Rockwell Automation 40072-107-01 Installation Instructions Manual

Taper
Installation Instructions Manual
Publication 1769-IN060C-EN-P - May 2002
Installation Instructions
Compact I/O DeviceNet Scanner Module
(Cat. No. 1769-SDN)
Inside...
For More Information.............................................................................. 2
European Communities (EC) Directive Compliance ................................ 3
Hazardous Location Considerations ....................................................... 4
Environnements dangereux .................................................................... 4
Module Description ................................................................................ 5
Module Installation................................................................................. 6
System Planning ..................................................................................... 8
System Assembly.................................................................................... 9
System Mounting.................................................................................. 10
Replacing the Scanner Module within a System................................. 13
Field Wiring Connections...................................................................... 14
Scanner Module Power-Up................................................................... 15
Configuring the 1769-SDN on DeviceNet............................................. 16
Data Organization ................................................................................. 17
Diagnostic Indicators ............................................................................ 18
Error Codes............................................................................................ 19
Specifications ....................................................................................... 21
2 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
For More Information
If you would like a manual, you can:
download a free electronic version from the internet:
www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting www.theautomationbookstore.com and placing your order
calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
For Refer to this Document Pub. No.
A more detailed description of how to use
your DeviceNet Scanner Module
Compact I/O DeviceNet Scanner
Module User Manual
1769-UM009A-EN-P
Detailed information on planning,
mounting, wiring, and troubleshooting your
CompactLogix System.
CompactLogix System User Manual 1769-UM007C-EN-P
Detailed information on planning,
mounting, wiring, and troubleshooting your
MicroLogix 1500 System.
MicroLogix 1500 Programmable
Controllers User Manual
1764-UM001A-US-P
DeviceNet network planning information. DeviceNet Cable System Planning and
Installation Manual
DN-6.7.2
More information on proper wiring and
grounding techniques.
Industrial Automation Wiring and
Grounding Guidelines
1770-4.1
TIP
Translated versions of these Installation Instructions are
available electronically. Obtain a translated version of this
publication at www.theautomationbookstore.com.
Compact I/O DeviceNet Scanner Module 3
Publication 1769-IN060C-EN-P - May 2002
European Communities (EC) Directive Compliance
This product carries the CE mark and is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet the
following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC Electromagnetic
Compatibility (EMC) by applying the following standards, in whole or in part,
documented in a technical construction file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial
Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by
applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 -
Equipment Requirements and Tests. For specific information required by
EN 61131-2, see the appropriate sections in this publication, as well as the
Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines
For Noise Immunity, publication 1770-4.1. and the Automation Systems Catalog,
B111.
This equipment is classified as open equipment and must be mounted in an
enclosure during operation to provide safety protection.
4 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
sapplique à une utilisation dans des environnements dangereux.
WARNING
!
EXPLOSION HAZARD
Substitution of components may impair suitability for Class
I, Division 2.
Do not replace components or disconnect equipment
unless power has been switched off or the area is known
to be non-hazardous.
Do not connect or disconnect components unless power
has been switched off or the area is known to be
non-hazardous.
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or
be protected by conduit or other means.
All wiring must comply with N.E.C. article 501-4(b).
AVERTISSEMENT
!
DANGER DEXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est
coupée et que l'environnement est classé non dangereux.
Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée ou que
l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.
Compact I/O DeviceNet Scanner Module 5
Publication 1769-IN060C-EN-P - May 2002
Module Description
Table A
1 bus lever (with locking function) 6 grounding screw
2A upper DIN rail latch 7A DeviceNet mating male receptacle
2B lower DIN rail latch 7B removable DeviceNet female connector
3A upper panel mounting tab 8A movable bus connector with female pins
3B lower panel mounting tab 8B bus connector with male pins
4 Module and Network status LEDs 9 nameplate label
5 Address and Error numeric displays
3A
1
2A
4
5
2B
6
7A
8A
8B
9
7B
3B
8B
6 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
Module Installation
The 1769-SDN module is suitable for use in an industrial environment when
installed in accordance with these instructions. Specifically, this equipment is
intended for use in clean, dry environments (Pollution Degree 2
(1)
) and with
circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Prevent Electrostatic Discharge
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the products insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
ATTENTION
!
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow these
guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
Compact I/O DeviceNet Scanner Module 7
Publication 1769-IN060C-EN-P - May 2002
Remove Power
ATTENTION
!
Remove power before removing or inserting this module. When
you remove or insert a module with power applied, an
electrical arc may occur. An electrical arc can cause personal
injury or property damage by:
sending an erroneous signal to your systems field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
8 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
System Planning
Consider the following when planning your system:
The scanner can communicate with up to 63 DeviceNet devices.
The scanner, as a master, can own up to 63 slave I/O nodes.
The scanner can simultaneously be a master and be a slave owned by
another DeviceNet master.
A 1769-ECR (right end cap) or 1769-ECL (left end cap) is required to
terminate the end of the Compact I/O bus.
Each bank of Compact I/O must have its own power supply (a MicroLogix
1500 acts as the power supply for modules directly connected to it).
A Compact I/O power supply, or MicroLogix 1500 Base Unit, has limits in
the amount of +5V dc and +24V dc current it can supply to modules in its
I/O bank. These limits depend on the catalog number (e.g. 1769-PA2) of the
supply. A bank of modules must not exceed the current limits of the I/O
bank power supply or MicroLogix 1500 Base Unit.
Refer to the Compact 1769 Expansion I/O Power Supplies Installation
Instructions, publication 1769-5.14 or the MicroLogix 1500 User Manual,
publication 1764-UM001A-EN-P.
The scanner has a distance rating of four, therefore the scanner must be
within four modules of the I/O banks power supply.
Determine the DeviceNet baud rate based on standard DeviceNet
considerations.
Consider the number of words of I/O data the host controller supports.
For more information on planning your DeviceNet network, refer to the DeviceNet
Cable System Planning and Installation Manual, publication DN-6.7.2.
Compact I/O DeviceNet Scanner Module 9
Publication 1769-IN060C-EN-P - May 2002
System Assembly
The module can be attached to an adjacent controller, power supply, or I/O
module. For mounting instructions, see Panel Mounting on page 10, or DIN Rail
Mounting on page 12. To work with a system that is already mounted, see
Replacing a Single Module within a System on page 13.
The following procedure shows you how to assemble the Compact I/O system.
1. Disconnect power.
2. Check that the bus lever of the module (A) is in the unlocked (fully right)
position.
3. Use the upper and lower tongue-and-groove slots (B) to secure the modules
together.
4. Move the module back along the tongue-and-groove slots until the bus
connectors (C) line up with each other.
5. Use your fingers or a small screw driver to push the bus lever back slightly
to clear the positioning tab (D).
6. Move the modules bus lever fully to the left (E) until it clicks. Ensure it is
locked firmly in place.
ATTENTION
!
When attaching I/O modules, it is very important that the
bus connectors are securely locked together to ensure
proper electrical connection.
G
F
E
D
B
A
B
C
10 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
7. Attach an end cap terminator (F) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (G).
System Mounting
Minimum Spacing
Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow 50
mm (2 in.) of space on all
sides for adequate
ventilation, as shown:
Allow at least 110 mm
(4.33 in.) of enclosure depth to accommodate the module and the DeviceNet
connector.
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead
screws. Mounting screws are required on every module.
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the serial communication bus.
ATTENTION
!
During panel or DIN rail mounting of all devices, be sure that
all debris (metal chips, wire strands, etc.) is kept from falling
into the module. Debris that falls into the module could cause
damage on power up.
Top
Side
Bottom
Side
Controller
Compact I/O
Compact I/O
Compact I/O
Compact I/O
Compact I/O
End Cap or Cable
Compact I/O DeviceNet Scanner Module 11
Publication 1769-IN060C-EN-P - May 2002
Panel Mounting Using the Dimensional Drawing
NOTE: All dimensions are in mm (inches). Hole spacing tolerance: ±0.04 mm (0.016 in.).
Compact I/O with CompactLogix Controller and Power Supply
Compact I/O with MicroLogix 1500 Base Unit and Processor
132 mm (5.19 in)
122.6 mm (4.83 in)
118 mm (4.65 in)
147.4 mm (5.81 in)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
28.5 mm
(1.12 in)
35 mm
(1.38 in)
70 mm
(2.76 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
50 mm
(1.97 in)
40 mm
(1.58 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
DIN Rail
Center Line
Mounting Hole
Dimension
132 mm (5.19 in)
122.6 mm (4.83 in)
118 mm (4.65 in)
147.4 mm (5.81 in)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
168 mm
(6.62 in)
147 mm
(5.79 in)
35 mm
(1.38 in)
13.5 mm
(0.53 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
28.5 mm
(1.12 in)
DIN Rail
Center Line
Mounting Hole
Dimension
12 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template
for drilling holes in the panel. Due to module mounting hole tolerance, it is
important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
7. Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN
rail mounting area of the module against the DIN rail. The latches will momentarily
open and lock into place. DIN rail mounting dimensions are shown below.
A
B
C
Dimension Height
A 118 mm
(4.65 in.)
B 59 mm
(2.325 in.)
C 59 mm
(2.325 in.)
Compact I/O DeviceNet Scanner Module 13
Publication 1769-IN060C-EN-P - May 2002
Replacing the Scanner Module within a System
The scanner can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power. See important note on page 7.
2. Remove the DeviceNet cable from the scanner by removing the DeviceNet
connector.
3. Remove the upper and lower mounting screws from the scanner (or open
the DIN latches using a flat-blade screwdriver).
4. On the scanner to be replaced and the right-side adjacent module (or end
cap if the scanner is the last module in the bank), move the bus levers to the
right (unlock) to disconnect the scanner from the adjacent modules.
5. Gently slide the disconnected scanner module forward.
If you feel excessive resistance, make sure that you disconnected the
scanner from the bus and that you removed both mounting screws (or
opened the DIN latches).
.
6. Before installing the replacement scanner, be sure that the bus lever on the
right-side adjacent module is in the unlocked (fully right) position.
7. Slide the replacement scanner into the open slot.
8. Connect the scanner and modules together by locking (fully left) the bus
levers on the replacement scanner and the right-side adjacent module or end
cap.
9. Replace the mounting screws (or snap the scanner onto the DIN rail).
10. Replace the DeviceNet cable on the scanner by attaching the connector to
the scanner.
TIP
It may be necessary to rock the scanner slightly from
front to back to remove it, or, in a panel-mounted
system, to loosen the screws of adjacent modules.
14 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
11. Restore scanner configuration using RSNetWorx for DeviceNet.
Field Wiring Connections
Grounding the Scanner Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the scanners mounting
tabs or DIN rail (if used), are not required unless the mounting surface cannot be
grounded.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1, for additional information.
IMPORTANT
Be sure that the new module has the same node address
and baud rate as the module that was replaced.
ATTENTION
!
The grounding screw on the front of the scanner must be
connected to a suitable ground source when operating in
electrically noisy environments. Use a #14 AWG wire to make
this connection.
Compact I/O DeviceNet Scanner Module 15
Publication 1769-IN060C-EN-P - May 2002
DeviceNet Wiring
1. Connect the DeviceNet cable to the removable connector as shown.
2. Insert the removable female connector into the mating male connector on
the DeviceNet scanner module.
3. Screw the removable connector to the scanner case with the upper and
lower mounting screws. Screw torque is 0.6 to 0.7 Nm (5 to 6 in-lbs).
Scanner Module Power-Up
When power is applied via the Compact I/O bus, the scanner module goes through
a self test sequence. Upon successful completion of the self test, the scanner is
ready to communicate.
The default scanner settings are:
baud rate = 125K
node address = 63
Use your configuration software to change the baud rate and node address.
IMPORTANT
If the 1769-SDN is the first or last device connected to the
DeviceNet network trunkline, be sure to add a termination resistor
(120 1% ¼W resistor, Allen-Bradley part number 1485A-C2)
across the Blue (CAN Low) and White (CAN High) wires.
DeviceNet Connector
Connect
(1)
To
Red Wire V+
White Wire CAN High
Bare Wire Shield
Blue Wire CAN Low
Black Wire V-
Grounding Screw
Use #14 AWG wire
to connect to panel
ground.
16 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
Configuring the 1769-SDN on DeviceNet
The 1769-SDN must be configured using a DeviceNet configuration tool. The
recommended configuration software is RSNetWorx for DeviceNet (version 3.00 or
higher).
This configuration tool allows you to identify all of the devices (I/O modules,
power supplies, expansion cables, end caps) and their locations in your system.
For more information, refer to the
Compact I/O DeviceNet Scanner Module
User
Manual, publication 1769-UM009A-EN-P.
TIP
If your RSNetWorx configuration software does not include the
required EDS (Electronic Data Sheet) file, it is available via
http://www.ab.com/networks/eds.
TIP
The controller must be in the Run mode, or the scanner in the
Idle mode (bit 0 of the Module Command Array = 0), for the
scanner to accept the configuration information.
Compact I/O DeviceNet Scanner Module 17
Publication 1769-IN060C-EN-P - May 2002
Data Organization
The scanner uses the input and output data images to transfer data, status and
command information between the scanner and the controller. The basic structure
is shown below. Refer to the
Compact I/O DeviceNet Scanner Module
User Manual,
publication 1769-UM009A-EN-P, for more detailed information.
Input Data Image
The input data image is transferred from the scanner module to the controller.
Output Data Image
The output data image is transferred from the controller to the scanner module.
The following table shows the bit descriptions for the Module Command Array.
Word Description Data Type
0 to 63 Status Structure 64-word array
64 and 65 Module Status Register 2 words
66 to 245 Input Data Image 180-word array
Word Description Data Type
0 and 1 Module Command Array 2-word array
2 to 181 Output Data Image 180-word array
Word Bit Operating Mode
0 0 1 = Run, 0 = Idle
1 1 = Fault
2 1 = Disable Network
3
Reserved
(1)
(1)
DO NOT manipulate Reserved Bits. Doing so may interfere with future compatibility.
4 1 = Reset
5 to 15
Reserved
(1)
10 to 15
Reserved
(1)
18 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
Diagnostic Indicators
Indicator Color/
Status
Indicates Recommended Action
Module Off No power applied to module. Apply power.
Flashing
Green
No Bus Master (MicroLogix or
CompactLogix controller) present.
Verify module connectors are properly
seated. If they are, cycle power to the
controller. If this does not correct the
problem, replace the controller. If
replacing the controller does not
correct the problem, replace the
1769-SDN.
Solid Green Normal operation. No action required.
Flashing
Red
Recoverable Fault - Memory has been
erased or is being programmed.
Complete flash update or start a new
update.
Solid Red Unrecoverable fault Verify module connectors are properly
seated. If they are, verify that bus
terminator/end cap is installed. Cycle
power. If still faulted, replace the
module.
Network Off No module power, no network power, or
communications are not occurring
between the module and the DeviceNet
network. (This may be an acceptable
condition.)
Verify module has power. Check that
the DeviceNet cable is securely
connected and the DeviceNet network
is powered. Verify that network power
is adequate (11 to 25V dc).
Flashing
Green
Device is operational. There are no
connections established with any of the
network devices.
If the module is supposed to be
controlling DeviceNet slaves,
configure the modules scan list.
Solid Green Normal operation. Scan list is
configured. Module is not in Idle mode.
No action required.
Flashing
Red
One or more of the devices that the
scanner is communicating with is in a
timed out state.
Monitor the status display, or the
modules status field to determine
which slave device is offline.
Solid Red Critical network failure. Duplicate
DeviceNet node address detected.
Reset module. Change modules node
address or change conflicting devices
node address. If failure continues,
replace module.
7-Segment
Numeric
Display
Node
Address
and Status
Display
Indicates diagnostic information about the status of the module.
When the numeric display is showing 0 to 63, it is indicating the 1769-SDN
modules DeviceNet node address.
When it shows 70 to 99, it indicates an Error Code for the displayed node address.
When it flashes alternating numbers, one is the Error Code (70 to 99), and the
other is the Node Number (0 to 63) that has generated the error.
See the list of Error Codes on page 19 for more information.
Compact I/O DeviceNet Scanner Module 19
Publication 1769-IN060C-EN-P - May 2002
Error Codes
The following table describes the Error Codes indicated by the 7-segment numeric
display.
