Installation Instructions
GP-IO-332, GP-IO-332-E
© Honeywell Page 1 - Printed in USA LT-GP-II-01 Rev. A
Before you begin
Before installing the GP-IO-332, configure it according to
the instructions in the Geopoint Hub and I/O Installation
and Operation Guide (LT-GPIOG) available on the Alerton
Support Network.
Overview
Warning! Always install equipment in accordance with the
instructions and in a manner consistent with electrical codes and
the authority having jurisdiction. Read all instructions before
mounting and wiring.
ATTENTION! Installez tout le matériel en conformité avec le
Code national de l'électricité et d'une manière acceptable pour
l'autorité locale compétente. Lisez tout instructions avant
l'installation du matériel. Le non respect des instructions peut
entraîner des dommages matériels ou une situation dangereuse.
The GP-IO-332 is a wireless device that eliminates the
need for long cabling between a unitary controller and its
physical I/O. Its multiple inputs and outputs can be
concentrated onto the BACnet bus by the GP-HUB-100
receiver. These instructions will help you mount and wire
the device and then verify that it functions correctly.
Fig. 1 GP-IO-332 dimensions in in. (mm).
Note The GP-HUB-100 signal receiver has the same
dimensions and mounting holes as the GP-IO-332.
Specifications
Supply Voltage: 24VAC (typical), 50/60Hz. 5VA (max)
Operating Temperature: -18°C to 70°C (0°F to 158°F)
Operating Humidity: RH 5% to 95%, non-condensing
Storage Temperatures: -40°C to 70°C (-40°F to 158°F)
Mounting
Choose a mounting location that reduces interference
between the GP-IO-332 and the GP-HUB. Some points to
consider when selecting a location:
The effective communication range is 400 feet through open
air and 100 feet through two non-metallic walls.
Any metal (ducting, equipment, metal studs, and so on) near
the device or between two devices will impede radio waves.
If a wall has metal components (studs, ductwork, and so on)
radio waves will tend to travel along the plane of the wall.
Mounting the device on the same wall as other device(s) will
increase signal strength.
When mounting near ductwork or other metal, use
doublesided tape to mount the device while testing radio
reception.
Mount the GP-IO-332 indoors or in a weatherproof enclosure.
Important! Enclosures, if used, must not block 2.4GHz RF. Use
polyester/fiberglass models. If unsure, consult the manufacturer.
DIN rail mounting
• To mount the GP-IO-332 on a 35mm DIN rail
1 Hold the device with its top tilted toward the DIN
rail and then hook the two top tabs on the back of
the device onto the top of the DIN rail.
2 Push down and in to snap the connector onto the
rail.
To remove the GP-IO-332 from a DIN rail, push straight up
from the bottom to release the top tabs and then pull the
top of the device outward.
Wall mounting
To mount the GP-IO-332 on a wall, position the device in
any orientation and secure it to the wall with size 6 or 8
screws appropriate for the mounting surface.
5.50
(139.6)
5.10
(129.4)
2.80 (71)
3.51 (89.1)
1.70
(43.3)
0.18 (4.6) MOUNTING HOLES x 4
DIN RAIL
1.4 (35)