STEINEL LuxMaster Operating Instructions Manual

Taper
Operating Instructions Manual
Bedienungsanleitung
LuxMaster
D
6298204 Technische Änderungen vorbehalten.
Operating instructions
GB
Mode d'emploi
F
Gebruiksaanwijzing
NL
Istruzioni per l'uso
I
Instrucciones de uso
E
Bruksanvisning
S
Brugsanvisning
DK
Käyttöohje
FIN
Bruksanvisning
N
D
STEINEL-Schnell-Service
Dieselstraße 80-84 · 33442 Herzebrock-Clarholz
Tel: +49/5245/448-188 · Fax:+49/5245/448-197 · www.steinel.de
A
I. MÜLLER
Peter-Paul-Str. 15 · A-2201 Gerasdorf bei Wien
Tel.: +43/2246/2146 · Fax: +43/2246/25466 · www.imueller.at
PUAG AG
Oberebenestrasse 51 · CH-5620 Bremgarten
Tel.: +41/56/6488888 · Fax: +41/56/6488880 · www.puag.ch
STEINEL U.K. LTD.
37, Manasty Road · Orton Southgate · GB-Peterborough PE2 6UP
Tel.: +44/1733/238-265 · Fax: +44/1733/238-270
www.steineluk.com
STC SOCKET TOOL COMPANY Limited
8, Queen Street, Smithfield · IRL-Dublin 7
Tel.: +353/1/8725433 · Fax: +353/1/8725195
F
DUVAUCHEL S.A.
ACTICENTRE - CTR 2
Rue des Famards - Bat. M - Lot 3 · F-59818 Lesquin Cedex
Tél.: +33/3/20 30 34 00 · Fax: +33/3/20 30 34 20
www.duvauchel.com
VAN SPIJK AGENTUREN BV
Postbus 2 · NL-5688 ZH Oirschot
De Scheper 260 · NL-5688 HP Oirschot
Tel.: +31/499/571810 · Fax: +31/499/575795
www.vsa-hegema.nl
B
VSA handel Bvba
Fabriekstraat 145 · B-3900 Overpelt
Tel.: +32/11/660720 · Fax: +32/11/660729 · www.vsahandel.be
L
A. R. Tech.
19, Rue Eugène Ruppert, Cloche D’Or · BP 1044
L-1010 Luxembourg
Tel.: +352/49/3333 · Fax: +352/40/2634 · www.artech.lu
I
THOELKE DISTRIBUZIONE S.N.C.
Via Adamello 2/4 · I-22070 Locate Varesino (Como)
Tel.: +39/331/836911 · Fax: +39/331/836913 · www.thoelke.it
E
SAET-94 S.L.
C/ Trepadella, n° 10 · Pol. Ind. Castellbisbal Sud
E-08755 Castellbisbal (Barcelona)
Tel.: +34/93/772 28 49 · Fax: +34/93/772 01 80 · www.saet94.com
P
Pronodis-Soluções
Tecnológicas, Lda · Rua do Caseiro no 87 A/B Vilar
P-3810-078 Aveiro
Tel.: +351/234/484031 · Fax: +351/234/484033 ·
www.
pronodis.pt
S
KARL H STRÖM AB
Verktygsvägen 4 · S-55302 Jönköping
Tel.: +46/36/31 42 40 · Fax: +46/36/31 42 49 · www.khs.se
BROMMANN ApS
Ellegaardvej 18 · DK-6400 Sønderborg
Tel.: +45/7442 8862 · Fax: +45/7443 43 60 · www.brommann.dk
Oy Hedtec Ab
Hedengren yhtiö · Lauttasaarentie 50 · FIN-00200 Helsinki
Tel.: +358/9/682881 · Fax: +358/9/673813 · www.hedtec.fi/valaistus
N
Vilan AS
Tvetenveien 30 B · N-0666 Oslo
Tel.: +47/22725000 · Fax: +47/22725001 · www.vilan.no
PANOS Lingonis + Sons O. E.
Aristofanous 8 Str. · GR-10554 Athens
Tel.: +30/210/3212021 · Fax: +30/210/3218630
EGE SENSÖRLÜ AYDINLATMA ‹TH.
‹HR. T‹C. VE PAZ. LTD. fiT‹.
GERSAN SAN. S‹TES‹ 659.
SOKAK · NO:510 · BATIKENT/ANKARA
Tel.: +90/312/2571233 · Fax: +90/312/2556041
www.egeaydinlatma.com
ATERSAN ‹TH. T‹C. ve SAN. KOLL. ST‹
Add. Tersane Caddesi Galata Hirdavatcilar Carsisi No: 45
Karakoy / ‹stanbul – TURKEY
Tel.: +90/212/2920664 Pbx. · Fax: +90/212/2920665
www.atersan.com
ELNAS s.r.o.
Oblekovice 394 · CZ-67181 Znojmo
Tel.: +420/515/220126 · Fax: +420/515/244347
www.elnas.cz
LANGE ŁUKASZUK Sp.j.
Byków 25a · PL-55-095 Mirków
Tel.: +48/71/3 98 08 861 · Fax: +48/71/3 98 19
www.langelukaszuk.pl
H
DINOCOOP Kft
Radvány u. 24 · H-1118 Budapest
Tel.: 36/1/3193064 · Fax: +36/1/3193066
www.dinocoop.hu
KVARCAS
Neries krantine 32 · LT-48463, Kaunas
Tel.: +370/37/408030 · Fax: +370/37/408031 ·
www.
kvarcas.lt
FORTRONIC AS
Teguri 45c · EST 50113 Tartu
Tel.: +372/7/475208 · Fax: +372/7/367229 ·
www.
fortronic.ee
LOG Zabnica D.O.O.
Podjetje Za Trgovino · Srednje Bitnje 70
SLO-4209 Zabnica
Tel.: +386/42/312000 · Fax: +386/42/312331 ·
www.
log.si
Neco s.r.o.
Ruzová ul. 111 · SK-01901 Ilava
Tel.: +421/42/4 44 14 55 · Fax: +421/42/4 44 14 56
www.neco.sk
STEINEL Trading s.r.l.
Str. Lunga 123 · RO-507055 Cristian-Brasov
Tel.: +40/2 68/25 74 00 · Fax: +40/2 68/25 76 00
www.steinel.ro
Daljinsko Upravljanje d.o.o.
B. Smetane 10 · HR-10 000 Zagreb
Tel.: +3 85/1/3 88 02 47 · Fax: +3 85/1/3 88 02 47
Ambergs SIA
Brivibas gatve 195-16 · LV-1039 Riga
Tel.: +3 71/7/55 07 40 · Fax: +3 71/7/55 28 50
www.ambergs.lv
IT und R GmbH
Kuibyshev Str. 78 · RUS-620026 Ekaterinburg
Tel.: +7/34 32/24 23 23 · Fax: +7/34 32/61 61 65
SVETILNIKI
Str. Malaya Ordinka, 39 · RUS-113184 Moskau
Tel.: +7/95/2 37 28 58 · Fax: +7/95/2 37 11 82
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 2
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Überwachungsbereich
Die sichere Anwesenheits-
erkennung der BLS-Sensoren
hängt maßgeblich von der
Anzahl, Beschaffenheit und
Anordnung der Linsenseg-
mente ab. Mit drei Pyro-Sen-
soren und einem Erfassungs-
bereich von 360°, der sich in
11 Ebenen mit 1320 Schaltzo-
nen darstellt, werden selbst
kleinste Bewegungen im
Nahbereich (2 m Radius um
den Sensor) und Gehbewe-
gungen im Fernbereich (bis
zu 12 m) registriert. Auf diese
Weise können selbst größere
Büros mit nur einem Sensor
überwacht werden.
Sollen bestimmte Bereiche
von der Erfassung ausgenom-
men werden, so kann der
Erfassungsbereich durch Auf-
setzen von Abdeckschalen
gezielt eingestellt werden
(s. Kapitel Reichweitenein-
stellung).
Optimaler Montageort:
Der Sensor ist nur zur
Deckenmontage in Räumen
geeignet. Er sollte grund-
sätzlich so installiert werden,
dass sitzende Personen den
Sensor in einem Abstand
von ca. 1 m vor sich sehen
(s. Abb.). In dieser Position ist
die Erfassungssicherheit im
Nahbereich am größten.
Gehende Personen werden
auch noch innerhalb des
Fernbereichs erfasst.
3
1m
360°
1
2
3
4
1m
1m
2m
2m
12 m
12 m
0
Sensor
Nahbereich (Radius 2 m)
Sitzposition
Fernbereich (Radius 12 m)
Sicherheitshinweise
D
Vor allen Arbeiten am
Sensor die Spannungs-
zufuhr unterbrechen!
Bei der Montage muss die
anzuschließende elektri-
sche Leitung spannungs-
frei sein. Daher als Erstes
Strom abschalten und
Spannungsfreiheit mit
einem Spannungsprüfer
überprüfen.
Bei der Installation des
Sensors handelt es sich
um eine Arbeit an der
Netzspannung. Sie muss
daher fachgerecht nach
den landesspezifischen
Installationsvorschriften
und Anschlussbedingun-
gen durchgeführt werden
(VDE 0100).
Das am 1–10 V-Steueraus-
gang zur Verfügung gestell-
te Signal ist eine Funkti-
onskleinspannung und
keine Schutzkleinspannung
(SELV). Daher sind zur Ver-
drahtung entsprechend
isolierte Leitungen zu ver-
wenden.
Funktionsweise / Grundfunktion
Die Infrarot-Sensoren der
Serie LuxMaster regeln die
Beleuchtung z. B. in Büros,
Schulen oder öffentlichen Ge-
bäuden in Abhängigkeit von
anwesenden Personen (Bewe-
gungserfassung) und Umge-
bungshelligkeit. Der im Sensor
integrierte Lichtfühler misst
stetig die Umgebungshellig-
keit und vergleicht sie mit
dem am Sensor eingestellten
Helligkeits-Sollwert (BLS /
BLS T 20 – 1300 Lux und
BLS D/BLS DF 100 – 1300 Lux).
Ist die Umgebungshelligkeit
ausreichend, wird die Be-
leuchtung nicht zugeschaltet.
Liegt die Umgebungshelligkeit
unterhalb des eingestellten
Helligkeits-Sollwertes, bewirkt
eine Bewegung im Raum das
Einschalten der Beleuchtung.
4 Varianten stehen zur Aus-
wahl:
BLS - anwesenheits- und
tageslichtunabhängiges
Ein- und Ausschalten der
Beleuchtung.
Licht nur bei Anwesenheit im
Raum. Erreicht die Umge-
bungshelligkeit den eingestell-
ten Sollwert, wird die Beleuch-
tung automatisch wieder abge-
schaltet.
BLS T - Präsenzmelder mit
Halbautomatik. Manuell AN.
Automatisch AUS, wenn kein
Licht mehr benötigt wird.
