S+S Regeltechnik RHEASGARD® KLGFT / KLGFVT RHEASGARD® KLGFT / KLGFVT Mode d'emploi

Taper
Mode d'emploi
RHEASGARD® KLGF xx
RHEASREG® KLSWxx
D G F r
D
Bedienungs- und Montageanleitung
Kanal-Luftstromfühler ⁄ Luftstromwächter,
inkl. Montageflansch, elektronisch,
mit aktivem ⁄ schaltendem Ausgang
G
Operating Instructions, Mounting & Installation
Duct air flow sensors ⁄ air flow monitors,
incl. mounting flange, electronic,
with active ⁄ switching output
F
Notice d’instruction
Capteur de débit d’air pour montage en gaine ⁄
contleur de débit d’air,
y compris bride de montage
, électronique,
avec sortie active tout ou rien
r
Руководство по монтажу и обслуживанию
Канальный датчик воздушного потока ⁄
реле контроля воздушного потока,
включ. присоединительный фланец, электронный,
с активным ⁄ релейным выходом
CA R TO NS
ET EMBALLAGE
PAPIER À TRIER
AUTOMATIC OUTPUT SWITCHING
AOS-PATENTED
KLGFVT
KLSW
/
KLGF
KLSW
/
KLGF
KLGFVT
KLSW-W230
6000-3950-0000-1XX 39500-2023 V121 04 ⁄ 2023
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS-STR. 22
90411 NÜRNBERG GERMANY
FON +49
(0) 911 5 19 47- 0
mail@SplusS.de
www
.
SplusS.de
2
RHEASGARD® KLGF xx
RHEASREG® KLSWxx
D G F r
KLGF xx
KLSW xx
Maßzeichnung
Dimensional drawing
Plan coté
Габаритный чертеж
[mm]
~
200
126
112
90
50
ø 20
ø32.3
13.4
20
60
87
~30
32
62
M4
ø5.2
ø
20
M16x1.5
20
M16x1.5
112
4
MFT - 20 - K
Montageflansch aus Kunststoff
Mounting flange, plastic
Bride de montage en matière plastique
Присоединительный фланец из пластика
KLSW-W230
~
200
126
112
90
50
ø 20
ø32.3
13.4
20
60
87
~30
32
62
M4
ø5.2
ø
20
M16x1.5
20
M16x1.5
112
4
126 90
50
20
13.4
M16x1.5
~ 200
20
ø32.3
ø20
4
~ 112
3
D RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Elektronischer Kanal-Luftstromfühler
RHEASGARD
®
KLGF
mit aktivem Ausgang,
Gehäuse aus schlagfestem Kunststoff mit Schnellverschlussschrauben, mit Kabelverschraubung,
mit/ohne Display, zur Ermittlung der Strömungs geschwindigkeit (0,1...20 m/s).
Der Messumformer wandelt das Messsignal in ein Norm signal von 0 - 10 V.
Elektronischer Kanal-Luftstromfühler/-wächter
RHEASGARD
®
KLGFT
(ohne Display) und
KLGFVT
(mit Display)
mit aktivem und schaltendem Ausgang, Gehäuse aus schlagfestem Kunststoff mit Schnellverschlussschrauben,
mit Kabelverschraubung, zur Ermittlung der Strömungs geschwindigkeit (0,1...20 m/s) und Temperatur (0...+50 °C).
Beim Getetyp
KLGFVT
ist alternativ zur Strömung die berechnete Kenngröße Volumenstrom abrufbar
(über Display konfigurierbar). Der Messumformer erkennt automatisch den erforderlichen Ausgangstyp und
wandelt die Messgrößen in das erforderliche Norm signal von 0 -10 V oder 4...20 mA (
Automatic Output Switching
).
Elektronischer Kanal-Luftstromwächter
RHEASREG
®
KLSW
mit schaltendem Ausgang,
Gehäuse aus schlagfestem Kunststoff mit Schnellverschlussschrauben, mit Kabelverschraubung,
mit/ohne Display, zur Ermittlung der Strömungs geschwindigkeit (0,1...20 m/s).
Die Strömungsfühler sind geeignet zur Überwachung oder Steuerung von Luftströmungen in Kanälen,
an Ventilatoren, Stell klappen, zum strömungsabhängigen Überwachen von Befeuchtern und elektrischen
Heiz registern gemäß DIN 57100 Teil 420 oder zum Einsatz in Verbindung mit DDC-Anlagen.
TECHNISCHE DATEN
Spannungsversorgung: 24 V AC ⁄ DC (± 10 %) (
KLSW-W24, KLGF xx
)
230 V AC, 50 Hz (
KLSW-W230
)
Stromaufnahme: ca. 3 VA (
KLGF, KLSW-W24, KLSW-W230
)
ca. 4 VA (
KLGFT, KLGFVT
)
Datenpunkte: Strömungs geschwindigkeit [m/s], Volumenstrom [m³/h], Temperatur [°C]
Ausgänge:
KLGF 1x
0 - 10 V (U-Variante)
KLGF
(
V
)
T 2x
0 -10 V 4...20 mA
(über
Automatic Output Switching
– das Gerät erkennt
den erforderlichen Ausgangstyp und schaltet automatisch auf U- oder I-Ausgang um);
Wechselkontakt 24 V (max. 5 A, cos ϕ = 1,0), Schalthysterese 2 % EW,
Schwellwert über Potentiometer einstellbar
KLSW-W24
Wechselkontakt 24 V (max. 5 A, cos ϕ = 1,0), Schalthysterese 2 % EW,
Schwellwert über Potentiometer einstellbar
KLSW-W230
Wechselkontakt
230 V AC
(max. 5 A, cos ϕ = 1,0), Schalthysterese 2 % EW,
Schwellwert über Potentiometer einstellbar
LUFTSTROM
Sensor: kalorimetrisch, temperaturkompensiert, Fühlerbruchsicherung,
mit manueller Nullpunktkalibrierung (über Taster)
Messbereich: 0,1...20 m/s
Genauigkeit: 0,5 m/s + 3 % MW
Langzeitstabilität: ± 0,5 % EW pro Jahr
Reproduzierbarkeit: ± 1,0 % EW
Einlaufzeit: < 2 min
Ansprechzeit: < 60 s
Anlaufüberbckung: 0 / 60 s (
KLGF
/
KLSW
ohne Display), über DIP-Schalter aktivierbar
0...120 s (
KLGF
/
KLSW
mit Display,
KLGFT
/
KLGFVT
), über Potentiometer einstellbar
TEMPERATUR
KLGF
(
V
)
T
Sensor: NTC 10k
Messbereich: 0...+50 °C
Genauigkeit: typisch ± 0,5 K bei +25 °C
Schutzrohr:
PLEUROFORM
TM, Werkstoff Polyamid (PA6), verdrehsicher, Ø 20 mm, NL = 220 mm,
vmax = 30 m/s (Luft), optional auf Anfrage
aus Edelstahl V2A
(1.4301)
,
Ø 16 mm
Gehäuse: Kunststoff,
UV-beständig,
Werkstoff Polyamid, 30 % glaskugelverstärkt,
mit Schnellverschlussschrauben(Schlitz ⁄ Kreuzschlitz-Kombination),
Farbe Verkehrsweiß (ähnlich RAL 9016), Deckel für Display ist transparent!
