red lion RAM-99x1 Series Manuel utilisateur

Taper
Manuel utilisateur
Sixnet
®
Series
RAM
®
9000
Hardware Guide | July 2015
Cellular RTUs
RAM 9000 Series Hardware Guide 2
Table of Contents Revised 2015-07-16
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Compliance Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Trademark Acknowledgments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Release Notes and Document Updates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Warnings/Cautions/Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Statement of Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1 Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
RAM 9000 Cellular RTU Product Highlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
General Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
RAM 9000 Model Comparison Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
RAM 9000 Cellular RTU View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Power Specifications and Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical Specifications and Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Bootup LED Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Data Interface Specifications: Serial, Ethernet & USB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mode/Reset Button functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ordering Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chapter 2 Hardware Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mounting the RAM 9000 Cellular RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
DIN Rail Mounting & Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mechanical Dimension Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Antennas and Wireless . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Cellular Antenna and Cable Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
GPS Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installation and Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Wi-Fi Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Ethernet cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
RAM 9000 Series Hardware Guide 3
Table of Contents Revised 2015-07-16
USB Device Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
USB Host Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Serial RS485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
RS485 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Serial RS232 Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Powering the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Testing the power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6-pin Screw Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Power Input Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Battery Removal and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
SIM Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
I/O Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Equivalent Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Thermal Performance and Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Service and Support Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
RAM 9000 Series Hardware Guide 4
Revised 2015-07-16
Preface
Disclaimer
Portions of this document are intended solely as an outline of methodologies to be followed during the mainte-
nance and operation of the RAM 9000 equipment/software. It is not intended as a step-by-step guide or a com-
plete set of all procedures necessary and sufficient to complete all operations.
While every effort has been made to ensure that this document is complete and accurate at the time of release,
the information that it contains is subject to change. Red Lion Controls is not responsible for any additions to or
alterations of the original document. Industrial networks vary widely in their configurations, topologies, and traf-
fic conditions. This document is intended as a general guide only. It has not been tested for all possible applica-
tions, and it may not be complete or accurate for some situations.
Users of this document are urged to heed warnings and cautions summarized at the front of the document, such
as electrical hazard warnings.
Compliance Information
Part 15 of the Federal Communications Commission (FCC) - A Rules: Interference
Every effort has been made to ensure that this equipment is designed to comply with the limits for a Class A digital
device, as described in the FCC Rules. This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable pro
-
tection against harmful interference in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. Operation of this device in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his/her own expense.
Industry Canada
This Class A digital apparatus meets all requirements of the Canadian Interference Causing Equipment Regula-
tions. Operation is subject to the following two conditions; (1) this device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired opera
-
tion.
Environmental Impact Statement
Red Lion equipment contains no hazardous materials as defined by the United States Environmental Protection
Agency (USEPA). Red Lion recommends that all failed product be returned to Red Lion for failure analysis and
proper disposal.
Toxic Emissions
Red Lion equipment releases no toxic emissions.
RAM 9000 Series Hardware Guide 5
Revised 2015-07-16
Trademark Acknowledgments
Windows
®
/98/2000/7/8, Windows XP
®
are registered trademarks of the Microsoft Corporation.
Microsoft is either a registered trademark or trademark of Microsoft Corporation in the United States and/or other
countries.
Release Notes and Document Updates
The hard copy and flash drive versions of this document are revised only at major releases and, therefore, may not
always contain the latest product information. As needed, Application Notes and or Product Bulletins will be pro-
vided between major releases to describe any new information or document changes.
The latest online version of this document and all product updates can be accessed through the Red Lion web site
at
http://www.redlion.net.
Publication History
The following information lists the release history of this document.
ISSUE/REVISION RELEASE DATE CONTENT DESCRIPTION
R04 March 2015 Updates to Warnings
R03 September 2014 Modifications to FCC Statement to cellular frequency bands.
R02 August 2014
Wi-Fi capability added. Change to operating temperature and
thermal performance.
R01 April 2014 First release.
Related Documents
The following information lists available documents related to this product.
ISSUE/REVISION RELEASE DATE DOCUMENT TITLE
version 6 June 2015 SN/RAM 6000 & RAM 9000 Software Manual
Document Ordering Information
To order additional documentation, the user can contact the local sales representative or Red Lion through the
c
ontact numbers and/or e-mail addresses listed on the back of the cover.
