Allen-Bradley ControlLogix 1756-OF4 Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

Publication 1756-IN035C-EN-P - October 2000
Installation Instructions
ControlLogix
Analog (10V) Output Module
(Catalog Number 1756-OF6VI)
Obtain a User Manual
This product also has a user manual (pub. no. 1756-6.5.9). To view it,
visit www.ab.com/manuals
or www.theautomationbookstore.com
You can also purchase a printed manual by:
contacting your local distributor or Rockwell Automation
representative
visiting www.theautomationbookstore.com and placing
an order
To: See page:
Obtain a User Manual 1
Identify the Module Components 2
Prevent Electrostatic Discharge 3
See Removal and Insertion Under Power (RIUP) 3
Understand Compliance to European Union Directive 4
Note the Power Requirements 5
Install the Module 5
Key the Removable Terminal Block/Interface Module 6
Wire the Module 8
Assemble the Removable Terminal Block and the Housing 9
Install the Removable Terminal Block onto the Module 9
Check the Indicators 11
Remove the Removable Terminal Block from the Module 12
Remove the Module 13
See 1756-OF6VI Specifications 13
Hazardous Location information 15
AB Spares
2 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
calling 800.963.9548 (USA/Canada) or 001.320.725.1574
(outside USA/Canada)
Identify the Module Components
You received the following components with your order:
1756-OF6VI module
Removable Terminal Block (RTB) door label
If you did not receive these components, contact your Rockwell
Automation sales office.
This module mounts in a ControlLogix chassis and uses a
separately-ordered RTB or a Bulletin 1492 Interface Module (IFM) to
connect all field-side wiring.
This module uses one of the following RTBs:
1756-TBNH 20 position NEMA RTB
1756-TBSH 20 position Spring Clamp RTB
Use an extended-depth cover (1756-TBE) for applications with heavy
gauge wiring or requiring additional routing space. When using an
IFM, consult the documentation that came with it to connect
all wiring.
IMPORTANT
Before you install your module, you should
have already:
installed and grounded a 1756 chassis and
power supply.
ordered and received an RTB or IFM and its
components for your application.
ControlLogix Analog (10V) Output Module 3
Publication 1756-IN035C-EN-P - October 2000
Prevent Electrostatic Discharge
Removal and Insertion Under Power (RIUP)
ATTENTION
!
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch backplane connector pins.
Follow these guidelines when you handle the module:
Touch a grounded object to discharge
static potential.
Wear an approved wrist-strap grounding device.
Do not touch the backplane connector or connector
pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield
box.
WARNING
!
This module is designed so you can remove and insert it
under backplane power and field-side power. When you
remove or insert a module while field-side power is
applied, you may cause an electrical arc. An electrical
arc can cause personal injury or property damage
because it may:
send an erroneous signal to your system’s field
devices, causing unintended machine motion or loss
of process control.
cause an explosion in a hazardous environment.
Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating connector.
Worn contacts may create electrical resistance.
When you insert or remove the module while backplane
power is on, or you connect or disconnect the RTB with
field-side power applied, an electrical arc can occur. This
could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
non-hazardous before proceeding.
AB Spares
4 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Understand Compliance to European Union Directive
If this product bears the CE marking, it is approved for installation
within the European Union and EEA regions. It has been designed
and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards, in
whole or in part, documented in a technical construction file:
EN 50081-2 EMC - Generic Emission Standard, Part 2 -
Industrial Environment
EN 50082-2 EMC - Generic Immunity Standard, Part 2 -
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Automation Systems Catalog, publication B111
This equipment is classified as open equipment and must be installed
(mounted) in an enclosure during operation as a means of providing
safety protection.
ControlLogix Analog (10V) Output Module 5
Publication 1756-IN035C-EN-P - October 2000
Note the Power Requirements
This module receives power from the 1756 chasis power supply and
requires 2 sources of power from the backplane:
250mA at 5.1V dc
175mA at 24V dc
Add this current/power value (5.5W) to the requirements of all other
modules in the chassis to prevent overloading the power supply.
Install the Module
You can install or remove the module while chassis power is applied.
ATTENTION
!