Abmaße Gehäuse: 126 x 90 x 50 mm (Tyr 2)
Kabelanschluss:
Kabelverschraubung
aus Kunststoff (M 16 x 1,5 ; mit Zugentlastung,
auswechselbar, max. Innendurchmesser 10,4 mm)
elektrischer Anschluss: 0,2 - 1,5 mm2, über Push-In-Klemme
Prozessanschluss: mittels Montageflansch (im Lieferumfang enthalten)
Umgebungstemperatur: Lagerung –20...+50 °C; Betrieb 0...+50 °C
Mediumstemperatur: 0...+70 °C
zulässige Luftfeuchte: < 98 % RH, nicht kondensierende, schadstofffreie Luft
Schutzklasse: II (nach EN 60 730) bei UB = 230 V (
KLSW-W230
)
III (nach EN 60 730) bei UB = 24 V (
KLSW-W24, KLGF xx
)
Schutzart:
IP 65
(nach EN 60 529) Gehäuse; Sensorik IP 20
Normen: CE-Konformität nach EMV-Richtlinie 2014 ⁄ 30 ⁄ EU, nach EN 61326-1, nach EN 61326-2-3
Optional:
Display mit Beleuchtung,
dreizeilig, Ausschnitt ca. 70 x 40 mm (B x H),
zur Anzeige von Strömungs geschwindigkeit, Volumenstrom und Temperatur
4
ANLAUFÜBERBRÜCKUNG
Es gibt Anwendungsfälle, bei welchen Lüftermotoren und Messgeräte ab- und wieder zugeschaltet werden.
Beim Zuschalten benötigen die Lüfter einige Sekunden zum Aufbau einer Strömung.
Während dieser Anlaufzeit könnte die GLT auf Störung schalten (fehlende Strömung).
Beim
KLGFxx
/
KLSWxx
(ohne Display) erfolgt die Aktivierung der Anlaufüberbrückung (60 s) über DIP-Schalter.
Beim
KLGFxx LCD
/
KLSWxx LCD
(mit Display) sowie beim
KLGFT
/
KLGFVT LCD
erfolgt die Aktivierung und Einstellung der Anlauberbckung (0...120 s) über ein Potentiometer.
Nach Zuschalten der Versorgungsspannung wird während dieser Anlaufzeit eine Stmung von 20 m/s bzw. größer
als die eingestellte Schaltschwelle angenommen und je nach Typ das Ausgangssignal auf 10V erht bzw. das Relais geschalten.
Nach Ablauf der Anlaufzeit wechselt das Gerät in den normalen Messmodus,
bei Gerätetypen ohne Wechsler wird eine messwertproportionale Spannung ausgegeben,
bei Gerätetypen mit Wechsler schaltet das Relais entsprechend Messwert < Schaltschwelle oder Messwert > Schaltschwelle.
SCHALTPUNKT
Bei Gerätetypen mit Wechsler erfolgt die Einstellung des Schaltpunkts (0,1...20 m/s) über ein Potentiometer.
WEITERE KENNGRÖSSEN
Beim
KLGFT
/
KLGFVT LCD
wird über einen weiteren Sensor (NTC 10k) die
Temperatur
erfasst.
Beim
KLGFVT LCD
wird intern die alternative Kenngröße
Volumenstrom
berechnet.
Dieser Wert kann anstatt der Strömung im Display angezeigt werden. Die Umschaltung erfolgt menügesteuert am Display.
D RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Typ ⁄ WG01 Spannungs-
versorgung
Ausgang
aktiv
Ausgang
schaltend
weitere
Display
Kenngrößen
Art.-Nr.
KLGF U-Variante
KLGF-U
24 V AC ⁄ DC
1x
0 -10 V – – 1701-4111-0101-000
KLGF-U
LCD
24 V AC ⁄ DC
1x
0 -10 V 1701-4111-1101-000
Optional: Kabelanschluss mit
M12-Steckverbinder
nach DIN EN 61076-2-101 auf Anfrage
KLGF
(
V
)
TAOS
KLGFT-W
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 Wechsler
T
1701-4118-0201-001
KLGFVT-W LCD
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 Wechsler
T | V
1701-4118-1401-001
KLSW-W24
KLSW-W24
24 V AC ⁄ DC
1 Wechsler
1701-4113-0101-001
KLSW-W24
LCD
24 V AC ⁄ DC
1 Wechsler
1701-4113-1101-001
KLSW-W230
KLSW-W
230 230 V
AC
1 Wechsler
1701-4133-0101-001
Hinweis:
Wechselkontakt
mit automatischen Reset
(Relais öffnet automatisch, wenn Schwellwert wieder unterschritten wird)
AOS
(
Automatic Output Switching
)
= patentierte Analog-Schnittstelle (Patent-Nr. DE 10 2015 015 941 B4),
Gerät erkennt automatisch den erforderlichen Ausgangstyp 0 -10 V oder 4...20 mA
T
=
Temperatur
(0...+5C) – zutzliche Messgröße
V
=
Volumenstrom
(0...200.000 m³/h) – alternative Kenngße, über Display konfigurierbar!
