Allen-Bradley ControlLogix 1756-OV32E Installation Instructions Manual

Taper
Installation Instructions Manual
Installation Instructions
Original Instructions
ControlLogix DC Digital I/O Modules
Catalog Numbers 1756-IB16, 1756-IB16K, 1756-IB16D, 1756-IB16DK, 1756-IB16I, 1756-IB16IK, 1756-IB16IF, 1756-IB16IFK,
1756-IB16ISOE, 1756-IB16ISOEK, 1756-IB32, 1756-IB32K, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV16K, 1756-IV32,
1756-IV32K, 1756-LSC8XIB8I, 1756-LSC8XIB8IK, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16DK, 1756-OB16E, 1756-OB16EK,
1756-OB16I, 1756-OB16IEF, 1756-OB16IEFK, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OB32K, 1756-OC8, 1756-OG16,
1756-ON8, 1756-OV16E, 1756-OV32E
ControlLogix® digital I/O modules are input and output modules that provide On/Off detection and actuation. By using the producer/consumer
network model, digital I/O modules can produce information when needed while providing additional system functions.
Topic Page
Installation Requirements 5
Install the Module 5
Key the Removable Terminal Block 5
Connect Wiring 5
Assemble the RTB and the Housing 6
Install the Removable Terminal Block 6
Removable Terminal Blocks (RTB) Ratings 7
Specifications 7
Additional Resources 10
2 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
ControlLogix DC Digital I/O Modules
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or
maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code
of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
注意:在安装、配置、操作和维护本产品前,请阅读本文档以及 其他资源 部分列出的有关设备安装、配置和操作的相应文档。除了所有适用规范、法
律和标准的相关要求之外,用户还必须熟悉安装和接线说明。
安装、调整、投运、使用、组装、拆卸和维护等各项操作必须由经过适当训练的专业人员按照适用的操作规范实施。
如果未按照制造商指定的方式使用该设备,则可能会损害设备提供的保护。
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la
instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de
práctica aplicable.
Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os
usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o
código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе
«Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по
установке и прокладке соединений, а также с требованиями всех применимых норм, законов и стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с
применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
注意 : 本製品を設置、構成、稼動または保守する前に、本書および本機器の設置、設定、操作についての参考資料の該当箇所に記載されている文書に目
を通してください。ユーザは、すべての該当する条例、法律、規格の要件に加えて、設置および配線の手順に習熟している必要があります。
設置調整、運転の開始、使用、組立て、解体、保守を含む諸作業は、該当する実施規則に従って訓練を受けた適切な作業員が実行する必要があります。
本機器が製造メーカにより指定されていない方法で使用されている場合、機器により提供されている保護が損なわれる恐れがあります。
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten,
bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den
Installations- und Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit
den anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer,
configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
주의 : 본 제품 설치 , 설정 , 작동 또는 유지 보수하기 전에 본 문서를 포함하여 설치 , 설정 및 작동에 관한 참고 자료 섹션의 문서들을 반드시 읽고 숙지
십시오 . 사용자는 모든 관련 규정 , 법규 및 표준에서 요구하는 사항에 대해 반드시 설치 및 배선 지침을 숙지해야 합니다 .
설치 , 조정 , 가동 , 사용 , 조립 , 분해 , 유지보수 등 모든 작업은 관련 규정에 따라 적절한 교육을 받은 사용자를해서만 수행해야 합니다 .
본 장비를 제조사가 명시하지 않은 방법으로 사용하면 장비의 보호 기능이 손상될 수 있습니다 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”,
riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi,
codici e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun
şekilde yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
注意事項:在安裝、設定、操作或維護本產品前,請先閱讀此文件以及列於 「其他資源」章節中有關安裝、設定與操作此設備的文件。使用者必須熟悉安裝
和配線指示,並符合所有法規、法律和標準要求。
包括安裝、調整、交付使用、使用、組裝、拆卸和維護等動作都必須交由已經過適當訓練的人員進行,以符合適用的實作法規。
如果將設備用於非製造商指定的用途時,可能會造成設備所提供的保護功能受損。
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace
a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků ech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające
instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi
kodeksami, prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller
utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert,
configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in
overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 3
ControlLogix DC Digital I/O Modules
ATTENTION: Before installing, configuring, operating, or
maintaining this product, read this document and the documents
listed in the additional resources section for installing,
configuring, or operating equipment. Users should familiarize
themselves with installation and wiring instructions in addition
to requirements of all applicable codes, laws, and standards.
