Mitsubishi Electric MSZ-FD09/12NA Manuel utilisateur

Catégorie
Climatiseurs split-system
Taper
Manuel utilisateur

Ce manuel convient également à

1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read these safety precautions and instructions.
 %HVXUHWRREVHUYHWKHZDUQLQJVDQGFDXWLRQVVSHFL¿HGKHUH
• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
JG79A015H01
SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
ENGLISH
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
2-9/16 in. (65 mm) hole saw
Torque wrench
Wrench (or spanner)
5/32 in. (4 mm) hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer
MSZ-FD09/12NA
When installing multi units, refer to
the installation manual of the multi
unit for outdoor unit installation.
NDo not install the unit by yourself (user).
 ,PSURSHURULQFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHHOHFWULFVKRFNLQMXU\GXHWR
WKHXQLWIDOOLQJRUZDWHUOHDNDJH&RQVXOWDTXDOL¿HGLQVWDOOHURUWKHGHDOHUIURP
whom you purchased the unit.
NFollow the instructions detailed in the installation manual.
 ,QFRPSOHWHLQVWDOODWLRQFRXOGFDXVH¿UHRUHOHFWULFVKRFNLQMXU\GXHWRWKHXQLWIDOO-
ing, or leakage of water.
NInstall the unit securely in a place that can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall
causing injury.
N Perform electrical work according to the installation manual and be sure to use
an exclusive circuit. Do not connect other electrical appliances to the circuit.
 ,IWKHFDSDFLW\RIWKHSRZHUFLUFXLWLVLQVXI¿FLHQWRUWKHUHLVLQFRPSOHWHHOHFWULFDO
ZRUNLWFRXOGUHVXOWLQD¿UHRUDQHOHFWULFVKRFN
NGround the unit correctly.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or tel-
ephone ground. Defective grounding could cause electric shock.
N Do not damage the wires.
 'DPDJHGZLUHVFRXOGFDXVH¿UH
N Be sure to shut off the main power when setting up the indoor P.C. board or
wiring.
Failure to do so could cause electric shock.
N 8VHWKHVSHFL¿HGZLUHVWRVHFXUHO\FRQQHFWWKHLQGRRUDQGRXWGRRUXQLWV$W-
WDFKWKHZLUHV¿UPO\WRDYRLGDSSO\LQJVWUHVVWRWKHWHUPLQDOEORFN
 ,PSURSHUFRQQHFWLRQFRXOGFDXVH¿UH
N 'RQRWLQVWDOOWKHXQLWLQDSODFHZKHUHÀDPPDEOHJDVPD\OHDN
If gas leaks and accumulates around the unit, it could cause an explosion.
NDo not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.
 ,WFRXOGFDXVHD¿UHRUDQHOHFWULFVKRFN
N 8VHWKHSDUWVSURYLGHGRUVSHFL¿HGSDUWVIRUWKHLQVWDOODWLRQZRUN
 7KHXVHRIGHIHFWLYHSDUWVFRXOGFDXVHDQLQMXU\RUOHDNDJHRIZDWHUGXHWRD¿UH
an electric shock, the unit falling, etc.
N When plugging the power supply plug into the outlet, make sure that there is
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that
the power supply plug is completely in the outlet.
If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could
FDXVHHOHFWULFVKRFNRU¿UH,IORRVHSDUWVDUHIRXQGRQWKHSRZHUVXSSO\SOXJUHSODFHLW
N Securely attach the electrical cover to the indoor unit and the service panel to
the outdoor unit.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
QRWDWWDFKHGVHFXUHO\GXVWZDWHUHWFFRXOGFROOHFWLQWKHXQLWDQGFRXOGFDXVHD¿UHRU
an electric shock.
N When installing or relocating the unit, make sure that no substance other than
WKHVSHFL¿HGUHIULJHUDQW5$HQWHUVWKHUHIULJHUDQWFLUFXLW
Any foreign substances in the refrigerant circuit can cause abnormal pressure rise
or an explosion.
N
Do not discharge the refrigerant into the atmosphere.
Check that the refrigerant gas
does not leak after installation has been completed.
If refrigerant leaks during
installation, ventilate the room.
 ,IUHIULJHUDQWFRPHVLQFRQWDFWZLWKD¿UHKDUPIXOJDVFRXOGEHJHQHUDWHG
 ,IUHIULJHUDQWJDVOHDNVLQGRRUVDQGFRPHVLQWRFRQWDFWZLWKWKHÀDPHRIDIDQ
heater, space heater, stove, etc., harmful gases will be generated.
N Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times higher than R22. Not using the appropriate
tools and materials, or improper installation could cause the pipes to burst causing
an injury.
N When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
N When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
If the compressor is started before the refrigerant pipes are connected and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
N )DVWHQDÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKLVPDQXDO
 ,IIDVWHQHGWRRWLJKWDÀDUHQXWFRXOGEUHDNDQGFDXVHUHIULJHUDQWOHDNDJH
N Install the unit according to national wiring regulations.
NDepending on the installation area, install a Ground Fault Interrupt (GFI) circuit
breaker.
If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric shock
could occur.
NPerform the drainage/piping work securely according to the installation
manual.
If there is defect in the drainage/piping work, water could drip from the unit, and
damage household items.
N 'RQRWWRXFKWKHDLULQOHWRUWKHDOXPLQXP¿QVRIWKHRXWGRRUXQLW
This could cause injury.
NDo not install the outdoor unit where small animals may live.
If small animals enter the unit and damage its electrical parts, it could cause a
PDOIXQFWLRQVPRNHHPLVVLRQRU¿UH.HHSWKHDUHDDURXQGWKHXQLWFOHDQ
CAUTION (Could lead to serious injury when operated incorrectly.)
WARNING (Could lead to death or serious injury.)
(OHFWULFDOVSHFL¿FDWLRQV
MODEL MSZ-FD09/12NA
INDOOR UNIT
Power supply (V, PHASE, Hz) 208/230, 1, 60
Min. Circuit Ampacity (A) 1.0
Fan motor (F.L.A.) (A) 0.76
OUTDOOR UNIT
Power supply (V, PHASE, Hz) 208/230, 1, 60
Max. Fuse size (time delay) (A) 15
Min. Circuit Ampacity (A) 12
Fan motor (F.L.A.) (A) 0.56
Compressor (R.L.A) (A) 8.6
(L.R.A) (A) 10.8
Control voltage Indoor unit - Remote controller: (Wireless)
Indoor unit - Outdoor unit: DC12-24 V (Polar)
Pipe
Outside
diameter
Minimum
wall thick-
ness
Insulation
thickness Insulation material
inch (mm)
For liquid 1/4 (6.35) 0.0315
(0.8) 5/16 (8) Heat resistant foam
SODVWLF6SHFL¿F
gravity
For gas 3/8 (9.52) 0.0315
(0.8) 5/16 (8)
Limits
Pipe length 65 ft. (20 m) max.
Height difference 40 ft. (12 m) max.
No. of bends 10 max.
Pipe length
Up to 25 ft. (7.5 m) No additional charge is
required.
Exceeding 25 ft. (7.5 m) Additional charge is required.
(Refer to the table below.)
Refrigerant to be
added 1.62 oz each 5 ft. (30 g/m)
1-3. SPECIFICATIONS
1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION
• Power should be taken from an exclusive branched circuit.
• Wiring work should be based on applicable technical standards.
• Wiring connections should be made following the diagram.
• Securely tighten screws.
Connecting wires and the ground wire
• Use solid conductor AWG14 or stranded conductor AWG14.
• Use double insulated copper wire with 600 V insulation.
• Use copper conductors only.
* Follow local electrical codes.
Power supply cable and ground wire
• Use solid or stranded conductor AWG14.
• Use copper conductors only.
* Follow local electrical codes.
Note:
When the indoor unit is powered from the outdoor unit, depending on local code, a
disconnect switch needs to be installed to a power supply circuit.
• Refrigerant adjustment... If pipe length exceeds 25 ft. (7.5 m), additional refrigerant
(R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 25 ft. [7.5 m])
 7KHXQLWKDVÀDUHGFRQQHFWLRQVRQERWKLQGRRUDQGRXWGRRUVLGHV
• Remove the valve cover from the outdoor unit, then connect the pipe.
• Refrigerant pipes are used to connect the indoor and outdoor units.
• Be careful not to crush or over bend the pipe in pipe bending.
1-3-2. REFRIGERANT PIPES
• To prevent condensation, insulate the two refrigerant pipes.
• Refrigerant pipe bending radius must be 4 in. (100 mm) or more.