5
D RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schaltbild
KLSW-W24
thershold rel. pow. s.b.
s.b.
zero
1 2 312 11 13
ON
1
+UB OUT GNDNC MNO
ON
1
SET-Potentiometer
Einstellung Schaltpunkt
(min. 0,1m/s ... max. 20m/s)
Relais
SET LEDs Taster DIP
LEDs
(on = aktiv)
rel.
= Relais / Schaltpunkt überschritten
pow.
= Betriebsanzeige
s.b.
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
DIP
Anlaufüberbrückung (60s)
(off = default)
Schaltbild
KLSW-W230
thershold rel. pow. s.b.
s.b.
zero
1 212 11 13
ON
1
230 VNC MNO
ON
1
SET-Potentiometer
Einstellung Schaltpunkt
(min. 0,1m/s ... max. 20m/s)
Relais
SET LEDs
Taster DIP
LEDs
(on = aktiv)
rel.
= Relais / Schaltpunkt überschritten
pow.
= Betriebsanzeige
s.b.
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
DIP
Anlaufüberbrückung (60s)
(off = default)
12
11
13
1
2
3
+UB 24V AC/DC
–UB GND
frei
Öffner
Schließer
Wurzel
Anschlussbild Anschlussbild
KLSW-W24
(ohne Display)
KLSW-W230
(ohne Display)
12
11
13
1
2
N
L
230 V AC
Öffner
Schließer
Wurzel
Schaltbild
KLGF-U
pow. s.b.
s.b.
zero
1 2 3
ON
1
+UB OUT GND
ON
1
LEDs Taster DIP
LEDs
(on = aktiv)
pow.
= Betriebsanzeige
s.b.
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
DIP
Anlaufüberbrückung (60s)
(off = default)
1
2
3
Ausgang 0-10V Strömung
+UB 24V AC/DC
–UB GND
Anschlussbild
KLGF-U
(ohne Display)
ON
1
SET-Potentiometer
Einstellung Schaltpunkt
(min. 0,1m/s ... max. 20m/s)
LEDs
(on = aktiv)
rel.
= Relais / Schaltpunkt überschritten
pow.
= Betriebsanzeige
s.b.
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
DIP
Anlaufüberbrückung (60s)
(off = default)
6
D RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schaltbild
KLGF
/
KLSW-xx LCD
KLGFT-W
/
KLGFVT-W LCD
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET-Potentiometer
thershold
= Schaltpunkt (min. 0,1m/s ... max. 20m/s)
sb
= Anlaufüberbrückung (min. 0s ... max. 120s)
offset
= Temperatur (± 5K)
Relais
LEDs
Taster
LEDs
(on = aktiv)
rel.
= Relais / Schaltpunkt überschritten
sb
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
Stecker
Display
Anschlussbild
Anschlussbild
Anschlussbild
KLGF-U LCD
KLGFVT-W LCD
KLGFT-W
KLSW-W24 LCD
12
11
13
1
2
3
4
+UB 24V AC/DC
–UB GND
Öffner
Schließer
Wurzel
frei
frei
1
2
3
4
+UB 24V AC/DC
–UB GND
Ausgang 0-10 V Strömung
frei
*
KLGFVT-W LCD:
Umschaltung von Messgröße Strömung
auf alternative Kenngröße
Volumenstrom
erfolgt menügesteuert am Display.
12
11
13
1
2
3
4
+UB 24V AC/DC
–UB GND
Öffner
Schließer
Wurzel
Ausgang 0-10 V / 4...20mA Strömung
Ausgang 0-10 V / 4...20mA Temperatur
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET-Potentiometer
thershold
= Schaltpunkt (min. 0,1m/s ... max. 20m/s)
sb
= Anlaufüberbrückung (min. 0s ... max. 120
s)
offset
= Temperatur (± 5K)
Relais
LEDs
Taster
LEDs
(on = aktiv)
rel.
= Relais / Schaltpunkt überschritten
sb
= Anlaufüberbrückung
Taster
Nullpunkt setzen (0m/s)
Stecker
Display
7
D
Montage
KLGF xx
KLSW xx
Einbauschema
> 5x
d
> 3x
d
> 115 mm
d
> 5x
d
> 3x
d
> 115 mm
d
Montagehinweis:
Sensor arbeitet unidirektional.
Markierungen zur Strömungsrichtung beachten!
8
Hinweise zur Montage
Der Einbau hat unter Berücksichtigung der einschlägigen, für den Mess ort gültigen Vorschriften und Standards
(wie z. B. Schwevor schriften usw.) zu erfolgen. Insbesondere sind zu becksichtigen:
VDE ⁄ VDI Technische Temperaturmessungen, Richtlinie, Mess an ordnungen für Temperaturmessungen
die EMV-Richtlinien, diese sind einzuhalten
eine Parallelverlegung mit stromhrenden Leitungen ist unbedingt zu vermeiden
es wird empfohlen abgeschirmte Leitungen zu verwenden, dabei ist der Schirm einseitig an der DDC SPS aufzulegen
die Leitungslänge zwischen Fühler und GLT sollte nicht mehr als 100 m betragen
eine Verpolung der Anschlüsse kann zu Beschädigungen am Gerät und/oder anderen Geräten am Leitungsstrang führen
Der Einbau hat unter Beachtung der Übereinstimmung der vor liegenden technischen Parameter des Messgeräts
mit den realen Einsatzbedingungen zu erfolgen, insbesondere:
– Messbereich
zulässiger maximaler Druck, Strömungsgeschwindigkeit
Schutzart und Schutzklasse
Einbaulänge, Rohrmaße
Schwingungen, Vibrationen, Sße sind zu vermeiden (< 0,5 g)
Nur für nicht kondensierende, schadstofffrei Luft ohne Über- oder Unterdruck geeignet!
Verunreinigungen nur mit Luft entfernen!
Minimale Einlaufstrecke von
5x d
vor und Auslaufstrecke von
3x d
beachten!
Einbaulage ist richtungsabhängig,
Markierung beachten!
Achtung!