The module is designed to support Removal and
Insertion Under Power (RIUP). However, when
you remove or insert an RTB with field-side power
applied, unintended machine motion or loss of
process control can occur. Exercise extreme
caution when using this feature.
20861–M 20862–M
1. Align circuit board with top and
bottom chassis guides.
2. Slide module into chassis until
module locking tabs ‘click’.
Printed
Circuit
Board
Locking tab
AB Spares
6 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Key the Removable Terminal Block/Interface Module
Wedge-shaped keying tabs and U-shaped keying bands came with
your RTB to prevent connecting the wrong wires to your module.
Key positions on the module that correspond to unkeyed positions
on the RTB. For example, if you key the first position on the module,
leave the first position on the RTB unkeyed.
Reposition the tabs to rekey future module applications.
Wire the Removable Terminal Block
Wire the RTB with a 5/16 inch (8mm) maximum flat-bladed
screwdriver before installing it onto the module.
Shielded cable is required when using this module. We recommend
using Belden 8761 cable to wire the RTB. The RTB terminations can
accommodate 14-22 gauge shielded wire.
Connect grounded end of the cable
1. Ground the drain wire.
IMPORTANT
We recommend grounding the drain wire at the
field-side. If you cannot ground at the field-side, ground
at an earth ground on the chassis as shown.
20850–M
1. Insert the U-shaped band as shown.
2. Push the band until it snaps in place.
U-shaped
bands
1. Insert the wedge-shaped tab with rounded edge first.
2. Push the tab until it stops.
20851–M
Wedge-shaped tab
Key the Module Key the RTB/IFM
ControlLogix Analog (10V) Output Module 7
Publication 1756-IN035C-EN-P - October 2000
2. Connect the insulated wires to the field-side.
Connect ungrounded end of the cable
1. Cut the foil shield and drain wire back to the cable casing and
apply shrink wrap.
2. Connect the insulated wires to the RTB (see page 8).
A. Remove a length
of cable jacket
from the
connecting cable.
B. Pull the foil shield
and bare drain
wire from the
insulated wire.
C. Twist the foil shield
and drain wire
together to form a
single strand.
D. Attach a ground lug
and apply heat
shrink tubing to the
exit area.
20104-M
20918-M
E. Connect the drain wire to a
chassis mounting tab.
Use any chassis mounting
tab that is designated as a
functional signal ground.
Chassis mounting tab
Drain wire with ground lug
4M or 5M (#10 or #12)
phillips screw and star
washer (or SEM screw)
4M or 5M (#10 or #12)
star washer
Spring Clamp RTB
A. Strip 7/16 inch (11mm) maximum
length of wire.
B. Insert the screwdriver into the
inner hole of the RTB.
C. Insert the wire into the open terminal and
remove the screwdriver.
NEMA Screw RTB
A. Strip 5/16 inch (8mm) maximum length
of wire.
B. Turn the terminal screw counterclockwise.
C. Wrap wire around the terminal.
D. Turn the terminal screw clockwise.
AB Spares
8 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Wire the Module
You can only connect wiring to your module through an RTB or IFM.
The example below shows how to wire the module.
After completing field-side wiring, secure the wires in the strain relief
area with a cable-tie.
20967-M
12
34
56
78
910
1112
1314
1516
1718
1920
+
Shield Ground
1756-OF6VI
OUT-1
Not used
RTN-1
OUT-3
RTN-3
Not used
OUT-5
Not used
Not used
RTN-5
OUT-0
Not used
RTN-0
OUT-2
RTN-2
Not used
OUT-4
Not used
Not used
RTN-4
User Analog
Output Device
NOTE: If separate power sources are used, do not exceed the specified isolation voltage.
ControlLogix Analog (10V) Output Module 9
Publication 1756-IN035C-EN-P - October 2000
Assemble the Removable Terminal Block and the Housing
Install the Removable Terminal Block onto the Module
WARNING
!
The RTB is designed to support Removal and Insertion
Under Power (RIUP). However, when you remove or
insert an RTB with field-side power applied, unintended
machine motion or loss of process control can
occur. Exercise extreme caution when using this feature.
It is recommended that field-side power be removed
before installing the RTB onto the module.