Document Comments
Red Lion appreciates all comments that will help us to improve our documentation quality. The user can submit
c
omments through the Red Lion Customer Service. Simply email us at customer[email protected]t.
RAM 9000 Series Hardware Guide 6
Revised 2015-07-16
Additional Product Information
Additional product information can be obtained by contacting the local sales representative or Red Lion through the
contact numbers and/or e-mail addresses listed on the back of the cover.
Safety Information
Environmental:
Warning: The unit may become very hot to the touch in high temperature environments, so extreme caution
should be exercised in handling when energized. The unit should be disconnected from power and allowed to cool
for approximately 5 minutes before touching in high temperature applications.
Pollution degree: 2 (Per IEC 61010-1)
Electrical:
Must be powered by a “Class 2 source” only.
Properly ground the unit before connecting anything else to it. If the equipment is used in a manner “not” speci-
fied by Red Lion, the protection provided by the equipment may be impaired.
Overvoltage category: II (Per IEC 61010-1)
Warnings/Cautions/Notes
Warnings apply to situations where personal injury or death may result.
Cautions apply where damage to equipment may result
Notes apply where additional noteworthy information, not in the general text flow but applicable, is made avail-
able to the user.
Hazardous Location and Installation Requirements
These products should not be used to replace proper safety interlocking. No software-based device (or any other solid-state
device) should ever be designed to be responsible for the maintenance of consequential equipment or personnel safety. In
particular, Red Lion disclaims any responsibility for damages, either direct or consequential, that result from the use of this
equipment in any application.
All power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with
the authority having jurisdiction.
Suitable for use in Class I, Division 2, Groups A, B, C and D hazardous locations, or non-hazardous locations only.
WARNING – EXPLOSION HAZARD: Substitution of components may impair suitability for Class 1, Division 2.
Must consult guide in all cases where this symbol is marked.
RAM 9000 Series Hardware Guide 7
Revised 2015-07-16
WARNING – EXPLOSION HAZARD: When in hazardous locations, disconnect power before replacing or wiring modules.
WARNING – EXPLOSION HAZARD: Do not disconnect equipment unless power has been switched off or the area is known to
be non-hazardous.
WARNING – EXPLOSION HAZARD: Exposure to some chemicals may degrade the sealing properties of materials used in the
relays.
WARNING – EXPLOSION HAZARD: Batteries must only be changed in an area known to be non-hazardous.
These products are operator interface units to be used within control panels in hazardous locations. The enclosure shall be
suitable for the location.
A minimum IP54 rated enclosure is needed for ATEX unless an equivalent degree of protection is supplied by the location.
Hot-swapping is not for use in hazardous locations.
AVERTISSEMENTS POUR INSTALLATION ET ENDROITS DANGEREUX
Ces produits ne doivent pas être utilisés pour remplacer le verrouillage de sécurité approprié. Aucun dispositif basé sur un
logiciel (ou tout autre dispositif à l'état solide) devraient jamais être conçus pour être responsable de l'entretien de l'équipe-
ment consécutifs ou la sécurité du personnel. En particulier, Red Lion décline toute responsabilité pour les dommages, directs
ou indirects, résultant de l'utilisation de cet équipement dans n'importe quelle application.
Tout courant, câblage entrée et sortie (I / O) doit être conforme aux méthodes de câblage à la Classe I, Division 2 et confor-
mément à l'autorité compétente.
Cet appareil est adapté pour utilisation en Classe I, Division 2, Groupes A, B, C, D endroits dangereux ou endroits non-dan-
gereux.
AVERTISSEMENT – RISQUE D’EXPLOSION: La subsitution de tout composant peut nuire à la conformité de Classe I, Division 2.
AVERTISSEMENT – RISQUE D’EXPLOSION: Lorsque dans des endroits dangereux, débranchez le cordon d’alimentation avant
de remplacer ou de brancher les modules.
AVERTISSEMENT – RISQUE D’EXPLOSION: Ne débranchez pas l’équipement à moins que l’alimentation ait été coupée ou que
l’environnement est connu pour être non dangereux.
