Rheem TWPH-8550EHT10 Le manuel du propriétaire

Catégorie
Thermostats
Taper
Le manuel du propriétaire
Effective: 08-06-2023
Replaces: 07-28-2023
P/N: 100-10000496 Rev. 02
Heat Pump Pool
& Spa Heater
Models: TWPH 4550, 5550, 6550,
6550EHC, 8550, & 8550EHC
FOR YOUR SAFETY: Do not store or use gasoline or other ammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance.
To do so may result in an explosion or re.
NOTE: The instructions in this manual are for the use of qualied individuals specially trained
and experienced in the installation and maintenance of this type of equipment and related system
components. Installation and service personnel are required by some states to be licensed. Persons
not qualied shall not attempt to install, service, or maintain this equipment.
This manual should be maintained in legible condition and kept adjacent to the heat pump pool heater or in a
safe place for future use.
INSTALLATION AND
OPERATION MANUAL
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
2
QUICK START GUIDE
CLEARANCES
Installation Considerations Page 6.
Installation Clearances Page 7.
Hurricane Tie Down Instructions Page 8.
PIPING
Water Connections Page 9.
Flow Rate & Pressure Drop Page 9.
Freeze Protection Page 34.
Plumbing Diagrams Page 38.
WATER CHEMISTRY
Water Chemistry Page 6.
Table A. Water Chemistry Page 6.
POWER
Electrical Connections Page 10.
Table C. Typical System Electrical Power
Requirements Page 10.
CONTROLS INTERFACE
Wiring Diagram -
208V/230V Single-Phase Page 11.
Heater Control Display Page 12.
Program Menu Page 17.
Digital Controls Operation Page 27.
Remote Mode Selector Page 31.
Connect to Wi-Fi with Raymote Page 43.
External Control Outputs Page 71.
Revision 02 reects the following changes:
Figure 4: Changed Tie Down Clip dimension from "10.000" to 8.00" - 10.00". Removed Steps 5 through 13 and Figure 62 in the "Service
Access to Heater" Section.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
3
TABLE OF CONTENTS
1. WARNINGS ............................................................. 4
Pay Attention to these Terms ..................................4
2. INTRODUCTION ...................................................... 5
3. WATER CHEMISTRY ............................................... 6
4. INSTALLATION CONSIDERATIONS ...................... 6
5. WATER CONNECTIONS ......................................... 9
6. FLOW RATE & PRESSURE DROP......................... 9
7. ELECTRICAL CONNECTIONS ............................... 9
8. WIRING DIAGRAM ................................................ 11
9. HEATER CONTROL DISPLAY .............................. 12
10. OPERATION MODES ............................................ 12
11. SERVICE MENU ..................................................... 14
Operations and Service Menu...............................16
12. PROGRAM MENU ................................................. 21
Program Menu Diagram ........................................20
13. INSTALLER MENU ................................................ 21
Installer Menu Diagram ......................................... 24
14. SCHEDULE MENU ................................................ 25
Schedule Menu Diagram.......................................26
15. DIGITAL CONTROLS OPERATION ...................... 27
Sequence of Operation .........................................27
System Start-Up ....................................................27
Operational Status Messages ...............................28
Error Messages .....................................................29
16. REMOTE MODE SELECTOR ................................ 31
17. SEASONAL START-UP OR
ANNUAL CHECK ................................................... 34
18. SUMMER SHUTDOWN.......................................... 34
19. FREEZE PROTECTION ......................................... 34
System Drain-Down ..............................................34
Continuous Pump Operation .................................34
20. MAINTENANCE ..................................................... 34
Air Coil Cleaning ...................................................35
Cabinet Care (optional) ......................................... 35
Unplug Condensation Drain Holes ........................35
21. TROUBLESHOOTING ........................................... 35
22. SERVICE CALL VERIFICATION ........................... 36
Power Supply ........................................................ 36
Water Flow ............................................................ 36
Time Clock Adjustment .........................................36
Set Factory Defaults..............................................36
Service Access to Heaters .................................... 37
23. PLUMBING DIAGRAMS ........................................ 38
24. RESISTANCE SENSOR VALUES ......................... 42
25. CONNECT TO WI-FI WITH RAYMOTE ................. 43
26. RAYMOTE MOBILE APP ....................................... 48
27. EXTERNAL CONTROL OUTPUTS ....................... 71
28. REPLACEMENT PARTS ....................................... 84
29. ILLUSTRATED PARTS LIST ................................. 85
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
4
1. WARNINGS
Pay Attention to these Terms
ADANGER Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial
property damage if ignored.
AWARNING Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or
substantial property damage if ignored.
ACAUTION Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product
or property damage if ignored.
CAUTION CAUTION used without the warning alert symbol indicates a potentially hazardous condition which could
cause minor personal injury or product or property damage if ignored.
NOTE Indicates special instructions on installation, operation, or maintenance which are important but not related
to personal injury hazards.
CAUTION: Improper chemical content in a swimming
pool or spa can damage the heater. DO NOT add pool/
spa chemicals to the pool/spa via the skimmer or any
other apparatus (feeder, chlorinator, etc.), that is on the
inuent side (i.e. before) of the heater. This will damage
the heater and could void the heater warranty. ALWAYS
follow the product manufacturer’s directions when
adding any chemicals to your pool.
This manual, as well as the pool heater itself, contains ANSI-approved product safety signs and labels. Please read these signs
and labels, as they convey important safety information about hazards that may be potentially present in and around the heater.
ACAUTION: Elevated water temperature can
be hazardous. The U.S. Consumer Product Safety
Commission has these guidelines:
1. Spa water temperatures should never exceed 104°F
(40°C). A temperature of 100°F (38°C) is considered
safe for a healthy adult. Special caution is suggested
for young children.
2. Drinking of alcoholic beverages before or during spa
or hot tub use can cause drowsiness which could
lead to unconsciousness and subsequently result in
drowning.
3. Pregnant Women Beware! Soaking in water over
102°F (39°C) can cause fetal damage during the first
three months of pregnancy resulting in the birth of a
brain-damaged or deformed child. Pregnant women
should stick to the 100°F (38°C) maximum rule.
4. Before entering the spa or hot tub, users should
check the water temperature with an accurate
thermometer; spa or hot tub thermostats may err
in regulating water temperatures by as much as 4°F
(2.2°C).
5. Persons with a medical history of heart disease,
circulatory problems, diabetes, or blood pressure
problems should obtain a physician’s advice before
using pools or hot tubs.
6. Persons taking medications which induce
drowsiness, such as tranquilizers, antihistamines,
or anticoagulants, should not use spas or hot tubs.
AWARNING: These heat pump pool heaters are
charged with R-410A refrigerant. Ensure that all service
work is done with gauges and equipment suitable for
R-410A.
EFFICIENCY TESTING NOTICE: For purposes of
verifying or testing efciency ratings, the test procedure
in Title 10 APPENDIX P to Subpart B of Part 430 (Uniform
Test Method for Measuring the Energy Consumption of
Pool Heaters) and the clarifying provisions provided in
the AHRI Operations Manual 1160 that were applicable
at the date of manufacture should be used for test set
up and performance. Charging Chart are available at
https://www.raypak.com/customer-support/heat-pump-
charging-charts. These should only be used by certied
HVAC technicians to check or adjust refrigerant charge
for proper operation.