Berücksichtigen Sie in jedem Fall die mechanischen und thermischen Belastungsgrenzen der Schutzrohre
nach DIN 43763 bzw. nach speziellen S+S-Standards!
D
Montage und Inbetriebnahme
Schaltbild
Parallelbetrieb
Schaltbild
Einzelbetrieb
VERSORGUNGSSPANNUNG:
Als Verpolungsschutz der Betriebsspannung ist bei dieser Gerätevariante
eine Einweggleichrichtung bzw. Verpolungschutzdiode integriert. Diese
interne Einweggleichrichtung erlaubt auch den Betrieb mit AC-Versorgungs-
spannung.
Das Ausgangssignal ist mit einem Messgerät abzugreifen. Hierbei wird
das Ausgangssignal gegen das Nullpotenial (O V) der Eingangsspannung
ge messen!
Wird dieses Get mit
DC - Versorgungsspannung
betrieben, ist der
Betriebsspannungseingang UB+ für 15...36 V DC - Einspeisung und UB
bzw. GND als Masseleitung zu verwenden!
Werden mehrere Gete von einer 24 V
AC - Spannung
versorgt, ist
darauf zu achten, dass alle „positiven“ Betriebsspannungseingänge (+) der
Feldgeräte miteinander verbunden sind, sowie alle „negativen“ Betriebs-
spannungseingänge (–) = Bezugspotential miteinander ver bunden sind
(phasen gleicher Anschluss der Feldgeräte). Alle Feld ge räte aus gänge
müssen auf das gleiche Potential bezogen werden!
Bei Verpolung der Versorgungsspannung an einem der Feldgeräte würde
über dieses ein Kurzschluss der Versorgungsspannung erzeugt. Der somit
über dieses Feldgerät fließende Kurzschlussstrom kann zur Beschädigung
dieses Gerätes führen.
Achten Sie daher auf die korrekte Verdrahtung!
Schaltung Schaltung
0-10V
0V/GND
0-10V
0V/GND
Versorgung mit
AC 24V~ 0V
DC 15-36V = GND
AC 24V~ 0V
DC 15-36V = GND
Schaltung
0-10V
0V/GND
V
Versorgung mit
9
D Wichtige Hinweise
Als AGB gelten ausschließlich unsere sowie die gültigen „Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elektro industrie“
(ZVEI Bedingungen) zuzüglich der Ergänzungsklausel „Erweiterter Eigentumsvorbehalt“.
Außerdem sind folgende Punkte zu beachten:
Vor der Installation und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten!
Der Anschluss der Gete darf nur an Sicherheitskleinspannung und im spannungslosen Zustand erfolgen. Um Scden und Fehler am Gerät
(z.B. durch Spannungsinduktion) zu verhindern, sind abgeschirmte Leitungen zu verwenden, eine Parallelverlegung zu stromführenden Leitungen
zu vermeiden und die EMV- Richtlinien zu beachten.
Dieses Gerät ist nur für den angegebenen Verwendungszweck zu nutzen, dabei sind die entsprechenden Sicherheitsvorschriften des VDE,
der Länder, ihrer Überwachungsorgane, des TÜV und der örtlichen EVU zu beachten.
Der Käufer hat die Einhaltung der Bau- und Sicherungsbestimmung zu gehrleisten und Gehrdungen aller Art zu vermeiden.
Für Mängel und Schäden, die durch unsachgemäße Verwendung dieses Gerätes entstehen,
werden keinerlei Gewährleistungen und Haftungen übernommen.
Folgeschäden, welche durch Fehler an diesem Gerät entstehen, sind von der Gewährleistung und Haftung ausgeschlossen.
Montage und Inbetriebnahme der Geräte darf nur durch Fachpersonal erfolgen.
Es gelten ausschließlich die technischen Daten und Anschlussbedingungen der zum Gerät gelieferten Montage- und Bedienungs anleitung,
Abweichungen zur Katalogdarstellung sind nicht zutzlich aufgeführt und im Sinne des technischen Fortschritts und der stetigen Verbesserung
unserer Produkte möglich.
Bei Veränderungen der Geräte durch den Anwender entfallen alle Gewährleistungsansprüche.
Dieses Get darf nicht in der Nähe von Wärmequellen (z.B. Heizkörpern) oder deren Wärmestrom eingesetzt werden,
eine direkte Sonnen einstrahlung oder Wärmeeinstrahlung durch ähnliche Quellen (starke Leuchte, Halogenstrahler) ist unbedingt zu vermeiden.
Der Betrieb in der Nähe von Geten, welche nicht den EMV- Richtlinien entsprechen, kann zur Beeinflussung der Funktionsweise führen.
Dieses Get darf nicht für Überwachungszwecke, welche dem Schutz von Personen gegen Gefährdung oder Verletzung dienen und
nicht als Not-Aus-Schalter an Anlagen und Maschinen oder vergleichbare sicherheitsrelevante Aufgaben verwendet werden.
Die Gehäuse- und Gehäusezubehörmaße können geringe Toleranzen zu den Angaben dieser Anleitung aufweisen.
Veränderungen dieser Unterlagen sind nicht gestattet.
Reklamationen werden nur vollständig in Originalverpackung angenommen.
Hinweise zur Inbetriebnahme:
Dieses Gerät wurde unter genormten Bedingungen kalibriert, abgeglichen und geprüft. Bei Betrieb unter abweichenden Bedingungen empfehlen wir
Vorort eine manuelle Justage erstmals bei Inbetriebnahme sowie anschließend in regelmäßigen Abständen vorzunehmen.
Eine Inbetriebnahme ist zwingend durchzuführen und darf nur von Fachpersonal vorgenommen werden!
Vor der Montage und Inbetriebnahme ist diese Anleitung zu lesen und die alle darin gemachten Hinweise sind zu beachten!
10
G RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Electronic duct air flow sensor
RHEASGARD
®
KLGF
with active output,
housing made of impact-resistant plastic with quick-locking screws, with cable gland,
with/without display, to determine the flow velocity (0.1...20 m/s).
The measuring transducer converts the measurement signal into a standard signal of 0 - 10 V.
Electronic duct air flow sensor/monitor
RHEASGARD
®
KLGFT
(without display) and
KLGFVT
(with display)
with active and switching output, housing made of impact-resistant plastic with quick-locking screws,
with cable gland, to determine the flow velocity (0.1...20 m/s) and temperature (0...+50 °C).