Der Nutzer schaltet das Licht
über einen zu integrierenden
Schalter (Öffnertaster) manuell
ein (Klassenraumfunktion).
Durch kurzes Betätigen und
sofortiges Lösen des Tasters /
Schalters (ca. 0,2 – 1 Sek.) wird
die Spannungsversorgung
kurzfristig unterbrochen, die
BLS T geht in den Standard-
Sensorbetrieb. Wird der Raum
ohne erneute Betätigung des
Tasters verlassen, geht die
Beleuchtung bei Ablauf des ein-
gestellten Zeitwertes bzw. bei
Überschreiten des eingestellten
Dämmerungswertes aus. Wird
beim Verlassen des Raums der
Taster erneut kurz betätigt
(ca. 0,2 – 1 Sek.) schaltet die
Leuchte automatisch aus und
nicht automatisch wieder ein.
Wird der Taster länger gedrückt,
(> 2 Sek.), ist die BLS komplett
spannungsfrei, führt beim Lö-
sen einen Selbsttest durch und
die Beleuchtung geht für die
eingestellte Zeit an.
BLS D – anwesenheits- und
tageslichtabhängiges Dim-
men der Beleuchtung
Der Sensor erfasst gleichzeitig
die Differenz zwischen einge-
stelltem Sollwert und Umge-
bungshelligkeit und dimmt die
Beleuchtung soweit herauf,
bis der eingestelle Sollwert im
Raum erreicht ist. Veränderun-
gen der Umgebungshelligkeit
werden permanent vom Sensor
erfasst und so ausgeregelt,
dass bei Anwesenheit eine kon-
stante Helligkeit im Raum herr-
scht.
BLS DF – anwesenheits-
und tageslichtabhängiges
Dimmen der Beleuchtung –
optional mit Fernbedienung
Bei diesem Sensor besteht zu-
sätzlich die Möglichkeit, das
Lichtniveau (Helligkeits-Soll-
wert) mit einer Infrarot-Fernbe-
dienung zu verändern. Somit
kann die Beleuchtung z. B. bei
Diavorträgen oder bei Verwen-
dung eines Projektors komfor-
tabel auf das gewünschte Licht-
niveau heruntergedimmt
werden.
Die mit der Fernbedienung
getätigten Veränderungen des
Helligkeits-Sollwertes können
mit der Reset-Funktion (gleich-
zeitiges Drücken beider Tasten
(+) und (–)) bequem wieder auf
das am Sensor eingestellte
Lichtniveau zurückgesetzt wer-
den.
2
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 4
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Elektrische Installation/Automatikbetrieb
Anschlussbeispiel/Manuelle Ausschaltung
Anschlussbeispiel BLS T mit Halbautomatik
BLS / BLS T
BLS BLS D / BLS DF
BLS D / BLS DF
L
LN
L
LN
+
Bei der Auswahl der Verdrah-
tungsleitungen sind grundsätz-
lich die Installationsvorschriften
nach VDE 0100 einzuhalten
(siehe Sicherheitshinweise auf
Seite 2). Für die Verdrahtung der
BLS D bzw. BLS DF gilt: Nach
VDE 0100 520 Abschn. 6 darf
für die Verdrahtung zwischen
Sensor und EVG eine Mehrfach-
Leitung verwendet werden, die
sowohl die Netzspannungslei-
tungen wie auch die Steuer-
leitungen (1–10 V) enthält
(z. B. NYM 5 x 1,5
2
).
Die Netzanschlussleitung darf
max. einen Durchmesser von
10 mm haben.
Der Klemmbereich der Netzan-
schlussklemme ist für maximal
2 x 1,5 mm
2
oder 1 x 2,5 mm
2
ausgelegt.
5
Soll die Automatikfunktion des
Sensors bewusst manuell
ausgeschaltet werden können,
so ist dem Sensor ein kon-
ventioneller Schalter vorzu-
schalten.
1) Leuchtengruppe, 2) BLS, 3) Externer Schalter
1) Öffnertaster, 2) BLS T, 3) Verbraucher, Beleuchtung
4) Leuchte mit DIMM EVG, 5) BLS D / BLS DF
Montage/Installation
Montageschritte
1. Zierring
durch leichtes
Andrücken an den Seiten
und gleichzeitiges Drehen
nach unten abziehen.
2. Sicherungsschraube
lösen.
3. Sensorgehäuse
in
Pfeilrichtung
von der
Montageplatte abziehen.
4. Montageplatte mit beilie-
genden Schrauben und
Dübeln unter die Decke
montieren.
5. Verdrahtung vornehmen
(siehe elektrische
Installation).
– Neutralleiter N
– Phase L
– geschaltete Phase L
– Erdungsleiter
(Schutzleiter)
– Steuerausgang +
– Steuerausgang –
– (nur BLS D bzw. BLS DF)
Bei Kabelzuleitung Aufputz ist
die Nut am Zierring zu durch-
stoßen und das Kabel seitlich
einzuführen.
16. Sensorgehäuse von der
Seite (gegen Pfeilrichtung)
auf die Montageplatte
aufstecken.
17. Sicherungsschraube
eindrehen.
18. Funktionstest durchführen
und Erfassungsbereich
einstellen (siehe Seiten
6 u. 9).
19. Ausschaltverzögerung und
Helligkeits-Sollwert an der
Stirnseite des Gehäuses
(Einstellregler) einstellen
(siehe Funktionen S. 7,
Kapitel Einstellungen).
10. Zierring aufsetzen (einra-
sten). (Abdeckblenden
werden durch den Zierring
fixiert).
4
Netzzuleitung
Leuchte mit
DIMM EVG
(z.B. NYM 5 x 1,5
2
)
Netzzuleitung
z.B. NYM 3 x 1,5
2
Leuchte
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 6
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Funktionen
BLS / BLS T / BLS D / BLS DF
BLS / BLS T
BLS D / BLS DF
7
Zur Bestimmung des Hellig-
keits-Sollwertes (Luxwert)
sowie der Ausschaltverzöge-
rung (Zeiteinstellung) steht je
ein Potentiometer zur
Verfügung.
Mit der Ausschaltverzögerung
(4–15 Minuten) wird die Dauer
festgelegt, in der das Licht
nach Registrierung der letzten
Bewegung eingeschaltet bleibt.
Bei jeder weiteren Bewegungs-
erfassung beginnt die einge-
stellte Nachlaufzeit von neuem,
so lange bis keine Bewegung
mehr erkannt wird oder die
Umgebungshelligkeit den
eingestellten Helligkeits-Soll-
wert erreicht hat.
Nur BLS / BLS T:
Impulsmodus: Stellen Sie den
Regler auf “ ” befindet sich
das Gerät im Impulsmodus,
d.h. der Ausgang wird für ca.
2 Sek. eingeschaltet (z.B. für
Treppenhausautomat). Danach
reagiert der Sensor für ca.
8 Sek. nicht auf Bewegung.
Der am Sensor einzustellende
Helligkeits-Sollwert (20–1300
Lux) bestimmt das tageslicht-
abhängige Schaltverhalten des
Sensors. Bei Betätigung des
Einstellreglers schaltet der
Sensor die Beleuchtung in je-
dem Fall ab. Nach Beendigung
der Einstellung gilt:
Liegt der Tageslichtanteil
unterhalb des eingestellten
Helligkeits-Sollwertes, wird
die Beleuchtung eingeschaltet;
liegt der Tageslichtanteil über
dem eingestellten Helligkeits-
Sollwert, wird die Beleuchtung
ausgeschaltet – auch bei Be-
wegung im Erfassungsbereich.
Der am Sensor einzustellen-
de Helligkeits-Sollwert (100 –
1300 Lux) bestimmt das Ge-
samtlichtniveau im Raum.
Liegt die Umgebungshelligkeit
bei Bewegungserfassung un-
terhalb des eingestellten Soll-
wertes, so erfasst der Licht-
fühler die Differenz und dimmt
die Beleuchtung soweit her-
auf, bis der gewünschte Soll-
wert erreicht ist. Veränderun-
gen des Tageslichtanteils wer-
den permanent vom Licht-
fühler erfasst und so ausgere-
gelt, dass bei Anwesenheit
eine konstante Helligkeit im
Raum herrscht.
Tipp: Der Helligkeits-Sollwert
lässt sich am besten im Test-
betrieb (Regler für Ausschalt-
verzögerung auf „Test“) ein-
stellen, da die Lichtregelung
(Dimmung) dann unmittelbar
allen Helligkeitsveränderungen
folgt.
Einstellung des Helligkeits-Sollwertes
Einstellung des Helligkeits-Sollwertes
Einstellung des Helligkeits-Sollwertes
Technische Daten
BLS / BLS T
Der Testbetrieb eignet sich zur
Überprüfung der Funktions-
fähigkeit sowie zur gezielten
Einstellung des Erfassungsbe-
reiches (siehe auch Kapitel
Reichweiteneinstellung).
Um den Testbetrieb zu akti-
vieren ist der Einstellregler für
die Dämmerungseinstellung
auf Stellung „Test“ zu drehen.
Im Test-Betrieb schaltet der
Sensor, unabhängig von der
Umgebungshelligkeit, die
Beleuchtung mit einer Nach-
laufzeit von 5 Sekunden.
Hinweis: Wenn der Sensor
die Beleuchtung abschaltet,
muss danach noch eine
kurze Wartezeit von ca. 4 Sek.
eingehalten werden, bevor
der Sensor erneut auf Bewe-
gung reagieren kann.
Um den Testbetrieb zu akti-
vieren ist der Einstellregler für
die Zeiteinstellung auf Stellung
„Test“ zu drehen. Während
des Testbetriebs folgt die
Lichtregelung (Dimmung)
unmittelbar allen Helligkeits-
veränderungen (z. B. Hand
vor die Sensorlinse halten).
Auf diese Weise lässt sich die
Richtigkeit der Verdrahtung
schnell überprüfen. Dimmt der
Sensor die Beleuchtung nicht
entsprechend den Helligkeits-
veränderungen, so wurde
die Verdrahtung nicht korrekt
vorgenommen.
Wird der Testbetrieb wieder
verlassen, so wird das Dimm-
verhalten des Sensors wieder
optimal dem menschlichen
Empfinden angepasst.
6
Netzspannung: 230 V, 50 Hz
Schaltleistung: max. 2000 W (ohmsche Last, z. B. Glühlampe)*
max. 1000 W (NV-Halogen)
max. 1000 W (Leuchtstofflampen mit KVGs, cos ϕ = 0,5)*
max. Anzahl EVGs:
16 x (1 x 36 W) oder 12 x (2 x 36 W) oder
12 x (1 x 58 W) oder 8 x (2 x 58 W)
Bei größeren Schaltleistungen ist ein Relais oder
Schütz vorzuschalten.
