PR 2204V104-UK Manuel utilisateur

Taper
Manuel utilisateur
2204
Isolation amplifier
No. 2204V104-UK
From ser. no. 970205001
1540
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi – og
din garanti for kvalitet.
PR electronics A/S oers a wide range of analog and digital signal
conditioning devices for industrial automation. The product range
includes Isolators, Displays, Ex Interfaces, Temperature Transmitters,
and Multifunctional Devices. You can trust our products in the
most extreme environments with electrical noise, vibrations and
temperature fluctuations, and all products comply with the most
exacting international standards. »Signals the Best« is the epitome
of our philosophy – and your guarantee for quality.
PR electronics A/S ore une large gamme de produits pour le
traite ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux acheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in-
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
DK
UK
FR
DE
2204V104-UK 1
ISOLATION AMPLIFIER
Type 2204
CONTENTS
Warning ....................................................................................................... 2
Symbol identification ............................................................................ 3
Safety instructions ................................................................................. 3
Applications............................................................................................... 6
Technical characteristics ...................................................................... 6
Input ............................................................................................................. 6
Output ......................................................................................................... 7
Electrical specifications ........................................................................ 7
Order: 2204 ............................................................................................... 9
Block diagram ........................................................................................... 9
Programming ............................................................................................ 10
2 2204V104-UK
WARNING
This device is designed for connection to hazardous electric volt-
ages. Ignoring this warning can result in severe personal injury or
mechanical damage.
To avoid the risk of electric shock and fire, the safety instructions
of this manual must be observed and the guidelines followed. The
electrical specifications must not be exceeded, and the device
must only be applied as described in the following.
Prior to the commissioning of the device, this manual must be
examined carefully.
Only qualified personnel (technicians) should install this device. If
the equipment is used in a manner not specified by the manufac-
turer, the protection provided by the equipment may be impaired.
WARNING
Until the device is fixed, do not connect hazardous voltages to the
device. The following operations should only be carried out on a
disconnected device and under ESD safe conditions:
Dismantlement of the device for setting of DIP switches
and jumpers.
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device and replacement of circuit breakers must
be done by PR electronics A/S only.
WARNING
To keep the safety distances, devices with two built-in relays must
not be connected to both hazardous and non-hazardous voltages
on the same device’s relay contacts.
SYSTEM 2200 must be mounted in socket type S3B Releco (order
no 7023).
HAZARDOUS
VOLTAGE
INSTAL-
LATION
GENERAL
2204V104-UK 3
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand. Potentially lethal
situations.
The CE mark proves the compliance of the device with the requirements
of the directives.
The double insulation symbol shows that the device is protected by dou-
ble or reinforced insulation.
SAFETY INSTRUCTIONS
DEFINITIONS
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50
to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the
knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the device
whether the type corresponds to the one ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as
well as rain and heavy moisture. If necessary, heating in excess of the stated limits
for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and instruc-
tions in the manual and who are able to follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please
contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
4 2204V104-UK
Mounting and connection of the device should comply with national legislation for
mounting of electric materials, i.a. wire cross section, protective fuse, and location.
Descriptions of Input / Output and supply connections are shown in the block
diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it
should be easily accessible and close to the device.
The power switch should be marked with a label telling it will switch off the volt-
age to the device.
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external volta-
ges must be carried out according to the specifications of this manual.
The technician must use tools and instruments that are safe to use.
NORMAL OPERATION
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with distil-
led water.
LIABILITY
To the extent the instructions in this manual are not strictly observed, the custom-
er cannot advance a demand against PR electronics A/S that would otherwise exist
according to the concluded sales agreement.
2204V104-UK 5
HOW TO DISMANTLE SYSTEM 2200
Picture 1:
The back panel of the module is
detached from the housing by way of
a screw-driver.
Picture 2:
After this, the back panel can be pulled
out together with the PCB, but please
notice the position of the PCB as there
is a number of different positions
in the house. Do not pull the wires
unnecessarily, instead pull the PCB.
Switches and jumpers can now be
moved. When assembling the back
plate and housing, please make sure
no wires are stuck.
6 2204V104-UK
ISOLATION AMPLIFIER 2204
• Input galvanically separated from output and supply
• Current or voltage input
• Signal conversion
• Current and voltage output
• 24 VDC supply or universally supplied
• Applicable in PELV/SELV circuits
Applications
Galvanic separation of analogue signals (ground loop elimination).
