KitchenAid W101871170D Manuel utilisateur

Taper
Manuel utilisateur

Ce manuel convient également à

30" (76.2 CM) AND 36" (91.4 CM)
RETRACTABLE (POP-UP) DOWNDRAFT
VENT SYSTEM
Installation Instructions and Use & Care Guide
SYSTÈME DE VENTILATION RÉTRACTABLE
(CLAPET) DE 30" (76,2 CM) ET 36" (91,4 CM) -
ASPIRATION PAR LE BAS
Instructions d’installation et Guide d’utilisation et d’entretien
Table of Contents/Table des matières.............................................................................2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
W10187117D
2
TABLE OF CONTENTS
VENT SYSTEM SAFETY..............................................................................3
INSTALLATION REQUIREMENTS .............................................................4
Tools and Parts......................................................................................... 4
Location Requirements.............................................................................4
Electrical Requirements............................................................................7
Venting Requirements ..............................................................................7
INSTALLATION INSTRUCTIONS
INTERIOR-MOUNTED VENT MOTOR.......................................................8
Venting Methods.......................................................................................8
Install Vent System ...................................................................................9
Rear Mounting - Blower Motor...............................................................13
Complete Installation ..............................................................................14
Make Electrical Connections ..................................................................15
Check Operation.....................................................................................16
INSTALLATION INSTRUCTIONS
EXTERIOR-MOUNTED VENT MOTOR....................................................16
Venting Methods.....................................................................................16
Install Vent System .................................................................................17
Complete Installation ..............................................................................19
Electrical Connection..............................................................................20
Check Operation.....................................................................................21
VENT SYSTEM USE ..................................................................................22
Operating Downdraft Vent......................................................................22
VENT SYSTEM CARE................................................................................22
Surface of Downdraft Vent .....................................................................22
Filters.......................................................................................................22
WIRING DIAGRAM ....................................................................................23
ASSISTANCE OR SERVICE......................................................................24
In the U.S.A.............................................................................................24
In Canada................................................................................................24
Accessories.............................................................................................24
WARRANTY ...............................................................................................25
TABLE DES MATIÈRES
SÉCURITÉ DE SYSTÈM DE VENTILATION RÉTRACTABLE
ASPIRATION PAR LE BAS ...................................................................... 27
EXIGENCES D'INSTALLATION................................................................ 29
Outillage et pièces .................................................................................. 29
Exigences d'emplacement ..................................................................... 29
Spécifications électriques....................................................................... 32
Exigences concernant l'évacuation........................................................ 32
INSTRUCTIONS D'INSTALLATION
VENTILATEUR MONTÉ À L'INTÉRIEUR................................................. 33
Méthodes d'extraction............................................................................ 33
Installation du système d’extraction....................................................... 34
Montage du ventilateur à l'arrière........................................................... 38
Achever l'installation............................................................................... 40
Raccordements électriques.................................................................... 40
Contrôle du fonctionnement................................................................... 41
INSTRUCTIONS D'INSTALLATION
VENTILATEUR MONTÉ À L'EXTÉRIEUR................................................ 42
Méthodes d’extraction............................................................................ 42
Installation du système d’extraction....................................................... 43
Achever l'installation............................................................................... 45
Raccordement électrique ....................................................................... 45
Contrôle du fonctionnement................................................................... 46
UTILISATION DU SYSTÈME D'EXTRACTION........................................ 47
Utilisation du système d'extraction........................................................ 47
ENTRETIEN DU SYSTÈME D'EXTRACTION .......................................... 48
Surface du système d'extraction ........................................................... 48
Filtres....................................................................................................... 48
SCHÉMA DE CÂBLAGE............................................................................ 49
ASSISTANCE OU SERVICE...................................................................... 50
Aux États-Unis........................................................................................ 50
Au Canada .............................................................................................. 50
Accessoires............................................................................................. 50
GARANTIE.................................................................................................. 51
3
VENT SYSTEM SAFETY
You can be killed or seriously injured if you don't immediately
You
can be killed or seriously injured if you don't
follow
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
follow instructions.
instructions.
DANGER
WARNING
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
Ducted fans must always be vented outdoors.
CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flambé).
Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING:
a
SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
NEVER PICK UP A FLAMING PAN - you may be burned.
DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started.
– The fire department is being called.
