- 2 -
Note:
Sentrol recommend that the detector is regularly walk tested and checked back at the
control panel.
Switch 1: LED indication:
"
ON
" enables
both LED's
on the detector at all time.
"
OFF
" puts
both LED's under the control
of the Walk test input when the system is
disarmed.
Switch 2: Range:
"
ON
" selects
max. stated range. i.e 50ft (15m).
"
OFF
" selects
min. stated range. i.e 33ft (10m).
Switch 3: Processing:
"
ON
" enables
Bi-curtain
processing, designed for harsh environment.
"
OFF
" provides the
Aritech 4D
processing.
Switch 4: How to signal "Trouble output" (Electronic Trouble Output (ETO)):
"
ON
" signals
the trouble signal
on
both
the ETO and alarm relay.
"
OFF
" signals
the trouble signal
on the ETO .
English
Français
Español
Remarque:
Sentrol préconise d’effectuer régulièrement des tests de marche du détecteur et de
vérifier son fonctionnement à la centrale de commande.
Interrupteur 1: Indication LED:
"
ON
" active en permanence les deux LED sur le détecteur.
"
OFF
" met les deux LED sous le contrôle de l’entrée Test de marche lorsque le
système est désarmé.
Interrupteur 2: Portée:
"
ON
" sélectionne la portée
50ft (15m).
"
OFF
" sélectionne la portée
33ft (10m).
Interrupteur 3: Programmation du mode:
"
ON
" active le mode
Double rideau
, conçu pour les environnements sévères.
"
OFF
" sélectionne le mode standard
Aritech 4D
.
Interrupteur 4: Signalisation "sortie ETO" ((SED) sortie électronique défauts):
"
ON
" envoie le signal défauts à la fois sur la ETO et le relais d’alarme.
"
OFF
" envoie le signal défauts sur la sortie ETO seulement.
Interrupteur 5: Sensibilité AM (AM = Anti-Masquage):
"
ON
" sélectionne un
niveau élevé de sensibilité AM.
"
OFF
" sélectionne la sensibilité
AM standard.
Interrupteur 6: RAZ de la "sortie ETO":
"
ON
" rétablit la
sortie ETO
après IRP-alarme.
"
OFF
" ne rétablit la
sortie ETO
que lorsque ce mode est permis.
Interrupteur 7: Quand signaler "sortie ETO"
"
ON
" signale la
sortie
au désarmement suivant du système.
"
OFF
" signale la
sortie
immédiatement.
Interrupteur 8: Polarité de contrôle:
"
ON
" fournit la
logique standard Aritech
avec 12V, pour activer les entrées Test
de marche et verrouillage.
"
OFF
" pour activer les entrées Test de marche et verrouillage.
Nota:
Sentrol recomienda que se efectúe periódicamente un prueba de condición con el
detector, comprobándolo al mismo tiempo en el panel de control.
Interruptor 1: LED indicador:
"ON"
Habilita
ambos LED
en todo momento.
"OFF"
Pone
ambos LED
bajo el control de la entrada de la prueba de condición,
cuando esté desarmado elsistema.
Interruptor 2: Alcance:
"ON"
Selecciona el alcance
máximo indicado
, es decir
50ft (15m).
"OFF"
Selecciona el alcance
mínimo indicado
, es decir
33ft (10m).
Interruptor 3: Tratamiento:
"ON"
Habilita el tratamiento de
doble cortina
, diseñado para entornos agresivos.
"OFF"
Proporciona el tratamiento
Aritech 4D.
Interruptor 4: Cómo señalizar ((ETO) Salida de problema electrónico):
"ON"
Señaliza la señal de problema tanto en el ETO como en el relé de alarma.
"OFF"
Señaliza la señal de problema en el ETO.
English
Switch 5: AM Sensitivity (AM = Anti Masking):
"
ON
" selects a
higher level of AM
sensitivity.
"
OFF
" selects the
standard AM
sensitivity.
Switch 6: Resetting the "Trouble output":
"
ON
" resets the
Trouble output
after PIR-alarm.
"
OFF
" resets the
Trouble output
only when authorized.
Switch 7: When to indicate the "Trouble output":
"
ON
" will signal the
Trouble output
the next time system is disarmed.
"
OFF
" will signal the
Trouble output
immediately.
Switch 8: Control polarity:
"
ON
" provides the
standard Aritech logic
with active High logic to enable Walk test
and Latch inputs.
"
OFF
" provides active
Low
logic to enable Walk test and Latch inputs.
Interruptor 5: Sensibilidad AM (AM = Anti Careta):
"ON"
Selecciona un
nivel superior de
sensibilidad
AM.
"OFF"
Selecciona la sensibilidad
estándar AM.