This equipment is certified for use only within the surrounding air
temperature range of 0…60 °C (32…140 °F). The equipment
must not be used outside of this range.
Installation, adjustments, putting into service, use, assembly,
disassembly, and maintenance shall be carried out by suitably
trained personnel in accordance with applicable code of practice.
In case of malfunction or damage, make no attempt at repair.
Return the module to the manufacturer for repair. Do not
dismantle the module.
Use only a soft dry anti-static cloth to wipe down equipment. Do
not use any cleaning agents.
IMPORTANT Any illustrations, charts, sample programs, and layout examples
that are shown in this publication are intended solely for the
purposes of example. Since there are many variables and
requirements associated with any particular installation, Rockwell
Automation® does not assume responsibility or liability for actual
use based on the examples shown in this publication.
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage Category II
applications (as defined in EN/IEC 60664-1), at altitudes up to
2000 m (6562 ft) without derating.
This equipment is not intended for use in residential
environments and may not provide adequate protection to radio
communication services in such environments.
This equipment is supplied as open-type equipment for indoor
use. It must be mounted within an enclosure that is suitably
designed for those specific environmental conditions that will be
present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the
spread of flame, complying with a flame spread rating of 5VA or
be approved for the application if nonmetallic. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information
regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
, for additional installation requirements.
NEMA Standard 250 and EN/IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic
discharge, which can cause internal damage and affect normal
operation. Follow these guidelines when you handle this
equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging
when not in use.
Removal and Insertion Under Power (RIUP)
WARNING: When you insert or remove the module while
backplane power is on, an electric arc can occur. This could cause
an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electric arcing causes excessive wear to
contacts on both the module and its mating connector. Worn
contacts can create electrical resistance that can affect module
operation.
Removable Terminal Blocks (RTB)
WARNING: When you connect or disconnect the removable
terminal block (RTB) with field-side power applied, an electric arc
can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Waste Electrical and Electronic Equipment (WEEE)
WARNING: At the end of its life, this equipment should be
collected separately from any unsorted municipal waste.
4 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
ControlLogix DC Digital I/O Modules
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous
locations.
Informations sur l'utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D,
Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on
the rating nameplate indicating the hazardous location temperature code. When combining
products within a system, the most adverse temperature code (lowest "T" number) may be used to
help determine the overall temperature code of the system. Combinations of equipment in your
system are subject to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de
température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans
un système, le code de température le plus défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au
moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area
is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been
removed or the area is known to be nonhazardous. Secure any external
connections that mate to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must be changed only in an area
known to be nonhazardous.
AVERTISSMENT: RISQUE D'EXPLOSION
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis, loquets
coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à
une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer
les piles.
European Hazardous Location Approval
The following applies to products marked , , II 3:
Such modules are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of
such equipment given in Annex II to Directive 94/9/EC. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.
The type of protection for catalog numbers 1756-IB16, 1756-IB16D, and 1756-IN16, is “Ex nA IIC T3 Gc” according to EN 60079-15.
The type of protection for the catalog numbers 1756-IB16I, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IV16, 1756-IV32, 1756-LSC8XIB8I,
1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OC8, 1756-OG16, 1756-ON8,
1756-OV16E, and 1756-OV32E is “Ex nA IIC T4 Gc” according to EN 60079-15.
Such modules as catalog numbers 1756-IB16, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-LSC8XIB8I, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, and 1756-OB32
comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO15ATEX1559X.
Such modules as catalog numbers 1756-IB16D, 1756-IB16I, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV32, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16I,
1756-OB16IS, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate
number DEMKO16ATEX1792X.
Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently
and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
Such modules can have catalog numbers followed by a “K” to indicate a conformal coating option
IEC Hazardous Location Approval
The following applies to products with IECEx certification:
Such modules are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently
and for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
The type of protection for catalog numbers 1756-IB16, 1756-IB16D, and 1756-IN16 is “Ex nA IIC T3 Gc” according to IEC 60079-15.
The type of protection for catalog numbers 1756-IB16I, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-IC16, 1756-IG16, 1756-IV16, 1756-IV32, 1756-LSC8XIB8I, 1756-OB8,
1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and
1756-OV32E is “Ex nA IIC T4 Gc” according to IEC 60079-15.
Such modules as catalog numbers 1756-IB16, 1756-IB16IF, 1756-IB16ISOE, 1756-IB32, 1756-LSC8XIB8I, 1756-OB16E, 1756-OB16IEF, 1756-OB16IEFS, and 1756-OB32
comply to Standards IEC 60079-0:2011, IEC 60079-15:2010 reference IECEx certificate number IECExUL15.0099X.
Such modules as catalog numbers 1756-IB16D, 1756-IB16I, 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV32, 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16I,
1756-OB16IS, 1756-OC8, 1756-OG16, 1756-ON8, 1756-OV16E, and 1756-OV32E comply to Standards IEC 60079-0:2011, IEC 60079-15:2010, reference IECEx certificate
number IECExUL16.0151X.
Such modules may have catalog numbers followed by a “K” to indicate a conformal coating option.
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 5
ControlLogix DC Digital I/O Modules
Installation Requirements
Before you install the module, you must complete the following steps.
1. Install a 1756 ControlLogix® chassis.
2. Install a 1756 ControlLogix power supply.
3. Installation instructions can be found in the ControlLogix
Digital I/O Modules User Manual,
publication 1756-UM058.
Install the Module
You can install or remove a module while chassis power is applied.
Slide the module into the slot in the chassis until the locking tabs click.
Key the Removable Terminal Block
Key the RTB to prevent inadvertently connecting the incorrect RTB to
your module.
1. Push the U-shaped band onto the module until the band snaps
into place.
2. Insert wedge-shaped tabs into positions on the RTB that
correspond to unkeyed module positions on the module until
they stop.
Connect Wiring
You can use an RTB or a Bulletin 1492 prewired interface module
(IFM) to connect wires to your module. If you are using an RTB, see
Recommendations for Wiring Your RTB
, to connect wires to the RTB.
IFMs are prewired before shipping.
WARNING: Special Conditions for Safe Use:
This equipment is not resistant to sunlight or other sources of
UV radiation
This equipment shall be mounted in an ATEX/IECEx Zone 2
certified enclosure with a minimum ingress protection rating
of at least IP54 (in accordance with EN/IEC 60079-15) and
used in an environment of not more than Pollution Degree 2
(as defined in EN/IEC 60664-1) when applied in Zone 2
environments. The enclosure must be accessible only by the
use of a tool.
This equipment shall be used within its specified ratings
defined by Rockwell Automation.
Secure any external connections that mate to this equipment
by using screws, sliding latches, threaded connectors, or other
means provided with this product.
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
Provision shall be made to prevent the rated voltage from
being exceeded by transient disturbances of more than 140%
of the peak rated voltage when applied in Zone 2
environments.
This equipment must be used only with ATEX/IECEx certified
Rockwell Automation backplanes.
The instructions in the user manual shall be observed.
ATTENTION: The module is designed to support removal and
insertion under power (RIUP). However, when you remove or
insert a removable terminal block (RTB) with field-side power
applied, unintended machine motion or loss of process control
can occur. Exercise extreme caution when using this feature. It is
recommended that field-side power be removed before installing
the RTB onto the module.
SHOCK HAZARD: If the RTB is installed onto the module while
the field-side power is applied, the RTB is electrically live. Do not
touch the RTB’s terminals. Failure to observe this caution may
result in personal injury.