Measurement of floating signals. Signal conversion within the ranges: 0...10
VDC or 0...50 mA on the input and 0...20 mA and 0...10 VDC in fixed ranges on the
output.
Technical characteristics
General
The 2204 uses microprocessor technology for the selection of gain and zero
offset, yet the signal conditioning is analogue with a fast response time of less
than 25 ms.
In standard ranges, the 2204 is programmable by use of internal dipswitches
within the input and output ranges of the order schedule. Provided that front
adjustments are still sealed, the unit needs no adjustment after programming.
Universally supplied units have a 3-port galvanic separation between input,
supply, and output.
Input
Current or voltage in standard or special ranges within the measuring range.
Standard input voltage: 0/0.2...1 V, 0/0.5...2.5 V and 0/2...10 V.
Input resistance: typ. 10 MΩ.
Standard input current: 0/1...5 mA or 0/4...20 mA.
Input resistance: norm. 50 Ω (0/4...20 mA).
2204V104-UK 7
Output
The output can be ordered for standard currents and voltages or special
versions within the signal range.
Standard output current (pin 3) 0/4...20 mA and 0/1...5 mA acc. to order schedule
with the possibility of reversal. Current limit: 23...28 mA.
Standard voltage output (pin 2) is achieved by short-circuiting pins 2 and 3. The
current signal is available between pins 2 and 1. For voltage signals in the range
0...1 VDC, a 50 Ω shunt (DP 2-1) is applied; in the range 0...10 VDC, a 500 Ω shunt
(DP 2-2) is applied. If both signals are used simultaneously, the mA loop to ground
must go through the internal shunt. Adjustment of 0 and 100% is possible in the
front ±10%, but please note that the basic calibration is thereby lost.
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, DC .................................................. 19.2...28.8 VDC
Supply voltage, universal ..................................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Max. consumption 2204--D (24 VDC) ............. 1.3 W
Max. consumption 2204--P (uni. supply) ....... 1.8 W
Isolation, test / operation ..................................... 3.75 kVAC / 250 VAC
Signal / noise ratio .................................................. Min. 60 dB
Response time (0...90%) ....................................... < 25 ms
Temperature coefficient ........................................ < ±0.01% of span/°C
Linearity error ........................................................... < ±0.1% of span
Effect of supply voltage change ....................... < ±0.002% of span/%V
EMC immunity influence ...................................... < ±0.5% of span
Relative air humidity .............................................. < 95% RH (non cond.)
Dimensions (HxWxD) .............................................. 80.5 x 35.5 x 84.5 mm
Protection degree .................................................... IP50
Weight DC / universally supplied ...................... 110 g / 160 g
8 2204V104-UK
Input:
Current:
Measurement range ................................................ 0...50 mADC
Min. measurement range (span) ........................ 4 mADC
Max. offset ................................................................. 20% of max. value
Input resistance........................................................ Nom. 50 Ω
Voltage:
Measurement range ................................................ 0...10 VDC
Min. measurement range (span) ........................ 0.2 VDC
Max. offset ................................................................. 20% of max. value
Input resistance........................................................ 10 MΩ
Output:
Current output:
Signal ranges ............................................................. 0...5 mA / 0...20 mA
Min. measurement range (span) ........................ 4 mA / 16 mA
Max. offset ................................................................. 20% of max. value
Load (max.) ................................................................. 20 mA / 600 Ω / 12 VDC
Load stability ............................................................. < ±0.01% of span / 100 Ω
Current limit ............................................................... 23...28 mA
Voltage output through internal shunt:
Signal ranges ............................................................. 0...0.25V / 0...1V / 0...2.5V / 0...10V
Min. measurement range (span) ........................ 0.2 V / 0.8 V / 2.0 V / 8.0 V
Max. offset ................................................................. 20% of max. value
Load (min.) .................................................................. 500 kΩ
Output resistance .................................................... 50 Ω / 500 Ω
Observed authority requirements: Standard:
EMC 2004/108/EC .................................................. EN 61326-1
LVD 2006/95/EC ...................................................... EN 61010-1
PELV/SELV .................................................................. IEC 364-4-41 and EN 60742
EAC TR-CU 020/2011 ............................................ EN 61326-1
Of span = Of the presently selected range
2204V104-UK 9
Order: 2204
BLOCK DIAGRAM
2204
5
6
9
10
1
V
3
A
V
A
2
0%
100%
DP1
50
0...20
mA
3 4
500
50
DP2
1 2
1
DP1
5
3
4 6 7
8
9 102
+
-
V
+
-
DP2
DC
DC
I +
V +
I
Out
V
Out
24
VDC
Gnd.