CAUTION: The appliance is not to be used by persons
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction.
Do not allow children to play near or with appliance,
severe damage can occur from moving parts.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
5
2. INTRODUCTION
AWARNING: This heat pump pool heater is an
electromechanical machine that incorporates a
pressurized refrigerant gas in a sealed system. ONLY
trained and qualied service personnel are authorized to
install or service this equipment. Without proper training
and knowledge of such equipment, any attempt to install or
service the unit could result in serious injury or even death.
This manual contains important information on the use,
maintenance and troubleshooting of your new heat
pump pool heater. This unit must be properly installed,
maintained and operated for optimal performance.
This heater is an extremely efcient, economical machine
designed specically for heating swimming pools. It is
similar in design and operation to a typical residential air
conditioning system. The unit employs a hermetic motor/
compressor operating in a refrigeration cycle to extract
heat from ambient air and deliver it to the circulating pool
water.
All heat pump pool heaters have a lower BTU/hr heating
capacity than a gas-red or oil-red heater for the same
pool and will have to operate more hours per day to keep
the pool at setpoint. It may operate up to 24-hours a day
at certain times. It is designed to do so. Even with long
runtime hours, it will heat the pool at less cost than other
heaters using fossil fuel.
Since evaporation is the main cause of heat loss from a
pool, keeping the pool covered whenever it is not in use will
greatly reduce the cost of keeping the pool heated. Even
during warmer weather, Raypak recommends keeping the
pool covered at night.
NOTE: 4x Hurricane tie-down brackets, 16x tie-down
screws, 2x union halves, the printed warranty, optional
harnesses and the I&O manual are located in an
accessory bag mounted on the front of the heater
inside the packaging. For Heat Only models, a check
valve is provided in the packaging. For Heat/Cool
models, a bypass assembly is provided. Please DO
NOT throw away the packaging before removing all of
their contents.
ATTENTION: Please Take This Opportunity
to Quickly Register Your Unit!!
While your unit is being installed by your professional and
licensed installer of choice, Please Take This Opportunity to
Quickly Register Your Unit!! With the necessary information
in hand, Registering your new Heat Pump Pool Heater only
takes a few moments and is the only way to assure any
veriable warranty procedures during the span of your unit’s
period of protection.
Using Figure 1, please locate and record your model and
serial number. Once you have done this, please make sure
you also have the following information on hand:
Name, phone number, and email address of
homeowner
Figure 1. Model and Serial Number Location
Warranty Registration Conrmation #:
Scan this QR with your smart device to register or verify
your new Raypak heater.
Nameplate
QR Code
Physical address of where the unit is installed; please
include any ‘subdivision’ or similar information
Any service challenges present at the house/
neighborhood: gated community, locked access at
house, guard dog, etc.
Date of installation of the new unit
Name and phone number of the professional and
licensed entity that performed the installation for you
With all of the above information in hand, please contact
Raypak and ask to register your brand new heat pump or
Online at:
https://www.raypak.com/support/registration_warranty/
You will be given a Warranty Registration Conrmation
number which you should notate and keep in one location
along with your Installation & Owner’s Manual, a copy of
your warranty (provided with your manual) and the above
information.
This unit is equipped with a QR Code on the rating plate, as
shown in Figure 1, which will take you to the www.raypak.com
website where the Installation & Owner’s manual and other
documents can be easily accessed.
This would also be a good time to review both the manual
and the warranty so that you are aware of how to correctly
operate your new equipment as well as how to keep from
voiding any aspects of your warranty. During the life of your
unit, please feel free to use the phone number conveniently
located right on the unit, to contact us with any questions you
may have about operation, warranty, and/or service.
Thank you very much choosing Raypak to satisfy your pool
heating needs!!
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
6
Recommended Level(s) Fiberglass Pools Fiberglass Spas Other Pool & Spa Types
Water Temp. 68 °F to 88 °F
(20°C to 31°C)
89 °F to 104 °F
(32°C to 40°C)
68 °F to 104 °F
(20°C to 40°C)
pH 7.3 to 7.4 7.3 to 7.4 7.6 to 7.8
Total Alkalinity (PPM) 120 to 150 120 to 150 80 to 120
Calcium Hardness (PPM) 200 to 300 150 to 200 200 to 400
Salt (PPM) 4500 MAXIMUM 4500 MAXIMUM 4500 MAXIMUM
Free Chlorine (PPM)* 2 to 3 2 to 3 2 to 3
Total Dissolved Solids (PPM) 3000 MAXIMUM** 3000 MAXIMUM** 3000 MAXIMUM**
Water Pressure (psi/kPa) 5 MIN. - 70 MAX.
(35 MIN. - 483 MAX.)
5 MIN. - 70 MAX.
(35 MIN. - 483 MAX.)
5 MIN. - 70 MAX.
(35 MIN. - 483 MAX.)
*Free Chlorine MUST NOT EXCEED 5 PPM!
** In salt water chlorinated pools, the total TDS can be as high as 6000 ppm.
Table A. Water Chemistry
3. WATER CHEMISTRY
IMPORTANT: Corrosive water voids all
warranties.
For your health and the protection of your pool equipment,
it is essential that your water be chemically balanced. The
following levels must be used as a guide for balanced
water.
Occasional chemical shock dosing of the pool or spa
water should not damage the heater providing the
water is balanced. However, it is highly recommended
that the heat pump pool heater is isolated via shut off
valves before any aggressive chemical treatment.
Automatic chemical dosing devices and salt
chlorinators are usually more efficient in heated
water. Unless controlled, they can lead to excessive
chlorine level which can damage your heater.
Further advice should be obtained from your pool
or spa builder, accredited pool shop, or chemical
supplier for the correct levels for your water.
4. INSTALLATION
CONSIDERATIONS
AWARNING: Do not install the unit within 3 ft (0.9 m) of
fossil-fuel-burning heaters. Air intake along the sides of
this heat pump pool heater could disturb the combustion
process of the unit, and could cause damage or personal
injury.
Mount the unit on a level, sturdy base, preferably a
concrete slab. The size of the base should be at least 3 ft
by 3 ft (0.9 m x 0.9 m) - slightly larger if hurricane tie-down
brackets are installed. See Figure 4 for more details.
CAUTION: The unit’s supporting base must be high
enough to keep it completely free of standing water at
all times.
Situate the heater carefully to minimize installation costs
while providing maximum efciency of operation, and to
allow adequate service access, as follows:
For unrestricted air intake and service access,
position each side of the unit at least 1 ft (30 cm)
from walls, pipes and other obstructions.
AWARNING: This unit is designed for outdoor
installation. It is NOT certied for indoor installation.
DO NOT install it in an enclosed area such as a shed or
garage, or under a porch or deck.