WARNING: If you connect or disconnect wiring while the
field-side power is on, an electric arc can occur. This could cause
an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
ATTENTION: If multiple power sources are used, do not exceed
the specified isolation voltage.
Locking Tab
U-shaped
Keying Band
Wedge-shaped
Keying Tab
6 Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
ControlLogix DC Digital I/O Modules
Wire a Cage Clamp-style RTB
1. Insert the wire into the terminal.
2. Turn the screw clockwise to close the terminal on the wire.
Wire a Spring Clamp
1. Insert the screwdriver into the outer hole of the RTB.
2. Insert the wire into the open terminal and remove the
screwdriver.
Recommendations for Wiring Your RTB
We recommend that you follow these guidelines when wiring your
RTB:
Begin wiring the RTB at the bottom terminals and move up.
Use a tie to secure the wires in the strain relief (bottom) area of
the RTB.
Order and use an extended-depth housing (catalog number
1756-TBE) for applications that require heavy gauge wiring.
Assemble the RTB and the Housing
A removable housing covers the wired RTB to protect wiring
connections when the RTB is seated on the module.
1. Align the grooves at the bottom of each side of the housing
with the side edges of the RTB.
2. Slide the RTB into the housing until it snaps into place.
Install the Removable Terminal Block
Follow these steps to install the RTB onto the module to connect the
wiring.
Before installing the RTB, verify the following:
Field-side wiring of the RTB is complete.
The RTB housing is snapped into place on the RTB.
The RTB housing door is closed.
The locking tab at the top of the module is unlocked.
1. Align the top, bottom, and left side guides of the RTB with the
guides on the module.
2. Press quickly and evenly to seat the RTB on the module until
the latches snap into place.
3. Slide the locking tab down to lock the RTB onto the module.
ATTENTION: When using catalog numbe1756-TBNH, do not wire
more than two 0.33…1.3 mm
2
(22…16 AWG) conductors on
any terminal. Use only the same size wires with no intermixing of
solid and stranded wire types.
When using the 1756-TBCH, 1756-TBS6H, or the 1756-TBSH, do
not wire more than one 0.33…2.1 mm
2
(22…14 AWG)
conductor on any terminal.
ATTENTION: The ControlLogix system has been agency certified
using only the ControlLogix RTBs. Any application that requires
agency certification of the ControlLogix system by using other
wiring termination methods may require application-specific
approval by the certifying agency.
IMPORTANT If additional wire routing space is required for your application,
use the extended-depth housing, catalog number 1756-TBE.
IMPORTANT The housings that are shown are used with a spring clamp RTB,
but the capacity for each remains the same regardless of RTB type.
WARNING: When you connect or disconnect the removable
terminal block (RTB) with field-side power applied, an electric arc
can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 7
ControlLogix DC Digital I/O Modules
Removable Terminal Blocks (RTB) Ratings
Specifications
Module Catalog Number
RTB Catalog
Number
RTB Type Torque and Wire Size (Where Applicable)
1756-IB16, 1756-IB16K
1756-IC16
1756-IG16
1756-IN16
1756-IV16, 1756-IV16K
1756-OB8
1756-OB16E, 1756-OB16EK
1756-OC8
1756-OG16
1756-ON8
1756-OV16E
1756-TBNH
NEMA
screw-clamp
removable block
20 pin
1.36 N•m (12 lb•in)
Single wire connection: 0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater,
1.2 mm (3/64 in.) insulation max
Double wire connection: 0.33…1.3 mm
2
(22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
greater, 1.2 mm (3/64 in.) insulation max
Do not wire more than two conductors on any terminal.
1756-TBSH
Spring-clamp
removable
terminal block
with standard
housing
20 pin
Single wire connection: 0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
greater, 1.2 mm (3/64 in.) insulation max
Do not wire multiple conductors on any terminal.