AVERTISSEMENT– RISQUE D’EXPLOSION: Lexposition à certain produits chimiques peut dégrader les propriétés d’étanchéité
des matériaux utilisés dans les relais.
AVERTISSEMENT – RISQUE D’EXPLOSION: Batteries doivent être changées dans une zone connue pour être non dangereuse.
Ces produits sont des unités d'interface opérateur qui doivent être utilisés à l'intérieur des panneaux de commande dans les
endroits dangereux. L'enclos doit être adapté à l’environnement.
Un boîtier IP54 minimum est nécessaire pour ATEX à moins qu’un degré équivalent de protection est fourni par l'emplace-
ment. Pas de remplacements à chaud des modules dans les zones dangereuses.
RAM 9000 Series Hardware Guide 8
Revised 2015-07-16
Statement of Limited Warranty
(a) Red Lion Controls Inc., Sixnet Inc., N-Tron Corporation, or Blue Tree Wireless Data, Inc. (the "Company") war-
rants that all Products shall be free from defects in material and workmanship under normal use for the period of
time provided in "Statement of Warranty Periods" (available at www.redlion.net) current at the time of shipment
of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO
WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABI-
LITY; (B) WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF
INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEAL-
ING, COURSE OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determin-
ing that a Product is suitable for Customer's use and that such use complies with any applicable local, state or
federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a
result of Customer's failure to store, install, commission or maintain the Product according to specifications; (ii)
Customer alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if
Company so requests, Customer shall, at Company's expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER'S SOLE AND EXCLUSIVE REMEDY AND
COMPANY'S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH IN PARAGRAPH (a).
RAM 9000 Series Hardware Guide 5-14
Product Overview Revised 2015-07-16
RAM 9000 Cellular RTU Product Highlight
Chapter 1 Product Overview
Using a single web-based user interface, our cellular units simplify I/O, network and security configurations to
integrate complex hardware settings. This easy-to-manage configuration reduces the cost and complexity of
deploying and administering multiple devices at remote locations. Furthermore, an integrated configurable state
-
ful firewall provides intrusion protection and encrypted data access while a built-in Software Development Kit
(SDK) enables users to develop custom applications.
Working in conjunction with SixView Manager remote monitoring and control software, RAM RTUs provide low-
cost, real-time access to outlying sites.
RAM 9000 Cellular RTU Product Highlight
Supports Multi-Carrier 4G LTE connectivity with fall back to 3G and 2G
Real-time access to mission-critical data through built-in Modbus gateway
Software Development Kit (SDK) for custom application support
Native support for DNP3 and Modbus protocols
Integrated security firewall provides intrusion protection
Simplified deployment and configuration with single web-based GUI
Support for new and legacy devices with RS232/485 serial or RJ45 Ethernet
Powerful event engine that can trigger built-in I/O or send SMS text messages based on real-time operational
data.
RAM 9000 Series Hardware Guide 5-15
Product Overview Revised 2015-07-16
Specifications
Specifications
General Specifications
Wireless Interfaces
AT&T LTE with fallback to HSPA+
Bell Mobility LTE with fallback to HSPA+
Generic LTE with fallback to HSPA+
Rogers LTE with fallback to HSPA+
TELUS LTE with fallback to HSPA+
Verizon LTE with fallback to EVDO
Programmable Platform
Configurable Events: up to 99 events can be triggered by I/O, Modbus registers, or over 200 system
variables which in turn can send text messages or control I/O
Software Development Kit (SDK)
C/C++/Perl
Protocol Gateway
I/O Controller
Modbus RTU/TCP/ASCII
DNP3 - slave