This unit features an ‘up-flow’ discharge for quiet
operation. Air is pulled up through the evaporator
coil and discharged through the top grill. Allow
at least 5 ft (1.5 m) clearance above the unit for
unrestricted air discharge. Do NOT install the
unit under a porch or deck. Refer to Figure 2 for
installation clearances. Allowing cold discharge air to
recirculate back into the evaporator coil will greatly
reduce the unit’s heating capacity and efficiency.
To minimize water piping, locate the unit as close as
possible to the existing pool pump and filter.
Irrigation water should be directed away from the
heat pump pool heater - irrigation water spray can
damage the heater.
Rain water runoffs - the unit is designed to operate
outdoors and can be exposed to rain. However, rain
water runoff falling directly onto the unit can cause
damage and/or shorten the life of your unit. Such
damage is NOT covered under warranty. Install rain
gutters or rain diverters on your roof if the unit is
installed in a position where contact with rain runoff
may occur.
It is important to keep the area next to the heater
clear of shrubs, bushes and chemicals containers.
They could prevent air from circulating fully through
the heater, and will affect the operation of the heater
or damage the heater.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
7
3 FT
(09.m)
MIN
AIR
FLOW
IN
AIR
FLOW
IN
AIR FLOW OUT
60" (1.52m) MIN
12"
(0.3m)
MIN
Figure 2. Installation Clearances
When installed in areas where freezing temperatures
can be encountered, drain the water circuit to
prevent possible freeze-up damage. Refer to "Freeze
Protection" on page 34 for proper procedures.
If the heater is located below the water line of the
pool, the Water Pressure Switch (WPS) or Water
Flow Switch (WFS) might need to be adjusted or an
external WFS might be needed.
For high-wind installation requirements, refer to
Figure 4 – depending on the model size.
Figure 3. Base Design - Handling
NOTE: The base is designed with recessed areas
to allow the use of hand trucks or lifting without the
possibility of pinching ngers as shown in Figure 3.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
8
UNIT HEIGHT
37.8” MAX
UNIT WIDTH
33.6” MAX
UNIT LENGTH
33.6” MAX
CONCRETE SLAB
BY OTHERS, TYP.
UNIT WIDTH
33.6” MAX
UNIT LENGTH
33.6” MAX
UNIT HEIGHT
37.8” MAX
CONCRETE SLAB
BY OTHERS, TYP.
CONTROL
COVER
3
Maximum Rated Wind Pressures:
± 140 psf Lateral, 111 psf Uplift
Hurricane tie-downs are a structural component designed to prevent wind uplift during severe weather, such as hurricanes or severe storms. For further information on tie-downs,
and technical support, contact Raypak at www.raypak.com or call 805-278-5300.
Minimum pad dimensions are 43-1/4”
x 43-1/4” x 4” thick.
Screws to attach brackets to unit are
supplied with the unit.
DO NOT use screws not specified or
provided by manufacturer. Screws
are stainless steel #10 x 3/4”
self-drilling. Each bracket requires 4
screws attached to the unit.
Miami Tech Clip: (0.07”) ASTM A653
Fu=90 KSI Steel (CUTD10) or 0.080”
5052-H32 Aluminum (CUTDA10). Florida
approval FL# 19731.1 or approved equal.
TIE-DOWN SCHEDULE
At-Grade ± 54 psf (0 psf) 4
At-Grade / Rooftop ± 140 psf (111 psf) 8
# of
Tie-Down
Clips
Installation
Condition
Max. ASD
Wind Pressures
Lateral (Uplift)
1.26 TYP.
32.5 TYP.
1.26 TYP.
1.26 TYP.
Tie-Down Clips
Tie-Down Clips Tie-Down Clips
Tie-Down Clips
# of
Tie-Down
Clips
8.00”- 10.00”
Figure 4. Hurricane Tie Down Instructions – Models: TWPH 4550, 5550, 6550, 6550EHC, 8550, & 8550EHC
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
9
5. WATER CONNECTIONS
CAUTION: The heater inlet and outlet are NOT
interchangeable. They must be connected as instructed
below.
A
WARNING: Improper installation of any type of
automatic chemical feeders can result in serious damage
to, or premature failure of, the heater and such damage
will not be covered under warranty. Install a check valve
and/or a Hartford loop AFTER the heater and BEFORE
any chlorinating devices. Install any automatic chemical
feeders AFTER the heater.
1. Connect the heater in the return water line between
the filter and the pool/spa. See plumbing diagrams
on page 38 (without bypass) and page 39 (with
bypass).
2. Connect the filter outlet to the fitting marked INLET at
the bottom front of the unit.
3. Connect the fitting marked OUTLET to the return
piping to the pool/spa. Unit inlet/outlet connection
fittings are 2-inch PVC unions on models 4550-8550.
Water connections from the unit to the main return line can
be PVC pipe or exible pipe approved for the purpose and,
in either case, should be at least equal in size to the main
pool/spa circulation piping.
Water flow to the unit will exceed 40 GPM (151 LPM)
for 4550 models or 50 GPM (189 LPM) for 5550-
8550 models. See Figure 63 for bypass instructions.
To protect (completely bypass) the unit from any
harmful chemical treatments (i.e. Acid wash, back-
to-back super chlorinators, stain treatments, etc.); or
to be able to isolate the unit for service/repair or
freeze preparation and still allow pool/spa circulation
to continue.
In Heat/Cool models, a bypass assembly is included.
Please refer to the plumbing on page 39, for further
instruction.
Please note that some municipalities do not allow the use
of a shutoff valve on the efuent/outlet side of any heating
equipment, especially when there is one on the inlet side.
These entities typically instead allow a PVC tee and spring
check valve on the efuent/outlet side. This is allowed
by Raypak and can also double as your protection from
chemical feeders and chlorinators that are downstream of
the unit.
4. Operate the pump and check the system for leaks.
5. Drain plugs are located on each union fitting as shown
in Figure 5 for draining the system during winterizing.
NOTE: While it is possible to mount the upper union
with the drain plug vertically, the manufacturer has
determined that installing both unions with the drain
plugs facing down, as shown in Figure 5, provides for
the best draining of the system.
Figure 5. Water Connections/Drain Plugs
CAUTION: When the drain plugs are removed for
draining the system, ensure that they are stored in a
safe place for re-installation when needed to restart the
system.
6. FLOW RATE & PRESSURE
DROP
For system pressure drop information, see Table B.
Flow
GPM (LPM)
Pressure Drop (PSI)
4550 5550 6550/
6550EHC
8550/
8550EHC
20 (750) 3.4
30 (113) 7 4 6 9
40 (151) 13 7 9 9
50 (189) 10 10 10
60 (227) 11 11 11
70 (265) 12 12 12
80 (303) 13 13 13
Note: Minimum recommended ow is 20 GPM. Multiply the pressure drop
in psi by 2.3067 to yield the pressure drop in Ft. H2O Head.
(Total Dynamic Head TDH)
Table B. Flow Rate & Pressure Drop Across the Heater
INLET
OUTLET
DRAIN PLUG
DRAIN PLUG
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
10
Model No. Power
Min.