For device type
KLGFVT
, the calculated volume flow parameter can be retrieved as an alternative to the flow
(configurable on the display). The measuring transducer automatically detects the required output type and
converts the measurands into the required standard signal of 0 - 10 V or 4...20 mA (
Automatic Output Switching
).
Electronic duct airflow monitor
RHEASREG
®
KLSW
with switching output,
housing made of impact-resistant plastic with quick-locking screws, with cable gland,
with/without display, to determine the flow velocity (0.1...20 m/s).
The flow sensors are suitable for monitoring or controlling airflows in ducts, at fans and dampers,
for flow-dependent monitoring of humidifiers and electric heating registers according to DIN 57100, Sect. 420,
or for use in connection with DDC systems.
TECHNICAL DATA
Power supply: 24 V AC ⁄ DC (± 10%) (
KLSW-W24, KLGF xx
)
230 V AC, 50 Hz (
KLSW-W230
)
Current consumption: approx. 3 VA (
KLGF, KLSW-W24, KLSW-W230
)
approx. 4 VA (
KLGFT, KLGFVT
)
Data points: flow velocity [m/s], volume flow [m³/h], temperature [°C]
Outputs:
KLGF 1x
0 - 10 V (U variant)
KLGF
(
V
)
T 2x
0 -10 V 4...20 mA
(via
Automatic Output Switching
– the unit recognises the required
output type and automatically switches to U or I output);
changeover contact 24 V (max. 5 A, cos ϕ = 1.0), switching hysteresis
2 % final value, threshold can be adjusted via potentiometer
KLSW-W24
changeover contact 24 V (max. 5 A, cos ϕ = 1.0), switching hysteresis
2 % final value, threshold can be adjusted via potentiometer
KLSW-W230
changeover contact
230 V AC
(max. 5 A, cos ϕ = 1.0), switching hysteresis
2 % final value, threshold can be adjusted via potentiometer
AIR FLOW
Sensor: calorimetric, temperature compensated, sensor breakage protection,
with manual zero-point calibration (via button)
Measuring range: 0.1...20 m/s
Accuracy: 0.5 m/s + 3% measured value
Long-term stability: ± 0.5% final value per year
Reproducibility: ± 1.0% final value
Warm-up time: < 2 min
Response time: < 60 s
Start-up override: 0 / 60 s (
KLGF
/
KLSW
without display), can be activated via DIP switch
0...120 s (
KLGF
/
KLSW
with display,
KLGFT
/
KLGFVT
), can be adjusted via potentiometer
TEMPERATURE
KLGF
(
V
)
T
Sensor: NTC 10k
Measuring range: 0...+50 °C
Accuracy: typical ± 0.5 K at +25 °C
Protective tube:
PLEUROFORM
TM, material polyamide (PA6), with torsion protection, Ø 20mm, NL = 220 mm,
vmax = 30 m/s (air),
stainless steel V2A
(1.4301)
,
Ø 16 mm available upon request as an option
Housing: plastic,
UV-resistant,
polyamide material, 30% glass-globe reinforced,
with quick-locking screws(slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover for display is transparent!
Housing dimensions: 126 x 90 x 50 mm (Tyr 2)
Cable connection:
cable gland
, plastic (M 16 x 1.5; with strain relief,
exchangeable, max. inner diameter 10.4 mm)
Electrical connection: 0.2 - 1.5 mm2, via push-in terminal
Process connection: by means of plastic mounting flange (included in the scope of delivery)
Ambient temperature: storage –20...+50 °C; operation 0...+50 °C
Medium temperature: 0...+70 °C
Permitted humidity: < 98% RH, non-precipitating air free of harmful substances
Protection class: II (according to EN 60 730) with UB = 230 V (
KLSW-W230
)
III (according to EN 60 730) with UB = 24 V (
KLSW-W24, KLGF xx
)
Protection type:
IP 65
(according to EN 60 529) housing; IP 20 sensor technology
Standards: CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU, according to EN 61326-1, according to EN 61326-2-3
Optional:
display with illumination,
three-line, cutout approx. 70 x 40 mm (W x H),
to display the flow velocity, volume flow and temperature
11
START-UP OVERRIDE
There are application scenarios in which fan motors and measuring instruments are switched off and on again.
When switched on, the fans take a few seconds to build up a flow.
During this start-up time, the GLT could switch to fault mode (lack of flow).
In the
KLGFxx
/
KLSWxx
(without display), the start-up override (60s) is activated by a DIP switch.
In the
KLGFxx LCD
/
KLSWxx LCD
(with display) and in the
KLGFT
/
KLGFVT LCD
,
the start-up override (0...120s) is activated and adjusted by a potentiometer.
After the supply voltage is switched on, a flow of 20 m/s or greater than the set switching threshold during
this start-up time is assumed and the output signal is increased to 10V or the relay is switched, depending on the type.
After the start-up time has elapsed, the unit switches to normal measuring mode,
in unit types without a changeover contact, a voltage proportional to the measured value is output,
in unit types with a changeover contact, the relay switches according to the measured value < switching threshold
or measured value > switching threshold.
SWITCHPOINT
In unit types with a changeover contact, the switching point (0.1...20 m/s) is adjusted by a potentiometer.
OTHER PARAMETERS
In the
KLGFT
/
KLGFVT LCD
, the
temperature
is captured by another sensor (NTC 10k).
In the
KLGFVT LCD
, the alternative parameter
Volume Flow
is calculated internally.
This value can be shown instead of the flow in the display. The switching is menu-controlled on the display.
G RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Type ⁄ WG01 Power
supply
Output
active
Output
switching
other
Display
Parameters
Item no.