System Performance
32-bit ARM9 400 MHz CPU
512 MB NAND Memory
128 MB RAM
Tunneling IPsec, GRE, OpenVPN
IP
NAT, port forwarding, dynamic DNS, DHCP
Stateful inspection firewall, IP Transparency
Routing Protocols OSPF, BGP, RIP
Clustering VRRP
GPS
GNSS supported: GPS L1, GLONASS L1, Galileo E1
High RF sensitivity plus jamming detection/removal
Connectors
Ethernet: One (1) or five (5) 10/100Base-T RJ-45 ports
WAN capability on port 2
Serial: One (1) RS-232 (DB9) 115200bps
One (1) RS-485 (screw block)115200bps
USB: One (1) USB 2.0 (mini)
Antennas: Three (3) SMA connectors (antenna, diversity, GPS)
One (1) RP-SMA connector (Wi-Fi optional)
RAM 9000 Series Hardware Guide 5-16
Product Overview Revised 2015-07-16
Specifications
Inputs & Outputs
2 digital inputs
2 digital outputs
3 analog inputs
1 Form C Relay
See detailed I/O specifications in Section 1.2.5 below
Wi-Fi Interface
(Optional)
Complies with IEEE802.11b/g/n
Maximum output power up to 25dBm
Supports up to 150Mbps with 40MHz channel
Power Input
Range: 8-30 VDC (12 or 24 VDC nominal)
Power consumption (less DO power):
Standby: 4W (all models)
Transmitting:
9911 & 9711: 5.0W - 9.4W (cellular only)
9931 & 9731: 5.0W - 13.6W (cellular and Wi-Fi)
Power consumption of DO (max each):
30W (1A @ 30 VDC)
Heat dissipation: 46 BTU/hour max; 20 BTU/hour typical
Mechanical
Dimensions: 132H x 127D x 70W mm (5.2” x 5.00” x 2.75”)
Material : Steel with black zinc coating
Weight: 906 g (2 lbs)
Environmental
Operating temperature: -40°C to +75°C*
Shock: IEC60068-2-27
Vibration: IEC60068-2-6
Humidity: 5 to 95% non-condensing
Ingress Protection: IP30
Ethernet Interface
(10/100 Auto Sensing)
1x or 2x RJ45 (Isolation 1500 Vrms 1 minute)
WAN capability on 2
nd
port
Serial interface
1x RS232 Serial DB9 115200bps
1x RS485 Serial Screws 115200bps (Isolation 1200 Vrms 1 minute)
USB interface
1x USB 2.0 Device mini
1x USB 2.0 Host type A
LED indicators Dual Power, Status Reset, WAN, RSSI, RS232, RS485, GPS, SD, Ethernet Link & Activity
Certification
EMI/EMC – Emissions: FCC, Part 15 and Industry Canada, ICES-003; Class A; EN55022, IEC61000-6-4
Immunity: IEC61000-6-2 (EN61000-4-2,3,4,5,6,8)
Hazardous locations: Class I, Div. 2, Groups A, B, C, D, ANSI/ISA 12.12.01
Electrical safety: UL508/CSA22.2/14 (CUL): IEC61010-1
Carrier specific approvals (Contact Red Lion for latest)
RoHS compliant
RAM 9000 Series Hardware Guide 5-17
Product Overview Revised 2015-07-16
Specifications
*-40°C to +75°C - See Thermal Performance and Considerations section in Chapter 2.
Note: All specifications are subject to change. Consult the Red Lion website for more information
Warranty 3 years on design and manufacturing defects
Compliances The Red Lion Sixnet Series RAM 9000 products meet the following standards plus others:
Electrical Safety
These devices have been designed to meet the basic safety requirements of the following standards:
CE per Low Voltage Directive and IEC 61010-1 (CE applies only to the -EU models. Please contact
Red Lion for availability)
UL508 (Industrial control equipment), ANSI/ISA 12.12.01 (Hazardous Locations)
CSA C22.2 No. 142 and No. 213 (per cUL)
EMC (emissions and immunity)
CE per the EMC directive (CE applies only to the -EU models. Please contact Red Lion for availabil-
ity)
IEC 61000-6-2: Immunity in industrial environments
IEC 61000-6-4: Emmissions in industrial environments
FCC part 15 and ICES 003. See FCC statement on page 6.
EN 55022 (CISPR22)
This equipment has been tested and found to comply with the limits for a Class A digital device, pur-
suant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy; and if not installed and used in accordance
with the instructions, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference to radio communications, in
which case the user will be required to correct the interference at their own expense. Warning:
Changes or modifications to this unit not expressly approved by the party responsible for compliance
could void the user's authority to operate the equipment.