Circuit
Ampacity
Breaker Size
(AMP) Recommended Wire Length from Breaker to Heater*, ft. (m)
MAX. 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG
4550
208/230V -
Single Phase
- 60Hz
38 60 NR** 89 (27.1) 142 (43.3) 225 (68.6) 359 (109.4)
5550 40 70 NR** 94 (28.7) 151 (46.0) 239 (72.8) 383 (116.7)
6550 46 70 NR** 97 (29.6) 156 (47.5) 247 (75.3) 396 (120.7)
8550 46 70 NR** NR** 110 (33.5) 175 (53.3) 280 (85.3)
* Reference only - see National Electrical Code or local codes for wire gauge length limits.
** NR= Not Recommended
Table C. Typical System Electrical Power Requirements
7. ELECTRICAL
CONNECTIONS
Refer to the unit rating plate below the control panel for
precise power requirements for your unit, and for ampacity
and over-current protection requirements.
All wiring must be in accordance with the National Electrical
Code, NFPA No. 70, latest edition, and all applicable state
and local codes. See wiring diagram on page 11.
AWARNING: This unit MUST be installed using
exible conduit for supply wiring to the unit. This will
allow movement of the conduit whenever the junction
box is removed for service - see "Service Access to
Heaters" on page 37.
Locate the equipment disconnect means within 3
feet (0.9 m) of the heater’s electrical enclosure, or
as close to the heater as possible. Always satisfy
applicable codes and standards.
A means to fully disconnect the unit from the main
power supply must be incorporated in the wiring of
the unit.
NOTE: Refer to the National Electrical Code, Article
680, for general requirements for swimming pools and
equipment, and to Article 440 for special considerations
necessary for circuits supplying hermetic refrigeration
motor/compressors.
In sizing power wiring, be especially aware of up-sizing
requirements necessary due to wiring distances.
Always satisfy applicable codes and standards.
Connect electrical Line 1 (L1) and Line 2 (L2) to
the terminals indicated in Figure 6 for proper wiring.
Electrical installation should be performed by a
licensed electrician only.
This unit is compatible to work with external control
systems, (optional harness provided in the packaging
per NOTE on page 5) heat-on-demand options and other
external time clock overrides. Refer to the external control
system’s instructions, and "Remote Mode Selector", on
page 31 of this manual, for installation information.
An earth ground lug is located to the right-side of the water
connections.
L1 GND
L2
For 208v operation, ensure to
change the transformer to the
208 and C terminals.
Figure 6. Terminals L1 and L2
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
11
USE COPPER WIRES ONLY
USE 75°C 600V WIRE
TORQUE SCREWS: 40 IN-LB
11
1
1
10K
10K
10K
100K
BK/BU
BK/BU
BK/RD
BK/RD
RD
RD
GN
GN/BK
GN
1 1
BN
BU
YE
BN
RD
YE
OG
OG
BN
YE
BN
YE
R V
BU
RD
C
F
H
C
F
H
1
`
YE
BU
YE BU
VT
VT
24VAC
208V
240V
T1
L1
T2
L2
C2
C1
CONTACTOR
T1
L1
T2
L2
C2
C1
CONTACTOR
C
S
R
C
S
R
COMPRESOR
C
S
R
COMPRESOR
RD
RD
BK
BK
RD
POWER SUPPLY:
208/240V – 1 PHASE – 60Hz
L1 L2
GND
FAN
MOTOR
WPSLPSHPS
YE
BK
RD
BK
OG
BN
C2
C1 14
36
C2
C1 14
36
GY
GY
BK/WH
RD/WH
BN
11
3A 3A
RS-485
COMM
OUTLET
TEMP
P12 P13 P10 P6
FLOW
SENSOR
TEMPERATURE
SENSORS
P16
USER INTERFACE
P7
REMOTE
SELECTOR
POWER
24VAC
P1
MAIN
FUSE
VALVES
FUSE
F1
F2
VARIABLE
SPEED PUMP
P8
PUMP
P5
P19P20
3-WAY
VALVE2
3-WAY
VALVE1
AUX2
AUX1
P4
P3
P11
P9
P2
FAN, REV. VALVE AND
COMPRESOR COIL
FAN RVS COMP
SOLAR
3-WAY VALVE
SAFETY SWITCHES
WPS LPS HPS
3A 3A
RS-485
COMM
OUTLET
TEMP
P12 P13 P10 P6
FLOW
SENSOR
TEMPERATURE
SENSORS
P16
USER INTERFACE
P7
REMOTE
SELECTOR
POWER
24VAC
P1
MAIN
FUSE
VALVES
FUSE
F1
F2
VARIABLE
SPEED PUMP
P8
PUMP
P5
P19P20
3-WAY
VALVE2
3-WAY
VALVE1
AUX2
AUX1
P4
P3
P11
P9
P2
FAN, REV. VALVE AND
COMPRESOR COIL
FAN RVS COMP
SOLAR
3-WAY VALVE
SAFETY SWITCHES
WPS LPS HPS
MODESERVICE DOWN
UP CONNECT
MODESERVICE DOWN
UP CONNECT
BN
BN/OG
YE
BU
1
COMPONENT CODE
SENSOR 10K
DUAL SENSOR 100K
PRESSURE SWITCH
R VREVERSING VALVE
CAPACITOR
CAPACITOR
GROUND
FAN RELAY
24VAC
TRANSFORMER
WIRE COLOR CODE
WPS WATER PRESSURE
SWITCH
HPS HIGH PRESSURE
SWITCH
LPS LOW PRESSURE
SWITCH
GND GROUND LUG
BK
BN
BU
GN
GY
VT
OG
RD
WH
YE
BLACK
BROWN
BLUE
GREEN
GRAY
VIOLET
ORANGE
RED
WHITE
YELLOW
OUTLET
INLET
COIL
AMBIENT
INSERT
A
NC NO COM L1 L2 L2
VOLTAGE MONITOR
NC NO COM L1 L2 L2
VOLTAGE MONITOR
L1 L2TRANSFORMER
NC NO COM L1 L2 L2
VOLTAGE MONITOR
L1 L2TRANSFORMER
INSERT
A
NC NO COM L1 L2 L2
VOLTAGE MONITOR
L1 L2TRANSFORMER
BK/BU
BK/BU
BK/RD
BK/RD
RD
RD
GN
GN/BK
GN
VT
VT
(HEAT/COOL ONLY)
24VC
208V/230V Single-Phase Heat only and Heat/Cool models
8. WIRING DIAGRAM
Figure 7. Heat Only and Heat/Cool Models Wiring Diagram
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
12
9. HEATER CONTROL
DISPLAY
The heater display is located in the front panel of the heat
pump, covered with a door. All operation and settings of
the heater control are accomplished through the use of the
ve (5) touch keys of the user interface. These keys are
displayed in Figure 8.
Mode Key
The Mode Key is used to select one of several modes
for pool or spa operation. It also allows the user to select
the OFF mode of operation, during which the LCD, while
displaying OFF, continues to show the water temperature.
Refer to section 10, "Operation Modes" for details.