Interruptor 6: Rearme de la "salida de problema":
"ON"
Rearma la salida de
problema
después de haber superado satisfactoria-
mente la prueba de condición.
"OFF"
Rearma la salida de
problema
únicamente cuando se autorice.
Interruptor 7: Cuándo debe indicarse la "salida de problema"
"ON"
Señalizará la
salida de problema
la próxima vez que se desarme el sistema.
"OFF"
Señalizará inmediatamente la
salida de problema
.
Interruptor 8: Polaridad de control:
"ON"
Proporciona la lógica estándar Aritech conlógica activa alta para activar las
entradas de la prueba de condición y del seguro.
"OFF"
Proporciona lógica activa baja para activar las entradas de la prueba de
condición y del seguro.
Remote enable/disable of Walk test LED.
To walk test the detector, the "CV" to terminal 9 (latch) must be disconnected. Connect
the "CV" to terminal 10. The detector’s LED will now light and go out again as the alarm
relay opens and closes, making possible walk testing.
Note: Enabling the walk test will not clear alarm memory. After disarming the system
after an alarm, you may switch to walk test. When you switch back out of walk test, the
indication 1.
Français
Activation/désactivation à distance de la LED du test de marche.
Pour effectuer un test de marche du détecteur, débrancher la "CV" de la borne 9
(verrouillage). Connecter la "CV" à la borne 10. La LED du détecteur va s’allumer et
s’éteindre à nouveau lorsque le relais d’alarme s’ouvre et se ferme, rendant possible
le test de marche.
Remarque: L’activation du test de marche n’efface pas la mémoire d’alarme. Après
avoir désarmé le système après une alarme, vous pouvez passer en mode de test de
marche. Lorsque vous quittez ce mode de test de marche, l’indication des alarmes
mémorisées réapparaît. Ce n’est que lorsque la T "CV" S est à nouveau appliquée à
la borne 9 (réarmement du système) que les LED et la mémoire sont effacées.
Mémoire d'alarme.
Remarque: Sélection d'abord la polarité de contrôle ("CV") avec le cavalier SW8.
(voir fig. 3b.)
(Par exemple SW8 = "OFF", alors "CV" = 0 V = "Negatif").
Tension de contrôle. (fig. 4).
Brancher la tension à la borne 9 lorsque le système est armé. Quand le système est
désarmé, débrancher la "CV". Si une alarme a eu lieu pendant la période où le
système était armé, le ou les détecteurs responsables de l’alarme sont indiqués par
le clignotement de la LED. Rétablir la "CV" (réarmer le système) afin de réactiver
l’indication par la LED et la mémoire.
Memoria de alarma.
Nota: En pirmer lugar, elegir la tensisn de control ("CV") con el interruptor SW8.
(ver fig. 3b.)
( Por ejemplo: SW8 = "OFF", entonces "CV" = 0 Tensisn = "Baja").
Tensión de control. (fig. 4).
Conecte la tensión de control (“CV”) al terminal 9 cuando esté armado el sistema.
Cuando el sistema esté desarmado, desconecte la tensión de control. Si se ha
producido alguna alarma durante el período en que el sistema estaba armado, un
LED intermitente indicará el detector o detectores que dieron lugar a la alarma.
Aplicando de nuevo la tensión de control (rearmando el sistema) se pone a cero la
indicación del LED y la memoria.
Activación y desactivación a distancia del LED de la prueba de condición.
Para efectuar la prueba de condición en el detector es necesario desconectar la
tensión de control en el terminal 9 (seguro). Conecte la tensión de control al terminal
10. Ahora se iluminará el LED del detector y se apagará de nuevo cuando se abra y
cierre el relé de la alarma, haciendo posible la prueba de condición.
Nota: Cuando se habilite la prueba de condición no se borra la memoria de alarmas.
Al desarmar el sistema después de una alarma se puede pasar a efectuar la prueba
de condición. Cuando se vuelva a salir de la prueba de condición aparecerá de
nuevo la indicación de las alarmas memorizadas. Los LED y la memoria únicamente
se borrarán cuando se aplique de nuevo la tensión de control al terminal 9 (es decir
cuando se rearme el sistema).
Español
Alarm memory
Note: First set the Control Voltage ("CV") by jumper SW8 (see fig. 3b).
(For example: SW8 = "OFF", then "CV" = 0 Volt = "Low").
Control voltage. (fig. 4).
Connect the Control Voltage ("CV") to terminal 9 when system is armed. When the
system is disarmed, disconnect the "CV". If an alarm has occurred during the armed
period, the detector or detectors which gave the alarm are indicated by a flashing LED.
Re-applying the "CV" re-arming the system) will reset LED indication and memory.