– You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
4
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools Needed
Jigsaw or keyhole saw
Drill
¹⁄₈" (3 mm) drill bit for pilot holes
Pencil
Tape measure or ruler
Flat-blade screwdriver
Phillips screwdriver
³⁄₈" (9.5 mm) nut driver or ratchet
Level
Pliers
Metal snips
Wire stripper or utility knife
Caulking gun and weatherproof caulking compound
Vent clamps
Parts Supplied
Other Parts Supplied
Bag of fasteners (1)
Metal cover (1)
Optional support and 2 screws (36" [91.4 cm] models only)
6" diameter backdraft damper
Parts Needed
Two UL listed or CSA approved ½" (12.7 mm) conduit
connectors. Three are required for exterior-mounted blower.
Wall cap for interior-mounted motor (1)
Vent system
Home power supply cable
UL listed wire connectors (4)
Wiring cable for optional remote blower kit.
Location Requirements
NOTE: Downdraft vent is installed directly behind the cooktop.
Install the downdraft vent first, then install the cooktop.
IMPORTANT: Observe all governing codes and ordinances.
Have a qualified technician install the downdraft vent. It is the
installer’s responsibility to comply with installation clearances
specified on the model/serial rating plate. The model/serial
rating plate is located on the front of the downdraft vent above
the terminal box cover.
Downdraft vent location should be away from strong draft
areas, such as windows, doors, and strong heating vents or
fans.
Cabinet opening dimensions that are shown must be used.
Given dimensions provide minimum clearance.
Consult the cooktop manufacturer installation instructions
before making any cutouts.
Check that the downdraft vent and cooktop location will
clear the cabinet walls, backsplash, and rear wall studs
inside the cabinet.
Check for the minimum distance between the front edge
of the countertop and the front edge of the cooktop. The
minimum horizontal distance between the overhead
cabinets is the same as the width of the installed
downdraft vent.
All openings in ceiling and wall where the downdraft vent will
be installed must be sealed.
Grounded electrical outlet is required. See “Electrical
Requirements” section.
When installing the downdraft vent, the cabinet drawer will
need to be removed and the drawer front installed
permanently to the cabinet.
Cabinet Construction:
Downdraft vent is designed for use in a cabinet with a depth of
24" (61 cm). Some installations require a countertop deeper than
25" (63.5 cm). See the Countertop Cutout Dimensions chart.
The maximum depth of the overhead cabinet is 13" (33 cm).
Overhead cabinets installed at either side of the downdraft vent
must be 18" (45.7 cm) above the cooking surface.
For Mobile Home Installations
The installation of this downdraft vent must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A*, or latest edition, or with local
codes.
A. Top trim (1)
B. End caps (2)
C. Overcounter support brackets (2)
D. Lower support legs (2)
E. Undercounter mounting brackets (2)
A
B
C
D
E
5
Product Dimensions
Cabinet Dimensions
Interior-mounted blower motor model Exterior-mounted blower motor model
NOTES:
See cooktop manufacturer’s instructions for cooktop cutout
depth and width.
Use dimensions for vent system cutout location that applies
to your installation.
Interior mounted blower systems connect with 6" (15.2 cm)
round vent. The cutout locations for this vent system will
depend on your specific installation.
NOTES:
See cooktop manufacturers instructions for cooktop cutout
depth and width.
Exterior-mounted blower systems connect with 10" (25.4 cm)
round vent. The cutout locations for this vent system will
depend upon your specific installation.
Top trim widths:
30¹⁄₄" (76.8 cm) for 30" (76.2 cm) vent
36¹⁄₄" (92.1 cm) for 36" (91.4 cm) vent
13¹⁄₂" (34.3 cm)
retractable
vent height
27" (68.6 cm) for 30" (76.2 cm) vent
33" (83.8 cm) for 36" (91.4 cm) vent
13" (33.0 cm)
9¹⁄₄"
(23.5 cm)
³⁄₄"
(1.9 cm)
2¹⁄₈" (5.4 cm)
28³⁄₄"
(73.0 cm)
³⁄₈" (0.95 cm)
1¹⁄₂" (3.8 cm)
13" (33.0 cm)
Interior-mounted blower motor model
Exterior-mounted blower motor model -
used with Part Number KPEC992M
¹⁄₄" (0.6 cm)
13" (33.0 cm)
6¹⁄₂"
(16.5 cm)
10" (25.4 cm)
diameter
vent collar
13" (33.0 cm)
6¹⁄₂"
(16.5 cm)
³⁄₄" (1.9 cm)
Terminal box cover
6" (15.2 cm)
diameter
vent collar
A= ¹⁄₂" (12.7 mm)
minimum
21⁄₁₆"
(54.1 cm)
All cutouts are
for 6" (15.2 cm)
diameter vent
system.