UP and DOWN Keys
If the heater is in pool or spa mode, the desired water
temperature (SETPOINT), can be adjusted using the UP
or DOWN keys.
MODESERVICE DOWN
UP CONNECT
CONNECT MENU
SERVICE MENU
Control 1.0
UI 1.0
UP TEMP ADJUST
DOWN TEMP ADJUST
MODE KEY
Figure 8. Heater Control Display
The display shows information on a 2-line, 16-character
back-lit Liquid Crystal Display (LCD). The back-light is
normally off, but it turns on for 5-minutes after power-up
and for 5-minutes after any button press. Use the LCD to
set up and monitor the operation of your heater.
If the control keys remains inactive for 5-minutes, the
screen will revert to the current view.
On a normal power-up, the control displays the current
software revision on the LCD for 2-seconds and then
resumes the user-selected mode it was in before power
was interrupted.
If unit type has not been set (like during the replacement
of the control), the control prompts the user to set the
model type (Heat Only or Heat/Cool) before any device
operation is enabled.
Upon initial installation, there are several items that
can be dened and programmed depending on the
conguration and accessories intended to be controlled
by the heater. Refer to "Program Menu" section on page
17 for details.
10. OPERATION MODES
The user may select one of several operating modes.
Each mode is selected by pressing the MODE key to cycle
between the modes. Each press of the MODE key selects
the next mode.
On Heat Only models, the options available by pressing
the MODE key are POOL, SPA, TIMED SPA and OFF.
On Heat/Cool models, the options available by pressing
the MODE key are POOL COOL, POOL HEAT, POOL
AUTO, SPA, TIMED SPA and OFF.
OFF
Water Temp 68F
OFF 8:05P
Water Temp 68F
OFF
No Demand
OFF
No Demand
8:05P
Figure 9. Alternating Display
Pool [Heat] and Spa Modes
The control is equipped with a Pool (heat) and Spa modes
which will automatically heat the pool to the heating
setpoint established in the selected mode.
The top row of the LCD displays the operation mode and
temperature setpoint. When Pool (heat) or Spa mode is
selected, each press of the UP or DOWN key will increase
/ decrease the water heating setpoint temperature. Holding
the UP or DOWN keys down will speed up the change of
the temperature values.
In these modes, the heater is set to heat when the water
temperature is 1°F (0.5°C) degree below the selected
temperature (setpoint). Heating is terminated when
setpoint is reached.
When the water temperature is above the setpoint, the
LCD will alternate “Water Temp” with “No Demand.” When
the water temperature is below the setpoint and the unit is
heating, the LCD will alternate “Water Temp” with “Heating”.
In POOL mode, default temperature setpoint is 80°F
(27°C) with a maximum temperature limit of 95°F (35°C).
In SPA mode, the default temperature setpoint is 100°F
(38°C). with a maximum temperature limit of 104°F (40°C).
Refer to "Program Menu", on page 18, to adjust pool or
spa maximum temperature limits.
Pool set 85F
Heating
Pool set 85F
Heating
Pool set 85F
Water Temp 68F
Pool set 85F
Water Temp 68F
Spa set 100F
Heating
Spa set 100F
Heating
Spa set 100F
Water Temp 68F
Spa set 100F
Water Temp 68F
Figure 10. Pool Heat and Spa Modes
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
13
Timed Spa Mode
The control is equipped with a mode which will heat the
spa to the Spa setpoint temperature for a specied period
of time selected in the TIMED SPA mode setup.
A
WARNING: If an external controller controls the spa
heating in a pool/spa system, manual adjustment of the
3-way valves may be necessary to use the TIMED SPA
feature of this heat pump. Failure to adjust the 3-way
valves properly may result in pool water overheating or
other undesirable results.
To activate the timed spa feature, press the MODE key until
“TIMED SPA” is displayed on the top line of the display.
The display will read “Up or Dn to Set”. This tells the user
to press the UP or DOWN keys to set the desired length of
time for the timed spa heating operation.
Press the UP or DOWN keys to select the desired duration
of spa heating, up to a maximum duration of 6-hours in
15-minute increments. After selection of time is completed
press MODE key to start heater operation.
The timer will start to count down from the selected period
and the unit will operate to heat the water based on the
previously selected spa setpoint temperature setting.
Once the unit turns on, the display will toggle between the
current spa water temperature and the current operating
state “Heating” and the timer.
The top row of the LCD displays the operation mode and
temperature setpoint. Timed Spa temperature setpoint
can be adjusted using the UP and DOWN keys while the
screen is displaying the Water Temperature and “Heating”
status.
To adjust the timer, press MODE key, then use the UP and
DOWN keys to increase or decrease the timer. To terminate
the timer, use DOWN key to set timer to 00:00:00.
When the TIMED SPA timer has expired, the control will
be set to OFF.
Timed Spa 100F
Up or Dn to Set
Timed Spa 100F
Up or Dn to Set
Timed Spa 100F
Heating 2:30:00
Timed Spa 100F
Heating 2:30:00
Timed Spa 100F
Water Temp 68F
Timed Spa 100F
Water Temp 68F
Figure 11. Timed Spa Mode
Pool Cool Mode - Heat/Cool Models Only
In heat/cool models, the control is equipped with a "Pool
Cool Mode" which will automatically cool the pool to the
cooling setpoint established in this mode.
The top row of the LCD displays the operation mode and
temperature setpoint. When pool cool mode is selected,
each press of the UP or DOWN key will increase /
decrease the water cooling setpoint temperature. Holding
the UP or DOWN keys down will speed up the change of
the temperature values.
In this mode, the heater is set to cool when the water
temperature is 1°F (0.5°C) degree above the selected
temperature (setpoint). Cooling is terminated when
setpoint is reached.
When the water temperature is below the setpoint, the
LCD will alternate “Water Temp” with “No Demand.” When
the water temperature is above the setpoint and the unit
is cooling, the display will alternate “Water Temp” with
“Cooling”.
In pool cool mode, default temperature setpoint is 80°F
(27°C) with a minimum temperature of 44°F (7°C) and
maximum temperature limit of 95°F (35°C). Refer to
"Program Menu", on page 18, to adjust pool maximum
temperature limits.
Pool Cool 85F
Cooling
Pool Cool 85F
Cooling
Pool Cool 85F
Water Temp 95F
Pool Cool 85F
Water Temp 95F
Figure 12. Pool Cool Mode
Pool Auto Mode - Heat/Cool Models Only
The control is equipped with a mode which will automatically
heat and cool the pool within the range of the heating
setpoint and the cooling deadband.
The top row of the LCD displays the operation mode and
temperature setpoint. When pool auto mode is selected,
each press of the UP or DOWN key will increase /
decrease the water setpoint temperature. Holding the UP
or DOWN keys down will speed up the change of the
temperature values.
In these modes, the heater is set to heat when the water
temperature is 1°F (0.5°C) degree below the selected
temperature (setpoint). Heating is terminated when
setpoint is reached. The heater is set to cool when the
water temperature is above the selected temperature
(setpoint) plus the specied cooling deadband. Cooling
is terminated when setpoint plus the cooling deadband is
reached.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
14
Example: When pool auto setpoint is set at 80°F (27°C)
and cooling deadband set at 6°F (3.5°C), the unit will
automatically heat the pool if the temperature drops below
80°F (27°C), and will automatically cool the pool if the
temperature is above 86°F (30.5°C).