1756-IB16D, 1756-IB16DK
1756-IB16I, 1756-IB16IK
1756-IB16IF, 1756-IB16IFK
1756-IB16ISOE, 1756-IB16ISOEK
1756-IB32, 1756-IB32K
1756-IV32, 1756-IV32K
1756-LSC8XIB8I, 1756-LSC8XIB8IK
1756-OB8EI
1756-OB16D, 1756-OB16DK
1756-OB16I
1756-OB16IEF, 1756-OB16IEFK
1756-OB16IEFS
1756-OB16IS
1756-OB32, 1756-OB32K
1756-OV32E
1756-TBCH
Cage-clamp
removable
terminal block
with standard
housing
36 pin
0.5 N•m (4.4 lb•in)
Single wire connection: 0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater,
1.2 mm (3/64 in.) insulation max
Do not wire multiple conductors on any terminal.
1756-TBS6H
Spring-clamp
removable
terminal block
with standard
housing
36 pin
Single wire connection: 0.33…2.1 mm
2
(22…14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or
greater, 1.2 mm (3/64 in.) insulation max
Do not wire multiple conductors on any terminal.
- 1756-TBE
Extended-depth
terminal block
housing
-
Specifications: 1756-IB16, 1756-IB16K, 1756-IB16D, 1756-IB16DK, 1756-IB16I, 1756-IB16IK, 1756-IB16IF, 1756-IB16IFK, 1756-IB16ISOE,
1756-IB16ISOEK, 1756-IB32, 1756-IB32K
Attribute
1756-IB16,
1756-IB16K
1756-IB16D,
1756-IB16DK
1756-IB16I,
1756-IB16IK
1756-IB16IF,
1756-IB16IFK
1756-IB16ISOE,
1756-IB16ISOEK
1756-IB32,
1756-IB32K
Voltage and current ratings
Backplane: 5.1V DC,
100 mA, 24V DC, 2 mA
Inputs: 10…31.2V DC,
10 mA
Backplane: 5.1V DC,
150 mA, 24V DC, 3 mA
Inputs: 10…30V DC,
13 mA max
Backplane: 5.1V DC,
135 mA, 24V DC, 3 mA
Inputs: 10…30V DC,
10 mA max
Backplane: 5.1V DC,
275 mA, 24V DC, 3 mA
Inputs: 10…30V DC,
5 mA max
Backplane: 5.1V DC,
320 mA, 24V DC, 2 mA
Input: 10…55V DC,
5.1 mA
Backplane: 5.1V DC,
120 mA, 24V DC, 2 mA
Inputs: 10…31.2V
DC, 5.5 mA
Temperature, operating
IEC 60068-2-1(Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Isolation voltage
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
250 V (continuous),
basic insulation type,
input group-to group
No isolation between
individual group
inputs
250V (continuous),
basic insulation type,
inputs-to-backplane,
and input
group-to-group
No isolation between
individual group
inputs
250V (continuous),
basic insulation type,
inputs-to-backplane,
and input-to-input
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
250V (continuous),
basic insulation type,
input-to-input
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
125V (continuous),
basic insulation type,
input-to-input
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
250V (continuous),
basic insulation type,
input group-to-group
No isolation between
individual group
inputs
North American temp code T3C T4 T4 A T4
ATEX temp code T3 T4
IECEx temp code T3 T4
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 8
ControlLogix DC Digital I/O Modules
Specifications: 1756-IC16, 1756-IG16, 1756-IN16, 1756-IV16, 1756-IV16K, 1756-IV32, 1756-IV32K, 1756-LSC8XIB8I, 1756-LSC8XIB8IK
Attribute 1756-IC16 1756-IG16 1756-IN16
1756-IV16,
1756-IV16K
1756-IV32,
1756-IV32K
1756-LSC8XIB8I,
1756-LSC8XIB8IK
Voltage and current ratings
Backplane: 5.1V DC,
135 mA, 24V DC, 3 mA
Inputs: 30…55V DC,
7 mA (60°C), and
30…60V DC, 7 mA
(55°C)
Backplane: 5.1V DC,
140 mA, 24V DC, 2 mA
Inputs: 0-5.5V DC, 4.1
mA (source)
Supply: 4.5-5.5V DC
160 mA
Backplane: 5.1V DC,
135 mA, 24V DC, 2 mA
Inputs: 10...30V AC,
50-60Hz, 25 mA
Backplane: 5.1V DC,
110 mA, 24V DC, 2 mA
Inputs: 10...30V
DC,1.5-10 mA/pin
(input)
Backplane: 5.1V DC,
175 mA, 24V DC, 2 mA
Inputs: 10...30V
DC,1.5-5 mA/pin
(input)
Backplane: 5.1V DC,
275 mA, 24V DC, 3 mA
Inputs: 10…30V DC,
5 mA max
Temperature, operating
IEC 60068-2-1(Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Isolation voltage
250V (continuous),
basic insulation type,
inputs-to-backplane
125V (continuous)
basic insulation type,
input group-to-group
No isolation between
individual group
inputs
250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group
No Isolation between individual group inputs
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
250V (continuous),
basic insulation type,
input-to-input
North American temp code T4 T5 T3 C T4 A
ATEX temp code T4 T3 T4
IECEx temp code T4 T3 T4
Specifications: 1756-OB8, 1756-OB8EI, 1756-OB16D, 1756-OB16DK, 1756-OB16E, 1756-OB16EK, 1756-OB16I, 1756-OB16IEF, 1756-OB16IEFK
Attribute 1756-OB8 1756-OB8EI
1756-OB16D,
1756-OB16DK
1756-OB16E,
1756-OB16EK
1756-OB16I
1756-OB16IEF,
1756-OB16IEFK
Voltage and current ratings
Backplane: 5.1V DC,
165 mA, 24V DC, 2 mA
Output: 10…30V DC, 2 A
Pilot Duty (DC-13/SQ)
MDL: 8 A (60°C)
Backplane: 5.1V DC,
250 mA, 24V DC, 2 mA
Output: 10…30V DC, 2 A
Pilot Duty (DC-13/SQ)
MDL: 10 A/16 A 60°/55°C
Backplane: 5.1V DC,
250 mA, 24V DC, 140 mA
Output: 19.2…30V DC,
2 A Pilot Duty (DC-13SQ)
2 A/1 A 30°/60°C
MDL: 8 A/4 A 30°/60°C
Backplane: 5.1V DC,
250 mA, 24V DC, 2 mA
Output: 10…31.2V
DC, 1 A, 2 A Inrush
MDL OUT: 8 A max
(60°C)
Backplane: 5.1V DC,
350 mA, 24V DC, 2.5 mA
Output: 10...30V DC, 2 A
Pilot Duty (DC-13/SQ)
Backplane: 5.1V DC,
320 mA, 24V DC, 3 mA
Outputs: 10...30V DC,
1 A max, 60 °C (140 °F)
10…30V DC, 2 A,
45 °C (113 °F) per
channel (4 channels
max)
Temperature, operating
IEC 60068-2-1(Test Ad,
Operating Cold)
IEC 60068-2-2 (Test Bd,
Operating Dry Heat)
IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Temperature, surrounding air,
max
60 °C (140 °F)
Enclosure type rating None (open-style)
Isolation voltage
250V (continuous), basic
insulation type,
outputs-to-backplane,
and output
group-to-group
No isolation between
individual group outputs
250V (continuous), basic
insulation type
outputs-to-backplane,
and output-to-output
250V (continuous), basic insulation type,
outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
250V (continuous), basic
insulation type,
outputs-to-backplane
125V (continuous), basic
insulation type,
output-to-output
250V (continuous),
reinforced insulation
type,
outputs-to-backplane
250V (continuous),
basic insulation type,
output-to-output
North American temp code T4 A T4 T4 A T4
ATEX temp code T4
IECEx temp code T4
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017 9
ControlLogix DC Digital I/O Modules
Specifications: 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OB32K, 1756-OC8, 1756-OG16, 1756-ON8
Attribute 1756-OB16IEFS 1756-OB16IS
1756-OB32,
1756-OB32K
1756-OC8 1756-OG16 1756-ON8
Voltage and current ratings
Backplane: 5.1V DC,
320 mA, 24V DC, 3 mA
Outputs: 10...30V DC, 1 A
max, 60 °C (140 °F),
10…30V DC, 2 A 45 °C
(113 °F) per channel
(4 channels max)
Backplane: 5.1V DC,
350 mA, 24V DC, 2.5 mA
Output: 10…30V DC,
2 A
Pilot Duty (DC-13/SQ)
Backplane: 5.1V DC,
300 mA, 24V DC, 2 mA
Output: 10…31.2V DC,
500 mA current per
channel, 50 °C (122 °F)
350 mA, 60 °C (140 °F),
1 A inrush 16 A
maximum current per
module 50 °C (122 °F)
10 A, 60 °C (140 °F)
Backplane: 5.1V DC,
165 mA, 24V DC, 2 mA
Output: 30 …60V DC,
2A Pilot Duty
(DC-13/SQ)
MDL: 8 A (60 °C)
Backplane: 5.1V DC,
210 mA, 24V DC, 2 mA
Output: 4.5-5.5V DC,
24 mA
User Supply: 5.5V DC,
384 mA, 60 °C
Backplane: 5.1V DC,
200 mA, 24V DC, 2 mA
Output: 10…30V AC,
50/60Hz 2A Pilot Duty
MDL: 5 A/4 A 30°/60°C
Temperature, operating
IEC 60068-2-1(Test Ad,
Operating Cold)
IEC 60068-2-2 (Test Bd,
Operating Dry Heat)
IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Isolation voltage
250V (continuous),
reinforced insulation
type, outputs-
to-backplane
250V (continuous), basic
insulation type,
output-to-output
250V (continuous), basic
insulation type,
outputs-to-backplane,
and output-to-output
250V (continuous),
reinforced insulation
type,
inputs-to-backplane
250V (continuous),
basic insulation type,
input group-to-group
No isolation between
individual group inputs
250V (continuous), basic insulation type, outputs-to-backplane, and output
group-to-group
No isolation between individual group outputs
North American temp code T4 T4A T3C T4 T4A
ATEX temp code T4
IECEx temp code T4
Specifications: 1756-OV16E, 1756-OV32E
Attribute 1756-OV16E 1756-OV32E
Voltage and current ratings
Backplane: 5.1V DC, 210 mA, 24V DC, 2 mA
Output: 10...30V DC, SINK OUTPUT 1A Pilot Duty (DC-13/SR)
MDL OUT: 8 A max
Backplane: 5.1V DC, 390 mA, 24V DC, 2 mA
Output: 10...30V DC, 350 mA, 60°C, 500 mA, 50°C Pilot Duty (DC-13/SS)
Group: 5 A/8 A 60°/50°C
Temperature, operating
IEC 60068-2-1(Test Ad, Operating
Cold)
IEC 60068-2-2 (Test Bd, Operating
Dry Heat)
IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Temperature, surrounding air, max 60 °C (140 °F)
Enclosure type rating None (open-style)
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
No isolation between individual group outputs
North American temp code T4
ATEX temp code T4
IECEx temp code T4
Allen-Bradley, Rockwell Automation, Rockwell Software, and ControlLogix are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
.
Publication 1756-IN062A-EN-P - August 2017 PN-460539
Supersedes Publication 1756-PC021B-EN-P - July 2017 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Additional Resources
These resources contain information about related products from Rockwell Automation.
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and
Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download
Center (PCDC)
Get help determining how products interact, check
features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
Resource Description
ControlLogix I/O Modules Specifications Technical Data, publication 1756-TD002 Provides specifications, wiring diagrams, and schematics for ControlLogix I/O modules.
ControlLogix Digital I/O Modules User Manual, publication 1756-UM058
Provides installation, configuration, operation, and maintenance information for ControlLogix
digital I/O modules.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Allen-Bradley ControlLogix 1756-OV32E Installation Instructions Manual

Taper
Installation Instructions Manual

dans d''autres langues