KLGF U Variant
KLGF-U
24 V AC ⁄ DC
1x
0 -10 V – – 1701-4111-0101-000
KLGF-U
LCD
24 V AC ⁄ DC
1x
0 -10 V 1701-4111-1101-000
Optional: Cable connection with
M12 connector
as per DIN EN 61076-2-101 on request
KLGF
(
V
)
TAOS
KLGFT-W
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 changeover contact
T
1701-4118-0201-001
KLGFVT-W LCD
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 changeover contact
T | V
1701-4118-1401-001
KLSW-W24
KLSW-W24
24 V AC ⁄ DC
1 changeover contact
1701-4113-0101-001
KLSW-W24
LCD
24 V AC ⁄ DC
1 changeover contact
1701-4113-1101-001
KLSW-W230
KLSW-W
230 230 V
AC
1 changeover contact
1701-4133-0101-001
Note:
Changeover contact
with automatic reset
(relay opens automatically when value falls below the threshold again)
AOS
(
Automatic Output Switching
)
= patented analogue interface (patent no. DE 10 2015 015 941 B4),
the unit automatically detects the required output type 0 - 10 V or 4...20mA
T
=
temperature
(0...+50°C) – additional measurand
V
=
volume flow
(0...200,000 m³/h) – alternative parameter, can be configured via display!
12
G RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schematic diagram
KLSW-W24
thershold rel. pow. s.b.
s.b.
zero
1 2 312 11 13
ON
1
+UB OUT GNDNC MNO
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
SET LEDs
Pushbutton
DIP
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
Relay
Schematic diagram
KLSW-W230
thershold rel. pow. s.b.
s.b.
zero
1 212 11 13
ON
1
230 VNC MNO
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
SET LEDs
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
Relay
Pushbutton
DIP
12
11
13
1
2
3
+UB 24V AC/DC
free
–UB GND
NC Normally Closed
NO Normally Open
M Common
Connecting diagram Connecting diagram
KLSW-W24
(without display)
KLSW-W230
(without display)
12
11
13
1
2
N
L
230 V AC
NC Normally Closed
NO Normally Open
M Common
Schematic diagram
KLGF-U
pow. s.b.
s.b.
zero
1 2 3
ON
1
+UB OUT GND
ON
1
Pushbutton
DIP
LEDs (on = active)
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
LEDs
1
2
3
Output 0-10V Flow velocity
+UB 24V AC/DC
–UB GND
Connecting diagram
KLGF-U
(without display)
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
13
G RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schematic diagram
KLGF
/
KLSW-xx LCD
KLGFT-W
/
KLGFVT-W LCD
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20m/s)
sb
= start bridging (min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
Connecting diagram
Connecting diagram
Connecting diagram
KLGF-U LCD
KLGFVT-W LCD
KLGFT-W
KLSW-W24 LCD
12
11
13
1
2
3
4
+UB 24V AC/DC
NC Normally Closed
NO Normally Open
M Common
–UB GND
free
free
1
2
3
4
+UB 24V AC/DC
–UB GND
Output 0-10 V Flow velocity
free
*
KLGFVT-W LCD:
Switching from flow measurand
to the alternative
volume flow
parameter
is menu-controlled on the display.
12
11
13
1
2
3
4
+UB 24V AC/DC
NC Normally Closed
NO Normally Open
M Common
–UB GND
Output 0-10 V / 4...20mA Flow velocity
Output 0-10 V / 4...20mA Temperature
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20
m/s)
sb
= start bridging (min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
14
G
Installation
KLGF xx
KLSW xx
Mounting diagram
> 5x
d
> 3x
d
> 115 mm
d
> 5x
d
> 3x
d
> 115 mm
d
Note when mounting:
Sensor works unidirectional.
Observe the markings for the direction of flow!
15
G
Installation and Commissioning
Connecting scheme
Parallel operation
Connecting scheme
Individual operation
Circuitry Circuitry
0...10V
0V/GND
0...10V
0V/GND
Power supply
AC 24V~ 0V
DC 15-36V = GND
Circuitry
0...10V
0V/GND
V
Power supply
AC 24V~ 0V
DC 15-36V = GND
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier on AC supply voltage.
The output signal is to be tapped by a measuring instrument. The output
signal is measured her against zero potential (O V) of the input voltage!
When this device is operated on
DC supply voltage
, the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!
When several devices are supplied by one 24 V
AC voltage supply
, it is to
be ensured that all ”positive“ operating voltage input terminals (+) of the
field devices are connected with each other and all ”negative“ operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Notes for mounting
Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding
instructions, etc.). It is particularly important to comply with the following:
VDE ⁄ VDI directive technical temperature measurements,
measurement set-up for temperature measurements
The EMC directives must be adhered to
It is imperative to avoid parallel laying of current-carrying lines
We recommend using shielded cables with
the shielding being attached at one side to the DDC ⁄PLC
the cable length between sensor and GLT should not exceed 100 m
- reversing the polarity of the connections can cause damage to the unit and/or other units on the wiring harness
Before mounting, make sure that the existing technical parameters of the measuring instrument comply with the actual conditions at the place of
utilisation, particularly with regard to:
Measuring range
Permissible maximum pressure, flow velocity
Protection type and protection class
Mounting length, tube dimensions
Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
Only suitable for non-precipitating, pollutant-free air without positive or negative pressure!
Contamination must be removed with air only!
Observe a minimum inlet distance of
5x d
in upstream and an outlet distance of
3x d
!
Mounting length depends on direction,
Observe marking!
Attention!
In all cases, please observe the mechanical and thermal load limits of protective tubes according to DIN 43763
respectively according to specific S+S standards!
16
Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the
Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive
terms and conditions.
In addition, the following points are to be observed:
These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device
(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided,
and EMC directives are to be observed.
This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities,
the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to
prevent perils of any kind.
No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
Consequential damages caused by a fault in this device are excluded from warranty or liability.
These devices must be installed and commissioned by authorised specialists.
The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid.
Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous
improvement of our products.
In case of any modifications made by the user, all warranty claims are forfeited.
This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
Operating this device close to other devices that do not comply with EMC directives may influence functionality.
This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,
or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
Dimensions of housings or housing accessories may show slight tolerances on the specifications provided in these instructions.
Modifications of these records are not permitted.
In case of a complaint, only complete devices returned in original packing will be accepted.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions,
we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!
G General notes
17
F RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Capteur de débit d’air électronique pour montage en gaine
RHEASGARD
®
KLGF
avec sortie active,
boîtier plastique résistant aux chocs avec vis de fermeture rapide, avec presse-étoupe,
avec⁄ sans écran, pour mesurer la vitesse d’écoulement (0,1...20m/s).