Centerline of cooktop cutout
23³⁄₄"
(60.3 cm)
21⁄₁₆"
(54.1 cm)
Locate power
supply junction
box at lower
left hand
rear corner
of the cabinet.
7⁵⁄₈" (19.4 cm)
¹⁄₂" (12.7 mm)
minimum
Locate power
supply junction
box at lower
left hand
rear corner
of the cabinet.
6
Countertop Cutout Dimensions
IMPORTANT: Countertops with a bull-nosed front edge are not recommended for these installations.
Some models require a countertop deeper than 25" (63.5 cm); see the following Countertop Cutout Dimensions Chart.
To avoid mistakes, it is recommended that the cooktop and vent cutouts be drawn on the countertop before making any cutouts.
See Cooktop Installation Instructions for complete cutout dimensions, location dimensions and installation details.
Countertop Cutout Dimensions Chart
A. Downdraft vent
B. Cooktop
C. Measurement of cooktop rear overhang.
D. D = Measurement of cooktop rear overhang (C) + 1
¹³⁄₁₆
" [46.2 mm] (E)
E. 1
¹³⁄₁₆
" (46.2 mm)
F. ½" (12.7 mm) minimum
G. ¼" (6.4 mm) minimum
H. Countertop and backsplash
I. ½" (12.7 mm) minimum
A. ½" (12.7 mm) minimum to backsplash or rear wall
B.
³⁄₄
" (19.1 mm) maximum backsplash depth
C. 27
¹⁄₂
" (69.9 cm) on 30" (76.2 cm) models
33
¹⁄₂
" (85.9 cm) on 36" (91.4 cm) models
D. D = Measurement of cooktop rear overhang +
1
¹³⁄₁
" (46.2 mm)
A
B
C
E
H
D
I
G
F
A
B
C
D
7
Electrical Requirements
IMPORTANT: Observe all governing codes and ordinances. Save
Installation Instructions for electrical inspector’s use.
It is the customer’s responsibility to contact a qualified electrical
installer, and to ensure that the electrical installation is adequate
and in conformance with National Electrical Code, ANSI/NFPA 70
(latest edition), or CSA Standards C22.1-94, Canadian Electrical
Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local
codes and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
This fan is suitable for use with solid state speed controls.
A 120 Volt, 60 Hz., AC only 15-amp fused, electrical circuit is
required.
Check with a qualified electrician if you are not sure the
downdraft vent is properly grounded.
The downdraft vent must be connected with copper wire only.
The downdraft vent should be connected directly to the circuit
breaker (or fused disconnect) box through flexible armored or
nonmetallic sheathed copper cable. Allow some slack in the
cable so the downdraft vent can be moved if servicing is ever
necessary.
Wire sizes (copper wire only) and connections must conform
with the rating of the appliance as specified on the model/
serial rating plate located on the front of the downdraft vent
above the wiring box cover.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22.1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
Two UL listed or CSA approved ½" (12.7 mm) conduit
connectors (Three are required if the exterior-mounted vent
motor is used.)
A wiring diagram is located on the downdraft vent base above
the power control board cover.
Venting Requirements
IMPORTANT: Make sure there is proper clearance within the wall
or floor before making exhaust vent cutouts.
Use heavy (rigid) metal vent.
Venting system must terminate to the outside.
Do not terminate the vent system in an attic or other enclosed
area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Do not install 2 elbows together.
Do not use plastic or metal foil vent.
The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
Use no more than three 90° elbows
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than one elbow is used.
Use clamps to seal all joints in the vent system.
Use caulking tape to seal the exterior wall or floor opening
around cap.
Do not cut joist or stud. If vent cutout falls over a joist or stud,
a supporting frame must be constructed.
Flexible metal vent is not recommended. If it is used, calculate
each foot of flexible vent as 2 ft (0.6 m) of rigid metal vent.
Flexible elbows count twice as much as standard elbows.