CAUTION
%HVXUHWRXVHWKHLQVXODWLRQRIVSHFL¿HGWKLFNQHVVWDEOHRQWKHULJKW([FHVVLYHLQVXOD-
tion may cause incorrect installation of the indoor unit, and too little insulation may cause
condensate to form.
1-2. SELECTING THE INSTALLATION LOCATION
INDOOR UNIT
 :KHUHDLUÀRZLVQRWEORFNHG
• Where cool air spreads over the entire room.
• On a rigid wall to reduce the possibility of vibration.
• Where it is not exposed to direct sunlight.
• Where it can be easily drained.
• At a distance 3 ft. (1 m) or more away from a TV and
radio. Operation of the air conditioner may interfere
with radio or TV reception. An amplifier may be re-
quired for the affected device.
• In a place as far away as possible from fluorescent
and incandescent lights (so the infrared remote control
can operate the air conditioner normally).
:KHUHWKHDLU¿OWHUFDQEHUHPRYHGDQGUHSODFHGHDVLO\
Note:
Install the indoor unit high on the wall where air can dis-
tribute over the entire room.
REMOTE CONTROLLER
• Where it is convenient to operate and easily visible.
• Where children cannot easily touch it.
 6HOHFWDSRVLWLRQDERXWIWPDERYHWKHÀRRU
Check that signals from the remote controller from
that position are received by the indoor unit (‘beep’
or ‘beep beep’ receiving tone sounds). Then, attach
remote controller holder to a pillar or wall and install
wireless remote controller.
Note:
,QURRPVZKHUHLQYHUWHUW\SHÀXRUHVFHQWODPSVDUHXVHG
the signal from the wireless remote controller may not be
received.
OUTDOOR UNIT
• Where it is not overly exposed to strong winds.
 :KHUHDLUÀRZLVJRRGDQGGXVWOHVV
Where neighbours are not annoyed by operation
sound or hot air.
• Where rigid wall or support is available to prevent the
increase of operation sound or vibration.
• Where there is no risk of combustible gas leakage.
• If installing the unit in a location high above the ground,
be sure to secure the unit legs.
• Where it is at least 10 ft. (3 m) away from the antenna
of TV set or radio. Operation of the air conditioner may
interfere with radio or TV reception in areas where re-
FHSWLRQ LV ZHDN $Q DPSOL¿HU PD\ EH UHTXLUHG IRU WKH
affected device.
• Install the unit horizontally.
• Please install it in an area not affected by snowfall or
blowing snow. In areas with heavy snow, please install
DFDQRS\DSHGHVWDODQGRUEDIÀHERDUGV
Note:
• It is advisable to make a piping loop near outdoor unit
so as to reduce vibration.
 )RU LQFUHDVHG HI¿FLHQF\ LQVWDOO WKH RXWGRRU XQLW LQ D
location where continuous direct sunlight or excessive
water can be avoided as much as possible.
Note:
When operating the air conditioner in low outside tem-
perature, be sure to follow the instructions described
below.
• Never install the outdoor unit in a place where its air
inlet/outlet side may be exposed directly to wind.
• To prevent exposure to wind, install the outdoor
unit with its air inlet side facing the wall and
DEDIÀH
board on the air outlet side.
Avoid the following places for installation where air
conditioner trouble is liable to occur.
 :KHUHÀDPPDEOHJDVFRXOGOHDN
• Where there is an excessive amount of machine oil
in the air.
• Salty places such as the seaside.
 :KHUHVXO¿GHJDVLVJHQHUDWHGVXFKDVDKRWVSULQJ
Where there is high-frequency or wireless equipment.
1-4. INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
(1) Installation plate 1
(2)
Attachment screws for the installa-
tion plate
4×25mm
5
(3) Remote controller holder 1
(4)
Screws for the remote controller
holder
3.5 × 16 mm (Black)
2
(5) Battery (AAA) for (6) 2
(6) Wireless remote controller 1
(7) Felt tape (For left or left-rear piping) 1
(8) Anti-Allergy Enzyme Filter 1
(9) 3ODWLQXPGHRGRUL]LQJ¿OWHU 1
FIELD-SUPPLIED PARTS
(A) Indoor/outdoor unit connecting wire* 1
(B) Extension pipe 1
(C) Wall hole sleeve 1
(D) Wall hole cover 1
(E) Pipe attachment strap 2 to 5
(F) Screw for (E) 4 × 20 mm 2 to 5
(G) Piping tape 1
(H) Putty 1
(I)
Drain hose
(or soft PVC hose, 19/32 in. [15 mm]
inner diameter or hard PVC pipe
VP16)
2to5
(J) Refrigerant oil 1
(K) Power supply cord 1
Units should be installed by licensed contractor
according to local code requirements.