Le convertisseur de mesure convertit le signal de mesure en un signal normalisé de 0-10V.
Capteur/ Contrôleur de débit d’air électronique pour montage en gaine
RHEASGARD
®
KLGFT
(sans écran)
et
KLGFVT
(avec écran) avec sortie active et en tout ou rien, btier plastique résistant aux chocs avec vis de fermeture rapide,
avec pressetoupe, pour mesurer la vitesse d’écoulement (0,1...20m/s) et la température (0...+50°C).
Sur l’appareil
KLGFVT,
il est possible de consulter le débit volumique calculé plut que le débit (configurable à l’écran).
Le convertisseur de mesure détecte automatiquement le type de sortie requis et convertit les grandeurs de mesure en
un signal normalisé de 0 à 10V ou de 4 à 20mA (
Automatic Output Switching
).
Contrôleur de débit d’air électronique pour montage en gaine
RHEASREG
®
KLSW
avec sortie tout ou rien,
boîtier plastique résistant aux chocs avec vis de fermeture rapide, avec presse-étoupe,
avec⁄ sans écran, pour mesurer la vitesse d’écoulement (0,1...20m/s).
Les capteurs de débit sont conçus pour la surveillance ou la commande de débits d’air dans des gaines,
sur des ventilateurs, des trappes de réglage, pour la surveillance en fonction du débit d’air d’humidificateurs
et de batteries de chauffe électriques selon DIN57100 partie420 ou pour une utilisation en combinaison avec
des systèmes à commande numérique directe.
CARACTÉRISTIQUES TECHNIQUES
Alimentation en tension: 24VCA ⁄ CC (± 10%) (
KLSW-W24, KLGF xx
)
230VCA, 50Hz (
KLSW-W230
)
Consommation de courant: env. 3VA (
KLGF, KLSW-W24, KLSW-W230
)
env. 4VA (
KLGFT, KLGFVT
)
Points de données: vitesse d’écoulement [m/s], débit volumique [m³/h], température [°C]
Sorties:
KLGF 1x
0 - 10 V (variante U)
KLGF
(
V
)
T 2x
0 -10 V 4...20 mA
(via
Automatic Output Switching
l’appareil reconnaît le type de sortie requis et commute automatiquement sur la sortie U ou I);
contact inverseur 24 V (max. 5 A, cos ϕ = 1,0), hyssis de commutation 2 % Vf,
valeur seuil réglable par potentiotre
KLSW-W24
contact inverseur 24 V (max. 5 A, cos ϕ = 1,0), hystérésis de commutation 2 % Vf,
valeur seuil réglable par potentiotre
KLSW-W230
contact inverseur
230 V AC
(max. 5 A, cos ϕ = 1,0), hystérésis de commutation
2 % Vf,
valeur seuil réglable par potentiotre
DÉBIT D’AIR
Capteur: calorimétrique, compensation de température, protection contre la rupture du capteur,
avec calibrage manuel du point zéro (via le bouton)
Plage de mesure: 0,1...20m/s
Précision: 0,5m/s + 3%MW
Stabilité à long terme: ± 0,5% Vf par an
Reproductibilité: ± 1,0% Vf
Temps de démarrage: < 2min
Temps de réponse: < 60s
Pontage de démarrage: 0/ 60s (
KLGF
/
KLSW
sans écran), activable via interrupteur DIP
0...120s (
KLGF
/
KLSW
avec écran,
KLGFT
/
KLGFVT
), réglable par potentiomètre
TEMPÉRATURE
KLGF
(
V
)
T
Capteur: NTC 10k
Plage de mesure: 0...+50 °C
Précision: typique ± 0,5K à +25 °C
Tube de protection:
PLEUROFORM
TM, matière polyamide (PA6), avec protection anti-torsion, Ø 20mm, NL = 220 mm,
vmax = 30m/s (air), en option sur demande
en acier inoxydable V2A
(1.4301)
,
Ø 16mm
Boîtier: plastique,
sistant aux UV
, matière polyamide, renforcé de billes de verre à 30 %,
avec vis de fermeture rapide (association fente/fente en croix),
coloris blanc signalisation (similaire à RAL 9016), le couvercle de l’écran est transparent!
Dimensions du boîtier: 126x90x50mm (Tyr 2)
Raccordement de câble:
presse-étoupe
en plastique (M 16 x 1,5; avec décharge de traction,
remplable, diamètre intérieur max. 10,4mm)
Raccordement électrique: 0,2 - 1,5mm2, par borne à ressort (push-in)
Raccordement process: avec bride de montage (comprise dans la livraison)
Température ambiante: stockage –20...+50°C; service 0...+50°C
Température moyenne: 0...+70°C
Humidité de l’air admissible: < 98 % h.r. , air non pollué sans condensation
Classe de protection: II (selon EN60730) pour UB = 230V (
KLSW-W230
)
III (selon EN60730) pour UB = 24V (
KLSW-W24, KLGF xx
)
Type de protection: boîtier
IP 65
(selon EN60529); capteurs IP20
Normes:
conformité CE selon directive «CEM» 2014 ⁄ 30 ⁄ EU, selon EN61326-1, selon EN61326-2-3
En option:
écran avec rétro-éclairage,
affichage sur troislignes, découpe env. 70 x 40mm (l x h),
pour l’affichage de la vitesse d’écoulement, du débit volumique et de la température
18
PONTAGE DE DÉMARRAGE
Il existe des cas d’application où les moteurs de ventilateurs et les appareils de mesure sont déconnectés et reconnectés.
Lors de la mise en marche, les ventilateurs ont besoin de quelques secondes pour établir un débit.
Pendant ce temps de démarrage, la gestion technique de bâtiment pourrait se mettre en défaut (absence de débit).
Pour le
KLGFxx
/
KLSWxx
(sans écran), l’activation du pontage de démarrage (60s) se fait par commutateurDIP.
Pour le
KLGFxx LCD
/
KLSWxx LCD
(avec écran) ainsi que le
KLGFT
/
KLGFVT LCD,
l’activation et le réglage du pontage de démarrage (0...120s) se font à l’aide d’un potentiomètre.