Erfassungsbereich: horizontal 360°, vertikal 180°
Empfohlene Montagehöhe: 2,5–3 m (Deckenmontage)
Max. Reichweite: hochauflösender Nahbereich: 4 x 4 m (sitzende Personen)
sicherer Fernbereich: 24 x 24 m (gehende Personen)
Schaltschwelle bzw. BLS / BLS T: 20 –1300 Lux, Tageslichtbetrieb
Konstantlichtniveau: BLS D / BLS DF: 100 –1300 Lux, Tageslichtbetrieb
Ausschaltverzögerung: 4 –30 Min., 2h
Schutzart: IP 20
Umgebungstemperatur: –15° bis 50° C
Steuersignal: 1–10 V (max. 50 EVGs)
(nur BLS D + BLS DF)
Reichweite (IR-Fernbed.): 4 m (nur BLS DF)
*
VDE-zertifiziert
Funktionstest / Testbetrieb
BLS D / BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 8
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Einstellung des Erfassungsbereiches/Reichweite
Zur gezielten Einstellung des
Erfassungsbereiches können
die beiliegenden Abdeckscha-
len verwendet werden. Hiermit
ist es z. B. möglich in einem
Großraumbüro einzelne
Arbeitsplatzbereiche sauber
voneinander zu trennen,
sodass nur Bewegungen im
Bereich der jeweiligen
Schreibtischgruppe erfasst
werden. Zur schnellen und
präzisen Einstellung des
Erfassungsbereiches empfeh-
len wir den Testbetrieb zu
aktivieren (siehe Seite 6).
1
2
3
4
5
6
7
8
Senkrechte Trennung =
Reduzierung des Erfassungswinkels
Waagerechte Trennung =
Reduzierung der Reichweite
Die Abdeckschalen sind in 8 Bereiche (waage-
recht) unterteilt. Entsprechend der aufgesetzten
Abdeckschalen (Anzahl der Bereiche) wird
die Reichweite reduziert.
Abdeckung Reichweite Reichweite
(siehe Skizze) (Montage in (Montage in
2,5 m Höhe) 5 m Höhe)
0 (ohne Abd.) = 12 m = ,12 m
1 = 6,5 m = ,10 m
2= 6,5 m = ,99 m
3 = 3,5 m = ,98 m
4= 3,3 m = ,96 m
5 = 2,3 m = 4,5 m
6 = 1,5 m = 3,3 m
7= 1,1 m = 2,2 m
8 < 0,5 m < 1,1 m
9
BLS DIMM
IR-Fernbedienung
Für den Sensor BLS DF be-
steht zusätzlich die Option,
den gewünschten Helligkeits-
Sollwert über eine Infrarot-
Fernbedienung einzustellen.
Die zuletzt gewählte Einstel-
lung bleibt dabei jeweils
erhalten. Durch dauerhaftes
Drücken der (–)-Taste kann
die Beleuchtung über die
Fernbedienung auch ganz
abgeschaltet werden. Durch
nachfolgendes Drücken der
(+)-Taste kann anschließend
das gewüschte Helligkeits-
niveau wieder eingestellt
werden.
Reset-Funktion
Durch gleichzeitiges Drücken
der beiden Tasten (+) und (–)
werden alle mit der Fernbedie-
nung getätigten Änderungen
wieder auf den am Sensor ein-
gestellten Helligkeits-Sollwert
zurückgesetzt.
Wichtiger Hinweis:
Bei der Einstellung des Hellig-
keits-Sollwertes ist zu beach-
ten, dass sich die gemesse-
nen Helligkeitswerte des Sen-
sors auf den Montageort des
Sensors unter der Decke
beziehen und deshalb nicht
unbedingt der gewünschten
Helligkeit am Arbeitsplatz
entsprechen können.
Richtwerte zur Einstellung des Lux- bzw. Zeitwertes
Folgende Richtwerte können zugrunde gelegt werden:
Helligkeits-Sollwert:
Durchgangszonen (kein Arbeitsbereich): 200 Lux
Arbeitsbereiche (Büros, Schulungsräume, Arbeitsstätten etc.): 500 Lux
Sehintensive Arbeitsbereiche:
(technisches Zeichnen, Labore, präzise Arbeiten) 700–1000 Lux
Ausschaltverzögerung:
Die Ausschaltverzögerung kann stufenlos entsprechend der Nutzung der jeweiligen Räume
eingestellt werden:
Vorwiegend stehende Tätigkeiten (z. B. Kopierraum, Durchgänge etc.): 00 4 Min.
Vorwiegend sitzende Tätigkeiten (Schreibtischarbeit von 3–4 Personen): 00 7 Min.
Vorwiegend sitzende Tätigkeiten (Schreibtischarbeit von 1–2 Personen): 0 10 Min.
Sitzende Tätigkeiten mit schwacher Bewegung (Lesen, EDV etc.): > 10 Min.
Sollte trotz Anwesenheit die Beleuchtung nach dem Abschalten auf eine Bewegung
hin sofort wieder einschalten, so ist die Ausschaltverzögerung zu erhöhen.
8
Funktionen
BLS DF
A
v
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 10
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Funktionsgarantie
Konformitätserklärung
Dieses Produkt erfüllt die
Niederspannungrichtlinie
06/95/EG die EMV-Richtlinie
04/108/EG und die RoHS-
Richtlinie 02/95/EG.
Dieses Steinel-Produkt ist mit
größter Sorgfalt hergestellt,
funktions- und sicherheitsge-
prüft nach geltenden Vorschrif-
ten und anschließend einer
Stichprobenkontrolle unterzo-
gen. Steinel übernimmt die
Garantie für einwandfreie Be-
schaffenheit und Funktion.
Die Garantiefrist beträgt 36
Monate und beginnt mit dem
Tag des Verkaufs an den Ver-
braucher. Wir beseitigen Män-
gel, die auf Material- oder Fa-
brikationsfehlern beruhen, die
Garantieleistung erfolgt durch
Instandsetzung oder Aus-
tausch mangelhafter Teile nach
unserer Wahl. Eine Garantielei-
stung entfällt für Schäden an
Verschleißteilen sowie für
Schäden und Mängel, die
durch unsachgemäße Behand-
lung oder Wartung auftreten.
Weitergehende Folgeschäden
an fremden Gegenständen
sind ausgeschlossen.
Die Garantie wird nur gewährt,
wenn das unzerlegte Gerät mit
kurzer Fehlerbeschreibung,
Kassenbon oder Rechnung
(Kaufdatum und Händlerstem-
pel), gut verpackt, an die zu-
treffende Servicestation einge-
sandt wird.
Reparaturservice:
Nach Ablauf der Garantiezeit
oder Mängeln ohne Garantie-
anspruch repariert unser Werk-
service. Bitte das Produkt gut
verpackt an die nächste Servi-
cestation senden.
11
Betriebsstörungen
Licht schaltet nicht ein
Licht schaltet nicht aus
Sensor schaltet trotz
Anwesenheit ab
Sensor schaltet zu spät ab
Sensor schaltet bei frontaler
Gehrichtung zu spät ein
Sensor schaltet bei
wechselnder Bewölkung
zu häufig
nur BLS D, DF:
Im Test-Betrieb reagiert
der Sensor nicht auf
Helligkeitsänderungen
nur BLS DF:
Sensor schaltet trotz
Dunkelheit bei Anwesenheit
nicht ein
Das mit dem Handsender
eingestellte Lichtniveau
ist nicht mehr gespeichert
keine Anschlussspannung
Lux-Wert zu niedrig
eingestellt
keine Bewegungserfassung
Lux-Wert zu hoch
Nachlaufzeit läuft ab
Störende Wärmequellen
z.B.: Heizlüfter, offene
Türen und Fenster,
Haustiere
Nachlaufzeit zu klein
Nachlaufzeit zu groß
Reichweite bei frontaler
Gehrichtung ist reduziert
Nachlaufzeit zu gering
eingestellt
Steuerleitungen (+,–)
nicht korrekt verdrahtet
Sensor zuvor mit Hand-
sender abgeschaltet
Lux-Wert zu niedrig
gewählt
Einstellungen gelöscht,
da Spannungszufuhr zum
Sensor unterbrochen
(z.B. durch Lichtschalter
oder Stromausfall)
Anschlussspannung
überprüfen
Lux-Wert langsam erhö-
hen bis Licht einschaltet
Freie Sicht auf den
Sensor herstellen
Erfassungsbereich über-
prüfen
Lux-Wert niedriger
stellen
Nachlaufzeit abwarten
ggf. Nachlaufzeit kleiner
stellen
Stationäre Störquellen
durch Abdeckschalen
ausblenden
Nachlaufzeit erhöhen
Nachlaufzeit verkleinern
weitere Sensoren
montieren
Abstand zwischen zwei
Sensoren reduzieren
Nachlaufzeit erhöhen
angenehmeres
Schaltverhalten
Steuerleitungen am
Sensor oder am EVG
tauschen
Sensor durch Drücken
der (+)-Taste am Hand-
sender aktivieren
Lux-Wert am Sensor
oder durch Drücken der
(+ )-Taste am Handsender
erhöhen
Spannungszufuhr zum
Sensor sicherstellen
Störung Ursache Abhilfe
10
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 12
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Detection zone
The reliable occupancy de-
tection of the BLS sensors
considerably depends on the
number, condition and arrange-
ment of the lens segments.
With three pyro sensors and a
detection zone of 360°, con-
sisting of 11 levels with 1320
switching zones, even the
smallest movements in the
close range (2 m radius
around the sensor) and walking
movements in the long-dis-
tance range (up to 12 m) are
recorded. In this manner, even
larger offices can be monitored
with only one sensor.
If specific areas are to be ex-
cluded from detection, the de-
tection zone can be deliberate-
ly adjusted by applying shrouds
(see Reach setting section).
Optimum installation site:
The sensor is only suitable for
ceiling installation in rooms. It
should always be installed so
that seated individuals see the
sensor at a distance of approx.
1 m in front of them (see Fig.).
Reliability of detection in the
close range is greatest in this
position. Walking individuals
are still detected within the
long-distance range.
13
1m
360°
1
2
3
4
1m
1m
2m
2m
12 m
12 m
0
Sensor
Close-up range (radius 2 m)
Seated
Long-distance range (radius 12 m)
Safety warnings
GB
Disconnect the power sup-
ply before attempting any
work on the sensor!
During installation, the
electric power cable to be
connected must be volt-
age-free. Therefore, switch
off the power first and use
a voltage tester to make
sure the wiring is off circuit.
Installing the sensor in-
volves work on the mains
power supply. This work
must therefore be carried
out professionally in accor-
dance with the applicable
national wiring regulations
and electrical operating
conditions (VDE 0100).
The signal provided on the
1–10 V control output is a
functional extra-low volt-
age and not a safety extra-
low voltage (SELV). Conse-
quently, appropriately insu-
lated leads are to be used
for wiring.
