Hz
Power supply
220-240V 50Hz
Power supply
220-240V 50Hz
Power supply
220-240V 50Hz
Ground
C
Ground
F
Ground
D
D
C
Ground
C
Ground
Inter-outdoor-unit control wiring
R2
R1
R2
R1
R2
R1
R2
R1
NOTE
(1) Refer to Section 5-2. Recommended Wire Length
and Wire Diameter for Power Supply System for
the explanation of A, B, C, D, and E, in the
above diagrams.
(2) The basic connection diagram of the indoor unit
shows the 7P terminal board, so the terminal
boards in your equipment may differ from the dia-
gram.
(3) Refrigerant Circuit (R.C.) address should be set
before turning the power on.
7P terminal board
1(L)
power
supply
2(N) U1 U2
Inter-unit
control
wiring
R1 R2
Remote
controller
10
Outdoor unit Outdoor unit Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
more than 1 m
more than 1 m
Branch
point
16 or fewer
Indoor unit
Indoor unit Indoor unit Indoor unit
less than 1 m
Indoor unit
Outdoor unit Indoor unit Indoor unit Indoor unit
Indoor unit Indoor unit Indoor unit
Outdoor unit
Indoor unit
NO
NO
Branch point
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no con-
nection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)
Outdoor unit Outdoor unit Outdoor unit
Prohibited
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Fig. 4-1
Fig. 4-2
Fig. 4-3
CAUTION
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address
setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.) (Fig. 4-3)
11
Fig. 4-4
Shielded wire
Ground
Ground
Fig. 4-5
Stranded wire
Ring
pressure
terminal
Strip 10 mm
Fig. 4-6
Wire
Special
washer
Screw
Ring pressure
terminal
Terminal plate
Screw and
Special washer
Ring
pressure
terminal
Wire
(5) Use shielded wires for inter-unit control wiring
(c) and ground the shield on both sides, other-
wise misoperation from noise may occur.
(Fig. 4-4)
Connect wiring as shown in Section 4-3.
Wiring System Diagrams.
WARNING
Loose wiring may cause
the terminal to overheat or
result in unit malfunction.
A fire hazard may also
exist. Therefore, ensure
that all wiring is tightly
connected.
When connecting each power wire to the terminal, fol-
low the instructions on How to connect wiring to the
terminal and fasten the wire securely with the fixing
screw of the terminal plate.
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10
mm and tightly twist the wire ends. (Fig. 4-5)
(2) Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw-
driver. (Fig. 4-6)
12
5. HOW TO PROCESS TUBING
The narrow tubing side is connected by a flare nut,
and the wide tubing side is connected by brazing.
5-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 30
50 cm longer than the tubing length you esti-
mate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
(Fig. 5-1)
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube. (Fig. 5-2)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a
flare tool.* (Fig. 5-3)
(*Use RIGID
®
or equivalent.)
A good flare should have the following characteristics:
inside surface is glossy and smooth
edge is smooth
tapered sides are of uniform length
NOTE
NOTE
Deburring
Before
After
Fig. 5-1
Reamer
Copper
tubing
Fig. 5-2
Flare tool
Flare nut
Copper
tubing
Fig. 5-3
13
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent
dust or water from entering the tubes before they
are used.
(2) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect-
ing them together. This is effective for reducing
gas leaks. (Fig. 5-4)
(3) For proper connection, align the union tube and
flare tube straight with each other, then screw in
the flare nut lightly at first to obtain a smooth
match. (Fig. 5-5)
Adjust the shape of the narrow tube (liquid tube)
using a tube bender at the installation site and
connect it to the narrow tubing side (liquid tubing
side) valve using a flare.
Cautions During Brazing
Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during
the brazing process. (Oxygen, carbon dioxide
and Freon are not acceptable.)
Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing
may overheat, causing refrigerant system
valves to become damaged. Therefore allow
the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the for-
mation of oxide film. These agents adversely
affect the refrigerant and refrigerant oil, and
may cause damage or malfunctions.
5-2. Connecting Tubing Between Indoor and Out-
door Units
(1) Tightly connect the indoor-side refrigerant tubing
extended from the wall with the outdoor-side tub-
ing.
(2) To fasten the flare nuts, apply specified torque as
at right:
When removing the flare nuts from the tubing con-
nections, or when tightening them after connecting
the tubing, be sure to use 2 monkey wrenches or
spanners as shown. (Fig. 5-6)
If the flare nuts are over-tightened, the flare may be
damaged, which could result refrigerant leakage
and cause in injury or asphyxiation to room occu-
pants.
For the flare nuts at tubing connections, be sure to
use the flare nuts that were supplied with the unit,
or else flare nuts for R410A (type 2). The refriger-
ant tubing that is used must be of the correct wall
thickness as shown in the table at right.
Apply refrigerant
lubricant here and here
Fig. 5-4
Flare nut
Union
Fig. 5-5
Fig. 5-6
Indoor unit
Outdoor unit
Spanner
Torque wrench
Tube diameter
φ
6.35 (1/4")
φ
9.52 (3/8")
φ
12.7 (1/2")
φ
15.88 (5/8")
Tightening torque,
approximate
14 – 18 N
·
m
(140 – 180 kgf
·
cm)
34 – 42 N
·
m
(340 – 420 kgf
·
cm)
49 – 61 N
·
m
(490 – 610 kgf
·
cm)
68 – 82 N
·
m
(680 – 820 kgf
·
cm)
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Tube thickness
Because the pressure is approximately 1.6 times
higher than conventional refrigerant pressure, the
use of ordinary flare nuts (type 1) or thin-walled
tubes may result in tube rupture, injury, or asphyxi-
ation caused by refrigerant leakage.
In order to prevent damage to the flare caused by
over-tightening of the flare nuts, use the table
above as a guide when tightening.
When tightening the flare nut on the narrow tube,
use a monkey wrench with a nominal handle length
of 200 mm.
14
Fig. 5-8
Fig. 5-7
Fig. 5-9
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tub-
ing, including distribution joint (purchased sepa-
rately).
* For gas tubing, the insulation material must be
heat resistant to 120°C or above. For other tubing,
it must be heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or
greater.
If the conditions inside the ceiling exceed DB 30°C
and RH 70%, increase the thickness of the gas
tubing insulation material by 1 step.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at
the wide tube connections. Then cover up the tubing
connections with the flare insulator, and fill the gap at
the union with the supplied black insulation tape.
Finally, fasten the insulator at both ends with the sup-
plied vinyl clamps. (Fig. 5-8)
Insulation material
The material used for insulation must have good insu-
lation characteristics, be easy to use, be age resis-
tant, and must not easily absorb moisture.
After a tube has been insu-
lated, never try to bend it
into a narrow curve
because it can cause the
tube to break or crack.
CAUTION
CAUTION
Never grasp the drain or refrigerant connecting
outlets when moving the unit.
Unit side
insulator
Insulation tape (white)
(supplied)
Sealer (supplied)
Flare insulator (supplied)
Tube insulator
(not supplied)
Heat resistant
120°C or above
Vin
y
l clamps (supplied)
Flare nut
The procedure used for
installing the insulator for
both wide and narrow
tubes is the same.
Seal
Flare
insulator
Vinyl
clamp
Insulation
tape
Refrigerant tubing and insulator
(not supplied)
Drain pipe and insulator
(not supplied)
Drain insulator
and clamp.
Large
(supplied)
Packing
clamp.
Small
hose band
(supplied)
Cosmetic
(finishing) tape
Wide tubing
Wide tubing
Narrow tubing
Narrow tubing
Insulation
Insulation
Balance tubing
Three tubes arranged together
Two tubes arranged together
If the exterior of the outdoor
unit valves has been finished
with a square duct covering,
make sure you allow suffi-
cient space to use the valves
and to allow the panels to be
attached and removed.
15
Fig. 5-10
Fig. 5-11
5-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped
together with armoring tape in 1 bundle. To pre-
vent the condensation from overflowing the drain
pan, keep the drain hose separate from the
refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it
enters the wall. As you wrap the tubing, overlap
half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1
clamp approx. each meter. (Fig. 5-10)
Do not wind the armoring tape too tightly since this
will decrease the heat insulation effect. Also ensure
that the condensation drain hose splits away from the
bundle and drips clear of the unit and the tubing.
5-5. Finishing the Installation
After finishing insulating and taping over the tubing,
use sealing putty to seal off the hole in the wall to pre-
vent rain and draft from entering. (Fig. 5-11)
NOTE
Insulated tubes
Drain hose
Clamp
Tubin
g
Apply putty here
16
6. APPENDIX
Name of Parts (Indoor Unit)
Care and Cleaning
CAUTION
WARNING
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before
cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-
nents and cause an electric shock hazard.
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic
parts using very hot water.
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be
especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be cleaned every year.
Consult your dealer or service center.
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them
(Indoor unit) with a clean, soft cloth.
Air filter
The air filter collects dust and other particles from the air and should be cleaned at regular intervals
as indicated in the table below or when the filter indication ( ) on the display of the remote control
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air
conditioner drops greatly.
<How to clean the filter>
1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the
filter in lukewarm, soapy water, rinse it in clean water, and dry it.