When you remove or insert a module while field-side
power is applied, you may cause an electrical arc. An
electrical arc can cause personal injury or property
damage because it may:
send an erroneous signal to your system’s field
devices, causing unintended machine motion or loss
of process control.
cause an explosion in a hazardous environment.
Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating connector.
Worn contacts may create electrical resistance.
When you insert or remove the module while backplane
power is on, or you connect or disconnect the RTB with
field-side power applied, an electrical arc can occur. This
could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
non-hazardous before proceeding.
20852-M
Groove
Groove
Side edge of the RTB
Side edge of the RTB
Strain relief area
1. Align the grooves at the bottom of the housing with the side edges of the RTB.
2. Slide the RTB into the housing until it snaps into place.
AB Spares
10 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Before installing the RTB, make certain:
field-side wiring of the RTB has been completed.
the RTB housing is snapped into place on the RTB.
the RTB housing door is closed.
the locking tab at the top of the module is unlocked.
20853–M
20854–M
Module
guide
RTB guides
Locking
tab
1. Align the side and top, bottom RTB guides with the
side, top and bottom module guides.
2. Press quickly and evenly to seat the RTB on the
module until the latches snap into place.
3. Slide the locking tab down to lock the RTB
onto the module.
ControlLogix Analog (10V) Output Module 11
Publication 1756-IN035C-EN-P - October 2000
Check the Indicators
The indicators show CAL status (green) and a bi-colored LED for
module "OK" (red/green).
During power up, an indicator test is done and the following occurs:
The "OK" indicator turns red for 1 second and then turns to
flashing green if it has passed the self-test.
This completes installation of the module. Use the information below
to remove the module.
LED
indicators:
This
display:
Means: Take this action:
OK Steady
green light
The outputs are in a normal
operating state.
None
OK Flashing
green light
The module has passed
internal diagnostics but is not
actively controlled.
Configure the module.
OK Flashing red
light
Previously established
communication has timed out.
Check controller and chassis
communication
OK Steady red
light
The module must be replaced. Replace the module.
CAL Flashing
green light
The module is in calibration
mode.
None
20965-M
ANALOG OUTPUT
CAL
OK
AB Spares
12 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Remove the Removable Terminal Block from the Module
Before removing the module, you must remove the RTB.
WARNING
!
Shock hazard exists. If the RTB is removed from
the module while the field-side power is applied,
the module will be electrically live. Do not touch
the RTB’s terminals. Failure to observe this caution
may cause personal injury.
The RTB is designed to support Removal and
Insertion Under Power (RIUP). However, when
you remove or insert an RTB with field-side power
applied, unintended machine motion or loss of
process control can occur. Exercise extreme
caution when using this feature. It is
recommended that field-side power be removed
before removing the module.
When you insert or remove the module while
backplane power is on, or you connect or
disconnect the RTB with field-side power applied,
an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be
sure that power is removed or the area is
non-hazardous before proceeding.
20855–M
2. Open the RTB door and pull the
RTB off the module.
1. Unlock the locking tab at the
top of the module.
42517
ControlLogix Analog (10V) Output Module 13
Publication 1756-IN035C-EN-P - October 2000
Remove the Module
1756-OF6VI Specifications
Number of Outputs 6 individually isolated channels
Module Location 1756 ControlLogix Chassis
Backplane Power Requirements
(No external power requirements)
250mA @ 5.1V dc & 175mA @ 24V dc
(Total backplane power 5.5W)
Power Dissipation within Module
Thermal Dissipation
4.85W
16.54 BTU/hr
Output Voltage Range +/- 10.5V maximum
Voltage Resolution 14 bits across 21V (1.3mV)
(13 bits across 10.5V +sign bit)
Data Format Integer mode (Left justified, 2s complement)
Floating point IEEE 32 bit
Output Impedance <1
Open Circuit Detection None
Output Overvoltage Protection 24V ac/dc maximum
Output Short Circuit Protection Electronically current limited
Drive Capability >
1000 loads, 10mA maximum
Output Settling Time <2ms to 95% of final value with resistive loads
Calibrated Accuracy at 25°C
Calibration Interval
Better than 0.1% of range
6 months typical
Output Offset Drift with
Temperature
60 µV/degree C typical
Gain Drift with Temperature 50 ppm/degree C typical (80 ppm maximum)