Indoor unit
Wall hole
sleeve (C)
Cut off the
extra length. Pipe attachment
strap (E)
Use the wall hole sleeve
(C) to prevent indoor/out-
door connecting wire (A)
from contacting metal
parts in the wall and to
protect the wiring from
rodents.
Wall hole cover (D)
Seal the wall hole
gap with putty (H).
Attach the pipe to
wall with pipe at-
tachment strap (E).
Attachment screw (F)
After the leak test, apply insulating mate-
rial tightly so that there is no gap.
When the piping is to be attached to a wall
comprised of tin plate or metal netting, use
chemically treated wooden piece 25/32 in.
(20 mm) or thicker between the wall and
the piping, or wrap insulation vinyl tape 7
to 8 turns around the piping.
To use existing piping, perform COOL
operation for 30 minutes and pump down
before removing the old air conditioner.
5HPDNHÀDUHDFFRUGLQJWRWKHGLPHQVLRQ
for new refrigerant.
* Note:
Place indoor/outdoor unit connecting wire (A)
and power supply cord (K) at least 3 ft. (1 m)
away from the TV antenna wire.
5-5/8 in.(60 mm) or
more/ 2-3/8 in.(142.5
mm) or more for left and
left back piping (using
spacer)
9/32 in. (7 mm)
or more
(B)
Open two sides of
left, right, or rear
side.
4in.
(100 mm)
or more
14 in.
(350 mm)
or more
8in.
(200 mm)
or more
Basically open 4 in.
(100 mm) or more
without any obstruction
in front and on both
sides of the unit.
4 in.
(100 mm)
or more
Unit: inch
Unit: mm
31-1/2
19-11/16
Air inlet
Air outlet
13-9/16
11-1/4
2-3/8
×
13/16 slot
12-12-3/4
1-9/16
800
500
Air inlet
Air outlet
2-10
×
21 slot
344.5
285
150
40
304-325
5-
15/16
3-5/16 in.(84
mm) or more
3-5/16 in.(84
mm) or more
• Connect wires to the appropriate terminals
• For future servicing, leave some slack in the connecting wires.
• Make ground wire a little longer than
others. (More than 1-9/16 in. [40 mm])
2-1. ATTACHING THE INSTALLATION PLATE
• Find a stud in the wall to attach installation plate (1) horizontally on the wall with screws (2).
• To prevent installation plate (1) from vibrating, be sure to install the attachment screws in
the holes indicated in the illustration. For added support, additional screws may also be
installed in other holes.
• When the indoor unit is to be attached to a concrete wall using recessed bolts, secure
installation plate (1) using 7/16 in. x 13/16 in · 7/16 in. x 1 in. (11 mm × 20 mm · 11 mm ×
26 mm) oval hole (17-3/4 in. [450 mm] pitch).
 ,IWKHUHFHVVHGEROWLVWRRORQJFKDQJHLWIRUDVKRUWHURQH¿HOGVXSSOLHG
2. INDOOR UNIT INSTALLATION
Wall
Outdoor side
2-2. DRILLING
1) Determine where the holes will be located on the wall.
2) Drill a ø 2-9/16 in. (65 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm)
lower than the indoor side.
3) Insert wall hole sleeve (C).
2-3. CONNECTING WIRES FOR INDOOR UNIT
Note:
When the indoor unit is powered from the outdoor unit, depending on local code, a discon-
nect switch needs to be installed to a power supply circuit.
1) Remove the panel assembly. (Refer to 5-1.)
2) Place the upper part of the indoor unit on the installation plate.
3) Remove corner box and conduit cover.
4) Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward piping) to
conduit cover with lock nut. The thread of the installed conduit pipe / elbow joint appear-
ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less
than 1-3/16 in. (30 mm) outside. (Fig. 2)
5) Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical
parts box.
6) Process the end of indoor/outdoor unit connecting wire (A) (Fig. 3). Attach it to the
terminal block. Be careful not to make mis-wiring. Attach the wire to the terminal block
securely so that its core cannot be seen, and no external force affects the connecting
section of the terminal block.
7) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fas-
tened.
8) Secure indoor/outdoor unit connecting wire (A) and the ground wire with conduit cover.
Never fail to hook the claw of the conduit cover to the electrical box. Attach the conduit
cover securely. (Fig. 4)
9) According to the piping direction, remove the shaded part of the left side of box (Fig. 5)
or corner box (Fig.6). Reinstall corner box and front panel.
Less than 3/8 in.
(10 mm)
Conduit cover
Conduit pipe or
elbow joint
Lock nut
6/32-9/32 in.
(5-7 mm)
Ø 2-9/16 in.
(65 mm)
Lead
wire
19/32 in.
(15 mm)
1 in.
(25 mm)
Indoor terminal
block
Fixing
screw
Conduit
cover
Lock nut
or
Conduit pipe
(for rear piping)
Elbow joint
(for right, left, or downward piping)
Elbow joint
(for right, left, or
downward piping)
Less than 1-3/16 in.
(30 mm)
Corner box
Remove panel for
piping on right side of
unit
1 in.
(25 mm)
Remove panel for
piping on bottom side
of unit
Hook
Conduit cover
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Fig. 5 Fig. 6
Box
Remove panel for
piping on left side of
unit
Remove panel for
piping on bottom left
side of unit
Level
Installation plate (1)
Plumb
Align the plumb
line with the
mark .
Center of
ø 2-9/16 in.
(65 mm) hole
3-5/16 in.
(84 mm)
or more
3-5/16 in.
(84 mm)
or more
Bind the line to the center hole.
5-5/8 in. (60 mm) or more
2-3/8 in. (142.5 mm) or more for left
and left back piping (using spacer)
Ceiling
Wall
Wall
Attachment screw (2)
* Same for left hole.
Insert
the
scale. *
Align the
scale with
the line. *
4 in.
(100 mm)
INDOOR UNIT
Terminal block
208/230 V AC
1phase, 60 Hz
Grouding
terminal**
Disconnect
switch*
OUTDOOR UNIT
Grouding terminal**
Ground
Power supply
208/230 V AC,
1phase 2wires.
60 Hz
Terminal
block 1
Remark:
* A disconnect switch is
required.
Check the local code.
** Use a ring tongue termi-
nal in order to connect a
ground wire to terminal.
Terminal block 2
2-4-2. DRAIN PIPING
• If the extension drain hose has to pass through a room, be sure to wrap it with insu-
ODWLRQ¿HOGVXSSOLHG
• The drain hose should point downward for easy drain. (Fig. 1)
 ,I WKH GUDLQ KRVH SURYLGHG ZLWK WKH LQGRRU XQLW LV WRR VKRUW FRQQHFW LW ZLWK D ¿HOG
supplied drain hose (I). (Fig. 2)
• When connecting the drain hose to a hard vinyl chloride pipe, be sure to insert it se-
curely into the pipe. (Fig. 3)
Do not make drain piping as shown below.
Do not raise Accumulated
drain water
Air
Waving
Water
leakage
Water
leakage
Water
leakage
Tip of drain
hose dipped
in water
Ditch
At least
1-31/32 in.
(50 mm)
gap
Downward
slope
Drain
hose
Soft hose I.D.
19/32 in.
(15 mm)
Drain hose
Hard vinyl chloride pipe
I.D. 1-3/16 in.
(30 mm)
Insert
securely
Different
diameter joint
27-9/16 in.
(70 cm)
or more
Fig. 1 Fig. 2 Fig. 3
Liquid pipe
Gas pipe
Felt tape (7)
Indoor/outdoor unit
connecting wire (A)
Piping tape (G)
2-4. PIPE FORMING AND DRAIN PIPING
2-4-1. PIPE FORMING
• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not crowded or bent.
• Do not pull the hose when applying the tape.
• When the drain hose passes the room, be sure to wrap it with insulation material
¿HOGVXSSOLHG
Note:
Make sure not to damage the cover of refrigerant pipe when attaching it back on with
screws.
Left or left-rear piping
Note:
Be sure to reattach the drain hose and the drain cap if the piping is being installed on
left or bottom left of unit, otherwise, water could drip down from the drain hose.
3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\IHOWWDSH
from the end.
Felt tape (7) overlap width should be 1/3 the tape width. Use a bandage stopper at
the end of felt tape (7).