Type Period
UMR Six months
The frequency with which the filter should be cleaned depends on the environment in which the
unit is used.
NOTE
04-235 AirCon_X-type 9/3/04 11:40 AM Page 19
Water drain
Air outlet
Air filter
17
Care: After a prolonged idle period
Care: Before a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a
blockage, remove it.
Operate the fan for half a day to dry out the inside.
Disconnect the power supply and also turn off the circuit breaker.
Clean the air filter and replace it in its original position.
Outdoor unit internal components must be checked and cleaned periodically. Con-
tact your local dealer for this service.
CAUTION
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled
improperly; special care should be taken when you clean these parts.
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt
or soot.
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-
cally. Consult your dealer or service center.
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work
properly, contact your dealer or a service center.
Air conditioner does not run at all
1. Power failure.
1.
After a power outage, press ON/
OFF operation
button
on the
wired remote control unit.
2. Leakage circuit breaker has
tripped.
2. Contact service center.
3. Line voltage is too low.
3. Consult your electrician or dealer.
4. Operation button is turned off.
4. Press the button again.
5. The wired remote control unit or
heat pump is
(
The inspection mark and the
letters E, F,
H, L, P in
combination with numbers
appear
the LCD of the wired
remote control unit.)
5. Consult your dealer.
Compressor runs but soon stops
1. Obstruction in front of condenser
coil
1. Remove obstruction
Poor cooling (or heating)
performance
1. Dirty or clogged air filter.
1. Clean air filter to improve the
2. Heat source or many people in
room.
2. Eliminate heat source if possible.
3. Doors and/or windows are open.
3. Shut them to keep the heat (or
cold) out.
4. Obstacle near air intake or air
discharge port.
4. Remove it to ensure good airflow.
5. Thermostat is set too high for
(or too low for heating).
5. Set the temperature lower (or
higher).
6. (Defrosting system does not work.)
6. (Consult your dealer.)
Trouble
Possible Cause
Remedy
airflow.
cooling
malfunctioning.
on
Tips for Energy Saving
Avoid
Do
Do not block the air intake and outlet of the unit. If either is obstructed, the unit
will not work well, and may be damaged.
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls
and ceiling of the room are warmed by the sun, it will take longer to cool the room.
Always try to keep the air filter clean. (Refer to Care and Cleaning.) A clogged filter
will impair the performance of the unit.
To prevent conditioned air from escaping, keep windows, doors and any other open-
ings closed.
Should the power fail while the unit is running
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is
restored using the same settings before the power was interrupted.
NOTE
04-235 AirCon_X-type 9/3/04 11:40 AM Page 20
18
Nom des pièces (unité intérieure)
Entretien et nettoyage
ATTENTION
AVERTISSEMENT
1. Pour toute sécurité, éteignez le climatiseur et débranchez-le de la prise secteur.
2. Ne versez pas deau sur lunité intérieure pour la nettoyer. Cela pourrait abîmer les com-
posants internes et provoquer des décharges électriques.
1. Ne utilisez jamais de dissolvants ni de produits chimiques puissants lorsque lunité
intérieure est nettoyée. Nessuyez pas les pièces en plastique avec de leau très chaude.
2. Certains bords métalliques et les ailettes étant coupants, ils doivent être manipulés avec
précaution lors du nettoyage sous peine de provoquer des blessures.
3. La bobine interne et les autres composants de lunité extérieure doivent être nettoyés
tous les ans. Consultez le concessionnaire ou un service après-vente.
Nettoyez larrivée dair et la sortie de lunité intérieure avec la brosse dun aspirateur ou les
essuyer avec un chiffon propre et doux.
Filtre à air
Le filtre à air recueille la poussière et les particules se trouvant dans lair et doit être nettoyé à inter-
valles réguliers comme indiqué dans le tableau cidessous ou lorsque le symbole du filtre ( )
affiché sur la télécommande (avec fil) indique que le filtre doit être nettoyé. Si le filtre est bloqué,
lefficacité du climatiseur diminue nettement.
<Comment nettoyer le filtre>
1. Retirez le filtre à air de la grille de larrivée dair.
2. Se servir dun aspirateur pour enlever la poussière légère. Si de la poussière adhère au
filtre, lavez celui-ci dans de leau tiède et savonneuse, puis rincez-le dans de leau propre
et séchez-le.
Type Période
UMR Six mois
La fréquence de nettoyage du filtre dépend de lenvironnement dans lequel lunité est utilisée.
REMARQUE
Larrivée dair et la sortie dair
(unité intérieure)
04-235 AirCon_X-type 9/3/04 11:40 AM Page 21
Drain
Sortie díair
Filtre à air
19
Entretien : après une période dinactivité
prolongée
Entretien : avant une période dinactivité
prolongée
Vérifiez larrivée dair et la sortie dair des unités intérieure et extérieure et
assurez-vous quelles ne sont pas obstruées ; si elles sont obstruées, remédiez
à ce problème.
Faites fonctionner le ventilateur pendant une demi-journée pour faire sécher
lintérieur de lunité.
Débranchez lalimentation et mettez le disjoncteur en position arrêt.
Nettoyez le filtre à air et remettez-le dans sa position initiale.
Les éléments internes de lunité extérieur doivent être vérifiés et nettoyés
régulièrement. Contactez votre distributeur le plus proche pour effectuer ces
opérations.
ATTENTION
1. Certains bords métalliques et les ailettes du condensateur étant coupants, ils doivent être
manipulés avec précaution lors du nettoyage sous peine de provoquer des blessures.
2. Vérifiez régulièrement que la sortie et larrivée dair ne soient pas obstruées par de la
poussière ou de la suie.
3. La bobine interne et les autres composants de lunité extérieure doivent être nettoyés
régulièrement. Consultez le concessionnaire ou un service après-vente.
04-235 AirCon_X-type 9/3/04 11:40 AM Page 22
20
Conseils pour économiser l’énergie
À éviter
Choses à faire
Obstruer les arrivées et les sorties dair de lappareil. Si elles sont bouchées,
lappareil ne fonctionnera pas de façon satisfaisante et il risque d’être endom-
magé.
Laisser le soleil pénétrer directement dans la pièce. Utiliser des persiennes ou des
rideaux. Si les murs et le plafond de la pièce sont chauds sous laction du soleil, il faudra
plus longtemps pour refroidir la pièce.
Toujours maintenir le filtre à air propre. (Voir Entretien et nettoyage) Un filtre obstrué
risque daffecter le fonctionnement de lunité.
Pour éviter que lair refroidi ne s’échappe, maintenir toutes les fenêtres, portes et autres
ouvertures fermées.
Si une panne de courant se produit lorsque lunité fonctionne
Si lalimentation de cette unité est temporairement arrêtée, lunité se remettra en marche, après rétablissement
de lalimentation, avec les mêmes réglages quavant la panne de courant.
REMARQUE
Guide de dépannage
Si le climatiseur ne fonctionne pas correctement, effectuez les vérifications suivantes avant de faire appel à un réparateur. Si le
problème persiste, prenez contact avec votre concessionnaire ou avec un service après-vente.
Panne Cause possible Remède
Le climatiseur ne fonctionne pas du
tout.
1. Coupure de courant. 1. Après une panne de courant,
appuyez sur le bouton de marche/
arrêt de fonctionnement de la
télécommande avec fil.
2. Le disjoncteur a fonctionné. 2. Prenez contact avec un service
après-vente.
3. Tension de ligne trop basse. 3. Consultez un électricien ou le
concessionnaire.
4. Le bouton de fonctionnement est en
position Off.
4. Appuyez à nouveau sur le bouton.
5. La télécommande avec fil ou la
pompe thermique ne fonctionne pas
correctement.
(La marque díinspection et les
lettres E, F, H, L, P ainsi que des
numéros apparaissent sur laffichage
à cristaux liquides de la
télécommande avec fil.)
5. Consultez le concessionnaire.
Le compresseur se met en marche
mais il sarrÍte aussitôt.
1. Il y a un obstacle devant la bobine du
condensateur.
1. Retirez ce qui fait obstruction.
Refroidissement (ou chauffage)
insuffisant.
1. Filtre à air sale ou obstrué. 1. Nettoyez le filtre à air afin
díaméliorer la circulation díair.
2. Source de chaleur ou trop de monde
dans la pièce.
2. Si possible, éliminez la source de
chaleur.
3. Portes et/ou fenÍtres ouv ertes. 3. Fermez-les pour empÍcher la
pénétration dair chaud (ou froid).
4. Obstacle devant larrivée ou la sortie
dair.
4. Retirez líobstacle pour assurer une
bonne circulation dair.
5. Le thermostat est réglé sur une
température trop élevée pour le
refroidissement (ou trop basse pour
le chauffage).
5. Réglez la température plus bas (ou
plus haut).
6. (Le dégivrage du système ne
fonctionne pas.)
6. (Consultez le concessionnaire
.)
04-235 AirCon_X-type 9/3/04 11:40 AM Page 23
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Sanyo SPW-UMR124EXH56 Manuel utilisateur

Catégorie
Climatiseurs split-system
Taper
Manuel utilisateur