In pool auto mode, default temperature setpoint is 80°F
(27°C) with a minimum temperature of 44°F (7°C) and
maximum temperature limit of 95°F (35°C). Cooling
deadband default is 6°F (3.5°C), adjustable from 2 to 10°F
(1 to 5.5°C) degrees. Refer to "Program Menu", on page
18, to adjust pool maximum temperature limits and
cooling deadband.
Pool Auto 85F
Heating
Pool Auto 85F
Heating
Pool Auto 85F
Water Temp 83F
Pool Auto 85F
Water Temp 83F
Pool Auto 85F
Cooling
Pool Auto 85F
Cooling
Pool Auto 85F
Water Temp 92F
Pool Auto 85F
Water Temp 92F
Figure 13. Pool Auto Mode
Control Lockout Mode
Prevent unauthorized access to the heater's control
settings with the "Control Lockout" feature. To activate
the lockout, press and hold the MODE and DOWN keys
simultaneously for 5-seconds. Select a three-digit PIN by
using the UP and DOWN keys to select each digit and the
MODE key to lock in the selection. Conrm your selection
and make a record of your PIN for future reference.
Control Lockout
Enter PIN 000
Conrm Lockout
Yes
Figure 14. Control Lockout
NOTE: Record this lockout code for future reference.
To unlock the controls, select the ENTER PIN menu by
pressing the MODE key followed by the UP or DOWN key.
Enter the three-digit PIN that was previously used to lock
the control. Please note that power cycling will not clear
the lockout. A successful PIN entry will display "LOCKBOX
CLEARED," whereas an incorrect PIN will result in
"INVALID PIN" being displayed.
If the user-selected PIN is lost or does not clear the
Control Lockout, you can use the Code 101 to temporary
override the lock box and then the Program Menu to SET
FACTORY DEFAULTS. This will remove the PIN and allow
normal operation, including the selection of a new PIN if
desired. Refer to the "Program Menu" section on page 16
for detailed instructions.
NOTE: If you choose to set FACTORY DEFAULTS, the
pool and spa setpoints will return to their default values
of 85°F (29°C) and 100°F (38°C), respectively, and the
maximum temperature settings for pool and spa will be
reset to 95°F (35°C) and 104°F (40°C). It will be necessary
to readjust these setpoints to your preferred settings.
Additionally, other default congurations will be restored.
Keypad Protection
After 30-minutes of inactivity, the controller will automatically
protect the keypad to avoid unintended key presses. Follow
the on-screen instructions to unlock the keypad: Press the
UP key three times, followed by the MODE key, to unlock.
11. SERVICE MENU
To access the "Service Menu" and fault history, press the
SERVICE key 1-time. The heater will continue to operate
while in the service menu.
In this mode, pressing the UP or DOWN keys will toggle
through the various information reported. Some items
("Fault History" and "Sensor Temperatures") have multiple
values. Press UP or DOWN buttons to scroll through the
additional information. The SERVICE menu may be exited
to return to the previous display be pressing the MODE
key or it will automatically be exited if no key is pressed
within 30-seconds.
Supply Voltage
The rst screen displayed is the "Supply Voltage" indicator,
which indicates the voltage supplied to the control board.
Normal readings range from 24 to 30 volts.
Brownout Detect.
230V
Supply Voltage
24V
Figure 15. Supply Voltage Indicator
Run Time Hours and Cycles
Press the DOWN key. The "Hours" run time indicates the
total hours of operation for the pool heater, as measured
by the amount of time that the compressor has been
energized. The "Cycles" count indicates the number of on/
off cycles of the heater, as measured by the number of
times the compressor has been energized.
Brownout Detect.
230V
Hours 451
Cycles
89
Figure 16. Run Time/Cycles
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
15
Faults History
Press the DOWN key. The "Fault History" displays up to ten
faults in memory. The order of the faults begins with "Last
Err", which is the most recent fault, and proceeds through
the ten most recent messages in reverse chronological
order.
Run time hours at the moment of the fault are displayed
at the end of the rst line. The second line of the display
shows the "Fault" message. If there are no faults in the
history buffer, the second line reads “All Faults Clear.”
Brownout Detect.
230V
Last Err 450
Brownout Detect.
230V
Fault 9 241
Inlet Temp Fail
Brownout
or
Brownout Detect.
230V
Last Err 0
All Faults Clear
Figure 17. Fault History
Press the Service key again to access the Advance
Service Menu.
Heat Pump Temperatures
The "In/Out Temp" screen indicates the water temperature
sensed in the inlet and at the outlet of the heater.
Brownout Detect.
230V
HPPH Temp
In 68F, Out 78F
Figure 18. Inlet and Outlet Temperature
Coil and Outdoor Temperature
Press the DOWN key. The "Coil Temp" screen indicates
the temperature sensed, displayed on the rst line. The
second line displays the temperature sensed by the
outdoor sensor.
Brownout Detect.
230V
Coil Temp
Outdoor 68F
47F
Figure 19. Coil and Outdoor Temperature
Solar Heater Temperature
(Heat/Cool Models Only)
Press the DOWN key. When enabled from "Installers
Menu", the "Solar Temperature" screen indicates the
temperature sensed with the solar heater sensor. The
"In" reading indicates the inlet of the solar heater. Solar
inlet temperature readings should come from a eld-
supplied 10K temperature sensor. Solar "Out" displays the
temperature at the outlet of the solar heater. This reading
comes from the Heat pump inlet sensor. This screen is
only displayed if the option “Solar Heating” is enabled
from "Installers Menu". For more details about solar heater
integration refer to section 13 Installers menu on page
21.
Brownout Detect.
230V
Solar Temp
In 61F, Out 68F
Figure 20. Solar Heater Temperature
Pump Status
Press the DOWN key. When enabled from "Installers
Menu", the "Pump Status" screen indicates current pump
mode and speed selection.
Pump control is compatible with Raypak Protégé Variable-
speed Pump and 4 digital outputs speed selector. By
default, "Pump Control" is disabled. See page 21 to
select and congure "Pump Control" option.
Brownout Detect.
230V
Protégé Pump
Speed2 1500 RPM
Brownout Detect.
230V
Pump Status
Speed 2
Figure 21. Pump Status
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
16
OFF mode
POOL Auto mode
Supply Voltage
Run Counters
Faults History
Inlet & Outlet
Temperatures
Pump Status
SERVICESERVICE
MODEMODE
MODEMODE
SERVICESERVICE
UPUP
DOWNDOWN
UPUP
DOWNDOWN
Pool Cool 80F
Cooling
Pool Auto 80F
Cooling
OFF 8:05PM
No Demand
OFF 8:05PM
No Demand
Pool Heat 80F
Heating
Pool Auto 80F
Heating
Protégé Pump
Speed2 1500 RPM
Protégé Pump
Speed2 1500 RPM
HPPH Temp
In 68F, Out 108F
HPPH Temp
In 68F, Out 108F
Hours 451
Cycles 89
Hours 451
Cycles 89
Supply Voltage
26V
Supply Voltage
26V
Available in some
configurations and kits
or
Last Err 0
All Faults Clear
Last Err 0
All Faults Clear
Fault 9 241
Brownout
Fault 9 241
Brownout
Last Err 450
Inlet Temp Fail
Last Err 450
Inlet Temp Fail
SPA mode
MODEMODE
Spa set 100F
Heating
Spa set 100F
Heating
POOL Cool modeAdjust
Temperature
UPUP
DOWNDOWN
Pool Cool 80F
Cooling
Pool Cool 80F
Cooling
POOL [Heat] mode
MODEMODE
Pool Heat 80F
Heating
Pool Heat 80F
Heating
OFF 8:05PM
Water Temp 68F
OFF 8:05PM
Water Temp 68F
Adjust
Temperature
UPUP
DOWNDOWN
Adjust
Temperature
UPUP
DOWNDOWN
MODEMODE
Adjust
Temperature
UPUP
DOWNDOWN
Timed SPA mode
Timed Spa 100F
Up or Dn to Set
Timed Spa 100F
Up or Dn to Set
Adjust Duration
UPUP
DOWNDOWN
Adjust
Temperature
UPUP
DOWNDOWN
Timed Spa 100F
Heating 2:30:00
Timed Spa 100F
Heating 2:30:00
MODEMODE
Options available only
in Heat/Cool models
Coil & Outdoor
Temperatures
Coil Temp 47F
Ambient Temp 68F
Coil Temp 47F
Ambient Temp 68F
Solar Heater
Temperature
Solar Temp
In 61F, Out 68F
Solar Temp
In 61F, Out 68F
Pump Status
Speed 2
Pump Status
Speed 2
SERVICESERVICE
Operations and Service Menu
Figure 22. Operation and Service Screen
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
17
12. PROGRAM MENU ( + )
To access the PROGRAM menu, press and hold SERVICE
and MODE keys simultaneously for 7 to 10 seconds until
"Language" screen appears on the display.
This menu allows to change and reset the factory default
settings, as well as providing access to the Installers and
Schedule menus. There are different features and settings
required for different model types. This section outlines
the items noted on the display in Heat Only and Heat/Cool
congurations, the default values and range of adjustable
values and a description of the feature.
Any changes to values are stored into the non-volatile
memory after selection is made using the UP or DOWN
keys. Pressing SERVICE key toggles to the next setting.
Failure to press any key for 5-minutes will cause the screen
to return to Operation mode screen. The Program mode
can also be exited by pressing the MODE key.
CAUTION: Changes to default program congurations
could affect normal functionality of the heater.
Language Selection
The initial display in PROGRAM Menus is "Language"
selection.
The UP and DOWN keys will select English, Spanish or
French language for all menus and Display messages.
Language
English
Lenguaje
Español
Langue
Français
Figure 23. Language Selection Mode
Set Factory Defaults
Press the SERVICE key again. "Set Defaults" option
is displayed. To set factory defaults, press and hold
SERVICE and MODE keys simultaneously for 3 to 5
seconds until "Defaults Set" appears. This operation
resets the operating program to its factory default values.
The pool setpoint is congured to 80°F (27°C), and the
SPA setpoints will default to 100°F (38°C). The maximum
temperature setting for pool and spa is limited to 95°F
(35°C) and 104°F (40°C), respectively. The language
is set to English, and the temperature display is set to
Fahrenheit. The cooling deadband is set to 6°F (3.5°C),
defrost temperature to 24°F (-4°C), defrost deadband
to 10°F (5.5°C) and outside lockout to 45°F (7°C),
respectively. The brownout is set to 230V, and the remote
pool mode is set to Heat. The local schedule is disabled
but not erased, and the "VS Pump Control" and other
add-ons are also disabled. Note that cooling deadband
and remote pool mode settings are only available in Heat/
Cool models.
The "Control Lockout PIN" will be cleared, and the control
will resume normal operation. See the "Control Lockout"
section on page 14.
Brownout Detect.
Set Defaults
Figure 24. Set Defaults Option
Reset Faults
Press the SERVICE key again. "Reset Faults" appears
on the digital display. To clear faults history, press and
hold SERVICE and MODE keys simultaneously for 3 to 5
seconds until "Faults Cleared" appears.
This function clears the historical fault available in
SERVICE menu.
NOTE: When the unit is connected to Wi-Fi, the historical
faults can be accessed in the timeline tab of Raymote.
Reset faults do not affect historical faults registered in
Raymote.
Brownout Detect.
Reset Faults
Figure 25. Reset Faults Option
Wi-Fi Reset
Press the SERVICE key again. "Wi-Fi Reset" appears
on the digital display. To clear stored Wi-Fi signal name
and password, press and hold SERVICE and MODE keys
simultaneously for 3 to 5 seconds until "Wi-Fi Initialized"
appears.
This operation resets the Wi-Fi credentials, leaving the unit
ready to congure connection with the Raymote app. For
details on how to connect your pool heater to Raymote,
follow the instructions on page 43.
Brownout Detect.
WiFi Reset
Figure 26. Wi-Fi Reset Option
Temperature Display
Press the SERVICE key again "Temp Display" appears
on the digital display. The UP or DOWN keys will select
"Fahrenheit" or "Celsius" on the temperature display.
Choose the desired temperature scale. After making
the selection, all temperature screens will be updated to
display degrees in either Fahrenheit or Celsius.
Temp Display
Fahrenheit
Temp Display
Celsius
Figure 27. Temperature Display Option
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
18
Spa Setpoint Maximum Adjustment
Press the SERVICE key again. "Spa Max Temp" appears
on the digital display. Using the UP and DOWN keys will
change the maximum temperature setting to your desired
value. The control can be set to limit the maximum setpoint
in the range of 65°F to 104°F (18°C to 40°C). The default
value is 104°F (40°C).
Spa Max Temp
104F
Figure 28. Spa Setpoint Maximum Adjustment Option
Pool Setpoint Maximum Adjustment
Press the SERVICE key again. "Pool Max Temp" appears
on the digital display. Using the UP and DOWN keys will
change the maximum temperature setting to your desired
value. The control can be set to limit the maximum setpoint
in the range of 65°F to 95°F (18°C to 35°C). The default
value is 95°F (35°C).
Pool Max Temp
95 F
Figure 29. Pool Setpoint Maximum Adjustment Option
Cooling Deadband Adjustment -
(Heat/Cool Models Only)
Press the SERVICE key again. "Cooling Deadband"
appears on the digital display. Using the UP and DOWN
keys will change the cooling deadband setting. In POOL
AUTO mode, the cooling setpoint is the heating setpoint
minus this cooling deadband value. This setting can be set
in the range of 2°F to 10°F degrees (1°C to 5.5°C). The
default value is 6°F (3.5°C).