Après la mise en marche de la tension d’alimentation, un débit de 20m/s ou supérieur au seuil de commutation réglé
est adopté pendant ce temps de démarrage et, selon le type, le signal de sortie est augmenté à 10V ou le relais est commuté.
Après écoulement du temps de démarrage, l’appareil passe en mode de mesure normal,
pour les types d’appareil sans inverseur, une tension proportionnelle à la valeur mesue est délivrée,
pour les types d’appareil avec inverseur, le relais est commuté en fonction de la valeur mesue < seuil de commutation ou de la valeur mesurée >
seuil de commutation.
POINT DE COMMUTATION
Pour les types d’appareil avec inverseur, le réglage du point de commutation (0,1...20m/s) se fait à l’aide d’un potentiotre.
AUTRES PARAMÈTRES
Pour le
KLGFT
/
KLGFVTLCD
, la
température
est relevée à l’aide d’un capteur supplémentaire (NTC10k).
Pour le
KLGFVTLCD
, le paratre alternatif
débit volumique
est calculé en interne.
Cette valeur peut être affichée à l’écran à la place du débit. La bascule se fait à l’écran avec un guidage par menu.
F RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Type ⁄ WG01 alimentation
en tension
sortie
active
sortie
tout ou rien
autres
écran
paramètres
référence
KLGF variante U
KLGF-U
24 V AC ⁄ DC
1x
0 -10 V – – 1701-4111-0101-000
KLGF-U
LCD
24 V AC ⁄ DC
1x
0 -10 V 1701-4111-1101-000
En option: Raccordement par câble avec
connecteur M12
selon DINEN 61076-2-101 sur demande
KLGF
(
V
)
TAOS
KLGFT-W
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 inverseur
T
1701-4118-0201-001
KLGFVT-W LCD
24 V AC ⁄ DC
2x
0 -10 V
⁄ 4...20 mA 1 inverseur
T | V
1701-4118-1401-001
KLSW-W24
KLSW-W24
24 V AC ⁄ DC
1 inverseur
1701-4113-0101-001
KLSW-W24
LCD
24 V AC ⁄ DC
1 inverseur
1701-4113-1101-001
KLSW-W230
KLSW-W
230 230 V
AC
1 inverseur
1701-4133-0101-001
Remarque:
Contact inverseur
avec réinitialisation automatique
(le relais s’ouvre automatiquement lorsque la valeur seuil n’est de nouveau pas atteinte)
AOS
(
Automatic Output Switching
)
= interface analogique brevetée (No brevet DE 10 2015 015 941 B4),
L’appareil reconnaît le type de sortie requis 0-10V ou 4...20mA.
T
=
température
(0...+50°C) – grandeur mesurée supplémentaire
V
=
débit volumique
(0...200000m³/h) – paratre alternatif, configurable via l’écran!
19
F RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schéma de connexion
KLSW-W24
thershold rel. pow. s.b.
s.b.
zero
1 2 312 11 13
ON
1
+UB OUT GNDNC MNO
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
SET LEDs
Pushbutton
DIP
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
Relay
Schéma de connexion
KLSW-W230
thershold rel. pow. s.b.
s.b.
zero
1 212 11 13
ON
1
230 VNC MNO
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
SET LEDs
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
Relay
Pushbutton
DIP
12
11
13
1
2
3
+UB 24V AC/DC
free
–UB GND
NC Normally Closed
NO Normally Open
M Common
Schéma de raccordement Schéma de raccordement
KLSW-W24
(sans écran)
KLSW-W230
(sans écran)
12
11
13
1
2
N
L
230 V AC
NC Normally Closed
NO Normally Open
M Common
Schéma de connexion
KLGF-U
pow. s.b.
s.b.
zero
1 2 3
ON
1
+UB OUT GND
ON
1
Pushbutton
DIP
LEDs (on = active)
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
LEDs
1
2
3
Output 0-10V Flow velocity
+UB 24V AC/DC
–UB GND
Schéma de raccordement
KLGF-U
(sans écran)
ON
1
SET potentiometer
setting switching point
(min. 0.1m/s ... max. 20m/s)
LEDs (on = active)
rel.
= relay / switching point exceeded
pow.
= device in operation
s.b.
= start bridging
Pushbutton
zero point setting (0m/s)
DIP
start bridging (60s)
(off = default)
20
F RHEASGARD® KLGFxx ⁄ RHEASREG® KLSWxx
Rev. Data - V35
Schéma de connexion
KLGF
/
KLSW-xx LCD
KLGFT-W
/
KLGFVT-W LCD
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20m/s)
sb
= start bridging (min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
Schéma de raccordement
Schéma de raccordement
Schéma de raccordement
KLGF-U LCD
KLGFVT-W LCD
KLGFT-W
KLSW-W24 LCD
12
11
13
1
2
3
4
+UB 24V AC/DC
NC Normally Closed
NO Normally Open
M Common
–UB GND
free
free
1
2
3
4
+UB 24V AC/DC
–UB GND
Output 0-10 V Flow velocity
free
*
KLGFVT-W LCD:
le passage de la grandeur mesurée «bit» au
paramètre alternatif
«débit volumétrique»
est commandé par menu à l’écran.
12
11
13
1
2
3
4
+UB 24V AC/DC
NC Normally Closed
NO Normally Open
M Common
–UB GND
Output 0-10 V / 4...20mA Flow velocity
Output 0-10 V / 4...20mA Temperature
thershold
rel. sb
zero
set
21 3 4
12 11 13
sb offset
up
down
OUT1
+UB
OUT2
GND
NC MNO
SET potentiometer
thershold
= switching point (min. 0.1m/s ... max. 20
m/s)
sb
= start bridging (min. 0s ... max. 120s)
offset
= temperature (± 5K)
Relay
LEDs
(on = aktiv)
rel.
= relay / switching point exceeded
sb
= start bridging
Pushbutton
zero point setting (0m/s)
LEDs
Pushbutton
Plug for
display
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

S+S Regeltechnik RHEASGARD® KLGFT / KLGFVT RHEASGARD® KLGFT / KLGFVT Mode d'emploi

Taper
Mode d'emploi