Information to the user: If this equipment causes interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: In order to meet FCC emissions limits, this
equipment must be used only with cables that comply with IEEE 802.3. If necessary, the user should
consult the dealer or an experienced radio/television technician for additional suggestions. The user
may find the following booklet prepared by the Federal Communications Commission helpful: “How
to Identify and Resolve Radio-TV Interference Problems”. This booklet is available from: U.S. Govern
-
ment Printing Office, Washington, DC 20402, Stock No. 004-000-00345-4
WEEE compliance
These devices comply with the WEEE directive. Do not throw away these devices in the standard
trash. Contact Red Lion regarding proper disposal.
RoHS compliance
These devices comply with the RoHS directive and are considered lead and other hazardous sub-
stance free.
RAM 9000 Series Hardware Guide 5-18
Product Overview Revised 2015-07-16
Specifications
RAM 9000 Model Comparison Chart
FEATURE RAM-9X01 RAM-9X11 RAM-9X31
Cellular x = 6 for 3G
x = 7 for 4G LTE
x = 9 for 4G LTE+
x = 6 for 3G
x = 7 for 4G LTE
x = 9 for 4G LTE+
x = 6 for 3G
x = 7 for 4G LTE
x = 9 for 4G LTE+
Wi-Fi - - 1
GPS 1 1 1
Ethernet Port 1 2 2
RS232 Port 1 1 1
RS485 Port 1 1 1
USB Host Port 1 1 1
USB Device Port 1 1 1
SIM Card Slot 2* 2* 2*
SD Card Slot 1 1 1
Discrete Input 2 2 2
Discrete Output 2 2 2
Relay Output 1 1 1
Analog Input 3 3 3
RAM 9000 Cellular RTU View
* A future firmware update is required to utilize the second SIM slot.
Contact Red Lion for availability of this feature.
RAM-9x01
RAM-9x11
RAM-9x31
RAM 9000 Series Hardware Guide 5-19
Product Overview Revised 2015-07-16
Specifications
Power Specifications and Consumption
Power Input:
Range: 8-30 VDC (12 or 24 VDC nominal)
Power consumption (less DO power):
Idle: 4W
Typical: 5 - 6 W
Maximum: 6 - 14 W (depends on model)
Power consumption of DO (max. each):
30W (1A @ 30 VDC)
Heat dissipation: 46 BTU/hour max.; 20 BTU/hour typical
Power input to the unit is protected against reverse polarity and over-voltage up to 33VDC. The routers power
consumption is as follows:
Note: Wiring instructions are provided in
I/O Wiring section in Chapter 2 of the Hardware Installation chapter.
Electrical Specifications and Pinout
Discrete Inputs:
2 Channels
Isolated fully differential
Isolation (channel to channel) = 1 KV
Voltage range = 8-30 VDC
Guaranteed ON voltage = 2.8 VDC
Guaranteed OFF voltage = 2.7 VDC
Input resistance = 315K Ohms
TYPICAL POWER CONSUMPTION (WATTS)
MODEL STANDBY
TRANSMITTING
MINIMUM
TRANSMITTING
MAXIMUM
RAM-99x1 4.0 5.0 9.4
RAM-97x1 4.0 5.0 9.4
RAM-96x1 4.0 4.6 5.5
RAM-9931 4.0 5.0 13.6
RAM-9731 4.0 5.0 13.6
RAM-9631 4.0 4.6 9.7
To meet UL requirements, a “Class 2 Source” power supply is required.