Code
(decimal)
Name Description Recommended Action
70 Duplicate Node Controller has Failed Duplicate
Node Address Check. The node
address selected is already in use.
Change the modules or conflicting
devices network address (node
number) to an available one.
71 Illegal Scan
List Data
Illegal data in Scan List. Reconfigure the scan list table and
remove any illegal data.
72 Slave Timeout One of the modules slave devices
has stopped communicating.
Inspect the modules slave devices and
verify the DeviceNet connections.
73 Electronic Key
Mismatch
The slave device Vendor ID key
parameter does not match the
slaves configuration in the
modules scan list.
Make sure that the device at the
flashing node address matches the
desired electronic key (vendor, product
code, product type)
75 No Messages
Received
No network traffic received by the
scanner. 10 seconds have elapsed
and no network traffic for the
module or for any other device have
been received by the module.
Verify the scan list is correctly
configured to scan slave devices. Verify
DeviceNet network connections.
76 No Message
For Scanner
No direct network traffic for the
scanner detected. 10 seconds
elapsed and no DeviceNet input
being screened by the module has
been received.
None. There are other active devices on
the network, initiating messages, but
none of the messages are for the
module.
77 Slave Data Size
Mismatch
The data being received from the
slave device does not match the
configuration in the scan list.
Either reconfigure the slave device, or
change the modules scan list to match
the slave device.
78 No Such
Device
Slave device in scan list does not
exist.
Either add the device to the DeviceNet
network, or delete the devices entry in
the scan list.
79 Transmit
Failure
The module has failed to transmit a
message.
Make sure that the module is
connected to a valid network. Check for
disconnected cables.
80 In Idle Mode Module is in Idle mode. Put the controller into Run mode and
enable the scanner Run bit (bit 0 of the
Module Command Array = 1). See page
17.
81 Scanner
Faulted
The Scanner has stopped producing
and consuming I/O data. This
condition does not affect the
scanners system or messaging
modes.
Check the FAULT value in the module
command array.
20 Compact I/O DeviceNet Scanner Module
Publication 1769-IN060C-EN-P - May 2002
82 Fragmentation
Error
Error detected in sequence of
fragmented I/O messages from
device.
Check scan list table entry for slave
device to make sure that input and
output data lengths are correct. Check
slave device configuration.
83 Slave Init Error Slave device is returning error
responses when the module
attempts to communicate with it.
Check slave devices configuration.
Reboot slave device.
84 Not Yet
Initialized
Module has not completed its initial
attempt to establish
communications with its slaves.
None. This code clears itself once the
module properly initializes all slave
devices on the network.
85 Receive Buffer
Overflow
Data size returned is larger than
expected.
Configure the slave device for a smaller
data size.
86 Device Went
Idle
Device is producing Idle state. Check the device configuration and
slave node status.
89 Auto Device
Replacement
(ADR) Error
Slave device responded with an
error to the initialization data sent
to it by the scanner; or the
configuration table in the scanners
flash memory is not valid for a slave
node.
Try the ADR download again. If it still
fails, try clearing the ADR flash by
downloading an empty ADR
configuration to the scanner and then
try the ADR configuration again.
90 Disabled
Network
DeviceNet Port is Disabled Check for the disable being set in the
module command array.
91 Bus Off Bus off condition detected on
integral DeviceNet port.
Check the DeviceNet connections and
physical media integrity. Check system
for failed slave devices or other
possible sources of network
interference. Check the Baud Rate.
92 No DeviceNet
Power
No network power detected on
DeviceNet port.
Provide network power. Make sure the
module drop cable is providing the
proper power to the DeviceNet port.
95 FLASH Update Flash Update In Progress None. DO NOT disconnect the module
from the network while a flash update
is in progress.
98 Firmware
Corrupted
Firmware is corrupted. Reflash module firmware. DO NOT
power cycle the module. Doing so may
cause the module to become
inoperable If the problem persists
contact Rockwell Automation Technical
Support.
99 Hard Fault Cycle Power. Reflash module firmware.
Contact Rockwell Automation Technical
Support.
Code
(decimal)
Name Description Recommended Action
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Rockwell Automation 40072-107-01 Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues