Tripp Lite Hot-Swap PDUs Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire

Ce manuel convient également à

1
Owner’s Manual
Hot-Swap PDU
with Maintenance Bypass Switch
Models: PDUB15, PDUB20, PDUB30, PDUBHV10, PDUBHV20
Important Safety Warnings 2
Mounting 2
Features 4
Connection & Operation 6
Troubleshooting 7
Service, Warranty & Product Registration 7
Español 8
Français 15
Русский 22
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. All trademarks are the sole property of their respective owners.
Mount in top or
bottom holes.
2
Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation and operation of this product.
Install the PDU indoors, away from excess moisture or heat, direct sunlight, dust or conductive contaminants. Do not install the PDU near
magnetic storage media, as this may cause data corruption.
Only operate the PDU at indoor temperatures between 32° F and 104° F (0 °C and 40° C). For best results, maintain indoor temperatures
between 62° F and 84° F (17° C and 29° C). For proper ventilation, leave adequate space around all sides of the PDU.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the
life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence
of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Do not connect the PDU to an ungrounded outlet or to adapters that eliminate the connection to ground. The ground connections are
provided for your safety. If the provided plug does not fit your outlet, have a compatible grounded outlet installed by a qualified electrician.
The PDU must be installed near the wall outlet and all plugs must be readily accessible for disconnection.
The PDU must be connected to a wall outlet that is protected by an overcurrent device with the rating shown in the table below:
Model Overcurrent Rating of Protection Device Model Overcurrent Rating of Protection Device
PDUB15 20A PDUBHV10 20A (cTUVus) or 16A (CE)
PDUB20 20A PDUBHV20 20A (cTUVus) or 16A (CE)
PDUB30 30A
Caution! Risk of electrical shock! The PDU is supplied by more than one power source. All power sources must be disconnected to de-
energize the unit before servicing.
Do not open the PDU for any reason. There are no user-serviceable parts inside.
Mounting
Mounting (2-Post or 4-Post Racks)
Mount the equipment in either a 2-post or 4-post open frame rack or rack enclosure. The user must determine the fitness of hardware
and procedures before mounting. The procedures described in this manual are for common rack and rack enclosure types and may not be
appropriate for all applications.
Note: Mounting procedures are the same for both 2-post and 4-post rack installation.
Step 1. Attach the mounting ears to the mounting holes of the PDU using the screws provided.
The ears should face forward.
Note: The top or bottom mounting holes of the PDU can be used.
Step 2. Attach the PDU to the rack with user-provided screws, nuts and washers. Insert the
screws through the mounting ears and into the rack rails.
Mounting in the Same Rack Space as a UPS System (4-Post Racks)
The Hot-Swap PDU can be mounted in the same rack space as a UPS system when the
UPS system is mounted using Tripp Lite’s 4POSTRAILKIT. (4POSTRAILKIT is included with
most Tripp Lite UPS systems and is also sold separately. Refer to the UPS system manual or
4POSTRAILKIT manual for UPS system mounting instructions. The procedure for mounting
the rear of the 4POSTRAILKIT mounting shelves to the rack will differ slightly, as shown in this
section.)
Step 1. Attach the mounting ears to the lower mounting holes of the unit using the screws
provided. The ears should face forward.
Step 1
Step 1
Step 2
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
26
25
24
B
B
A
A
3
Step 2. Install 4POSTRAILKIT into the rack using only the top mounting hole
A
at each
side of the rear of the 4POSTRAILKIT mounting shelves. (The screws at the front
of the shelves will not change from the standard procedure shown in your UPS or
4POSTRAILKIT manual.)
Step 3. Install the PDU into the rack using the bottom two mounting holes
B
at each side
of the rear of the 4POSTRAILKIT mounting shelves.
Mounting (continued)
Step 2
Step 3
Warning! Refer to the diagrams below to make sure the UPS system’s airflow is not obstructed. If the UPS system’s
airflow is obstructed, the UPS system will overheat.
PDUB15
PDUB20
PDUB30
12A MAX.
12A MAX.
OUTPUT
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
15A MAX.
15A MAX.
OUTPUT
16A MAX.
16A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT
24A MAX.
OUTPUT 20A MAX.
LOAD1
LOAD2
20A OUTPUT
BREAKERS
PUSH TO RESET
TO
UPS OUTPUT
UTILITY
30A
30A
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
1
1
6
6
7
7
9
9
397
11 6 10
1
2
2 11
8
8
8
10
10
4
Features
1
5-15R AC Outlets: Connect to 5-15P equipment plugs.
2
5-20R AC Outlets: Connect to 5-15P or 5-20P equipment plugs.
3
L5-30R AC Outlets: Connect to L5-30P equipment plugs.
4
C13 AC Outlets: Connect to C14 equipment plugs.
5
C19 AC Outlets: Connect to C20 equipment plugs.
6
UPS Source Input: Connects to a compatible outlet on the UPS system.
7
Maintenance Bypass Switch: Selects the power source that is powering the load – either the UPS source or the utility source. When
the switch is set to “Utility,” connected equipment receives AC utility power from the PDU, but the equipment will not receive UPS battery
backup power in the event of a utility power failure. See “Manual Bypass Operation” for more information.
8
Diagnostic Lights (UPS Available and Maintenance Bypass Available): A green “UPS Available” light will illuminate when the UPS
source is connected and turned on. A yellow “Maintenance Bypass Available” light will illuminate when the utility source is connected and
turned on.
9
Utility Source Input: Connects to the utility power source. Models PDUB15, PDUB20 and PDUB30 each have a fixed input cord and
plug. Model PDUBHV10 has a C14 inlet and model PDUBHV20 has a C20 inlet. Models PDUBHV10 and PDUBHV20 both include an
extension jumper and can also be used with a user-supplied power cord. (See below for a selection of compatible Tripp Lite power cords.)
10
UPS Connection Outlet: Connects to the UPS system’s input power cord. The user must match the UPS system’s input power cord to a
compatible PDU model.
11
20-Amp Branch-Rated AC Output Breakers (PDUB30 Only): Control power to the PDU’s outlets.
PDUBHV10
PDUBHV20
OUTPUT 10A MAX. OUTPUT 10A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT 10A MAX. OUTPUT 10A MAX. OUTPUT 16A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
10
10
4
4
4
54
6
6
7
7
9
9
8
8
5
Features (continued)
Choose a PDU model compatible with your UPS system’s input plug and power specifications:
Model
Compatible UPS
System Rating
Utility Source
Input Plug/
Cord Length
UPS
Connection
Outlet
UPS Source
Input Plug/
Cord Length Outlets for Equipment
PDUB15 100-127V, Up to 1500VA 5-15P / 10 ft. 5-15R 5-15P / 6 ft. 8 (5-15R)
PDUB20 100-127V, 2200-2600VA 5-20P / 10 ft. 5-20R 5-20P / 6 ft. 4 (5-15R), 4 (5-20R)
PDUB30 100-127V, 3000VA L5-30P / 10 ft. L5-30R L5-30P / 6 ft. 6 (5-20R), 1 (L5-30R)
PDUBHV10 200-240V, Up to 1500VA C14 / 6 ft. (Or User-Supplied) C13 C13 / 6 ft. 8 (C13)
PDUBHV20 200-240V, 2000-3000VA C20 / 5 ft. (Or User-Supplied) C19 C19 / 5 ft. 6 (C13), 2 (C19)
PDUBHV10 Cord Options (Sold Separately)
Model Length Plug Type
P005-002 2 ft. C14
P005-006 6 ft. C14
P005-010 10 ft. C14
P011-006 6 ft. L6-20P
P032-007 7 ft. C20
P054-006 6 ft. CEE 7/7
P056-006 6 ft. BS1363
PDUBHV20 Cord Options (Sold Separately)
Model Length Plug Type
P036-006 6 ft. C20
P036-002 2 ft. C20
P040-010 10 ft. L6-20P
P047-002 2 ft. C14
P047-004 4 ft. C14
P047-006 6 ft. C14
P047-010 10 ft. C14
P050-008 8 ft. CEE 7/7
P052-008 8 ft. BS1363
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
C
A
E
E
D
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
B
6
Connection & Operation
Input/Output Power Connections
Step 1. Shut down the equipment plugged into the UPS system and unplug the equipment cables from the UPS system.
Step 2. Shut down the UPS system and unplug it from the utility source.
Step 3. Set the PDU’s Maintenance Bypass Switch
A
to the “Utility” position and connect
the PDU’s utility source input cord
B
to your facility’s utility AC power source. The
PDU’s yellow “Maintenance Bypass Available” light
C
will illuminate.
Step 4. Connect the UPS system’s input power cord to the PDU’s UPS connection outlet
(labeled “Connect UPS Line Cord Here”) and turn on the UPS system.
Step 5. Connect the PDU’s UPS source input cord (labeled “To UPS Output”) to a compatible
outlet on the UPS system. The PDU’s green “UPS Available” light
D
will illuminate.
Step 6. Connect the equipment cables
to compatible PDU outlets
E
and
set the Maintenance Bypass
Switch
A
to the “UPS” position.
The connected load now has UPS
protection.
Manual Bypass Operation For Hot-Swap UPS Replacement
Step 1. Make sure the PDU’s yellow “Maintenance Bypass Available” light
A
is illuminated.
Switch the Maintenance Bypass Switch
B
from “UPS” to “Utility”. The connected
load is now being supported by the utility power source and will not receive battery
backup power in the event of a utility power failure.
Step 2. Turn off the UPS system that requires maintenance or replacement and remove all
power connections between the UPS system and the PDU. The PDU’s green “UPS
Available” light will be off.
Step 3. Replace the UPS system. Connect the new UPS system’s input power cord to the
PDU’s UPS connection outlet (labeled “Connect UPS Line Cord Here”) and turn on
the new UPS system.
Step 4. Connect the PDU’s UPS source input cord (labeled “To UPS Output”) to a
compatible outlet on the new UPS system. The PDU’s green “UPS Available” light
will illuminate.
Step 5. Switch the Maintenance Bypass Switch
B
from “Utility” to “UPS”. The connected
load is now has UPS protection.
Step 3
Step 4
Step 5
Step 6
Models vary.
Models vary.
Models vary.
Models vary.
Step 1
Step 5
7
Troubleshooting
Use the following chart to make minor adjustments or attempt to solve problems. Do not attempt to open the PDU, as there are no user-
serviceable parts inside. If problems persist after troubleshooting, please visit www.tripplite.com/support.
Problem Possible Cause Possible Solution
Yellow light does not illuminate. No utility power. Contact your utility company or a qualified
electrician.
The PDU is not plugged into the utility source. Connect the PDU to a compatible utility source.
Green light does not illuminate. The UPS system has no output. Refer to the UPS manual for proper startup.
Input and output of UPS not connected to the PDU. Connect UPS input and output to the PDU.
Some loads not receiving power. Tripped circuit breaker on the PDU (PDUB30 only). Reset the PDU’s circuit breaker.
Loads not receiving power after reset-
ting the circuit breaker.
The connected load is overloading the PDU. Reduce the connected load.
Service, Warranty and Product Registration
Service
Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more
information on service, visit www.tripplite.com/support. Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. From here you can request a Returned Material Authorization (RMA) number,
which is required for service. This simple on-line form will ask for your unit’s model and serial numbers, along with other general purchaser information. The RMA number, along
with shipping instructions will be emailed to you. Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized
Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark
the RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your sales receipt. Return the product for service using an insured
carrier to the address given to you when you request the RMA.
Warranty
2-YEAR LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and workmanship for a period of 2 years from the date
of initial purchase. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the product, in its sole discretion. Service under
this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite; 1111 W. 35th Street; Chicago IL 60609;
USA. Seller will pay return shipping charges. Visit www.tripplite.com/support before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES
OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES
OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND
CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from
jurisdiction to jurisdiction).
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; USA
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe for the use intended. Since individual applications are
subject to great variation, the manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific application.
PRODUCT REGISTRATION
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You’ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from
Tripp Lite they are entitled to:
Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
Send the new equipment back for recycling when this ultimately becomes waste
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the
product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The
series number should not be confused with the marking name or model number of the product.
Tripp Lite follows a policy of continuous improvement. Product specifications are subject to change without notice.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
8
Manual del propietario
PDU con cambio en operación
e interruptor de rodeo de
mantenimiento
Modelos: PDUB15, PDUB20, PDUB30, PDUBHV10, PDUBHV20
Advertencias de seguridad importantes 9
Montaje 9
Características 11
Conexión y operación 13
Solución de problemas 14
Servicio y garantía 14
English 1
Français 15
Русский 22
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. Todas las otras marcas registradas son propiedad de sus respectivos dueños.
Montar en los ori-
ficios superiores o
inferiores
9
Montaje
Montaje (racks de 2 ó 4 puestos)
Monte el equipo en un rack de bastidor abierto o rack de 2 ó 4 puestos. El usuario debe determinar la aptitud de los accesorios y los pasos antes de
montarlo. Las instrucciones de este manual son para racks comunes y gabinetes de rack y pueden no ser adecuadas para todas las aplicaciones.
Nota: Los procedimientos de montaje son los mismos para los racks de 2 y 4 puestos.
Paso 1. Una las orejas de montaje a los orificios de montaje de la PDU usando los tornillos
proporcionados. Las orejas deben estar hacia el frente.
Nota: Se pueden usar los orificios de montaje superiores o inferiores de la PDU.
Paso 2. Una la PDU al rack con los tornillos con los tornillos suministrados por el usuario. Coloque los
tornillos a través de las orejas de montaje y en los rieles del rack.
Montaje en el mismo espacio de rack que un sistema UPS (rack de 4 puestos)
La PDU con cambio en operación se puede montar en el mismo espacio de rack que un
sistema UPS, siempre que para el montaje se haya usado el 4POSTRAILKIT de Tripp Lite. (El
4POSTRAILKIT se incluye con la mayoría de los sistemas UPS de Tripp Lite y también se vende por
separado. Para las instrucciones de montaje del sistema UPS consulte el manual del sistema UPS
o el manual del 4POSTRAILKIT. El procedimiento para montar la parte posterior de los estantes de
montaje 4POSTRAILKIT al rack será ligeramente distinto, tal como se muestra en esta sección.)
Paso 1. Una las orejas de montaje a los orificios de montaje inferiores de la unidad usando los
tornillos proporcionados. Las orejas deben estar hacia el frente.
Advertencias de seguridad importantes
GUARDE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias importantes que deben seguirse durante la instalación y operación de este producto.
• Instale la PDU en interiores, alejada de la humedad o el calor excesivos, la luz solar directa, polvo o contaminantes conductores. No coloque la PDU cerca
de medios de almacenamiento magnéticos, podría causar corrupción de datos.
• Opere la PDU únicamente en temperatura ambiente interior entre 32 °F y 104 °F (0 °C y 40° C). Para obtener los mejores resultados, mantenga la
temperatura interior entre 62 °F y 84 °F (17 °C y 29 °C). Para una ventilación adecuada, deje espacio suficiente alrededor de la PDU.
• No se recomienda usar este equipo en aplicaciones de mantenimiento artificial de la vida, donde se puede esperar razonablemente que su falla cause la
falla del equipo de mantenimiento de la vida o que afecte de manera importante su seguridad o eficiencia. No use este equipo en presencia de mezclas
anestésicas inflamables con aire, oxígeno u óxido nitroso.
• No conecte la PDU a un tomacorriente sin descarga a tierra o a adaptadores que eliminen la conexión a tierra. Las conexiones a tierra se realizan
en función de su seguridad. Si el enchufe proporcionado no se corresponde con su tomacorriente, llame a un electricista calificado para instalar un
tomacorriente compatible con descarga a tierra.
• Se debe instalar la PDU cerca de un toma de pared y todos los enchufes tienen que ser de fácil acceso para su desconexión.
• La PDU se debe conectar a un toma de pared protegido por un dispositivo contra sobrecorriente conforme los valores nominales que se muestran en la
siguiente tabla:
Valor nominal de sobrecorriente del Valor nominal de sobrecorriente del
Modelo dispositivo de protección Modelo dispositivo de protección
PDUB15 20 A PDUBHV10 20A (cTUVus) ó 16A (CE)
PDUB20 20 A PDUBHV20 20A (cTUVus) ó 16A (CE)
PDUB30 30 A
¡Precaución! ¡Riesgo de descargas eléctricas! La PDU recibe alimentación de más de una fuente de energía. Antes de realizarle servicio a la unidad se
deben desconectar todas las fuentes de energía.
Bajo ninguna circunstancia abra la PDU. No tiene partes internas que el usuario pueda reparar.
Paso 1
Paso 1
Paso 2
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
26
25
24
B
B
A
A
Instalación correcta: el flujo de aire del sistema UPS no está obstruido
Rack – Vista lateral
Rieles frontales del rack
Rieles posteriores del rack
Los equipos en 2U encima del sistema
UPS no pueden exceder la profundidad
del sistema UPS.
Los equipos en 2U debajo del sistema
UPS no pueden exceder la profundidad
del sistema UPS.
Sistema UPS 2U
PDU con
cambio en
operación
Las 2U encima
de la PDU
deben estar
abiertas.
Las 2U debajo
de la PDU
deben estar
abiertas.
Instalación incorrecta: el flujo de aire del sistema UPS está obstruido
Rack – Vista lateral
Rieles frontales del rack
Rieles posteriores del rack
Los equipos en 2U encima del sistema UPS no pueden exceder la profundidad
del sistema UPS.
Los equipos en 2U debajo del sistema UPS no pueden exceder la profundidad
del sistema UPS.
Sistema UPS 2U
PDU con
cambio en
operación
Las 2U encima
de la PDU
deben estar
abiertas.
Las 2U debajo
de la PDU
deben estar
abiertas.
10
Paso 2. Instale el 4POSTRAILKIT en el rack usando solo el orificio de montaje superior
A
que se
encuentra a cada lado en la parte posterior de los estantes de montaje 4POSTRAILKIT.
(La ubicación de los tornillos en la parte frontal de los estantes no será distinta a la del
procedimiento estándar que se describe en el manual del UPS o 4POSTRAILKIT.)
Paso 3. Instale el PDU en el rack usando los dos orificios de montaje inferiores
B
que se encuentran
a cada lado de La parte posterior de los estantes de montaje 4POSTRAILKIT.
Montaje (continuación)
Paso 2
Paso 3
¡Advertencia! Consulte los diagramas que se encuentran a continuación para asegurarse de que el flujo de aire del sistema UPS no está
obstruido. Si el flujo de aire está obstruido, el sistema UPS se sobrecalentará.
PDUB15
PDUB20
PDUB30
12A MAX.
12A MAX.
OUTPUT
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
15A MAX.
15A MAX.
OUTPUT
16A MAX.
16A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT
24A MAX.
OUTPUT 20A MAX.
LOAD1
LOAD2
20A OUTPUT
BREAKERS
PUSH TO RESET
TO
UPS OUTPUT
UTILITY
30A
30A
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
1
1
6
6
7
7
9
9
397
11 6 10
1
2
2 11
8
8
8
10
10
11
Características
1
Tomacorrientes de CA 5-15R: para conectar clavijas de equipos 5-15P.
2
Tomacorrientes de CA 5-20R: para conectar clavijas de equipos 5-15P ó 5-20P.
3
Tomacorrientes de CA L5-30R: para conectar clavijas de equipos 5-30P.
4
Tomacorrientes de CA C13: para conectar clavijas de equipos C14.
5
Tomacorrientes de CA C19: para conectar clavijas de equipos C20.
6
Entrada de la fuente UPS: se conecta a un tomacorriente compatible en el sistema UPS.
7
Interruptor de rodeo de mantenimiento: selecciona la fuente de energía que alimenta a la carga (fuente del UPS o fuente de la red pública). Cuando el
interruptor se fija en “Utility” (Red pública), los equipos conectados reciben alimentación de CA de la red pública desde la PDU pero no recibirán respaldo
de energía del UPS en el caso de una falla de la energía de la red pública. Para más información, consulte “Operación de rodeo manual”.
8
Luces de diagnóstico (UPS disponible y Rodeo de mantenimiento disponible): la luz verde “UPS Available” (UPS disponible) se ilumina cuando el
UPS está conectado y encendido. La luz amarilla “Maintenance Bypass Available” (Rodeo de mantenimiento disponible) se ilumina cuando la energía de
la red pública está conectada y encendida.
9
Entrada de fuente red pública: se conecta a la fuente de energía de la red pública. Los modelos PDUB15, PDUB20 y PDUB30 tienen un cable y
enchufe de entrada fijos. El modelo PDUBHV10 tiene una entrada C14 y el modelo PDUBHV20 tiene una entrada C20. Los modelos PDUBHV10 y
PDUBHV20 incluyen un jumper de extensión y también puede usarse con un cable de alimentación suministrado por el usuario. (Vea a continuación por
una selección de cables de alimentación Tripp Lite.)
10
Tomacorrientes de conexión del UPS: se conecta al cable de alimentación de entrada del sistema UPS. El usuario debe corresponder el cable de
alimentación de entrada del sistema UPS con un modelo de PDU compatible.
11
Interruptor de ramal de salida de CA, 20 amp. (PDUB30 únicamente): Controla la alimentación a los tomacorrientes de la PDU.
PDUBHV10
PDUBHV20
OUTPUT 10A MAX. OUTPUT 10A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT 10A MAX. OUTPUT 10A MAX. OUTPUT 16A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
10
10
4
4
4
54
6
6
7
7
9
9
8
8
12
Características (continuación)
Elija un modelo de PDU compatible con la clavija de entrada y especificaciones de alimentación de su sistema UPS:
Modelo
Valor nominal del sistema UPS
compatible
Long. del enchufe/cable de entrada
de la fuente red pública
Tomacorrientes
de conexión del
UPS
Long. del enchufe/
cable de entrada de
la fuente UPS Tomacorrientes por equipo
PDUB15 100-127V, hasta 1500VA 5-15P / 10 pies (3 m) 5-15R 5-15P / 6 pies (1,8 m) 8 (5-15R)
PDUB20 100-127V, 2200-2600VA 5-20P / 10 pies (3 m) 5-20R 5-20P / 6 pies (1,8 m) 4 (5-15R), 4 (5-20R)
PDUB30 100-127V, 3000VA L5-30P / 10 pies (3 m) L5-30R L5-30P / 6 pies (1,8 m) 6 (5-20R), 1 (L5-30R)
PDUBHV10 200-240V, hasta 1500VA C14 / 6 pies (1,8 m)
(o suministrado por el usuario)
C13 C13 / 6 pies (1,8 m) 8 (C13)
PDUBHV20 200-240V, 2000-3000VA C20 / 5 pies (1,5 m)
(o suministrado por el usuario)
C19 C19 / 5 pies (1,5 m) 6 (C13), 2 (C19)
Opciones de cable PDUBHV10
(se vende por separado)
Modelo Longitud
Tipo de en-
chufe
P005-002 2 pies C14
P005-006 6 pies C14
P005-010 10 pies C14
P011-006 6 pies L6-20P
P032-007 7 pies C20
P054-006 6 pies CEE 7/7
P056-006 6 pies BS1363
Opciones de cable PDUBHV20
(se vende por separado)
Modelo Longitud
Tipo de en-
chufe
P036-006 6 pies C20
P036-002 2 pies C20
P040-010 10 pies L6-20P
P047-002 2 pies C14
P047-004 4 pies C14
P047-006 6 pies C14
P047-010 10 pies C14
P050-008 8 pies CEE 7/7
P052-008 8 pies BS1363
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
C
A
E
E
D
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
B
13
Conexión y operación
Conexiones eléctricas de entrada/salida
Paso 1. Apague los equipos conectados en el sistema UPS y desenchufe los cables conectados en el
UPS.
Paso 2. Apague el sistema UPS y desenchúfelo de la fuente de red pública.
Paso 3. Fije el interruptor de rodeo de mantenimiento
A
de la PDU en la posición “Utility” (Red
pública) y conecte el cable de entrada
B
de la fuente red pública de la PDU a la fuente
de alimentación de CA de red pública de su instalación. Se iluminará la luz amarilla
“Maintenance Bypass Available” (Rodeo de mantenimiento disponible)
C
de la PDU.
Paso 4. Conecte el cable de alimentación de entrada del sistema UPS al tomacorriente de la PDU
para conexión del UPS (con la etiqueta “Connect UPS Line Cord Here” -Conecte el cable de
línea del UPS) y encienda el sistema UPS.
Paso 5. Conecte el cable de entrada de la fuente UPS de la PDU (con la etiqueta “To UPS Output” –A
la salida del UPS) a un tomacorriente compatible en el sistema UPS. Se iluminará la luz verde
“UPS Available” (UPS disponible)
D
de la PDU.
Paso 6. Conecte los cables de los equipos a los
tomacorrientes compatibles en la
PDU
E
y Fije el interruptor de rodeo
de mantenimiento
A
en la posición
“UPS”. La carga conectada ahora está
protegida por el UPS.
Paso 1. Cerciórese de que la luz amarilla “Maintenance Bypass Available” (Rodeo de mantenimiento
disponible)
A
de la PDU está iluminada. Cambie el interruptor de rodeo de mantenimiento
B
“UPS” a “Utility” (Red pública). La carga conectada ahora recibe soporte de la fuente de
energía de la red pública y no recibirá respaldo de energía en el caso de una falla de la red
pública.
Paso 2. Apague el sistema UPS que require mantenimiento o reemplazo y quite todas las conexiones
de alimentación entre el UPS y la PDU. La luz “UPS available” (UPS disponible) estará
apagada.
Paso 3. Reemplace el sistema UPS. Conecte el cable de alimentación de entrada del nuevo sistema
UPS al tomacorriente de la PDU para conexión del UPS (con la etiquta “Connect UPS Line
Cord Here” –Conecte el cable de línea del UPS) y encienda el nuevo sistema UPS.
Paso 4. Conecte el cable de entrada de la fuente UPS de la PDU (con la etiqueta “To UPS Output” –A
la salida del UPS) a un tomacorriente compatible en el nuevo sistema UPS. Se iluminará la
luz verde “UPS Available” (UPS disponible) de la PDU.
Paso 5. Cambie el interruptor de rodeo de mantenimiento
B
de “Utility” (Red pública) a “UPS”. La
carga conectada ahora está protegida por el UPS.
Paso 3
Paso 4
Paso 5
Paso 6
Varía según
el modelo
Varía según
el modelo
Varía según
el modelo
Varía según
el modelo
Paso 1
Paso 5
Rodeo manual para el reemplazo del UPS en operación
14
Solución de problemas
Use el siguiente cuadro para realizar ajustes menores o intentar la solución de problemas. No intente abrir la PDU, no tiene partes internas que el usuario
pueda reparar. Si los problemas continúan después de la solución de problemas, visite www.tripplite.com/support.
Problema Causa posible Solución posible
La luz amarilla no se ilumina. No recibe energía de la red pública. Póngase en contacto con su compañía proveedora de
servicios públcos o con un electricista calificado.
La PDU no está enchufada en la fuente de la red pública. Conecte la PDU a una fuente de la red pública.
La luz verde no se ilumina. El sistema UPS no posee salida. Consulte el manual del UPS para el inicio apropiado.
La entrada y salida del UPS no están conectadas a la PDU. Conecte la entrada y salida del UPS a la PDU.
Algunas cargas no reciben energía. Se disparó el interruptor automático en la PDU (PDUB30 únicamente). Reinicie el interruptor automático de la PDU.
Las cargas no reciben energía después de
reinicializar el interruptor automático.
La carga conectada supera la capacidad de la PDU. Disminuir la carga conectada.
Servicio y garantía
Servicio
Su producto Tripp Lite está cubierto por la garantía descrita en este manual. Tripp Lite también pone a disposición una variedad de garantías extendidas y programas de servicio en
el sitio. Para obtener más información sobre el servicio, visite www.tripplite.com/support. Antes de devolver su producto, haga lo siguiente:
1. Revise los procedimientos de instalación y operación descritos en este manual para asegurarse de que el problema de servicio no se origina en una mala comprensión de las
instrucciones.
2. Si el problema persiste, no se ponga en contacto ni devuelva el producto mayorista. En lugar de eso visite www.tripplite.com/support.
3. Si el problema requiere servicio, visite www.tripplite.com/support y haga clic en el enlace Devolución de productos. Aquí puede solicitar un número de autorización de devolución
de mercadería (RMA), que es necesario para el servicio. En este simple formulario en línea se le pedirá el modelo y números de serie de su unidad, junto con otra información
general sobre el comprador. El número RMA y las instrucciones para el envío se le enviarán por correo electrónico. Esta garantía no cubre ningún daño (directo, indirecto,
especial o consecuencial) que el producto sufra durante el envío a Tripp Lite o un centro de servicio autorizado por Tripp Lite. Los productos que se envían a Tripp Lite o un centro
de servicio autorizado por Tripp Lite debe tener prepagos los cargos de envío. Escriba el número RMA en el exterior del paquete. Si el producto se encuentra dentro del período
de garantía, adjunte una copia del recibo de venta. Envíe el producto para servicio a través de un transportador asegurado a la dirección que se le proporcione cuando solicite el
RMA.
Garantía
GARANTÍA LIMITADA POR 2 AÑOS
El vendedor garantiza que este producto no tiene defectos originales de materiales ni de mano de obra por un período de dos años a partir de la fecha original de compra, si se
utiliza de acuerdo con todas las instrucciones correspondientes. En caso de demostrarse dentro de ese período que el producto tiene defectos de materiales o de mano de obra,
el vendedor lo reparará o reemplazará a su exclusiva discreción. El servicio bajo esta garantía solo puede ser obtenido si usted entrega o envía el producto (con todos los cargos de
envío o entrega prepagos) a: Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; EE. UU. El vendedor abonará los cargos de envío de devolución. Visite www.tripplite.com/support
antes de enviar cualquier equipo para reparación.
ESTA GARANTÍA NO CUBRE EL DESGASTE NORMAL NI LOS DAÑOS CAUSADOS POR ACCIDENTES, MAL USO, ABUSO O NEGLIGENCIA. EL VENDEDOR NO OFRECE NINGUNA
GARANTÍA EXPRESA QUE NO SEA LA ESTABLECIDA EXPRESAMENTE EN EL PRESENTE DOCUMENTO. EXCEPTO EN LA MEDIDA EN QUE LO PROHIBAN LAS LEYES APLICABLES, LA
DURACIÓN DE TODAS LAS GARANTÍAS IMPLÍCITAS, INCLUIDAS LAS DE COMERCIABILIDAD O APTITUD, SE LIMITA AL PERÍODO DE GARANTÍA ANTES MENCIONADO Y ESTA GARANTÍA
EXCLUYE EXPRESAMENTE TODOS LOS DAÑOS INCIDENTALES E INDIRECTOS. (Algunos Estados no permiten las limitaciones a la duración de una garantía implícita y algunos
Estados no permiten la exclusión o limitación de los daños incidentales o indirectos, de modo que las limitaciones o exclusiones antes mencionadas pueden no corresponder en su
caso. Esta garantía le otorga derechos legales específicos y usted puede tener otros derechos que varían de una jurisdicción a otra).
Tripp Lite; 1111 W. 35th Street; Chicago IL 60609; EE. UU.
ADVERTENCIA: Antes de usar este dispositivo, cada usuario debe ocuparse de determinar si es apto, adecuado o seguro para el uso que pretende darle. Dado que las aplicaciones
individuales están sujetas a diversas variaciones, el fabricante no representa ni garantiza la idoneidad o condición de estos dispositivos para cualquier aplicación específica.
Información sobre el cumplimiento de la WEEE para clientes de Tripp Lite y técnicos de reciclaje (Unión Europea)
Bajo la Directiva de Residuos de Aparatos Eléctricos y Electrónicos (WEEE) y las reglamentaciones reguladoras, cuando los clientes compran cualquier equipo eléctrico y
electrónico nuevo de Tripp Lite tienen derecho a:
Regresar el equipo viejo para reciclaje por uno igual o por uno semejante (esto varía de acuerdo con el país)
Regresar el equipo nuevo para que sea reciclado cuando finalmente se convierte en un desecho
Conformidad con las regulaciones sobre números de identificación
Con el objeto de cumplir con las regulaciones de certificaciones e identificación, a su producto Tripp Lite se le ha asignado un número de serie único. Puede encontrar el número de
serie en la etiqueta o placa de identificación del producto, junto con todas las marcas de aprobación e información necesarias. Cuando solicite información de cumplimiento de este
producto, siempre haga referencia al número de serie. El número de serie no debe confundirse con el nombre de marca o el número de modelo del producto.
Tripp Lite tiene la política de mejora continua. Las especificaciones del producto están sujetas a cambios sin notificación previa.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
15
Guide de l’utilisateur
PDU remplaçable à chaud avec
un sectionneur de dérivation
pour maintenance
Modèles : PDUB15, PDUB20, PDUB30, PDUBHV10, PDUBHV20
Consignes de sécurité importantes 16
Montage 16
Caractéristiques 18
Connexion et fonctionnement 20
Dépannage 21
Service et garantie 21
English 1
Español 8
Русский 22
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Tous droits réservés © 2019 Tripp Lite Toutes les marques de commerce appartiennent à leurs propriétaires respectifs.
Monter dans les
trous supérieurs
ou inférieurs.
16
Montage
Montage (bâtis à 2 montants ou à 4 montants)
Monter votre équipement dans un bâti ouvert à 2 supports ou à 4 supports ou un boîtier sur bâti. L’utilisateur doit déterminer l’aptitude du matériel et les
procédures avant le montage. Les procédures décrites dans ce manuel sont pour les types de bâti et de boîtier ordinaires sur bâti et elles peuvent ne pas
être appropriées pour toutes les applications.
Remarque : Les procédures de montage sont les mêmes pour l’installation d’un bâti à 2 supports et à 4 supports.
Étape 1. Fixer les oreilles de montage aux trous de montage du PDU à l’aide des vis prévues à cette fin.
Les oreilles devraient donner sur le devant.
Remarque : Les trous de montage supérieurs ou inférieurs du PDU peuvent être utilisés.
Étape 2. Fixer le PDU au bâti avec les vis, les écrous et les rondelles prévus par l’utilisateur.
Insérer les vis dans les oreilles de montage et dans les rails du bâti.
Montage dans le même espace de bâti qu’un système UPS (bâtis à 4 supports)
Le PDU remplaçable à chaud peut être monté dans le même espace de bâti qu’un système UPS lorsque
le système UPS est monté à l’aide du 4POSTRAILKIT de Tripp Lite. (Le 4POSTRAILKIT est compris avec la
plupart des systèmes UPS et est également vendu séparément. Se référer au manuel du système UPS
ou du manuel du 4POSTRAILKIT pour les consignes de montage du système UPS. La procédure pour le
montage de l’arrière des étagères de montage 4POSTRAILKIT sur le bâti différera légèrement, tel qu’il est
indiqué dans la présente section.)
Étape 1. Fixer les oreilles de montage aux trous de montage inférieurs de l’appareil à l’aide des vis
prévues à cette fin. Les oreilles devraient donner sur le devant.
Consignes de sécurité importantes
CONSERVER CES DIRECTIVES
Le présent guide contient des consignes et des mises en garde importantes qui devraient être suivies durant l’installation et le fonctionnement du présent
produit.
Installer le PDU à l’intérieur, loin de l’humidité ou de la chaleur excessive, de la lumière solaire directe, de la poussière ou de contaminants conducteurs.
Ne pas installer le PDU près d’un moyen de stockage magnétique pour éviter la corruption des données.
Faire Uniquement fonctionner le PDU à des températures intérieures entre 32 °F et 104 °F (0 °C et 40 °C). Pour obtenir de meilleures performances,
maintenir les températures intérieures entre 62 °F et 84 °F (17 °C et 29 °C). Pour une ventilation appropriée, laisser un espace adéquat autour de tous les
côtés du PDU.
L’utilisation du présent appareil dans les applications de maintien des fonctions vitales où la défaillance de cet équipement pourrait raisonnablement causer
la défaillance de l’équipement de maintien de la vie ou affecter sa sécurité ou son efficacité n’est pas recommandée. Ne pas utiliser le présent équipement
en présence d’un mélange d’agent anesthésique inflammable et d’air, d’oxygène ou d’oxyde nitreux.
Ne pas connecter le PDU à une prise non mise à la terre ou à des adaptateurs qui éliminent la connexion de terre. Les connexions de terre sont fournies
pour votre sécurité. Si la fiche prévue n’est pas adaptée à votre prise de courant, avoir une prise compatible mise à la terre installée par un électricien
agréé.
Le PDU doit être installé près d’une prise murale, et toutes les fiches doivent être facilement accessibles pour la déconnexion.
Le PDU doit être connecté à une prise murale qui est protégée par un dispositif de protection contre les surintensités avec la puissance nominale indiquée
dans le tableau ci-dessous :
Modèle Dispositif de protection contre les surintensités Modèle Dispositif de protection contre les surintensités
PDUB15 20 A PDUBHV10 20 A (cTUVus) ou 16 A (CE)
PDUB20 20 A PDUBHV20 20 A (cTUVus) ou 16 A (CE)
PDUB30 30 A
Mise en garde! Danger de choc électrique! Le PDU est alimenté par plus d’une source d’alimentation. Toutes les sources d’alimentation doivent être
déconnectées avant de mettre hors tension l’appareil pour l’entretien courant.
En aucune circonstance le PDU ne doit être ouvert. Il ne contient aucun élément qui puisse être réparé par l’utilisateur.
Étape 1
Étape 1
Étape 2
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
26
25
24
B
B
A
A
Installation correcte : la circulation d'air du système UPS n'est pas obstruée
Boîtier sur bâti – Vue latérale
Rails du boîtier sur bâti avant
Rails du boîtier sur bâti arrière
L'équipement à 2U au-dessus du
système UPS ne doit pas excéder la
profondeur du système UPS.
L'équipement à 2U en dessous du
système UPS ne doit pas excéder la
profondeur du système UPS.
Système UPS 2U
PDU
remplaçable
à chaud
2U au-dessus
du PDU doit
être ouvert.
2U en dessous
du PDU doit
être ouvert.
Installation incorrecte : la circulation d'air du système UPS est obstruée
Boîtier sur bâti – Vue latérale
Rails du boîtier sur bâti avant
Rails du boîtier sur bâti arrière
L'équipement à 2U au-dessus du système UPS ne doit pas excéder la
profondeur du système UPS.
L'équipement à 2U en dessous du système UPS ne doit pas excéder la
profondeur du système UPS.
Système UPS 2U
PDU
remplaçable
à chaud
2U au-dessus
du PDU doit
être ouvert.
2U en dessous
du PDU doit
être ouvert.
17
Étape 2. Installer le 4POSTRAILKIT sur le bâti en utilisant uniquement le trou de montage supérieur
A
de chaque côté de l’arrière des étagères de montage 4POSTRAILKIT. (Les vis sur le devant
des étagères ne seront pas différentes de la procédure standard indiquée dans le manuel de
votre UPS ou 4POSTRAILKIT.)
Étape 3. Installer le PDU sur le bâti en utilisant les deux trous de montage inférieurs
B
de chaque
côté de l’arrière des étagères de montage 4POSTRAILKIT.
Montage (suite)
Étape 2
Étape 3
Avertissement! Se référer aux schémas ci-dessous pour vous assurer que la circulation d’air du système UPS n’est pas obstruée. Si la
circulation d’air du système UPS est obstruée, le système UPS surchauffera.
PDUB15
PDUB20
PDUB30
12A MAX.
12A MAX.
OUTPUT
12A MAX.
12A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
15A MAX.
15A MAX.
OUTPUT
16A MAX.
16A MAX.
OUTPUT
TO UPS OUTPUT
UTILITY
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT
24A MAX.
OUTPUT 20A MAX.
LOAD1
LOAD2
20A OUTPUT
BREAKERS
PUSH TO RESET
TO
UPS OUTPUT
UTILITY
30A
30A
UTILITYUPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
1
1
6
6
7
7
9
9
397
11 6 10
1
2
2 11
8
8
8
10
10
18
Caractéristiques
1
Sorties CA 5-15R : se connectent aux fiches de l’équipement 5-15P.
2
Sorties CA 5-20R :
se connectent aux fiches de l’équipement 5-15P ou 5-20P.
3
Sorties CA L5-30R :
se connectent aux fiches de l’équipement L5-30P.
4
Sorties CA C13 :
se connectent aux fiches de l’équipement C14.
5
Sorties CA C19 :
se connectent aux fiches de l’équipement C20.
6
Entrée de source de l’UPS :
se connecte à la sortie compatible du système UPS.
7
Sectionneur de dérivation pour maintenance :
sélectionne la source d’alimentation qui alimente la charge – soit la source de l’UPS ou la source de
secteur. Lorsque le sectionneur est réglé sur « Utility » (Secteur), l’équipement connecté reçoit l’alimentation secteur CA du PDU, mais l’équipement ne
recevra pas l’alimentation de secours de la batterie de l’UPS dans le cas d’une panne du secteur. Voir le « Fonctionnement manuel de la dérivation » pour
plus de renseignements.
8
Voyants de diagnostic (UPS disponible et dérivation pour maintenance disponible) :
Un voyant vert « UPS Available » (UPS disponible) s’allumera
lorsque la source de l’UPS est connectée et sous tension. Un voyant jaune « Maintenance Bypass Available » (Dérivation pour maintenance disponible)
s’allumera lorsque la source de secteur est connectée et sous tension.
9
Entrée de source de secteur :
se connecte à la source d’alimentation secteur. Les modèles PDUB15, PDUB20 et PDUB30 possèdent chacun un cor-
don et une fiche d’entrée fixe. Le modèle PDUBHV10 possède une entrée C14 et le modèle PDUBHV20 possède une entrée C20. Les modèles PDUB-
HV10 et PDUBHV20 comprennent une bretelle d’extension et peuvent être utilisés avec un cordon d’alimentation fourni par l’utilisateur. (Voir ci-dessous
pour une sélection des cordons d’alimentation compatibles Tripp Lite.)
10
Sortie de connexion de l’UPS :
se connecte au cordon d’alimentation de l’entrée de l’UPS. L’utilisateur doit apparier le cordon d’alimentation de l’entrée
de l’UPS avec un modèle de PDU compatible.
11
Disjoncteurs de sortie CA de dérivation de 20 A (PDUB30 uniquement) :
contrôlent l’alimentation des sorties de PDU.
PDUBHV10
PDUBHV20
OUTPUT 10A MAX. OUTPUT 10A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
OUTPUT 10A MAX. OUTPUT 10A MAX. OUTPUT 16A MAX.
TO UPS OUTPUT
UTILITY
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
CONNECT UPS
LINE CORD HERE
10
10
4
4
4
54
6
6
7
7
9
9
8
8
19
Caractéristiques (suite)
Choisir un modèle de PDU compatible avec la fiche d’entrée du système UPS et les spécifications d’alimentation :
Modèle
Valeur nominale du système
UPS compatible
Fiche d'entrée de la source de
secteur / Longueur du cordon
Sortie de con-
nexion de l'UPS
Fiche d'entrée de
la source de l'UPS /
Longueur du cordon Sorties pour l'équipement
PDUB15 100-127 V, jusqu’à 1 500 VA 5-15P / 10 pi 5-15R 5-15P / 6 pi 8 (5-15R)
PDUB20 100-127 V, 2 200-2 600 VA 5-20P / 10 pi 5-20R 5-20P / 6 pi 4 (5-15R), 4 (5-20R)
PDUB30 100-127 V, 3 000 VA L5-30P / 10 pi L5-30R L5-30P / 6 pi 6 (5-20R), 1 (L5-30R)
PDUBHV10 200-240 V, jusqu’à 1 500 VA C14 / 6 pi (ou fourni par l'utilisateur) C13 C13 / 6 pi 8 (C13)
PDUBHV20 200-240 V, 2 000-3 000 VA C20 /5 pi (ou fourni par l'utilisateur) C19 C19 /5 pi 6 (C13), 2 (C19)
Cordons en option PDUBHV10
(vendus séparément)
Modèle Longueur Type de fiche
P005-002 2 pi C14
P005-006 6 pi C14
P005-010 10 pi C14
P011-006 6 pi L6-20P
P032-007 7 pi C20
P054-006 6 pi CEE 7/7
P056-006 6 pi BS1363
Cordons en option PDUBHV20
(vendus séparément)
Modèle Longueur Type de fiche
P036-006 6 pi C20
P036-002 2 pi C20
P040-010 10 pi L6-20P
P047-002 2 pi C14
P047-004 4 pi C14
P047-006 6 pi C14
P047-010 10 pi C14
P050-008 8 pi CEE 7/7
P052-008 8 pi BS1363
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
C
A
E
E
D
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
UTILITY
UPS
UPS
AVAILABLE
MAINTENANCE BYPASS
AVAILABLE
A
B
B
20
Connexion et fonctionnement
Connexions d’alimentation d’entrée / de sortie
Étape 1. Mettre hors tension l’équipement branché dans le système UPS, puis débrancher les câbles du système UPS.
Étape 2. Mettre hors tension le système UPS, puis le débrancher de la source de secteur.
Étape 3. Régler le sectionneur de dérivation pour maintenance
A
du PDU en position « Utility »
(Secteur), puis connecter le cordon d’alimentation d’entrée de la source de secteur
B
du
PDU à la source d’alimentation CA de secteur de votre établissement. Le voyant jaune
C
«
Maintenance Bypass Available » (Dérivation pour maintenance disponible) du PDU s’allumera.
Étape 4. Connecter le cordon d’alimentation d’entrée de l’UPS à la sortie de la connexion de l’UPS du
PDU (étiquetée « Connect UPS Line Cord Here » (Connecter le cordon d’alimentation de l’UPS
ici), puis mettre sous tension le système UPS.
Étape 5. Connecter le cordon d’entrée de source de l’UPS du PDU (étiqueté “TO UPS Output”)
(À la sortie de l’UPS) à une sortie compatible du système UPS. Le voyant vert
D
“UPS
Available” (UPS disponible) s’allumera.
Étape 6. Connecter les câbles de l’équipement
aux sorties
E
du PDU, puis régler
le sectionneur de dérivation pour
maintenance
A
à la position UPS. La
charge connectée a désormais une
protection de l’UPS.
Étape 1. S’assurer que le voyant jaune
A
« Maintenance Bypass Available » (Dérivation pour
maintenance disponible) du PDU est allumé. Faire passer le sectionneur de dérivation pour
maintenance
B
de « UPS » à « Utility » (Secteur). La charge connectée est maintenant
supportée par la source d’alimentation de secteur, et elle ne recevra pas l’alimentation de
secours de la batterie en cas de panne du secteur.
Étape 2. Mettre hors tension le système UPS qui exige des travaux de maintenance ou qui doit être
remplacé, puis retirer toutes les connexions d’alimentation entre le système UPS et le PDU.
Le voyant vert « UPS Available » (UPS disponible) du PDU s’éteindra.
Étape 3. Remplacer le système UPS. Connecter le cordon d’alimentation d’entrée du système UPS
à la sortie de la connexion de l’UPS du PDU (étiquetée « Connect UPS Line Cord Here »
(Connecter le cordon d’alimentation de l’UPS ici), puis mettre sous tension le nouveau
système UPS.
Étape 4. Connecter le cordon d’entrée de la source de l’UPS du PDU (étiqueté « To UPS Output » (À la
sortie de l’UPS) à une sortie compatible sur le nouveau système UPS. Le voyant vert « UPS
Available » (UPS disponible) du PDU s’allumera.
Étape 5. Transférer le sectionneur de dérivation pour maintenance
B
de « Utility » (Secteur) à UPS. La
charge connectée a désormais une protection de l’UPS.
Étape 3
Étape 4
Étape 5
Étape 6
Les modèles
varient.
Les modèles
varient.
Les modèles
varient.
Les modèles
varient.
Étape 1
Étape 5
Fonctionnement manuel de la dérivation pour le remplacement de l’UPS remplaçable à chaud
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Tripp Lite Hot-Swap PDUs Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
Ce manuel convient également à

dans d''autres langues