How it works / basic function
The LuxMaster series of in-
frared sensors control the
lighting, e.g. in offices,
schools or public buildings
depending on persons present
(motion detection) and sur-
rounding brightness. The light
sensor incorporated in the
sensor constantly measures
ambient light level and com-
pares it with the brightness
setting adjusted on the sensor
(BLS / BLS T 20 – 1300 lux
and BLS D/BLS DF 100 – 1300
lux). If the surrounding bright-
ness is sufficient, the lighting
is not switched ON. If the sur-
rounding brightness is below
the adjusted brightness set-
ting, a movement in the room
causes the light to be
switched ON. A choice of 4
versions is available:
BLS - switching ON and OFF
of the light independently of
occupancy and daylight.
Light only with presence in the
room. Once the surrouding
brightness reaches the set the-
oretical value, the lighting is au-
tomatically switched OFF again.
BLS T - semi-automatic oc-
cupancy detector. ON manu-
ally. OFF automatically, when
light is no longer needed.
The user switches the light ON
manually (classroom function)
using a switch to be incorporat-
ed (break-contact button). By
briefly pressing and immediate-
ly releasing the button / switch
(approx. 0.2 – 1 sec.), the volt-
age supply is briefly interrupted
and the BLS T transfers to stan-
dard sensor mode. If the room
is left without operating the but-
ton again, the light goes out
once the set time value has
elapsed or once the set twilight
value is exceeded. If the button
is briefly pressed again on leav-
ing the room (approx. 0.2 –
1 sec.), the light switches OFF
automatically and does not
switch ON again automatically.
If the button is pressed for
longer (> 2 sec.), the BLS is
completely free of voltage, per-
forms a self-test on release and
the lighting goes ON for the set
time.
BLS D – dimming of the light-
ing depending on presence
and daylight
The sensor simultaneously de-
tects the difference between the
set theoretical value and the
surrounding brightness and
raises the brightness of the
lighting until the set theoretical
value is achieved in the room.
Changes in the surrounding
brightness are constantly de-
tected by the sensor and are
adjusted such that with occu-
pancy, a constant brightness
prevails in the room.
BLS DF – dimming of the
lighting depending on occu-
pancy and daylight – optional-
ly with remote control
With this sensor, it is also possi-
ble to alter the light level (bright-
ness setting) with an infrared re-
mote control. The lighting can
therefore be conveniently
dimmed to the desired light lev-
el, for example during slide
shows or when using a projec-
tor.
The modifications in the light
level made with the remote
control can be conveniently re-
set to the light level adjusted on
the sensor using the reset func-
tion (simultaneous pressing of
both buttons (+) and (–)) .
12
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 14
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Electrical installation/automatic mode
Wiring example/manual switch-off
Wiring example semi-automated BLS T
BLS / BLS T
BLS BLS D / BLS DF
BLS D / BLS DF
L
LN
L
LN
+
In selecting the wiring leads, the
wiring regulations according to
VDE 0100 must be complied
with (see safety warnings on
page 12). The following applies
for wiring of the BLS D and
BLS DF: According to VDE 0100
520 sect. 6, a multiple lead may
be used for wiring between the
sensor and electronic ballast,
containing both the mains volt-
age leads and the control leads
(1–10 V) (e.g. NYM 5 x 1.5
2
).
The mains supply lead must
be no greater than 10 mm in
diameter.
The clamping range of the
mains terminal is designed for
a maximum of 2 x 1.5 mm
2
or
1 x 2.5 mm
2
.
15
If it is to be possible to delib-
erately switch off the auto-
matic function of the sensor
manually, a conventional
switch is to be positioned
upstream from the sensor.
1) Light group, 2) BLS, 3) External switch
1) Break-contact button, 2) BLS T, 3) Load, lighting
4) Light with dimming electronic ballast, 5) BLS D / BLS DF
Assembly/Installation
Installation procedure
1. Pull off the decorative
ring by pressing lightly on
the sides and simultaneous-
ly turning downwards.
2. Unscrew the
locking
screw.
3. Pull the sensor enclosure
off the mounting plate
in the direction of the
arrow
.
4. Install the mounting plate
under the ceiling using the
enclosed screws and dow-
els.
5. Perform wiring (see Electri-
cal installation).
– Neutral conductor N
– Phase L
– Switched phase L
– Earth conductor (protective-
earth conductor)
– Control output +
– Control output –
– (only BLS D and BLS DF)
For surface wiring, the groove
on the decorative ring is to be
pierced and the cable is to be
introduced from the side.
16. Push-fit the sensor hous-
ing on to the mounting
plate from the side
(against the direction of
the arrow)
.
17. Screw in the locking
screw
.
18. Perform a function test
and adjust the detection
zone (see pages 16 and 19).
19. Adjust the switch-off delay
and brightness setting on
the front of the enclosure
(control dial) (see Func-
tions p. 17, Adjustments
section).
10. Apply the decorative ring
(clip in place). (Shrouds
are fixed with the decora-
tive ring).
14
Mains lead
Light with
dimming
electonic ballast
(e.g. NYM 5 x 1.5
2
)
Mains lead
e.g. NYM 3 x 1.5
2
Light
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 16
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Functions
BLS / BLS T / BLS D / BLS DF
BLS / BLS T
BLS D / BLS DF
17
One potentiometer is provided
in order to determine the
brightness setting (lux value) in
addition to the switch-off delay
(time setting) respectively.
Using the switch-off delay
(4–15 minutes), the period is
determined during which the
light remains switched ON after
recording the last movement.
With each further detection of
movement, the set overshoot
time begins again until motion
is no longer detected or the
surrounding brightness reaches
the adjusted brightness setting.
Only BLS / BLS T:
Pulse mode: If the controller is
set to “ ”, the device is in
pulse mode, i.e. the output is
switched ON for approx. 2 sec.
(e.g. for an staircase lighting
timer). Afterwards, the sensor
does not react to movement for
approx. 8 sec.
The brightness setting to be
set on the sensor (20–1300 lux)
determines the daylight-de-
pendent switching behaviour
of the sensor. On operation of
the control, the sensor switch-
es the lighting OFF in any
case. On completion of adjust-
ment, the following applies:
if the amount of daylight is
below the set brightness set-
ting, the lighting is switched
ON; if the amount of daylight
is above the brightness set-
ting, the lighting is switched
OFF – even in case of move-
ment within the detection
zone.
Thebrightness setting to be
set on the sensor (100–1300
lux) determines the total light
level in the room. If the sur-
rounding brightness lies below
the set theoretical value on
motion detection, the light
sensor detects the difference
and dims the lighting until the
desired theoretical value is
achieved. Changes in the
amount of daylight are con-
stantly detected by the light
sensor and are adjusted such
that with occupancy, a con-
stant brightness prevails in the
room.
Hint: The brightness setting is
best adjusted in test mode
(control for switch-off delay
set to "Test"), since the light
control (dimming) follows all
changes in brightness in this
case.
Adjusting the brightness setting
Adjusting the light level
Adjusting the brightness setting
Technical specifications
BLS / BLS T
The test mode is suitable for
verifying operational status
and for specifically adjusting
the detection zone (also see
Reach setting section).
In order to activate test
mode, the control for the light
threshold is to be turned to
the "Test" position. In test
mode, the sensor switches on
the lighting with an overshoot
time of 5 seconds, regardless
of the surrounding brightness.
Note: When the sensor
switches the lighting off, a
short waiting time of approx.
4 sec. must be observed be-
fore the sensor can react to
movement again.
In order to activate test mode,
the control for the time setting
is to be turned to the "Test"
position. During test mode, the
light control (dimming) directly
follows all changes in bright-
ness (e. g. hold a hand in front
of the sensor lens). The correct-
ness of the wiring can be rapid-
ly checked in this manner.
If the sensor does not dim the
lighting in accordance with the
changes in brightness, the
wiring has not been performed
correctly.
When test mode is quitted, the
dimming behaviour of the sen-
sor is optimally readjusted to
human perception.
16
Power supply: 230 V, 50 Hz
Switching capacity: max. 2000 W (resistive load, e.. g. filament bulb)*
max. 1000 W (low-voltage halogen)
max. 1000 W (fluorescent lamps with capacitive ballasts, cos ϕ = 0,5)*
max. number of electronic ballasts:
16 x (1 x 36 W) or 12 x (2 x 36 W) or
12 x (1 x 58 W) or 8 x (2 x 58 W)
A relay or contactor must be provided on the line side for higher
switching capacity
Detection zone: 360° horizontally, 180° vertically
Recommended
installation height: 2.5–3 m (ceiling installation)
Max. reach: High-resolution close-up range: 4 x 4 m (persons seated)
reliable long-distance range: 24 x 24 m (persons walking)
Switching threshold or BLS / BLS T: 20 –1300 lux, daylight operation
constant light level: BLS D / BLS DF: 100 –1300 lux, daylight operation
Switch-off delay: 4 – 30 min., 2h
Enclosure: IP 20
Ambient temperature: –15° to 50° C
Control signal: 1 – 10 V (max. 50 electronic ballasts)
(only BLS D + BLS DF)
Reach (IR rem. control): 4 m (BLS DF only)
*
VDE certified
Function test / test mode
BLS D / BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 18
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Adjustment of the detection zone/reach
The shrouds supplied can be
used for deliberate adjustment
of the detection zone. Using
these, it is possible for exam-
ple to cleanly separate individ-
ual workplace areas in an
open-plan office so that only
movements in the area of the
respective desk group are de-
tected. We recommend acti-
vating test mode for rapid and
precise adjustment of the de-
tection zone (see page 16).
1
2
3
4
5
6
7
8
Vertical separation =
reduction of the angle of coverage
Horizontal separation =
reduction of the reach
The shrouds are divided into 8 areas (horizon-
tally). The reach is reduced depending on the
shrouds applied (number of areas).
0 (without cov.) = 12 m = 12 m
1 = 6.5 m = 10 m
2 = 5 m = 9 m
3 = 3.5 m = 8 m
4 = 3 m = 6 m
5 = 2.3 m = 4.5 m
6 = 1.5 m = 3 m
7 = 1 m = 2.2 m
8 < 0.5 m < 1 m
19
BLS DIMM
IR remote control
For the sensor BLS DF the op-
tion also exists of adjusting
the desired light level by
means of an infrared remote
control. The last selected set-
ting is respectively maintained
in this case. By constantly
pressing the (–)-button, the
lighting also be switched OFF
completely using the remote
control. By subsequent press-
ing the (+) button, the desired
level of brightness can be
readjusted.
Reset function
By simultaneously pressing
both buttons (+) and (–), all the
modifications made using the
remote control are reset to the
brightness setting adjusted on
the sensor.
Important note:
During adjustment of the
brightness setting, it should
be noted that the measured
brightness values of the sen-
sor refer to the installation site
of the sensor under the ceiling
and may therefore not neces-
sarily correspond to the
desired brightness at the
workplace.
Guideline values for adjusting the lux and time value
The following guideline values may be taken as a basis:
Brightness setting:
Passageways (not working areas): 200 lux
Working areas (offices, training rooms, workshops etc.): 500 lux
Working areas requiring good light:
(technical drawing, laboratories, precise work) 700 – 1000 lux
Switch-off delay:
The switch-off delay can be continuously adjusted according to the use of the respective rooms:
Mainly standing activities (e. g. photocopier room, passageways etc.): 4 min.
Mainly seated activities (desk work by 3–4 individuals): 7 min.
Mainly seated activities (desk work by 1–2 individuals): 10 min.
Seated activities with little movement (reading, EDP, etc.): > 10 min.
If the lighting immediately switches ON again in response to movement in spite of occupancy,
the switch-off delay is to be increased.
18
Functions
BLS DF
A
r
Shroud
(see drawing)
Reach
(installation
at a height
of 2.5 m)
Reach
(installation
at a height
of 5 m)
AC
SE
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 20
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Functional Warranty
Declaration of conformity
This product complies with
Low Voltage Directive
06/95/EC, EMC Directive
04/108/EC and RoHS
Directive 02/95/EC.
This Steinel product has been
manufactured with utmost
care, tested for proper opera-
tion and safety and then sub-
jected to random sample in-
spection. STEINEL undertakes
the guarantee for perfect con-
dition and function.
The warranty period is 36
months and starts on the date
of sale to the consumer. We
will remedy defects caused by
material flaws or manufactur-
ing faults. The warranty will be
met by repair or replacement
of defective parts at our own
discretion. The warranty shall
not cover damage to wear
parts, damage or defects
caused by improper treatment
or maintenance. Further con-
sequential damage to other
objects is excluded.
Claims under the warranty
shall only be accepted if the
product is sent fully assem-
bled and well packed com-
plete with a brief description of
the fault, a receipt or invoice
(date of purchase and dealer's
stamp) to the appropriate Ser-
vice Centre.
Repair Service:
Our Customer Service Depart-
ment will repair faults not cov-
ered by warranty or after the
warranty period. Please send
the product well packed to
your nearest Service Centre.
21
Troubleshooting
Malfunction Cause Remedy
20
Light does not switch ON No supply voltage
Lux value set too low
No motion detection
Check supply voltage
Slowly increase lux value
until light switches ON
Establish a clear view of
the sensor
Check detection zone
Light does not switch OFF Lux value too high
Overshoot time running out
Interferring sources of
heat, e.g.: fan heaters,
open doors and windows,
pets
Reduce lux value
Wait until overshoot time
elapses; reduce overshoot
time if necessary
Blank off stationary
sources of interference
using shrouds
Sensor switches OFF
in spite of occupancy
Overshoot time too short Increase overshoot time
Sensor switches OFF
too late
Overshoot time too long Reduce overshoot time
Sensor switches ON too
late when approached
frontally
Reach is reduced when
approached frontally
Install further sensors
Reduce distance between
two sensors
Sensor switches
too frequently with chang-
ing cloud cover
Overshoot time set too
short
Increase overshoot time
more pleasant switching
behaviour
only BLS D, DF:
Sensor does not react to
changes in brightness in
test mode
Control leads (+,–)
not correctly wired
Replace the control leads
on the sensor or electronic
ballast
only BLS DF:
Sensor does not switch ON
with occupancy in spite of
darkness
Sensor previously switched
OFF with hand-held trans-
mitter
Lux value selected too low
Activate sensor by press-
ing the (+) button on the
hand-held transmitter
Increase lux value on the
sensor or by pressing the
(+ ) button on the hand-
held transmitter
The light level set with the
hand-held transmitter is no
longer saved
Settings deleted, since
voltage supply to the sen-
sor cut off
(e.g. by light switch or
power failure)
Ensure voltage supply to
the sensor
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 22
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Zone de détection
L’efficacité du pilotage de
l’éclairage par BLS dépend
dans une large mesure du
nombre, de l'état et de la dis-
position des segments de len-
tille. Avec trois détecteurs py-
roélectriques et une zone de
détection de 360°, compre-
nant 11 niveaux avec 1320
zones de commutation, même
les plus faibles mouvements
sont détectés en zone proche
(rayon de 2 m autour du dé-
tecteur) et les mouvements
de marche en zone lointaine
(jusqu'à 12 m). Ainsi, même
les grands bureaux peuvent
être surveillés avec seulement
une détecteur.
Si des zones particulières
doivent être exclues du
champ de détection, il suffit
de régler celui-ci à l'aide de
caches enfichables (voir
chapitre Réglage de la portée).
Lieu de montage optimum :
Ce détecteur convient unique-
ment pour le montage au pla-
fond. De manière générale et
pour garantir une détection
optimale en zone proche, il
convient de le monter de ma-
nière à ce que les personnes
assises puissent le voir devant
elles à une distance d’environ
1 m (voir illustration). Les per-
sonnes en déplacement sont
également détectée en zone
lointaine.
23
1m
360°
1
2
3
4
1m
1m
2m
2m
12 m
12 m
0
Détecteur
Zone proche (rayon 2 m)
Position assise
Zone lointaine (rayon 12 m)
Consignes de sécurité
F
Avant toute intervention sur
le détecteur, couper l'ali-
mentation électrique !
Pendant le montage, les
conducteurs à raccorder
doivent être hors tension.
Il faut donc d'abord couper
le courant et s'assurer de
l'absence de courant à l'ai-
de d'un testeur de tension.
L'installation du détecteur
implique une intervention
sur le réseau électrique et
doit donc être effectuée
correctement et conformé-
ment à la norme
NF C-15100.
Le signal au niveau de la
sortie de commande 1–10 V
est alimenté en basse ten-
sion fonctionnelle en non
en basse tension de pro-
tection (SELV). C'est la rai-
son pour laquelle le câblage
doit être réalisé avec des
fils isolés de manière
adéquate.
Fonctionnement / Fonction de base
Les détecteurs infrarouges
de la série LuxMaster règlent
l'éclairage par ex. dans des
locaux comme les bureaux,
les écoles ou d'autres bâti-
ments publics, en fonction
de la présence de personnes
(détection de mouvement)
et de la luminosité ambiante.
Le capteur lumineux intégré
dans le détecteur mesure en
permanence la luminosité
ambiante et compare cette
valeur avec la valeur de
consigne sélectionnée au
niveau du détecteur (BLS /
BLS T 20 – 1300 lux et BLS
D/BLS DF 100 – 1300 lux).
Lorsque la luminosité ambian-
te est suffisante, l'éclairage
n’est pas déclenché. Lorsque
la luminosité ambiante est
inférieure à la valeur de
consigne, l’éclairage est
déclenché dès qu'un mouve-
ment est détecté dans la pièce.
4 variantes sont possibles :
BLS - Allumage et extinction
de l'éclairage indépendam-
ment de la présence de
personnes et de la lumino-
sité ambiante.
Eclairage uniquement en cas
de présence de personnes
dans la pièce. Lorsque la lumi-
nosité ambiante atteint la va-
leur de consigne programmée,
l'éclairage est automatique-
ment coupé.
BLS T - Détecteur de pré-
sence semi-automatique.
Mise en MARCHE manuelle.
ARRET automatique lorsque
la lumière n'est plus néces-
saire.
L'utilisateur allume manuelle-
ment la lumière en appuyant
sur un bouton (fonction salle
de classe). Si l’on appuie briè-
vement sur le bouton (env.
0.2-1 s), l'alimentation en cou-
rant est interrompue pour un
bref instant, le BLS T passe au
fonctionnement standard par
détecteur. Lorsque l'utilisateur
quitte la pièce sans actionner
à nouveau la touche, l'éclairage
s'éteint une fois que le temps
programmé est écoulé ou
lorsque la valeur de crépuscu-
larité est dépassée. Si, en
quittant la pièce, l’on appuie à
nouveau brièvement sur le
bouton, la lampe, la lampe
s'éteint automatiquement et
ne se rallume pas automati-
quement.
Lorsque la touche est action-
née plus longtemps, (> 2 s), le
BLS est mis entièrement hors
tension. Un autotest est effec-
tué et l'éclairage s'allume pour
la durée programmée.
BLS D – Variation de l'éclai-
rage en fonction de la
présence et de la lumière
du jour
Le détecteur capte simultané-
ment la différence entre la va-
leur de consigne programmée
et la luminosité ambiante et
module l’éclairage jusqu'à
ce que la valeur de consigne
programmée soit atteinte
dans la pièce. Les variations
de luminosité sont captés en
permanence par le détecteur
et compensés de manière
à ce qu'il règne une lumino-
sité constante dans la pièce
lorsqu'une personne y est
présente.
BLS DF – Variation de
l'éclairage en fonction de
la présence et de la lumière
du jour – en option avec
télécommande
Ce détecteur permet en plus
de modifier le niveau luminosité
(valeur de consigne de lumi-
nosité) au moyen d'une télé-
commande à infrarouge. Ainsi,
il est possible de réduire aisé-
ment la luminosité jusqu'au
niveau souhaité par ex. pour
la présentation de diapositives
ou lors de l'utilisation d'un
projecteur.
La fonction reset (actionne-
ment simultané des deux
touches (+) et (-)) permet de
retourner confortablement au
degré de luminosité program-
mé au niveau du détecteur.
22
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 24
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Installation électrique/Commande automatique
Exemple de branchement/Extinction manuelle
Exemple de branchement BLS T semi-automatique
BLS / BLS T
BLS BLS D / BLS DF
BLS D / BLS DF
L
LN
L
LN
+
Lors du choix des câbles, res-
pecter toujours les consignes
d'installation conformément à la
norme NF C-15100 (cf.
consignes de sécurité page 22).
Pour le câblage des détecteurs
BLS D et BLS DF les instructions
suivantes sont valables :
Conformément à NF C-15100
520 alinéa 6, une ligne multiple
comprenant tant bien les câbles
de tension de secteur que les fils
pilotes (1–10 V) peut être utilisée
pour le câblage entre détecteur
et ballast (par ex NYM 5 x 1,5
2
).
Le diamètre de la conduite sec-
teur ne doit pas dépasser 10 mm.
La borne de connexion au sec-
teur convient pour 2 x 1,5 mm
2
maximum ou 1 x 2,5 mm
2
.
25
Si une extinction manuelle du
fonctionnement automatique
du détecteur est souhaitée, il
est nécessaire de raccorder
un interrupteur conventionnel
en amont du détecteur.
1) Groupe de lampes, 2) BLS, 3) Interrupteur externe
1) Interrupteur, 2) BLS T,
3) Consommateur, éclairage
4) Lampe avec ballast électronique à variateur,
5) BLS D / BLS DF
Câble secteur
Lampe avec
ballast électron. à
variateur (par ex. NYM 5 x 1,5
2
)
Câble secteur
par ex.
NYM 3 x 1,5
2
Lampe
Montage/Installation
Séquences de montage
1. Défaire l'anneau enjoliveur
en appuyant légèrement
sur les côtés et en tournant
simultanément vers le bas.
2. Desserrer la vis de blocage
.
3. Retirer le boîtier du détec-
teur
de la plaque de
montage en direction de
la flèche
.
4. Fixer la plaque de montage
au plafond avec les vis et
les chevilles comprises
dans la livraison.
5. Effectuer le câblage (voir
installation électrique).
– Neutre N
– Phase L
– Phase connectée L
– Terre
– Sortie de commande +
– Sortie de commande –
– (uniquement BLS D ou
bien BLS DF)
En cas d'arrivée de câble sur
crépi, percer la rainure de l'an-
neau enjoliveur afin de passer
le câble latéralement.
16. Placer le boîtier du détec-
teur sur la plaque de mon-
tage en procédant du côté
(contre la direction de la
flèche)
.
17. Insérer la vis de blocage
.
18. Effectuer un test de fonc-
tionnement et régler la zo-
ne de détection (cf. pages
26 et 29).
19. Programmer la temporisa-
tion de l'extinction et la
valeur de consigne de lu-
minosité sur la face avant
du boîtier (bouton de ré-
glage) (cf. Fonctionnement
p. 27, chapitre Réglages).
10. Mettre en place l'anneau
enjoliveur (jusqu’au clic).
(Les caches enfichables
sont fixés au moyen de
l'anneau).
24
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 26
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Fonctionnement
BLS / BLS T / BLS D / BLS DF
BLS / BLS T
BLS D / BLS DF
27
Un potentiomètre permet de
définir la valeur de consigne
de luminosité (en lux) et de la
temporisation.
La temporisation détermine la
durée pendant laquelle la lu-
mière reste allumée après le
dernier mouvement détecté (de
4 à 15 mn). La temporisation
programmée reprend à chaque
nouveau mouvement détecté
jusqu'à ce qu'aucun mouve-
ment ne soit plus enregistré ou
que la luminosité ambiante ait
atteint la valeur de consigne de
luminosité.
Uniquement BLS / BLS T :
Mode à impulsions : Si vous
réglez l'appareil sur “ ” il est
en mode à impulsions, c'est-à-
dire que la sortie sera mise
sous tension pendant 2 s en-
viron (p. ex. pour une minuterie
de cage d'escalier). Ensuite,
le détecteur ne réagit pas aux
mouvements pendant 8 s
environ.
Le réglage de la valeur de
consigne de la luminosité (de
20 à 1300 lux) détermine le
seuil de luminosité à partir du-
quel le détecteur doit déclen-
cher l’allumage des lampes.
Lorsque l’on procède aux ré-
glages, le détecteur éteint au-
tomatiquement les lampes.
Une fois le réglage terminé,
observer les indications sui-
vantes :
Si la luminosité ambiante est
inférieure à la valeur program-
mée, les lampes s’allument ; si
elle est supérieure à la valeur
programmée, les lampes
s’éteignent – même en cas de
mouvement dans la zone de
détection.
Le degré de luminosité total de
la pièce dépend de la valeur de
consigne de luminosité pro-
grammée au niveau du détec-
teur (100 – 1300 lux). Lorsque,
en cas de détection de mouve-
ment la luminosité ambiante, est
inférieure à la valeur de consigne
programmée, le capteur lumi-
neux enregistre la différence et
varie l'éclairage de manière à ce
que la valeur de consigne sou-
haitée soit atteinte. Les varia-
tions de la lumière du jour sont
enregistrées en permanence par
le capteur lumineux et compen-
sés de manière à ce qu'il règne
une luminosité constante dans
la pièce lorsqu'une personne y
est présente.
Conseil : Il est recommandé de
régler la valeur de consigne de
luminosité en mode test (bouton
de réglage de temporisation de
l'extinction en position « Test ».
De cette façon, l’intensité lumi-
neuse s’adapte instantanément
à toute modification d’intensité
lumineuse.
Réglage de la valeur de consigne de luminosité
Réglage de la temporisation
Réglage de la valeur de consigne de luminosité
Caractéristiques techniques
BLS / BLS T
Le mode test permet de contrô-
ler le bon fonctionnement et
de régler la zone de détection
(voir également chapitre
Réglage de la portée).
Positionner le bouton de ré-
glage de crépuscularité sur
"Test" afin de démarrer le
mode test. En mode test,
indépendamment de la lumi-
nosité ambiante, le détecteur
allume la lampe avec une
temporisation de 5 s.
Remarque : Une fois que le
détecteur a éteint la lampe,
il est nécessaire d'attendre
encore env. 4 s avant que le
détecteur réagisse aux
mouvements.
Pour démarrer le mode test,
positionner le bouton de ré-
glage de la temporisation sur
"Test". Pendant le mode test,
le réglage de luminosité (varia-
tion de l'intensité lumineuse)
s'adapte simultanément à
tous les changements de
lumière (tenir par. ex. la main
devant la lentille de détection).
Ceci permet de contrôler rapi-
dement le bon câblage. Si le
détecteur ne varie pas la
lumière en fonction des varia-
tions de luminosité, le câblage
n'a pas été réalisé de manière
correcte.
Une fois le mode test terminé,
la variation du détecteur
s'adapte à nouveau de manière
optimale à l'impression de
luminosité des utilisateurs.
26
Tension : 230 V, 50 Hz
Puissance commandée : max. 2000 W (charge ohmique, par. ex. lampe à incandescence)*
max. 1000 W (halogène NV)
max. 1000 W (tube fluorescent avec ballasts conventionnels,
cos ϕ = 0,5)*
nombre maximum de ballasts électroniques :
16 x (1 x 36 W) ou 12 x (2 x 36 W) ou
12 x (1 x 58 W) ou 8 x (2 x 58 W)
Pour les puissances d'éclairage plus élevées monter un relais ou
un contacteur en amont.
Zone de détection : horizontalement 360°, verticalement 180°
Haut. d'installation recommandée : 2,5 3 m (montage au plafond)
Portée maximale : Zone de proximité à haute résolution: 4 x 4 m (personne assise)
zone lointaine sûre : 24 x 24 m (marcheur)
Crépuscularité BLS / BLS T : 20 – 1300 lux, fonctionnement diurne
niveau d'éclairage constant : BLS D / BLS DF: 100 – 1300 lux, fonctionnement diurne
Temporisation : 4 – 30 min, 2h
Indice de protection : IP 20
Température ambiante : de – 15° à 50° C
Signal de commande: 1 – 10 V (50 ballasts max.)
(uniquement BLS D + BLS DF)
Portée (télécommande IR) : 4 m (uniquement BLS DF)
*
Certifié VDE
Test de fonctionnement / mode test
BLS D / BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 28
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Réglage de la zone de détection/Portée
La mise en place de caches
enfichables permet de régler
précisément la zone de détec-
tion. Il est possible par ex. de
séparer clairement les diffé-
rents postes de travail dans un
bureau de manière à ce qu'uni-
quement les mouvements dans
les zones de travail respectives
soient enregistrés. Pour un
réglage rapide et précis de
la zone de détection, il est
recommandé d'activer le
mode test (cf. page 26).
1
2
3
4
5
6
7
8
Séparation verticale =
Réduction de l'angle de détection
Séparation horizontale =
Réduction de la portée
Les caches enfichables sont divisés en 8 zones
(horizontalement). La portée est réduite en
fonction des coques enfichables appliqués
(nombre de zones).
Cache Portée Portée
(voir croquis) (Mont. dans (Mont. dans
hauteur 2,5 m) hauteur 5 m)
0 (sans ill.) = 12 m = ,12 m
1 = 6,5 m = ,10 m
2= 6,5 m = ,99 m
3 = 3,5 m = ,98 m
4= 3,3 m = ,96 m
5 = 2,3 m = 4,5 m
6 = 1,5 m = 3,3 m
7= 1,1 m = 2,2 m
8 < 0,5 m < 1,1 m
29
BLS DIMM
Télécommande IR
Une télécommande infrarouge
est proposée en option pour
régler la valeur de consigne de
la luminosité sur le détecteur
BLS DF. C’est la dernière
valeur programmée qui est
prise en compte. Il est égale-
ment possible d'éteindre
complètement l'éclairage à
l'aide de la télécommande
en appuyant continuellement
sur la touche (–). En appuyant
de manière répétée sur la
touche (+), il est ensuite pos-
sible de retourner au niveau
de luminosité souhaité.
Fonction de réinitialisation
Appuyer simultanément sur
les deux touches (+) et (-) de
la télécommande pour retrou-
ver les réglages d’usine.
Remarque importante :
Lors du réglage de la valeur
de consigne de luminosité,
prendre en compte que les
valeurs de luminosité mesu-
rées par le détecteur sont
celles au niveau du lieu de
montage au plafond et ne
correspondent donc pas obli-
gatoirement à la luminosité
souhaitée au lieu de travail.
Valeurs indicatives pour le réglage de la valeur lux et de temporisation
Les valeurs indicatives suivantes peuvent servir de base :
Valeur de consigne de luminosité :
Zones de passage (hors de la zone de travail) : 200 lux
Zones de travail (bureaux, lieux de formation, lieux de travail etc.) : 500 lux
Zones de travail nécessitant beaucoup de lumière :
(dessins techniques, laboratoires, travaux de précision) 700 – 1000 lux
Temporisation :
Il est possible de régler la temporisation de l'extinction en continu selon
l'utilisation des différentes pièces :
Travaux effectués en majeure partie debout (par. ex. pièce avec photocopieuse, couloirs etc.) : 4 min
Travaux effectués en majeure partie assis (travaux de bureaux 3–4 personnes) : 00 7 min
Travaux effectués en majeure partie assis (travaux de bureaux 1–2 personnes) 10 min
Travaux effectués assis avec peu de mouvements (lecture, travaux informatiques etc.) : > 10 min
Si malgré la présence de personnes dans la pièce les lampes s’éteignent
et se rallument suite à la détection d’un mouvement, il convient
d’augmenter la temporisation.
28
Fonctionnement
BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 30
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Garantie de fonctionnement
Déclaration de conformité
Ce produit est conforme à la
directive basse tension
06/95/CE, à la directive com-
patibilité électromagnétique
04/108/CE et à la directive
RoHS 02/95/CE.
Ce produit Steinel a été fabri-
qué avec le plus grand soin.
Son fonctionnement et sa
sécurité ont été contrôlés
conformément aux directives
en vigueur et il a été soumis
à un contrôle final par sonda-
ge. STEINEL garantit un état
et un fonctionnement irrépro-
chables.
La durée de garantie est de
36 mois et débute au jour de
la vente au consommateur.
Nous remédions aux défauts
provenant d'un vice de matiè-
re ou de construction. La ga-
rantie sera assurée à notre
discrétion par réparation ou
échange des pièces défec-
tueuses. La garantie ne s’ap-
plique ni aux pièces d’usure,
ni aux dommages et défauts
dus à une utilisation ou main-
tenance incorrectes. Les dom-
mages consécutifs causés à
d'autres objets sont exclus de
la garantie.
La garantie ne s'applique que
si l'appareil non démonté est
retourné au service après-
vente le plus proche, dans un
emballage adéquat, accompa-
gné d’une brève description
du défaut et d'un ticket de
caisse ou d'une facture por-
tant la date d'achat et le ca-
chet du vendeur.
Service de réparation :
Le service après-vente de
notre usine effectue égale-
ment les réparations non cou-
vertes par la garantie ou sur-
venant après l'expiration de
celle-ci. Veuillez envoyer le
produit correctement emballé
à la station de service après-
vente la plus proche.
31
Dysfonctionnements
Problème Cause Remède
30
l'éclairage ne s'allume pas pas de tension d'alimen-
tation
valeur lux programmée
trop faible
pas de détection de
mouvement
vérifier la tension d'alimen-
tation
augmenter doucement la
valeur lux jusqu'à ce que
l'éclairage s'allume
dégager le champ de
détection
vérifier la zone de détection
la lumière ne s'éteint pas valeur lux trop élevée
la temporisation s'écoule
sources de chaleur pertur-
bantes par ex. : radiateur
soufflant, portes ou fe-
nêtres ouvertes, animaux
domestiques
réduire la valeur lux
attendre que la temporisa-
tion soit écoulée et la ré-
duire éventuellement
masquer les sources fixes
de perturbation avec des
caches enfichables
le détecteur allume trop
tard l'éclairage pour le
sens de passage frontal
portée pour sens de pas-
sage frontal réduite
installer des détecteurs
supplémentaires
réduire l'écart entre deux
détecteurs
en cas de variation de lumi-
nosité causée par le passage
de nuages, le détecteur
commute trop souvent
temporisation programmée
trop courte
augmenter la temporisation
conditions d’éclairage
plus agréables
uniquement BLS D, DF :
en mode test, le détecteur
ne réagit pas aux modifica-
tions de luminosité
le câblage est incorrect refaire le câblage au niveau
du détecteur ou du ballast
uniquement BLS DF :
malgré l'obscurité, le
détecteur n'allume pas
l'éclairage en cas de
présence
détecteur déconnecté au-
paravant avec la télécom-
mande radio de poche
valeur lux programmée
trop faible
actionner le détecteur en
appuyant sur la touche (+)
de la télécommande radio
de poche
augmenter la valeur lux au
niveau du détecteur ou en
appuyant sur la touche (+ )
de la télécommande radio
de poche
le degré de luminosité pro-
grammé au moyen de la
télécommande radio de
poche n'est plus enregistré
réglages effacés parce que
l'alimentation en tension du
détecteur a été interrom-
pue (par ex. par interrup-
teur ou en raison d'une
panne de courant)
assurer l'alimentation en
courant du détecteur
le détecteur éteint trop tard
l'éclairage
temporisation trop longue réduire la temporisation
le détecteur éteint l'éclaira-
ge malgré une présence
temporisation trop courte augmenter la temporisation
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 32
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Observeringsgebied
De betrouwbare aanwezig-
heidsherkenning van de
BLS-sensoren hangt groten-
deels van het aantal, de aard
en de plaatsing van de lens-
segmenten af. Met drie pyro-
sensoren en een registratiebe-
reik van 360°, dat in 11 niveaus
met 1320 schakelzones ver-
deeld is, worden zelfs de
kleinste bewegingen dichtbij
(2 m radius rondom de sensor)
en loopbewegingen veraf
(max. 12 m) geregistreerd.
Op die manier kunnen zelfs
grote kantoren met slechts
één sensor worden bewaakt.
Als bepaalde gebieden niet
geregistreerd moeten worden,
kan het registratiebereik door
plaatsing van afdekplaatjes
gericht worden beperkt
(zie hoofdstuk 'Reikwijdte-
instelling').
Optimale montageplaats:
de sensor is alleen geschikt
voor montage aan het pla-
fond. Hij moet altijd zo geïn-
stalleerd worden dat zittende
personen de sensor op een
afstand van ca. 1 m voor zich
zien (zie afb.). In deze positie
is de registratiebetrouwbaarheid
dichtbij het grootst. Lopende
mensen worden ook nog in
het bereik veraf geregistreerd.
33
1m
360°
1
2
3
4
1m
1m
2m
2m
12 m
12 m
0
Sensor
Bereik dichtbij (radius 2 m)
Zitpositie
Bereik veraf (radius 12 m)
Veiligheidsvoorschriften
NL
Voor alle werkzaamheden
aan de sensor dient de
spanningstoevoer te
worden onderbroken!
Bij de montage moet de
elektrische leiding die u wilt
aansluiten zonder spanning
zijn. Daarom eerst de
stroom uitschakelen en op
spanningsloosheid testen
met een spanningstester.
Bij de installatie van de
sensor werkt u met net-
spanning. Dit moet vak-
kundig en volgens de ge-
bruikelijke installatievoor-
schriften en aansluitings-
voorwaarden worden uit-
gevoerd. (NL: NEN 1010,
B: (AREI) NBN 15-101)
Het bij de 1–10 V-regeluit-
gang ter beschikking ge-
stelde signaal is een func-
tionele lage spanning en
geen veilige lage spanning
(SELV). Gebruik daarom bij
de bekabeling overeenkom-
stig geïsoleerde leidingen.
Werking / basisfuncties
De infraroodsensoren van de
serie LuxMaster regelen de
verlichting, bijv. in kantoren,
scholen of openbare gebou-
wen, afhankelijk van de aan-
wezige personen (bewegings-
registratie) en omgevingslicht-
sterkte. De in de sensor geïn-
tegreerde lichtvoeler meet
continu de omgevingslicht-
sterkte en vergelijkt die met
de op de sensor ingestelde
waarde voor de gewenste
lichtsterkte (BLS / BLS T 20 –
1300 lux en BLS D/BLS DF
100 – 1300 lux). Als de omge-
vingslichtsterkte voldoende
is, wordt de verlichting niet
ingeschakeld. Ligt de omge-
vingslichtsterkte onder de in-
gestelde waarde voor de ge-
wenste lichtsterkte, zorgt een
beweging in de ruimte ervoor
dat de verlichting wordt inge-
schakeld. Er kan gekozen
worden uit 4 varianten:
BLS – in- en uitschakelen
van de verlichting onafhan-
kelijk van aanwezigheid en
daglicht.
Licht alleen bij aanwezigheid
in de ruimte. Als de omge-
vingslichtsterkte de ingestelde
waarde bereikt, wordt de ver-
lichting automatisch weer
uitgeschakeld.
BLS T – half automatische
aanwezigheidsmelder.
Manueel AAN. Automatisch
UIT, als er geen licht meer
nodig is.
De gebruiker schakelt het licht
met een integreerbare schake-
laar (opener) met de hand in
(klaslokaalfunctie). Door het
kort activeren en onmiddellijk
loslaten van de knop / scha-
kelaar (ca. 0,2 – 1 sec.) wordt
de stroomtoevoer voor korte
tijd onderbroken, de BLS T
gaat over op standaard-sen-
sorwerking. Als de ruimte ver-
laten wordt zonder de schake-
laar opnieuw te activeren, dan
gaat de verlichting bij afloop
van de ingestelde tijd of bij
overschrijden van de ingestelde
schemerwaarde uit. Als de
knop bij het verlaten van de
ruimte opnieuw kort wordt in-
gedrukt (ca. 0,2 – 1 sec.) scha-
kelt de lamp automatisch uit
en niet automatisch weer aan.
Als de knop langer wordt in-
gedrukt (> 2 sec.), dan is de
BLS compleet spanningsvrij
en voert bij het loslaten een
zelftest uit; de verlichting gaat
voor de ingestelde tijd aan.
BLS D – dimmen van de
verlichting, afhankelijk van
aanwezigheid en daglicht
De sensor registreert tegelij-
kertijd het verschil tussen de
ingestelde waarde en de om-
gevingslichtsterkte en dimt de
verlichting zover tot de inge-
stelde waarde in de kamer is
bereikt. Veranderingen in de
omgevingslichtsterkte worden
continu door de sensor gere-
gistreerd en zo gecompen-
seerd, dat bij aanwezigheid
een constant lichtniveau in
de ruimte heerst.
BLS DF – dimmen van de
verlichting, afhankelijk van
aanwezigheid en daglicht –
naar keuze met afstandsbe-
diening
Bij deze sensor kan het licht-
niveau (ingestelde waarde
voor lichtsterkte) ook met een
infrarood-afstandsbediening
worden veranderd. Hierdoor
kan de verlichting, bijv. bij dia-
presentaties of bij gebruik van
een projector, eenvoudig tot
het gewenste lichtniveau wor-
den gedimd.
De met de afstandsbediening
uitgevoerde veranderingen
van de ingestelde waarde voor
de lichtsterkte kunnen met de
reset-functie (tegelijkertijd in-
drukken van beide toetsen (+)
en (–)) weer eenvoudig gereset
worden naar het op de sensor
ingestelde lichtniveau.
32
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 34
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Elektrische installatie/automatische werking
Aansluitvoorbeeld/handmatige uitschakeling
Aansluitvoorbeeld BLS T, halfautomatisch
BLS / BLS T
BLS BLS D / BLS DF
BLS D / BLS DF
L
LN
L
LN
+
Bij het kiezen van de bekabe-
lingsleidingen moeten altijd de
installatievoorschriften volgens
VDE 0100 worden opgevolgd
(zie de veiligheidsvoorschriften
op pagina 32). Voor de bekabe-
ling van BLS D en BLS DF
geldt: volgens VDE 0100 520
punt 6 mag voor de bekabeling
tussen sensor en elektronisch
voorschakelapparaat een meer-
voudige leiding worden ge-
bruikt, die zowel de netspan-
ningskabels als de regelkabels
(1–10 V) bevat (bijv. NYM 5 x 1,5
2
).
De stroomtoevoerkabel mag
een max. diameter van 10 mm
hebben.
Het klembereik van de stroom-
toevoerklem is voor maximaal
2 x 1,5 mm
2
of 1 x 2,5 mm
2
geschikt.
35
Als de automatische functie van
de sensor bewust met de hand
uitgeschakeld moet kunnen wor-
den, moet een conventionele
schakelaar worden voorgescha-
keld bij de sensor.
1) Lampengroep, 2) BLS, 3) Externe schakelaar
1) Openerschakelaar, 2) BLS T, 3) Verbruiker, verlichting
4) Lamp met elektronisch DIM-voorschakelapparaat,
5) BLS D / BLS DF
Stroomtoe-
voerkabel
Lamp met
elektronisch
DIM-voorschakel-
apparaat (bijv. NYM 5 x 1,5
2
)
Stroomtoe-
voerkabel
bijv. NYM 3 x 1,5
2
Lamp
Montage/installatie
Montagestappen
1. Sierring
door licht aan-
drukken aan de zijkanten en
gelijktijdig draaien naar on-
deren toe wegnemen.
2. Borgschroef
losdraaien.
3. Sensorhuis
in pijlrichting
van de montageplaat
trekken.
4. Montageplaat met de
meegeleverde schroeven
en pluggen aan het pla-
fond bevestigen.
5. Aansluiting maken (zie
elektrische installatie).
– nuldraad N
– fase L
– geschakelde fase L
– aarde
(aardedraad)
– regeluitgang +
– regeluitgang –
– (alleen BLS D resp. BLS DF)
Bij leidingen op de muur moet
de gleuf van de sierring door-
gestoten worden en de kabel
vanaf de zijkant worden door-
gevoerd.
16. Sensorhuis vanaf de zij-
kant (tegen de pijlrichting
in)
op de montageplaat
steken.
17. Borgschroef
indraaien.
18. Functietest uitvoeren en
het registratiebereik instellen
(zie pagina's 36 en 39).
19. Uitschakelvertraging en
gewenste waarde voor de
lichtsterkte aan de kopse
kant van de behuizing
(instelregelaar) instellen
(zie functies pag. 37,
onder 'Instellingen').
10. Sierring plaatsen (vastklik-
ken). Afdekplaatjes worden
door de sierring gefixeerd.
34
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 36
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Functies
BLS / BLS T / BLS D / BLS DF
BLS / BLS T
BLS D / BLS DF
37
Zowel voor de bepaling van de
gewenste lichtsterktewaarde
(lux-waarde) als voor de uitscha-
kelvertraging (tijdsinstelling)
staat een potentiometer ter
beschikking.
Met de uitschakelvertraging
(4 – 15 minuten) wordt de tijds-
duur vastgelegd, dat het licht
na registratie van de laatste
beweging ingeschakeld blijft.
Bij iedere volgende bewegings-
registratie begint de ingestelde
nalooptijd opnieuw, net zolang
tot er geen beweging meer
wordt herkend of de omge-
vingslichtsterkte de ingestelde
waarde voor de lichtsterkte
heeft bereikt.
Alleen BLS / BLS T:
Impulsmodus: als u de regelaar
op ' ' zet, staat het apparaat
in de impulsmodus, d.w.z. de
uitgang wordt voor ca. 2 sec.
ingeschakeld (bijv. voor de au-
tomatische verlichting van het
trappenhuis). Daarna reageert
de sensor ca. 8 sec. niet op
bewegingen.
De waarde voor de lichtsterkte
die op de sensor kan worden
ingesteld (20 – 1300 lux) be-
paalt het daglichtafhankelijke
schakelgedrag van de sensor.
Als het instelknopje wordt
gedrukt, schakelt de sensor
de verlichting in ieder geval
uit. Na beëindiging van het
instellen geldt:
als het daglichtpercentage
onder de ingestelde waarde
voor de lichtsterkte ligt, wordt
de verlichting ingeschakeld;
als het daglichtpercentage
boven de ingestelde waarde
voor de lichtsterkte ligt, wordt
de verlichting uitgeschakeld –
ook wanneer er een beweging
in het registratiebereik is.
De gewenste waarde voor de
lichtsterkte die op de sensor
kan worden ingesteld (100 –
1300 lux) bepaalt het totale
lichtniveau in de ruimte. Als de
omgevingslichtsterkte bij een
bewegingsregistratie onder de
ingestelde waarde ligt, regis-
treert de lichtvoeler het ver-
schil en voert de verlichting zo-
ver op tot de gewenste waarde
is bereikt. Veranderingen in het
daglichtpercentage worden
continu door de lichtvoeler
geregistreerd en zo gecom-
penseerd, dat bij aanwezig-
heid een constant lichtniveau
in de ruimte heerst.
Tip: de ingestelde waarde
voor de lichtsterkte kan het
beste in de testmodus worden
ingesteld (knopje voor uit-
schakelvertraging op 'Test'),
omdat de lichtregeling (dimmen)
dan meteen alle lichtsterkte-
veranderingen volgt.
Instelling van de gewenste waarde voor lichtsterkte
Instelling van de gewenste waarde voor lichtsterkte
Instelling van de gewenste waarde voor lichtsterkte
Technische gegevens
BLS / BLS T
De testmodus is bedoeld om
de functie te controleren, maar
ook voor de gerichte instelling
van het registratiebereik
(zie ook onder 'Reikwijdte-
instelling').
Om de testmodus te active-
ren moet het instelknopje voor
de schemerinstelling op 'Test'
worden gedraaid. In de test-
modus schakelt de sensor de
verlichting met een naloop-
duur van 5 seconden, onaf-
hankelijk van de omgevings-
lichtsterkte.
Opmerking: als de sensor de
verlichting uitschakelt, moet
daarna nog een korte wacht-
tijd van ca. 4 sec. worden
aangehouden, voordat de
sensor opnieuw op bewegin-
gen kan reageren.
Om de testmodus te active-
ren moet het instelknopje voor
de tijdsinstelling op 'Test' wor-
den gedraaid. Tijdens de test-
modus volgt het licht (dim-
men) meteen alle lichtsterkte-
veranderingen (bijv. hand voor
de sensorlens houden). Op die
manier kan snel gecontroleerd
worden of de kabels goed zijn
aangesloten. Als de sensor de
verlichting niet passend bij de
lichtsterkteveranderingen
regelt, is de aansluiting niet
correct uitgevoerd.
Als de testmodus weer wordt
verlaten, wordt het dimgedrag
van de sensor weer optimaal
aan het menselijke gevoel
aangepast.
36
Netspanning: 230 V, 50 Hz
Schakelvermogen: max. 2000 W (ohmse belasting, bijv. gloeilamp)*
max. 1000 W (halogeen laag voltage)
max. 1000 W (TL-lampen met conventionele
voorschakelapparaten, cos ϕ = 0,5)*
max. aantal elektronische voorschakelapparaten:
16 x (1 x 36 W) of 12 x (2 x 36 W) of
12 x (1 x 58 W) of 8 x (2 x 58 W)
Bij grotere schakelvermogens moet een relais of beveiliging
voorgeschakeld worden.
Registratiebereik: horizontaal 360°, verticaal 180°
Aanbevolen montagehoogte: 2,5 – 3 m (montage aan het plafond)
Max. reikwijdte: hoge resolutie dichtbij: 4 x 4 m (zittende personen)
veilig bereik verder weg: 24 x 24 m (lopende mensen)
Schakelniveau resp. BLS / BLS T: 20 – 1300 lux, daglichtstand
constant lichtniveau: BLS D/BLS DF: 100 – 1300 lux, daglichtstand
Uitschakelvertraging: 4 – 30 min., 2h
Bescherming: IP 20
Omgevingstemperatuur: –15 tot 50 °C
Stuursignaal: 1–10 V (max. 50 elektronische voorschakelapparaten)
(alleen BLS D + BLS DF)
Reikwijdte (IR-afstandsbed.): 4 m (alleen BLS DF)
*
VDE-gecertificeerd
Functietest / testmodus
BLS D / BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 38
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
Instelling van het registratiebereik/reikwijdte
Voor een gerichte instelling
van het registratiebereik kun-
nen de meegeleverde afdek-
plaatjes worden gebruikt.
Hierdoor kunnen bijv. in een
groot kantoor verschillende
werkgebieden goed van elkaar
worden gescheiden, zodat al-
leen bewegingen binnen een
bepaalde bureaugroep worden
geregistreerd. Wij adviseren
voor een snelle en nauwkeuri-
ge instelling van het registra-
tiebereik om de testmodus te
activeren (zie pagina 36).
1
2
3
4
5
6
7
8
Verticale scheiding =
verkleining van de registratiehoek
Horizontale scheiding =
verkleining van de reikwijdte
De afdekplaatjes zijn in 8 segmenten (horizon-
taal) verdeeld. Afhankelijk van de geplaatste
afdekplaatjes (aantal segmenten) wordt de
reikwijdte verkleind.
Afdekking Reikwijdte Reikwijdte
(zie tekening) (montage op (montage op
2,5 m hoogte) 5 m hoogte)
0 (zonder afd.) = 12 m = ,12 m
1 = 6,5 m = ,10 m
2= 6,5 m = ,99 m
3 = 3,5 m = ,98 m
4= 3,3 m = ,96 m
5 = 2,3 m = 4,5 m
6 = 1,5 m = 3,3 m
7= 1,1 m = 2,2 m
8 < 0,5 m < 1,1 m
39
BLS DIMM
IR-afstandsbediening
Voor sensor BLS DF bestaat
bovendien de mogelijkheid om
de gewenste waarde voor de
lichtsterkte met een IR-af-
standsbediening in te stellen.
De als laatste gekozen instel-
ling blijft dan steeds opgesla-
gen. Door continu op de (–)-
toets te drukken, kan de ver-
lichting met de afstandsbedie-
ning ook helemaal worden uit-
geschakeld. Door herhaalde-
lijk op de (+)-toets te drukken,
kan daarna het gewenste
lichtsterkteniveau weer worden
ingesteld.
Reset-functie
Door tegelijkertijd op de twee
toetsen (+) en (–) te drukken,
worden alle met de afstands-
bediening uitgevoerde veran-
deringen weer gereset naar de
op de sensor ingestelde waarde
voor de lichtsterkte.
Belangrijke informatie:
houd er bij de instelling van de
gewenste waarde voor de
lichtsterkte rekening mee dat
de door de sensor gemeten
lichtsterktewaarden betrek-
king hebben op de montage-
plaats van de sensor onder
het plafond en daarom niet
altijd overeenkomen met de
gewenste lichtsterkte op de
werkplek.
Richtwaarden voor de instelling van de lux- en tijdwaarde
De volgende richtwaarden kunnen ten grondslag worden gelegd:
ingestelde waarde voor de lichtsterkte:
doorgangszones (geen werkbereik): 200 lux
werkbereiken (kantoren, cursusruimtes, werkplaatsen etc.): 500 lux
zichtintensieve werkbereiken:
(technisch tekenen, laboratoria, nauwkeurig werken) 700 – 1000 lux
Uitschakelvertraging:
de uitschakelvertraging kan traploos worden ingesteld, passend bij het gebruik van
de betreffende ruimte:
hoofdzakelijk staande bezigheden (bijv. kopieerruimte, doorgangen etc.): 00 4 min.
hoofdzakelijk zittende bezigheden (bureauwerk van 3 à 4 personen): 00 7 min.
hoofdzakelijk zittende bezigheden (bureauwerk van 1 à 2 personen): 0 10 min.
zittende bezigheden met weinig beweging (lezen, computer etc.): > 10 min.
Mocht de verlichting ondanks aanwezigheid na het uitschakelen door een beweging
meteen weer inschakelen, dan moet de uitschakelvertraging worden verhoogd.
38
Functies
BLS DF
LuxMaster_10spr 27.08.2008 13:32 Uhr Seite 40
PK Elektronik Vertriebs GmbH, E-Mail: [email protected], Internet: www.pkelektronik.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

STEINEL LuxMaster Operating Instructions Manual

Taper
Operating Instructions Manual

dans d''autres langues