Cooling Deadband
6 F
Figure 30. Cooling Deadband Adjustment Option
Remote Pool Mode -
(Heat / Cool Models Only)
Press the SERVICE key again. "Remote Pool Mode"
appears on the digital display.
When Remote mode (3-wire selector) is enabled, and
the unit is a Heat/Cool model, this setting can be used to
dene the operation mode of the “Pool” wire selector. Use
UP and DOWN keys to set Remote pool mode to Pool
Heat, Pool Cool or Pool Auto. The default value for remote
pool mode is "Heat".
Remote Pool Mode
Heat
Figure 31. Remote Pool Mode Option
Defrost Temperature Adjustment
To adjust the defrost temperature, press the SERVICE
key and select "Defrost Temp" on the digital display. Use
the UP and DOWN keys to adjust the temperature setting,
which is measured on the coil during defrost mode. The
range of available settings is 20°F to 35°F (-6.5°C to
1.5°C), with a default value of 24°F (-4°C).
Defrost Temp
24F
Figure 32. Defrost Temperature Adjustment Option
Defrost Deadband Adjustment
To adjust the defrost deadband, press the SERVICE key
and select "Defrost Deadband" on the digital display. Use
the UP and DOWN keys to adjust the deadband setting,
which determines when defrost mode ends based on
the coil temperature. The defrost cycle ends when the
coil temperature is higher than the Defrost Temperature
plus the Defrost Deadband. You can set this value in the
range of 5°F to 20°F (2.5°C to 11°C), with a default value
of 10°F (5.5°C).
Defrost Deadband
10F
Figure 33. Defrost Deadband Adjustment Option
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
19
Outside Lockout Temperature
Adjustment
To adjust the outside lockout temperature limit, press
the SERVICE key and select "Outside Lockout" on the
digital display. Use the UP and DOWN keys to set the
ambient temperature at which the unit will be locked out
of operation. This setting can be adjusted in the range of
30°F to 50°F (-1°C to 10°C), with a default value of 45°F
(7°C).
Outside Lockout
45F
Figure 34. Outside Lockout Temperature Adjustment
Brownout Detection Mode
To adjust the brownout detection mode, press the
SERVICE key and navigate to "Brownout Detect" on the
digital display. You can then use the UP and DOWN keys
to choose from three options: 230V, 208V, or Disabled.
Enabling brownout detection will cause the unit to shut
down automatically if the Transformer's 24VAC signal
drops below a certain threshold, specically below
21VAC for 230V or below 24VAC for 208V. This function is
intended to protect the unit from low voltage situations. If
you prefer not to use this feature, simply select “Disabled”.
The default setting for brownout detection is 230V.
Brownout Detect.
230V
Figure 35. Brownout Detection Mode Option
Installer Menu
To access the Installer Menu, press the SERVICE key
and select "INSTALLER Menu" on the digital display. You
can use the UP key to enter the Installer menu, or press
SERVICE to move to the next option. For more details on
the "Installer Menu", please refer to page 21.
INSTALLER Menu
UP key to Enter
Figure 36. Installer Menu Option
Schedule Menu
To access the SCHEDULE Menu, press the SERVICE
key and select "SCHEDULE Menu" on the digital display.
You can use the UP key to enter the Schedule menu and
editor, or press SERVICE to return to the beginning of the
Program menu. For more information on the "Schedule
Menu", please refer to page 25.
SCHEDULE Menu
UP key to Enter
Figure 37. Schedule Menu Option
NOTE: Disabling "Brownout Detection" limits the ability
of the heater to protect the compressor.
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
20
Program Menu Diagram
Figure 38. Program Menu
+
5 sec
PROGRAM Menu
Set Defaults
Reset Faults
Temperature Display
Max Spa Setpoint
Max Pool Setpoint
WiFi Reset
OFF Pool Spa Timed Spa
Operation Mode
MODEMODE
SERVICESERVICE MODEMODE
SERVICESERVICE
SERVICESERVICE
SERVICESERVICE
+
3 sec
SERVICESERVICE
Defaults SetDefaults Set
Faults ClearedFaults Cleared
Temp Display
Fahrenheit
Temp Display
Fahrenheit
Temp Display
Celsius
Temp Display
Celsius
Spa Max Temp
104 F
Spa Max Temp
104 F
Pool Max Temp
95 F
Pool Max Temp
95 F
WiFi ResetWiFi Reset
WiFi InitializedWiFi Initialized
Reset FaultsReset Faults
Set DefaultsSet DefaultsSet DefaultsSet DefaultsSet Defaults
Language
SERVICESERVICE
Language
English
Language
English
Lenguaje
Español
Lenguaje
Español
Langue
Français
Langue
Français
SERVICESERVICE
Select
Display
Language
UPUP
DOWNDOWN
MODEMODE
SERVICESERVICE
Set Factory
Defaults
+
3 sec
MODEMODE
SERVICESERVICE
Reset Fault
History
+
3 sec
MODEMODE
SERVICESERVICE
Clear Wi-Fi
Configuration
Select
Temperature
Scale
UPUP
DOWNDOWN
Adjust Spa
Temperature
Limit
UPUP
DOWNDOWN
Cooling Deadband
SERVICESERVICE
Cooling Deadband
6 F
Cooling Deadband
6 F
Remote Pool Mode
Remote Pool Mode
Heat
Remote Pool Mode
Heat
Select
Remote Pool
Operation
UPUP
DOWNDOWN
SERVICESERVICE
65°F - 104°F
Adjust Spa
Temperature
Limit
UPUP
DOWNDOWN
65°F - 95°F
Adjust
Cooling
Deadband
UPUP
DOWNDOWN
2°F - 10°F
Defrost Temperature
SERVICESERVICE
Defrost Temp
24 F
Defrost Temp
24 F
Adjust
Defrost
Temperature
UPUP
DOWNDOWN
20°F - 35°F
Defrost Deadband
SERVICESERVICE
Defrost Deadband
10 F
Defrost Deadband
10 F
Adjust
Defrost
Deadband
UPUP
DOWNDOWN
5°F - 20°F
Outside Lockout
SERVICESERVICE
Outside Lockout
45 F
Outside Lockout
45 F
Adjust Outside
Lockout Temp.
UPUP
DOWNDOWN
30°F - 50°F
Heat, Cool
or Auto
Brownout Detection
SERVICESERVICE
Brownout Detect.
230V
Brownout Detect.
230V
Select
Brownout
voltage option
UPUP
DOWNDOWN
230v, 208v
or Disabled
Installer Menu
SERVICESERVICE
INSTALLER Menu
UP key to Enter
INSTALLER Menu
UP key to Enter
Press UP key to
enter Installer
Menu
UPUP
Schedule Menu
SERVICESERVICE
SCHEDULE Menu
UP key to Enter
SCHEDULE Menu
UP key to Enter
Press UP key to
enter Schedule
Menu
UPUP
SERVICESERVICE
Options available only in Heat/Cool models
APPROVED
UNCONTROLLED DOCUMENT IF PRINTED
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176

Rheem TWPH-8550EHT10 Le manuel du propriétaire

Catégorie
Thermostats
Taper
Le manuel du propriétaire

dans d''autres langues