RAM 9000 Series Hardware Guide 5-20
Product Overview Revised 2015-07-16
Specifications
Input current @ 24 VDC = 10 mA
Filtered ON/OFF delay = 25 ms (10 Hz max count rate)
Count resolution = 16 or 32 bits
Discrete Outputs:
2 Channels
Sourcing of module power 8-30 VDC
Max. output load per channel = 1 A (up to 35°C)
Derate to 0.7 A up to 50°C
Derate to 0.55 A up to 70°C
Derate to 0.4 A up to 80°C
Derate to 0.3 A p to 85°C
Min. output load per channel = 1 mA
Max. OFF state leakage current = <0.05 mA
Inrush current (100 mA surge) = 5A
Typical ON voltage drop (@1 A) = 0.13 VDC
Short circuit protection = self-reset fuses (trip above 1.5 Amp at 20C)
Relay Outputs Specs:
1 channel
Relay type = Form C (NO/NC)
Minimum output voltage = 0 VAC/VDC
Maximum output voltage = 110 VDC, 125 VAC
Minimum switching capacity = 10μA, 10 mV DC
Maximum load current per output (30 VDC) = 2 Amps
Maximum load current per output (125 VAC) = 0.3 Amps
Minimum OFF resistance = 1000 Meg Ohms
Maximum relay turn ON time = 4 ms
Maximum relay turn OFF time = 4 ms
Load current versus contact voltage chart:
RAM 9000 Series Hardware Guide 5-21
Product Overview Revised 2015-07-16
Specifications
Analog Input Specs:
3 channels
Ranges = 4-20 mA or 0-10 VDC
Ranges are software selectable
A/D resolution = 16 bits (0.003%)
Input resolution = 2 uA or 0.5 mV
Full scale accuracy (@20°C) (after field calibration) = +/- 0.1%
Input span adjustability = +/- 25%
Input offset adjustability = +/- 25%
Span temperature coefficient +/- 50 ppm per °C
Offset temperature coefficient +/- 50 ppm per °C
Input impedance
Current ranges = 100 Ohms
Voltage ranges = 10KOhms
Current protection (current range) = self-resetting fuses
DMRR at 50/60 Hz = 66dB
Fastest update time = 120 ms per channel
Self-calibration interval = 5 seconds
RAM 9000 Series Hardware Guide 5-22
Product Overview Revised 2015-07-16
Specifications
Indicator Lights
LED STATUS CORRESPONDING STATE
P1
ON Power is being applied to the primary input
OFF Power is not being applied to the primary input
P2
(Backup Power)
ON Power is being applied to the secondary input
OFF Power is not being applied to the secondary input
SD
ON SD Card mounted
OFF No SD Card mounted
GPS
ON Position fix available
OFF No position fix available
WAN
ON Cellular connection is established
OFF Cellular connection is not established
RSSI
Low Signal / No service
> - 109 dBm (Low but valid signal)
> - 99 dBm (Lower but valid signal)
> - 89 dBm (Avg signal)
> - 80 dBm (Excellent signal)
Reset
ON
Unit is booting. Not ready.
OFF
Unit is functioning normally
Status
ON
Unit is booting up.
OFF
Normal operation
FLASH
Unit entering reflashing mode. Do not disturb.
STROBE (Fast
Flash)
System error. Contact Red Lion Technical Support.
Ethernet Link and
Activity
(Yellow)
ON
Link detected
OFF
No link detected
FLASH
Linked and active communications detected
Ethernet Speed
(Green)
ON
100 Mbps link speed detected
OFF
10Mbps link speed detected
RS485
ON
Serial connection is configured for use
OFF
Serial connection is not configured for use
RS232
ON
Serial connection is established – with no data activity with host
OFF
Serial connection is not established
SLOW FLASH
Serial connection is established – with data activity with host
STROBE (Fast
Flash)
Unit is reflashing. Do not disconnect power!
RLY1
ON
The relay output is being activated. The Normally Open terminal
will be ON (closed). The Normally Closed terminal will be OFF
(open)
OFF
The relay output is not being activated. The Normally Open terminal
will be OFF (open). The Normally Closed terminal will be ON
(closed).
RAM 9000 Series Hardware Guide 5-23
Product Overview Revised 2015-07-16
Specifications
Bootup LED Sequence
Stage 1: Power On
When the unit is first powered on, the P1/P2 LEDs will indicate that power has been detected.
Stage 2: CPU Initialized
The LED stacks on each side of the unit will scroll rapidly. When initialization is complete, all front LEDs will be on.
Stage 3: Kernel Loading
The Reset LED will turn off, but Status, A, B and RS232 will remain on.
Stage 4: Filesystem Mounted
The Status and RS232 LEDs will turn off and go into normal mode. A and B will remain on.
Stage 5: System services starting
The A and B lights will now turn off. All front panel LEDs should be in normal mode operation. Your unit should be
fully functional within a few seconds.
Data Interface Specifications: Serial, Ethernet & USB
Ethernet Port
The units 10/100Mbps port is compliant with the EIA-568 standard. The modem’s ports are auto-sensing so they
can be used with either a straight or crossover RJ45 cable to connect to host ports.
The RAM-9701 model has one Ethernet port and the RAM-9711, RAM-9731, RAM-9911, and RAM-9931 models
have two Ethernet ports.
DO1/DO2
ON
The corresponding discrete output is ON and sourcing power.
OFF
The corresponding discrete output is OFF and not sourcing power.
DI1/DI2
ON
A valid voltage is detected on the corresponding discrete input.
OFF
A valid voltage is not being detected on the corresponding discrete
input.
A
Future
Reserved for future use.
B
Future
Reserved for future use.
Ethernet Plug &
Connector Pin Positions
LED STATUS CORRESPONDING STATE
RAM 9000 Series Hardware Guide 5-24
Product Overview Revised 2015-07-16
Specifications
USB Device Port
This is a USB 2.0 Device interface on a Mini B connector. It offers Ethernet-over-USB RNDIS driver
connection with all major operating systems. Driver installation and detection should be auto-
matic on a properly configured Operating System.
USB Host Port
This is a USB 2.0 Host interface on a standard type A connector.
Specifications:
USB Host USB 2.0 (1.5 / 12 / 480 MBit/s)
Complies with Univ
ersal Serial Bus Specification Rev 2.0
Har
dware over current protected (1.0 A max per port)
Incr
eased Retention Connector (Complies with Class 1,. DIV II minimum withdrawal requirement of 15N)
Not electric
ally isolated
Only use shielded USB s
tandard cable
Ma
ximum cable length: 5 m
Note: No software functions have been defined for this port yet. This functionality will be available in a future firmware
release.
Serial Port
The units serial port is an RS232 DTE, compliant with EIA-232 standard. The connector used is DB9 male and is
shown in the illustration below.
Serial Connector (looking at front of unit)
RAM 9000 Series Hardware Guide 5-25
Product Overview Revised 2015-07-16
Specifications
RS485 Port
The units RS485 serial port is for 2 wire, half-duplex connections up to 115,200 baud rate. This
port is fully isolated up to 1200 Vrms (1 minute). A pluggable screw terminal is provided to make
the RS485 connections. Refer to the RS485 wiring section for more details.
Mode/Reset Button functions
The Mode and Reset buttons are found on the front of the unit. Each is a momentary tactile button. It is recom-
mended to use a straightened paper clip to press these buttons. Refer to the table below for the function of each
but
ton.
Reset Button:
Mode But
ton:
This button has 2 full feature sets depending on WHEN it is pressed: Boot time or Run time.
Boot Time: These features are only active at boot time. To use these features, power cycle your unit (or hold
Reset) and immediately push and hold the Mode button for the desired function sequence listed below:
Run Time: These features are active during run time, once the unit is fully booted and idle.
Usage of the Mode push button, during normal runtime:
1. Hold in the Mode button for about 3 seconds until the 4 RSSI signal lights flash. The lights will then go dark. This is
entering action selection mode.
2. Push the button 1 time to increment the action counter. Each time the button is pressed, the RSSI lights will increment
once. The lights count in a binary pattern.
3. Once an action number is selected, the pattern on the light bar will flash. This indicates your action is executing.
FUNCTION PATTERN DESCRIPTION
Hard Reset Press and hold for more than 7 seconds Unit will perform a hard reset without a clean shutdown.
FUNCTION PATTERN DESCRIPTION
Reset to Factory Defaults Hold until RS485 LED flashes Restores unit config to the original state.
Advanced Firmware
Upgrade
Hold until WAN LED flashes
Sets the unit to automatically download firmware files
using the advanced upgrade procedure.
RF module USB bypass
mode: SIM1
Hold until GPS LED flashes
Puts modem into RF module USB bypass mode with SIM1
selected.
RF module USB bypass
mode: SIM2
Hold until SD LED flashes
Puts modem into RF module USB bypass mode with SIM2
selected.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

red lion RAM-99x1 Series Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues