Centrometal CAS-HV Technical Instructions

Taper
Technical Instructions
za montažu toplinske izolacije akumulacijskog spremnika za hladnu i toplu tehnološku vodu /
za montažo toplotne izolacije akumulacijskega rezervoarja za hladno in toplo procesno vodo /
for installation of thermal insulation and jacket for accumulation tanks for cold and hot process water /
zur Montage der Isolierung (Wärmedämmung) des Speichers für kaltes und warm technologisches Wasser /
pro montáž tepelné izolace akumulační zásobníky pro studenou a teplé technologickou vodu /
pour l'installation de l'isolation thermique et de l'enveloppe pour les réservoirs d'accumulation pour l'eau
de process froide et chaude
TU-M-CAS-HV-4-2023-HR-SLO-ENG-DE-CZ-FR
TEHNIČKE UPUTE / TEHNIČNA NAVODILA /
TECHNICAL INSTRUCTIONS /
TECHNISCHE ANLEITUNG / TECHNICKÉ POKYNY /
INSTRUCTIONS TECHNIQUES
TEHNIKA GRIJANJA
Centrometal d.o.o. - Glavna 12, 40306 Macinec, Hrvatska, tel: +385 40 372 600, fax: +385 40 372 611
CAS-HV 303 - 5003
HR
SLO
ENG
DE
CZ
FR
Tehničke upute..................................................3
Tehnična navodila.............................................7
HR
SLO
Technical instructions....................................11
ENG
DE Technische Anleitung.....................................15
CZ Technické pokyny...........................................19
Sadržaj / Vsebino / Contents / Inhalt / Obsah / Contenu HR / SLO / ENG / DE / CZ / FR
2Montaža toplinske izolacije CAS-HV
FR Instructions techniques.................................23
1.0. OPĆENITO
Oplata CAS-HV akumulacijskih spremnika izrađena je od izolacijskog materijala Armaflex. Oplata služi
kao toplinska i mehanička zaštita akumulacijskog spremnika.
2.0. STANJE KOD ISPORUKE
Toplinska izolacija CAS-HV akumulacijskih spremnika dolazi zapakirana u najlonskoj PVC zaštiti.
2.1. SADRŽAJ ISPORUKE
Montaža toplinske izolacije CAS-HV
HR
3
Montaža toplinske izolacije CAS-HV
Armaflex izolacija
postolja
Armaflex izolacija za
vrh i za dno spremnika
Armaflex traka za ljepljenje
po rubovima izolacije
4
3
1 2
1Veći otvori za priključke (4 kom.)
2Manji otvori za priključke (4 kom.)
3Veći otvori za priključke (4 kom.)
4Manji otvori za priključke (4 kom. - ne koristi se)
Montaža toplinske izolacije CAS-HV
U ovim je uputama prikazan postupak postavljanja toplinske izolacije na akumulacijske spremnike
CAS-HV.
HR
3.0. POSTAVLJANJE TOPLINSKE IZOLACIJE
Postaviti spremnik na vodoravnu plohu te osjetnik/osjetnike temperature postavite ispod držača
osjetnika na visini na kojoj želite da osjetnik mjeri temperaturu spremnika (slika 3.).
slika 3.
Polegnuti spremnik CAS-HV (slika 1.) i zalijepiti toplinsku zaštitu za dno spremnika (slika 2.).
Toplinska zaštita mora biti zalijepljena po cijelom dnu spremnika. Nakon toga uspraviti spremnik,
maknuti drvenu paletu i postaviti spremnik na čvrstu i ravnu podlogu.
slika 1.
3.1. MICANJE DRVENE PALETE I LIJEPLJENJE TOPLINSKE ZAŠTITE ZA DNO
SPREMNIKA
3.2. POSTAVLJANJE TEMPERATURNIH OSJETNIKA
12
34
Držač
osjetnika
osjetnik
4Montaža toplinske izolacije CAS-HV
slika 2.
Kada se otpakira izolacija, potrebno je skinuti foliju s ljepljive strane izolacije. Izolacija se postavi na
priključke 6/4'', obavije oko spremnika i rukom se prilagodi spremniku (slika 4.). Na spoju dviju polovica
izolacije potrebno je zalijepiti armaflex traku. Zalijepiti izolaciju na vrh i na postolje spremnika (slika 5.).
Tuljce za termometre (termometri su dodatna oprema) potrebno je toplinski i zrakonepropusno izolirati.
Izolacija priključaka nije u isporuci izolacije spremnika (slika 6.).
slika 4. slika 5. slika 6.
3.3. POSTUPAK POSTAVLJANJA TOPLINSKE IZOLACIJE
HR
5
Montaža toplinske izolacije CAS-HV
Montaža toplinske izolacije CAS-HV
Armaflex traka * Izolacija priključaka (nije u
isporuci izolacije spremnika)
Armaflex izolacija
za vrh spremnika
* Armaflex traka lijepi se po svim spojevima (rubovima) izolacije
Armaflex traka *
Armaflex izolacija za
postolje spremnika
Spremnik je spreman za spajanje na sustav centralnog grijanja/hlađenja.
Toplinska izolacija se isporučuje presavinuta pa su moguće manje nepravilnosti u izgledu. Te
nepravilnosti će nestati u roku 48 sati od montaže.
U slučaju naknadnog postavljanja osjetnika, izolacija se ne treba skidati nego samo nožem odrezati
potrebne otvore za temperaturne osjetnike i ponovno zalijepiti odrezani dio izolacije.
Kod nižih temperatura se mijenjaju svojstva izolacije pa se stoga izolacija mora montirati
na sobnoj temperaturi. Preporučuje se montaža na cca. 20°C, u protivnom će montaža biti
otežana.
Ako se izolacija nalazi u hladnom prostoru, potrebno je do 24 sata držati izolaciju na sobnoj
temperaturi da izolacija bude spremna za montažu.
VAŽNO!
1.
2.
4.0. VAŽNO
Radi lakše montaže, postupno skidati foliju s donje strane izolacije i lijepiti izolaciju na
tijelo spremnika. Na taj se način sprječava pogrešno nalijeganje izolacije na spremnik.
3.
6Montaža toplinske izolacije CAS-HV
Montaža toplinske izolacije CAS-HV HR
7
Montaža toplotne izolacije CAS-HV
1.0. SPLOŠNO
Opaž rezervoarjev CAS-HV je izdelan iz izolacijskega materiala Armaflex. Opaž služi kot toplotna in
mehanska zaščita akumulacijskega rezervoarja.
2.0. STANJE OB DOSTAVI
Toplotna izolacija rezervoarjev CAS-HV je pakirana v najlonsko PVC zaščito.
2.1. VSEBINA DOSTAVE
Montaža toplotne izolacije CAS-HV
SLO
Armaflex izolacija
podnožja rezervoarja
Armaflex izolacija za
zgornji in spodnji del
rezervoarja
Armaflex trak za lepljenje
po robovih izolacije
4
3
1 2
1Večje odprtine za priključke (4 kosa)
2Manjše odprtine za priključke (4 kosa)
3Večje odprtine za priključke (4 kosa)
4Manjše odprtine za priključke (4 kosa - ni v uporabi)
Montaža toplotne izolacije CAS-HV
V teh navodilih je prikazan postopek postavljanja toplotne izolacije na akumulacijske rezervoarje CAS-
HV.
SLO
3.0. MONTAŽA TOPLOTNE IZOLACIJE
Rezervoar postavite na vodoravno površino in temperaturno tipalo(-a) postavite pod držalo tipala na
višino, kjer želite da tipalo meri temperaturo rezervoarja (slika 3.).
slika 3.
Rezervoar CAS-HV položite (slika 1) in na dno posode prilepite toplotno zaščito (slika 2). Toplotna
zaščita mora biti nalepljena po celem dnu rezervoarja. Nato dvignite rezervoar, odstranite leseno
paleto in postavite rezervoar na trdno in ravno površino.
slika 1.
3.1. PREMIKANJE LESENE PALETE IN LEPLJENJE TOPLOTNE ZAŠČITE ZA
DNO REZERVOARJA
3.2. MONTAŽA TEMPERATURNIH TIPALA
12
34
Držalo tipala
tipalo
slika 2.
8Montaža toplotne izolacije CAS-HV
Ko je izolacija razpakirana, je potrebno odstraniti folijo z lepljive strani izolacije. Izolacijo je treba
namestiti na priključke 6/4'', oviti okoli rezervoarja in ročno prilagoditi rezervoarju (slika 4.). Na stičišču
obeh polovic izolacije je potrebno nalepiti armaflex trak. Na vrh in stojalo rezervoarja prilepite izolacijo
(slika 5.). Tulci za termometre (termometri so dodatna oprema) morajo biti toplotno in zrakotesno
izolirani. Izolacija priključkov ni vključena v dobavo izolacije rezervoarja (slika 6.).
3.3. POSTOPEK VGRADNJE TOPLOTNE IZOLACIJE
SLO Montaža toplotne izolacije CAS-HV
9
Montaža toplotne izolacije CAS-HV
slika 4. slika 5. slika 6.
Armaflex trak * Izolacija priključkov (ni
vključena v dobavo izolacije
rezervoarja)
Armaflex izolacija
za vrh rezervoarja
* Na vseh spojih (robovih) izolacije lepi se Armaflex trak
Armaflex trak *
Armaflex izolacija za
stojalo rezervoarja
Rezervoar je pripravljen za priključitev na sistem centralnega ogrevanja/hlajenja.
Toplotna izolacija je dobavljena prepognjena, zato so možne manjše nepravilnosti pri njenem videzu.
Te nepravilnosti bodo izginile v roku 48 ur od montaže.
V primeru da se tipala nameščajo naknadno toplotne izolacije ni treba snemati dol, ampak samo
odrezati izolacijo do želenega položaja tipala in ga vstaviti v držalo tipala in odrezani del izolacije
ponovno zalepite.
Pri nižji temperaturah se lastnosti izolacije spreminjajo, zato je potrebno izolacijo montirati
pri sobni temperaturi. Priporočamo montažo pri cca. 20°C, v nasprotnem bo montaža
otežena.
Če se izolacija nahaja v hladnem prostoru, je treba do 24 ur ohranjati izolacijo pri sobni
temperaturi, zato da bo izolacija pripravljena za montažo.
POMEMBNO!
1.
2.
4.0. POMEMBNO
Za lažjo namestitev postopoma odstranjujte folijo s spodnje strani izolacije in izolacijo
prilepite na telo rezervoarja. To preprečuje, da bi se izolacija napačno prilepila na
rezervoar.
3.
SLO
Montaža toplotne izolacije CAS-HV
10 Montaža toplotne izolacije CAS-HV
1.0. GENERAL
The jacket of the CAS-HV accumulation tanks is made of insulating material Armaflex. The jacket is
intended as thermal and mechanical protection of the accumulation tank.
2.0. DELIVERY
The thermal insulation of the CAS-HV accumulation tanks comes packaged in nylon PVC protection.
2.1. STATUS OF DELIVERY
Installation of thermal insulation CAS-HVENG
Armaflex insulation
for tank base
Armaflex insulation for
the top and bottom of
the tank
Armaflex tape for gluing
around the edges of the
insulation
4
3
1 2
1Larger openings for connections (4 pcs.)
2Smaller openings for connections (4 pcs.)
3Larger openings for connections (4 pcs.)
4Smaller openings for connections (4 pcs. - it is not used)
11
Installation of thermal insulation CAS-HV
Procedure for the assembling of the thermal insulation of the accumulation tanks CAS-HV is described
in the extension of this manual.
3.0. INSTALLATION OF THERMAL INSULATION
Place the tank on a horizontal surface and insert the temperature sensor(s) under the sensor holder at
the height where you want the sensor to measure the accumulation tank temperature (figure 3).
figure 3.
Put in down the CAS-HV tank (figure 1.) and glue the thermal insulation to the bottom of the tank
(figure 2.). The thermal protection must be glued all over the bottom of the tank. After that, lift up the
tank, remove the wooden pallet and place the tank on a hard horizontal surface.
figure 1.
3.1. MOVING THE WOODEN PALLET AND GLUING THE THERMAL
INSULATION FOR THE BOTTOM OF THE TANK
3.2. INSTALLATION OF TEMPERATURE SENSORS
12
34
Sensor holder
sensor
figure 2.
Installation of thermal insulation CAS-HV ENG
12 Installation of thermal insulation CAS-HV
Installation of thermal insulation CAS-HVENG
13
Installation of thermal insulation CAS-HV
When unpacking the insulation, it is necessary to remove the foil from the adhesive side of the
insulation. Adjust the insulation on connection (6/4"), then wrap it around the tank, push the insulation
with the hand to fit the tank (figure 4.). Join the two halfs of the insulation cover with Armaflex tape. Glue
the insulation on top and base of the tank (figure 5.). Thermometer sleeves (thermometers are
additional equipment) must be thermally and air-tightly insulated. Thermal insulation of the connections
is not included in the tank insulation (figure 6.).
3.3. THERMAL INSULATION INSTALLATION PROCEDURE
figure 4. figure 5. figure 6.
Armaflex tape * Connection insulation
(not included in delivery)
Armaflex insulation
of the top of the tank
* Armaflex tape is glued on all joints (edges) of the insulation.
Armaflex tape *
Armaflex insulation
for tank base
14 Installation of thermal insulation CAS-HV
Installation of thermal insulation CAS-HV ENG
The tank is ready for the installation on the central heating and cooling system.
The thermal insulation is delivered bended, so it can have some anomaly in looks. These anomalies will
disappear in 48 hours from mounting.
If the sensors are installed later, it is not necessary to remove the thermal insulation, but just cut off the
insulation to the desired position of the sensor and insert it into the sensor holder and re-glue the cut
part of the insulation.
By lower room temperature the material of the insulation changes his properties, so jacket
must be mounted on room temperature. It is recommended to mount the jacket on ca. 20°C,
if not, the mounting will be hard.
If the insulation is in cold room, it is necessary to keep the jacket on room temperature for
24 hours to be prepared for mounting.
IMPORTANT!
1.
2.
4.0. IMPORTANT
For easier installation, gradually remove the foil from the underside of the insulation and
stick the insulation to the tank body. This prevents the insulation from sticking to the tank
incorrectly.
3.
1.0. ALLGEMEIN
Die Mantel der CAS-HV Speicher besteht aus Wärmedämmung Armaflex. Die Mantel dient als
thermischer und mechanischer Schutz des Pufferspeicher.
2.0. ALLGEMEINES ZUR LIEFERUNG
Die Wärmedämmung der CAS-HV Pufferspeicher wird in einer Nylon-PVC-Schutz.
2.1. LIEFERUMFANG
Installation der Wärmedämmung CAS-HV
DE
Armaflex Wärmedämmung
für Basis
Armaflex-Dämmung für
die Ober- und Unterseite
des Speichers
Armaflex Klebeband zum
Umkleben der Dämmkanten
4
3
1 2
1Größere Öffnungen für Anschlüsse (4 Stk.)
2Kleinere Öffnungen für Anschlüsse (4 Stk.)
3Größere Öffnungen für Anschlüsse (4 Stk.)
4Kleinere Öffnungen für Anschlüsse (4 Stk. - wird nicht verwendet)
15
Installation der Wärmedämmung CAS-HV
16 Installation der Wärmedämmung CAS-HV
Installation der Wärmedämmung CAS-HV DE
Diese Anleitung beschreibt die Vorgehensweise zur Montage der Wärmedämmung an CAS-HV
Pufferspeicher.
3.0. MONTAGE DER WÄRMEDÄMMUNG
Stellen Sie den Pufferspeicher auf eine waagerechte Fläche und Platzieren Sie den/die
Temperatursensor(en) unter dem Sensorhalter in der Höhe, wo der Sensor die Pufferspeicher
temperatur messen soll (Bild 3).
Bild 3.
Legen Sie den CAS-HV Pufferspeicher ab (Bild 1.) und kleben Sie den Wärmedämmung auf den
Boden des Pufferspeicher (Bild 2.). Der Wärmedämmung muss vollflächig auf den Tankboden geklebt
werden. Heben Sie danach den Pufferspeicher an, entfernen Sie die Holzpalette und stellen Sie den
Pufferspeicher auf eine harte horizontale Oberfläche.
Bild 1.
3.1. NEHMEN DER HOLZPALETTE UND KLEBEN DER WÄRMEDÄMMUNG
AUF DEN TANKBODEN
3.2. INSTALLATION VON TEMPERATURSENSOREN
12
34
Sensorhalter
Sensor
Bild 2.
17
Installation der Wärmedämmung CAS-HV
Beim Auspacken der Wärmedämmung muss die Folie von der klebrigen Seite der Wärmedämmung
entfernt werden. Die Wärmedämmung wird auf die 6/4''-Anschlüsse aufgelegt, um den Tank gewickelt
und von Hand an den Tank angepasst (Bild 4). An der Verbindungsstelle der beiden Hälften der
Wärmedämmung muss ein Armaflex-Streifen geklebt werden. Kleben Sie die Wärmedämmung oben
und unten auf den Tank (Bild 5). Rohre für Thermometer (Thermometer sind Zubehör) müssen wärme-
und luftdicht isoliert sein. Die Wärmedämmung der Anschlüsse ist nicht im Lieferumfang (Bild. 6).
Bild 4. Bild 5. Bild 6.
3.3. INSTALLATIONSVERFAHREN FÜR DIE WÄRMEDÄMMUNG
Armaflex-Band * Anschlüssisolierung
(ist nicht im Lieferumfang)
Armaflex-Dämmung
für die Oberseite
des Speicher
* An allen Stoßstellen (Rändern) der Wärmedämmung wird Armaflex Klebeband verklebt
Armaflex-Band *
Armaflex-Dämmung
für Basis
Installation der Wärmedämmung CAS-HV
DE
18 Installation der Wärmedämmung CAS-HV
Der Pufferspeicher ist bereit für den Anschluss an das Heiz-/Kühlsystem.
Der Wärmedämmung wird gefaltet geliefert, daher sind kleine Unregelmäßigkeiten im Aussehen
möglich. Diese Unregelmäßigkeiten verschwinden innerhalb von 48 Stunden nach der Installation.
Bei einem nachträglichen Einbau der Sensoren ist es nicht notwendig die Wärmedämmung zu
entfernen, sondern einfach den Wärmedämmung bis zur gewünschten Position des Sensors zu
Abschneiden und in den Sensorhalter einzusetzen und der abgeschnittene Teil der Isolierung wieder
verklebt werden.
4.0. WICHTIG
Bei niedrigeren Temperaturen ändern sich die Eigenschaften der Dämmung, daher muss
die Dämmung bei Raumtemperatur eingebaut werden. Empfohlen wird eine Montage auf
ca. 20°C, sonst wird die Montage erschwert.
Wenn sich die Isolierung in einem kalten Raum befindet, ist es notwendig, die Isolierung
bis zu 24 Stunden bei Raumtemperatur zu halten, damit die Isolierung für die Installation
bereit ist.
WICHTIG!
1.
2.
Zur einfacheren Montage die Folie von der Unterseite der Dämmung nach und nach
abziehen und die Dämmung auf den Pufferspeicherkörper kleben. Auf diese Weise wird ein
falscher Sitz der Isolierung am Pufferspeicher verhindert.
3.
Installation der Wärmedämmung CAS-HV DE
19
Montáž tepelné izolace CAS-HV
Montáž tepelné izolace CAS-HV
CZ
1.0. OBECNĚ
Bednění zásobníků CAS-HV je vyrobeno z izolačního materiálu Armaflex. Bednění slouží jako tepelná
a mechanická ochrana akumulačních zásobníků.
2.0. OBECNĚ O DODÁNÍ
Tepelná izolace akumulačních zásobníků CAS-HV je balena v nylonové PVC ochraně.
2.1. STAV DODÁNÍ
Armaflex izolace spodní
části zásobníků
Izolace Armaflex pro
horní a spodní část
zásobníků
Páska Armaflex pro lepení
kolem okrajů izolace
4
3
1 2
1Větší otvory pro připojení (4 ks)
2Menší otvory pro připojení (4 ks)
3Větší otvory pro připojení (4 ks)
4Menší otvory pro připojení (4 ks - nepoužívá se)
20 Montáž tepelné izolace CAS-HV
Montáž tepelné izolace CAS-HV CZ
Tento návod popisuje postup montáže tepelné izolace na zásobníky CAS-HV.
3.0. MONTÁŽ TEPELNÉ IZOLACE
Umístěte zásobník na vodorovnou plochu a umístěte teplotní čidlo/čidla pod držák senzoru ve výšce,
kde chcete, aby čidlo měřil teplotu zásobníku (obrázek 3).
obrázek 3.
Položte zásobníky CAS-HV (obrázek 1) a přilepte tepelnou izolaci na dno zásobníky (obrázek 2).
Tepelná izolaci musí být nalepena po celém dně zásobníku. Poté nádobu zvedněte, vyjměte dřevěnou
paletu a umístěte zásobníky na tvrdý vodorovný povrch.
obrázek 1.
3.1. PŘESUNUTÍ DŘEVĚNÉ PALETY A PŘILEPENÍ TEPELNÉ IZOLACE NA DNO
ZÁSOBNÍKY
3.2. INSTALACE ČIDLA TEPLOTY
12
34
Držák čidlo
čidlo
obrázek 2.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Centrometal CAS-HV Technical Instructions

Taper
Technical Instructions

dans d''autres langues