Recommended vent system length:
For either interior-mounted or exterior-mounted blower
installations, the vent system length should not exceed the
maximum lengths listed in the Maximum Length of Vent System
chart. See “Calculating Vent System Length” in the “Venting
Methods” section in the Installation Instructions for the interior- or
exterior-mounted vent motor.
8
INSTALLATION INSTRUCTIONS
INTERIOR-MOUNTED VENT MOTOR
Venting Methods
Determine which venting method is best for your application.
Vent system can terminate either through the wall or floor.
Island location
NOTE: For island locations, the blower motor can be mounted for
right, left, or rear venting if needed for your application. Most
island applications would still require the venting to be directed
down through the floor.
Built-in cabinet locations
Island Location
Vent system installed under a concrete slab using PVC
sewer pipe.
Front (Standard) Mounted Blower Motor
Rear Mounted Blower Motor
Calculating Vent System Length
It is recommended that you use round vent instead of rectangular
vent, especially if elbows are required. If rectangular vent is
required, it should be transitioned to 6" (25.4 cm) round vent as
soon as possible.
Front (standard) mounted
blower motor
Rear mounted blower motor
A. Down vent
A. Down vent
B. Rear vent
C. Left vent
D. Right vent
A
A
B
C
D
A
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round metal vent
F. 6" (15.2 cm) round PVC coupling
G. Concrete slab
H. 6" (15.2 cm) round PVC sewer pipe
I. 6" (15.2 cm) round 90° PVC sewer pipe elbow
J. Tightly pack gravel or sand completely around pipe.
K. 6" (15.2 cm) round 90° PVC sewer pipe elbow
L. 6" (15.2 cm) round PVC coupling
M. 12" (30.5 cm) minimum
A
B
C
D
E
F
G
H
I
J
K
L
M
A
B
C
D
E
F
G
H
I
J
K
L
M
9
Maximum Length of Vent System
To calculate the length of the system you need, add the equivalent
feet (meters) for each vent piece used in the system.
Example Vent System
The following example falls within the maximum vent length of
35 ft (8.9 m).
Install Vent System
1. Place cardboard or similar material on top of a flat surface
where you can easily assemble the downdraft vent system.
2. Remove parts packages, downdraft vent and blower box from
the carton.
3. Remove all shipping materials, tape and film from the
downdraft vent and blower box.
4. Remove screws from each side of the vent. Attach the left and
right side overcounter support brackets to the downdraft vent
and push up to align the screw holes. Use screws to secure
the brackets.
5. Attach the left and right side end caps to the downdraft vent.
Place the end cap upon the overcounter support, slide the tab
into the slot and snap into place over the plastic tabs.
Vent Length
6" (15.2 cm) round 35 ft (8.9 m)
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) 35 ft (8.9 m)
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft
(0.8 m)
90° elbow 5.0 ft
(1.5 m)
6" (15.2 cm)
wall cap
0.0 ft
(0.0 m)
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) transition
4.5 ft
(1.4 m)
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) transition
1 ft
(0.3 m)
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) 90° elbow
transition
5.0 ft
(1.5 m)
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) 90° elbow
transition
5.0 ft
(1.5 m)
A. Blower motor
B. Transition
C. 90° elbows
D. 6" backdraft damper (supplied)
A
B
C
6 ft
(1.8 m)
2 ft (0.6 m)
D
2 - 90° elbow = 10.0 ft (3 m)
1 - wall cap = 0.0 ft (0.0 m)
8 ft (2.4 m) straight = 8.0 ft (2.4 m)
Transition = 4.5 ft (1.4 cm)
Length of 6" (15.2 cm) system = 22.5 ft (6.8 m)
A. Overcounter support bracket
B. Blower motor box
C. Overcounter support bracket screw
A. End cap
WARNING
Excessive Weight Hazard
Use two or more people to move and install
downdraft vent.
Failure to do so can result in back or other injury.
A
B
C
A
10
6. Attach support legs to the side of the downdraft vent with
2 screws in each leg. Do not tighten screws.
7. Using 2 or more people, insert the downdraft vent into the
countertop cutout. Check that downdraft vent is parallel to
side of cutout and that mounting brackets overlap countertop.
8. Move support legs down against cabinet floor. Place a level
against the front of the downdraft vent base and adjust until
downdraft vent is level vertically. Use a pencil to mark the top
of each leg on the downdraft vent and the location of the
support leg mounting holes on the cabinet floor.
9. Remove downdraft vent from cutout. Drill starter holes at each
mounting screw location on the cabinet floor. Align top of legs
with pencil marks on the face of the downdraft vent. Tighten
screws in legs.
Determine which direction is best for your installation.
When installed in a cabinet, vent system can exhaust through the
bottom, right, left or rear of the cabinet.
Bottom venting:
Downdraft vent is shipped with blower in down venting
position so no modification is required. See “Complete
Installation - Interior Mounted Motor” section.
Left or right venting:
1. Loosen the 2 hex/slotted head screws that attach the top
bracket that secures the motor to the vent box enough to slide
the bracket into the “Z” slots. This will move the bracket away
from the top mounting lip of the blower box and allow it to tilt
away from the vent box panel.
2. Lift up the blower box from the bottom mounting channel.
3. Rotate it 90 degrees to the left or right so that the vent blower
damper is repositioned in the direction needed. Do not twist or
bind the wires or disconnect the wiring from the blower.
4. Place the bottom tab of the blower box into the bottom
mounting channel.
A. Blower motor box
B. Support leg
A. Level
B. Mark locations.
A
B
B
A
A. Bracket with “Z” slots
B. Hex/slotted head screws (2)
A. Blower box
B. Bottom mounting channel
A. Blower box
B. Bottom mounting channel
B
A
B
A
B
A
B
11
5. Tilt blower box top tab so it is flush with the vent box panel
and position it under the top mounting bracket. Slide bracket
in the “Z” slots and tighten the 2 hex/slotted head screws to
secure.
6. See “Complete Installation - Interior Mounted Motor” section.
Rear Venting:
1. Remove the vent box. Loosen the 2 hex/slotted head screws
that attach the top bracket that secures the motor to the vent
box enough to slide the bracket into the “Z” slots. This will
move the bracket away from the top mounting lip of the
blower box and allow it to tilt away from the vent box panel.
2. Lift up the blower box from the bottom mounting channel and
set aside.
3. Disconnect the wire connector from the blower motor.
4. Remove the 2 screws that mount the motor mounting bracket
to the vent box. Remove the blower motor and mounting
bracket assembly from the vent box.
5. Remove the 4 screws from the small cover plate on the rear of
the vent chamber and set screws and cover plate aside.
6. Install blower motor and mounting bracket assembly to the
bracket just below the downdraft tower motor. The blower
exhaust opening should fit through the hole in the large cover
plate on the opposite side of the vent chamber where the
small cover plate was removed. Replace the 2 blower motor
mounting bracket screws and tighten.
A. Bracket with “Z” slots
B. Hex/slotted head screws (2)
A. Blower box
B. Bottom mounting channel
B
A
B
A
B
A. Blower motor
B. Wire connector
A. Blower motor mounting bracket screws (2)
A. Downdraft tower motor
B. Large cover plate
C. Blower exhaust opening
A
B
A
A
A
B
C
12
7. Plug in the wire connector to the blower motor.
8. Place the vent extension for the 6" (15.2 cm) diameter venting
over the vent exhaust and screw into place using the 4
screws.
9. Replace the vent box over the blower motor.
10. Place the bottom tab of the blower box into the bottom
mounting channel.
11. Tilt blower box top tab so it is flush with the vent box panel
and position it under the top mounting bracket.
12. Slide bracket into the “Z” slots.
13. Tighten the 2 hex/slotted head screws to secure.
14. Place the small vent cover over the hole in the vent box and
secure in place with the 4 screws.
15. See “Complete Installation - Interior Mounted Motor” section.
A. Blower motor
B. Wire connector
A. Vent extension screws (4)
A. Blower motor
B. Vent box
A
B
A
A
A
B
A. Blower box
B. Bottom mounting channel
A
B
13
Rear Mounting - Blower Motor
NOTE: Optional blower motor mounting position (opposite side).
The blower motor box assembly can also be moved to the
opposite side (rear) of the vent box.
1. Loosen the 2 hex/slotted head screws that attach the top
bracket that secures the motor to the vent box enough to slide
the bracket into the “Z” slots. This will move the bracket away
from the top mounting lip of the blower box and allow it to tilt
away from the vent box panel.
2. Lift up the blower box from the bottom mounting channel.
3. Disconnect the wire connector from the blower motor.
4. Remove panel from the opposite side of blower motor. Loosen
the 2 hex/slotted head screws that attach the top bracket that
secures the panel to the vent box enough to slide the bracket
into the “Z” slots. This will move the bracket away from the
top mounting lip of the panel and allow it to tilt away from the
vent box panel.
5. Lift up the panel from the bottom mounting channel.
A. Panel
B. Blower motor - rear mounting
A. Bracket with “Z” slots
B. Hex/slotted head screws (2)
A. Blower box
B. Bottom mounting channel
A
B
B
A
B
A
B
A. Blower motor
B. Wire connector
A. Bracket with “Z” slots
B. Hex/slotted head screws (2)
A. Blower mounting channel
B. Panel
A
B
B
A
B
A
B
14
6. Install the blower motor box assembly to the opposite side
(rear) of the vent box with the vent located in the bottom
venting position. Place the bottom tab of the blower into the
bottom mounting channel.
7. Plug in the wire connector to the blower motor.
8. Tilt blower box top tab so it is flush with the vent box panel
and position it under the top mounting bracket. Slide bracket
into the “Z” slots and tighten the 2 hex/slotted head screws to
secure.
9. Reinstall panel to front side of vent box panel. Place bottom
tab of the panel into the bottom mounting channel.
10. Tilt panel top tab so it is flush with the vent box panel and
position it under the tip mounting bracket. Slide bracket into
the “Z” slots and tighten the 2 hex/slotted head screws to
secure.
11. See “Complete Installation - Interior Mounted Motor” section.
Complete Installation
(Interior Mounted Motor)
1. Attach backdraft damper over 6" (15.2 cm) vent extension.
Secure with vent clamp.
A. Blower box
B. Bottom mounting channel
A. Blower motor
B. Wire connector
A
B
A
B
A. Blower mounting channel
B. Panel
A. 6" (15.2 cm) vent extension
B. Backdraft damper
A
B
A
B
15
2. Remove screw attaching the terminal box cover.
3. Determine which direction (rear or bottom) electrical
connection will need to run from vent system terminal box.
Remove rear or bottom knockout and install a UL listed or
CSA approved conduit connector.
4. Using 2 or more people, insert the downdraft vent into the
countertop cutout. Position downdraft vent so it is centered in
cutout and parallel to edge of cutout. Check that downdraft
vent is level vertically. Then fasten lower support legs to the
cabinet floor with screws.
5. Attach 1 undercounter bracket on front upper right corner of
downdraft vent with slot over vent mounting hole and flange
against countertop. Attach other bracket to left side of the
downdraft vent. Drill starter holes through undercounter
mounting brackets into the underside of the countertop. Insert
appropriate length screws into holes and tighten brackets to
countertop.
Make Electrical Connections
1. Disconnect power.
2. Feed the power supply cable through the conduit connector
and into the terminal box.
3. Attach the green (or green and yellow) ground wire to the
green ground screw. Tighten the conduit connector clamp
screws.
4. Connect the 2 white wires together using UL listed wire
connectors.
5. Connect the 2 black wires together using UL listed wire
connectors.
6. Replace the terminal box cover and secure with screw.
7. Reconnect power.
A. Terminal box cover
A. When attaching undercounter bracket to underside
of countertop, make sure that the screw length will
not go through countertop when tightened.
B. Backsplash
C. Countertop
A
A
B
C
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
A. Green or green and yellow ground wire
B. Green ground screw
C. White wires
D. UL listed wire connectors
E. Black wires
F. UL listed or CSA approved conduit connector
G. Downdraft vent wiring
WARNING
Fire Hazard
Electrically ground the blower.
Use copper wire.
Connect ground wire to green ground screw in
terminal box.
Failure to do so can result in death, fire, or
electrical shock.
A
B
C
D
E
F
G
16
Check Operation
1. Remove the vent filter shipping bracket screws and bracket.
2. Push and hold the button on the top of the downdraft vent for
a few seconds. The retractable section of the downdraft vent
will rise, and the blower will start. Position the top trim over the
retractable section and snap trim into place.
Trim kits for matching your cooktop color are available from
your dealer.
For information on ordering, see the “Assistance or Service”
section.
3. Slide the control slider on the side of vent to check the
operation and speed of the blower.
4. If the blower does not operate:
Check that filter or filters are pressed in as far as they will
go.
Check that the circuit breaker has not tripped or a
household fuse blown.
Check downdraft vent fuse located under power board.
5. Connect vent system to blower. Vent system must end with a
wall or roof cap. Use clamps to seal all joints.
6. Install cooktop according to manufacturer’s instructions.
Check that rear of cooktop overlaps edge of retractable
downdraft vent by ³⁄₈" (9.5 mm). See “Countertop Cutout
Dimensions” in the “Location Requirements” section.
NOTE: To get the most efficient use from your new retractable
downdraft vent, read the “Vent System Use” section.
INSTALLATION INSTRUCTIONS
EXTERIOR-MOUNTED VENT MOTOR
IMPORTANT: Exterior blower Model Number KPEU722M
[1200 cfm (34.0 m
3
/3)] cannot be used with this retractable
downdraft vent system.
NOTE: Exterior-mounted vent motor installations require exterior
blower system, Model Number KPEC992M [900 cfm (25.5 m
3
/m)],
available from your dealer or authorized parts supplier.
Venting Methods
Determine which venting method is best for your application. Vent
system can terminate through either the wall or roof.
Island location - front vent
Island location - rear vent
A. Vent filter shipping bracket
B. Screws
A
B
A. Top trim
B. ON/OFF button
C. Blower control slider
D. End cap
E. Filters
A
B
D
E
C
17
Built-in cabinet locations
Roof Venting
Calculating Vent System Length
It is recommended that you use round vent instead of rectangular
vent, especially if elbows are required. If rectangular vent is
required, it should be transitioned to 10" (25.4 cm) round vent as
soon as possible.
Maximum Length of Vent System
To calculate the length of the system you need, add the equivalent
feet (meters) for each vent piece used in the system.
Example Vent System
The following example falls within the maximum vent length of
40 ft (12.2 m).
NOTE: The exterior-mounted vent motor requires a separate
wiring cable that should be installed at the same time the vent
work is installed.
Install Vent System
1. Place cardboard or another form of covering on top of a flat
surface where you can easily assemble the downdraft vent
system.
2. Remove parts packages and downdraft vent from carton and
set on covered surface.
3. Remove all shipping materials, tape and film from downdraft
vent.
Front Vent Rear Vent
A. Left venting
B. 10" round 90
° elbow
A. Right venting
B. 10" round 90° elbow
A. 10" (25.4 cm) round vent
Vent Length
10" (25.4 cm) round 40 ft (12.2 m)
A
B
B
A
A
A
Vent Piece 10" (25.4 cm) Round
45° elbow 2.5 ft
(0.8 m)
90° elbow 5.0 ft
(1.5 m)
A. External blower motor
B. Straight vent
C. 90° elbows
2 - 90° elbows = 10.0 ft (3 m)
10 ft (3 m) straight = 10.0 ft (3 m)
Length of 10" (25.4 cm) system = 20 ft (6 m)
A
B
WARNING
Excessive Weight Hazard
Use two or more people to move and install
downdraft vent.
Failure to do so can result in back or other injury.
18
4. Remove screws from each side of the vent. Attach the left and
right side overcounter support brackets to the downdraft vent
and push up to align the screw holes. Use screws to secure
the brackets.
5. Attach the left and right side end caps to the downdraft vent.
Place the end cap upon the overcounter support, slide the tab
into the slot and snap into place over the plastic tabs.
6. Attach support legs to side of downdraft vent with 2 screws in
each leg. Do not tighten screws.
7. Using 2 or more people, insert the downdraft vent into the
countertop cutout. Check that downdraft vent is parallel to
side of cutout and that mounting brackets overlap countertop.
8. Move support legs down against cabinet floor. Place a level
against the front of the downdraft vent base and adjust until
downdraft vent is level vertically. Use a pencil to mark the top
of each leg on the downdraft vent and the location of the
support leg mounting holes on the cabinet floor.
9. Remove downdraft vent from cutout. Drill starter holes at each
mounting screw location on the cabinet floor. Align the top of
the legs with pencil marks on the face of the downdraft vent.
Tighten screws in legs.
Determine which venting direction is best for your
installation.
When installed in a cabinet, vent system can exhaust through the
front or rear of the vent box.
Front venting:
Downdraft vent is shipped with a vent collar in the front
position so no modification is required. See “Complete
Installation” section.
Rear venting:
NOTE: The blank panel and 10" (25.4 cm) diameter vent collar
need to be removed and placed in the opposite position.
1. To remove panels, loosen the 2 hex/slotted head screws that
attach the top bracket that secures the motor to the vent box
enough to slide the bracket into the “Z” slots. This will move
the bracket away from the top mounting lip of the blower box
and allow it to tilt away from the vent box panel.
A. Overcounter support bracket
B. 10" round vent mounting collar plate
C. Overcounter support bracket screw
A. End cap
A. Blower motor box
B. Support leg
A
B
C
A
A
B
A. Level
B. Mark locations.
A. Bracket with “Z” slots
B. Hex/slotted head screws (2)
B
A
B
A
B
19
2. Lift up the panel from the bottom mounting channel.
3. Reinstall both panels to the opposite side of the vent box
panel from which they were removed. Place bottom tab of the
panel into the bottom mounting channel.
4. Tilt panel top tab so it is flush with the vent box panel and
position it under the tip mounting bracket. Slide bracket into
the “Z” slots and tighten the 2 hex/slotted head screws to
secure.
5. See “Complete Installation” section.
Complete Installation
1. Remove the Phillips-head screw attaching the terminal box
cover and remove cover.
Remove either the back or bottom knockout inside the
terminal box and install a UL listed or CSA approved conduit
connector.
NOTE: Power supply cable needed between exterior blower
assembly and blower box is not provided.
Flexible armored or nonmetallic cable must be used. A
½" (12.7 cm) UL listed or CSA approved strain relief must be
provided at each end of the power supply cable.
2. Determine the location where the exterior blower box will be
located. Cut opening in roof or wall for vent system to exterior
blower. Install exterior blower according to instructions
supplied with the blower kit.
Wall Installations:
Use caulking compound between mounting flange and
wall.
Roof Installations:
Follow standard roofing procedures. Refer to the “Roof
Installations” section of the Exterior Blower Installation
Instructions.
The flashing sheet should be centered over the roof
opening.
Lower edge of flashing should lie on top of shingles and
upper edge underneath shingles.
Seal assembly between roof, fan and flashing with roofing
mastic to avoid leaks.
3. Using 2 or more people, insert the downdraft vent into the
countertop cutout. Position downdraft vent so it is centered in
cutout and parallel to edge of cutout. Check that downdraft
vent is level vertically. Then fasten lower support legs to the
cabinet floor with screws.
A. Blower mounting channel
B. Panel
A. Blower mounting channel
B. Panel
A
B
A
B
A. Terminal box cover
A
20
4. Attach 1 undercounter bracket on front upper right corner of
downdraft vent with slot over vent mounting hole and flange
against countertop. Attach other bracket to left side of the
downdraft vent. Drill starter holes through undercounter
mounting brackets into the underside of the countertop. Insert
appropriate length screws into holes and tighten brackets to
the countertop.
Electrical Connection
1. Disconnect power.
2. Feed the home power supply cable through the conduit
connector and into the terminal box.
3. Remove vent box knockout and install a UL listed or CSA
approved conduit connector. Feed exterior-mounted vent
motor wiring through conduit connector.
4. Attach the green (or green and yellow) ground wires from the
home power supply cable and the exterior-mounted vent
motor wiring to the green ground screw.
IMPORTANT: Exterior vent motor wires must be connected in
the terminal box as shown.
5. Connect the 2 blue wires together using UL listed wire
connectors.
6. Connect the 2 brown wires together using UL listed wire
connectors.
A. When attaching undercounter bracket to underside
of countertop, make sure that the screw length will
not go through countertop when tightened.
B. Backsplash
C. Countertop
A
B
C
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
A. Green or green and yellow ground wires
B. Green ground screw
C. Blue wires
D. UL listed wire connector
E. Brown wires
F. Downdraft vent wiring
G. Black wires
H. White wires
I. UL listed or CSA approved conduit and connector,
(Home power supply cable).
J. UL listed or CSA approved conduit and connector,
(Exterior-mounted vent motor wiring).
A
B
H
D
G
C
E
F
I
J
WARNING
Fire Hazard
Electrically ground the blower.
Use copper wire.
Connect ground wire to green ground screw in
terminal box.
Failure to do so can result in death, fire, or
electrical shock.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

KitchenAid W101871170D Manuel utilisateur

Taper
Manuel utilisateur
Ce manuel convient également à

dans d''autres langues