2) Pull out the drain cap at the back right of the indoor unit. (Fig. 1)
• Hold the convex section at the end and pull the drain cap.
3) Pull out the drain hose at the back left of the indoor unit. (Fig. 2)
• Hold the claw marked by the arrows and pull out the drain hose forward.
4) Put the drain cap into the section to which the drain hose is to be attached at the rear
of the indoor unit. (Fig. 3)
• Insert a screwdriver into the hole on the cap and insert the cap fully into the drain
pan.
5) Insert the drain hose fully into the drain pan at the back right of the indoor unit. (Fig. 4)
• Check if the hose is hooked securely to the projection of its inserting part at the
drain pan.
6) Insert the drain hose into wall hole sleeve (C), and attach the upper part of indoor
unit onto the installation plate (1). Then, shift the indoor unit completely to the left to
make placing the piping in the back of the unit easier.
7) Cut out a piece of cardboard from the shipping box, roll it up, hook it onto the back
rib, and use it as a spacer to lift the indoor unit. (Fig. 5)
8) Connect the refrigerant piping with the extension pipe (B).
9) Attach the lower part of the indoor unit into the installation plate (1).
Remove panel for piping
on left side of unit.
Drain cap
Drain hose
Drain cap
Drain hose
Fig. 1 Fig. 2
Fig. 3 Fig. 4
Fig. 5
Piping tape (G)
Felt tape (7)
Rear or bottom piping
3ODFHWKHUHIULJHUDQWSLSLQJDQGWKHGUDLQKRVHWRJHWKHUWKHQ¿UPO\DSSO\SLSLQJWDSH
(G) from the end.
2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the up-
per part of the indoor unit on the installation plate (1).
3) Check if the indoor unit is attached securely on the installation plate (1) by moving
the unit to left and right.
4) Attach the lower part of the indoor unit into the installation plate (1).
Right piping
Note:
Before performing the following, make sure that wiring is completed, and the conduit
cover is installed. (Refer to 2-3.)
1) Place the refrigerant piping and the drain hose together, shift them to left side of the
XQLWDQGWKHQ¿UPO\DSSO\SLSLQJWDSH*IURPWKHHQG
2) Insert the piping and the drain hose into the wall hole sleeve (C), and attach the up-
per part of the indoor unit on the installation plate (1).
3) Check if the indoor unit is attached securely on the installation plate (1) by moving
the unit to left and right.
4) Attach the lower part of the indoor unit into the installation plate (1).
To the left
Remove panel
for piping on
right side of
unit
Remove panel for piping on
bottom side of unit
3-1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connector to conduit plate with lock nut then secure it against unit with
screws.
4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K)
to the TB support.
5) Loosen the terminal screw, and attach indoor/outdoor unit connecting wire (A) from the indoor
unit correctly on the terminal block. Attach the wire to the terminal block securely so that its
core cannot be seen, and no external force affects the connecting section of the terminal
block.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.
7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.
3-2. FLARE CONNECTION
1) Cut the copper pipe as straight as possible with a pipe cutter. (Fig. 1, 2)
2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to
avoid getting metal shavings into the piping. (Fig. 3)
5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWVWKHQSXWWKHPRQSLSH
4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A
mm from the table according to the tool you use.
5) Check
 &RPSDUHWKHÀDUHGZRUNZLWK)LJ
 ,IÀDUHLVGHIHFWLYHFXWRIIWKHVHFWLRQDQGUHSHDWSURFHGXUH
Terminal block
Conduit cover
Lead wire
3. OUTDOOR UNIT INSTALLATION
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
• Make earth wire a little longer than others.
(More than 2-3/8 in. [60 mm])
• For future servicing, leave some slack in
the connecting wires.
Pipe diameter
inch (mm)
Nut
inch
(mm)
A inch (mm) Tightening torque
Clutch
type tool
for R410A
Clutch
type tool
for R22
Wing nut
type tool
for R22
N•m ft•lb
(kgf•cm)
ø 1/4 (6.35) 1/4
(17)
0 to 0.02
(0 to 0.5)
0.04 to
0.06
(1.0 to
1.5)
0.06 to
0.08
(1.5 to
2.0)
13.7 to 17.7 10 to 13
(140 to 180)
ø 3/8 (9.52) 3/8
(22)
34.3 to 41.2 25 to 30
(350 to 420)
ø 1/2 (12.7) 1/2
(26) 0.08 to
0.10
(2.0 to
2.5)
49.0 to 56.4 36 to 42
(500 to 575)
ø 5/8 (15.88)
5/8
(29)
73.5 to 78.4 54 to 58
(750 to 800)
Power supply cord (K)
L1 L2
1-3/8 in.
(35 mm)
19/32 in.
(15 mm)
Service panel
Lock nut
Conduit cover
Conduit plate
Connector
Grounding
terminal
Copper
pipe
Good
90°
Tilted
No good
Fig. 1 Fig. 2
Burr Copper pipe
Spare reamer
Pipe cutter
Fig. 4
Fig. 3
Smooth all around
Even length
all around
Inside is shin-
ing without any
scratches.
Fig. 5
Fig. 6
A
Flare nut
Die
Copper pipe
Clutch type
Flaring tool
Wing nut type
Uneven Burred
TB support
3-3. PIPE CONNECTION
 )DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOHUHIHUWR
 :KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\HYHQWXDOO\EUHDNDQGFDXVHUHIULJHUDQWOHDNDJH
Indoor unit connection
Connect both liquid and gas pipings to indoor unit.
• Apply a thin coat of refrigerant oil (J) on the seat surface of pipe.
 7RFRQQHFW¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXW
• Use tightening torque table above as a guideline for indoor unit side joints, and tighten
XVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure
detailed in Indoor unit connection.
• For tightening, use a torque wrench or spanner.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, insulate the piping, including valves.
3) Apply piping tape (G) starting from the connection on the outdoor unit.
• When piping has to be installed through a ceiling, closet or where the temperature
DQGKXPLGLW\DUHKLJKXVHDGGLWLRQDO¿HOGVXSSOLHGLQVXODWLRQWRSUHYHQWFRQGHQVD-
tion.
4-1. PURGING PROCEDURES AND LEAK TEST
1)
Remove service port cap of stop valve on the side of the outdoor unit gas pipe.
2) Connect gauge manifold valve and vacuum pump to service port of stop valve on the
gas pipe side of the outdoor unit.
4-5. EXPLANATION TO THE USER
• Using the OPERATING INSTRUCTIONS, explain to the user how to use the air condition-
HUWKHUHPRWHFRQWUROOHUUHPRYLQJWKHDLU¿OWHUVSODFLQJRUUHPRYLQJWKHUHPRWHFRQWUROOHU
from the remote controller holder, cleaning methods, precautions for operation, etc.)
• Recommend that the user read the OPERATING INSTRUCTIONS carefully.
Stop valve for
GAS
Stop valve cap
(Torque 19.6 to
29.4 N•m, 200
WRNJIƒFP
Vacuum pump (or the vacuum
pump with the function to
SUHYHQWWKHEDFNÀRZ
Gauge manifold valve
(for R410A)
Compound pressure gauge
(for R410A)
–0.101 MPa
(–30 in.Hg
[–760 mHg])
Handle
Low Handle High
Adapter for pre-
venting the back
ÀRZ
Charge hose
(for R410A)
*Close
*Open
Hexagonal wrench
Precautions when using the control valve When attaching the control valve
to the service port, valve core may
deform or loosen if excess pressure
is applied. This may cause gas leak.
Service port
Charge hose
Body
Close
Open
Control valve
A
When attaching the control valve to
the service port, make sure that the
valve core is in closed position, and
then tighten part A. Do not tighten
part A or turn the body when valve
core is in open position.
Service port cap
(Torque 13.7 to
17.7 N•m, 140 to
180 kgf•cm)
*4 to 5 turns
3) Run the vacuum pump 15 minutes or more.
4) Check the vacuum with the gauge manifold valve, then close it and shut off the vacuum
pump.
5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve remains
LQ WKH VDPH SRVLWLRQ &RQ¿UP WKDW SUHVVXUH JDXJH VKRZV ± 03D >*DXJH@ ±
in.Hg [–760 mmHg]).
6) Quickly remove gauge manifold valve from service port of stop valve.
7) After refrigerant pipes are connected and evacuated, fully open all stop valves on both
sides of gas pipe and liquid pipe. Operating the unit without fully opening the valves
lowers the performance and causes problems.
8) Refer to 1-3. SPECIFICATIONS, and charge the prescribed amount of refrigerant if
needed. Be sure to charge slowly with liquid refrigerant. Otherwise, composition of the
refrigerant in the system may be changed and affect performance of the air conditioner.
9) Tighten cap of service port.
10) Conduct a leak test
Stop valve
for LIQUID
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN
Pressure gauge
(for R410A)
4-2. TEST RUN
1) Insert power supply plug into the power outlet and/or turn
on the breaker.
2) Press the E.O. SW once. Test run will be performed for
30 minutes. If the power lamp blinks every 0.5 seconds,
inspect the indoor/outdoor unit connecting wire (A). After
the test run, emergency COOL mode (75ºF [24ºC] COOL)
will start.
3) To stop operation, press the E.O. SW several times until
all LED lamps turn off. Refer to operating instructions for
details.
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and listen for an audible indicator from
the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
• Once the compressor stops, the restart preventive device operates so the compressor
will not operate for 3 minutes to protect the air conditioner.
4-3. AUTO RESTART FUNCTION
This product is equipped with an auto restart function. When the power supply is cut off
during operation, such as during blackouts, the function automatically starts operation in
the previous setting once the power supply is resumed. (Refer to the operating instructions
for details.)
Emergency
operation switch
(E.O. SW)
Caution:
• After test run or remote signal reception check, turn off the unit with the E.O. SW or
the remote controller before turning off the power supply. If this procedure is not per-
formed, the unit will automatically begin operation when power supply is resumed.
To the user
• After installing the unit, explain to the user about auto restart function.
• If auto restart function is unnecessary, it can be deactivated. Consult the service rep-
resentative to deactivate the function. Refer to the service manual for details.
Installation posi-
tion
Left Center Right
Slide switch
Remote controller
display
(Left) (Center)(Right)
RESET
button
SLIDE SWITCH
4-4. REMOTE CONTROLLER SETTING
Set the slide switch of the remote controller according to where the indoor unit is installed
in the area. If the switch is not set correctly, the air conditioner may not function properly.
Location of unit in area:
Left: Distance to objects (wall, cabinet, etc.) is less
than 19-11/16 in. (50 cm) to the left
Center: Distance to objects (wall, cabinet, etc.) is
more than 19-11/16 in. (50 cm) to the left and right
Right: Distance to objects (wall, cabinet, etc.) is less
than 19-11/16 in. (50 cm) to the right
1) Remove the front lid.
2) Set the slide switch according to the installed position of the indoor unit.
3) Insert two (AAA) batteries.
4) Reattach the front lid.
5) Press the RESET button gently using a thin instrument.
5-3. PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following
the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas
pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely
so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge]
(0 lbf/in.2[0 kgf/cm2]).
4) Start the emergency COOL operation.
To start the emergency operation in COOL mode, disconnect the power supply
plug and/or turn off the breaker. After 15 seconds, connect the power supply plug
and/or turn on the breaker, and then press the E.O. SW once. (The emergency
COOL operation can be performed continuously for up to 30 minutes.)
5)
Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure
gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 lbf/in2[0.5 to 0 kgf/cm2]).
6) Stop the emergency COOL operation.
Press the E.O. SW twice to stop the operation.
5. RELOCATION AND MAINTENANCE
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO
100-8310, JAPAN
5-1. REMOVING AND INSTALLING THE PANEL
ASSEMBLY
Removal procedure
1) Remove the two screws that attach the panel assembly.
5HPRYHWKHSDQHODVVHPEO\%HVXUHWRUHPRYHLWVERWWRPHQG¿UVW
5-2. REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
When releasing the corner part, release both left and right bottom corner part of
LQGRRUXQLWDQGSXOOLWGRZQZDUGDQGIRUZDUGDVVKRZQLQWKH¿JXUHRQWKHULJKW
Push
Lower
Square hole
Installation procedure
1) Install the panel assembly following the removal procedure in reverse.
2) Be sure to press the positions as indicated by the arrows in order to attach the
assembly completely to the unit.
If the above method cannot be used
Remove the front panel. Then, insert hexagonal wrenches into the square holes on
WKHOHIWDQGULJKWVLGHVRIWKHXQLWDQGSXVKWKHPXSDVVKRZQLQWKHIROORZLQJ¿JXUH
The bottom of the indoor unit lowers and releases the hooks.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Mitsubishi Electric MSZ-FD09/12NA Manuel utilisateur

Catégorie
Climatiseurs split-system
Taper
Manuel utilisateur
Ce manuel convient également à

dans d''autres langues