Module Error over Full Temp. Range 0.5% of range
Module Scan Time for all Channels 25ms maximum floating point
10ms maximum integer
Isolation Voltage
Channel to channel
User to system
Optoisolated, transformer isolated
100% tested at 1700V dc for 1s, based on 250V ac
100% tested at 1700V dc for 1s, based on 250V ac
1. Push in top and bottom locking tabs. 2. Pull module out of the chassis.
20856–M 20857–M
AB Spares
14 ControlLogix Analog (10V) Output Module
Publication 1756-IN035C-EN-P - October 2000
Additional Notes
The ControlLogix system must be mounted within a suitable enclosure to
prevent personal injury resulting from accessibility to live parts. The interior of
this enclosure must be accessible only by the use of a tool.
This industrial control equipment is intended to operate in a Pollution Degree
2 environment, in overvoltage category II applications, as defined in IEC
publication 664A, at altitudes up to 2000 meters without derating.
Module Conversion Method R-Ladder DAC, monotonicity with no missing codes
Capacitive Load <1 µFd
RTB Screw Torque (NEMA) 7-9 inch-pounds (0.8-1Nm)
Module Keying (Backplane) Electronic
RTB Keying User defined
Field Wiring Arm and Housing
20 Position RTB (1756-TBNH or TBSH)
1
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
0 to 60°C (32 to 140°F)
-40 to 85°C (-40 to 185°F)
5 to 95% noncondensing
Conductors Wire Size
Category
22-14 gauge (2mm
2
) stranded
1
3/64 inch (1.2mm) insulation maximum
2
2, 3
Screwdriver Width for RTB 5/16 inch (8mm) maximum
Agency Certification
(when product or
packaging is marked)
1
Maximum wire size will require extended housing - 1756-TBE.
2
Use this conductor category information for planning conductor routing as described in the system
level installation manual.
3
Refer to publication 1770-4.1 “Industrial Automation Wiring and Grounding Guidelines’.
Marked for all applicable directives
Approved Class I, Division 2, Group A, B, C, D
Certified Process Control Equipment
Certified Class I, Division 2, Group A, B, C, D
Marked for all applicable acts
N223
Listed Industrial Control Equipment
ControlLogix Analog (10V) Output Module 15
Publication 1756-IN035C-EN-P - October 2000
Hazardous Location information
The following information applies when operating this equipment in
hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with markings
on the rating nameplate indicating the hazardous location
temperature code. When combining products within a system, the
most adverse temperature code (lowest “T” number) may be used to
help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.
WARNING
!
EXPLOSION HAZARD
Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this equipment
unless power has been removed or the area is
known to be nonhazardous. Secure any external
connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or
other means provided with this product.
Substitution of components may impair suitability
for Class I, Division 2.
If this product contains batteries, they must only be
changed in an area known to be nonhazardous.
AB Spares
Publication 1756-IN035C-EN-P - October 2000 PN 957424-85
Supersedes Publication 1756-5.35 - September 1999 © 2000 Rockwell International Corporation. Printed in USA
Informations sur l’utilisation de cet équipement en environnements
dangereux :
Les produits marqués « CL I, DIV 2, GP A, B, C, D » ne conviennent qu’à une
utilisation en environnements de Classe I Division 2 Groupes A, B, C, D
dangereux et non dangereux. Chaque produit est livré avec des marquages
sur sa plaque d’identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont combinés dans
un système, le code de température le plus défavorable (code de température
le plus faible) peut être utilisé pour déterminer le code de température global
du système. Les combinaisons d’équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au moment de l’installation.
AVERTISSEMENT
!
RISQUE D’EXPLOSION
Couper le courant ou s’assurer que l’environnement
est classé non dangereux avant de débrancher
l’équipement.
Couper le courant ou s’assurer que l’environnement
est classé non dangereux avant de débrancher les
connecteurs. Fixer tous les connecteurs externes
reliés à cet équipement à l’aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens
fournis avec ce produit.
La substitution de composants peut rendre cet
équipement inadapté à une utilisation en
environnement de Classe 1, Division 2.
S’assurer que l’environnement est classé non
dangereux avant de changer les piles.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16