I + V
Out
Universal sup. only
Input +
Input gnd.
Supply (+), (P)
Supply (gnd), (N)
Or
24...230 VAC &
24...250 VDC
Type Input Output Supply
2204
0...20 mA
4...20 mA
0...1 V
0.2...1 V
0...10 V
2...10 V
Special
: A
: B
: C
: D
: E
: F
: X
Special
0...20 mA
4...20 mA
0...5 mA
0...1 V
0.2...1 V
0...10 V
2...10 V
: 0
: 1
: 2
: 3
: 4
: 5
: 6
: 7
24 VDC
24...230 VAC &
24...250 VDC
: D
: P
10 2204V104-UK
PROGRAMMING
INPUT
PROGRAMING
DP1 (10-pole)
SW 1, 2, 3, 4, 5
SW ON SW OFF
0...0.5 mA
0...20 mA
0...1 V
0...2.5 V
0...10 V
1, 3
1, 4
2, 3
2, 4
2, 3, 4
2, 4, 5
2, 3, 5
1, 4, 5
1, 3, 5
1, 5
For 20% oset on input,
set DP1 SW5 ON
e.g. input 4...20 mA 1, 4, 5 2, 3
OUTPUT
PROGRAMING
DP2 (4-pole)
SW 1 - 4
DP1 (10-pole)
SW 6, 7, 8, 9, 10
SW ON SW OFF ON OFF
0...5 mA
0...20 mA
0...5 mA / 0...250 mV
0...20 mA / 0...1 V
0...5 mA / 0...2.5 V
0...20 mA / 0...10 V
4
3
1, 4
1, 3
2, 4
2, 3
1, 2, 3
1, 2, 4
2, 3
2, 4
1, 3
1, 4
7
8
6
6, 7
6, 8
6, 7, 8
6, 8, 9, 10
6, 7, 9, 10
7, 8, 9, 10
8, 9, 10
7, 9, 10
9, 10
For 20% oset on output,
set DP1 SW9 ON
e.g. output 4...20 mA 3 1, 2, 4 8, 9 6, 7, 10
For reversed output set DP1,
SW10 ON
e.g. output 20...4 mA 3 1, 2, 4 8, 9, 10 6, 7
Note: At other spans than the above-mentioned, DP1 and DP2 have a different
setting which applies to the delivered special range.
Programmable displays with a wide selection
of inputs and outputs for display of temperature, volume and
weight, etc. Feature linearization, scaling, and dierence
measurement functions for programming via PReset software.
Displays
A wide selection of transmitters for DIN form
B mounting and DIN rail devices with analog and digital bus
communication ranging from application-specific to universal
transmitters.
Temperature
Galvanic isolators for analog and digital
signals as well as HART signals. A wide product range with both
loop-powered and universal isolators featuring linearization,
inversion, and scaling of output signals.
Isolation
Interfaces for analog and digital signals as well
as HART signals between sensors / I/P converters / frequency
signals and control systems in Ex zone 0, 1 & 2 and for some
devices in zone 20, 21 & 22.
Ex interfaces
PC or front programmable devices with
universal options for input, output and supply. This range oers
a number of advanced features such as process calibration,
linearization and auto-diagnosis.
Universal
Head oce
Denmark www.prelectronics.com
PR electronics A/S sales-dk@prelectronics.com
Lerbakken 10 tel. +45 86 37 26 77
DK-8410 Rønde fax +45 86 37 30 85
www.prelectronics.fr
sales-fr@prelectronics.com
www.prelectronics.de
sales-de@prelectronics.com
www.prelectronics.es
sales-es@prelectronics.com
www.prelectronics.it
sales-it@prelectronics.com
www.prelectronics.se
sales-se@prelectronics.com
www.prelectronics.com
sales-uk@prelectronics.com
www.prelectronics.com
sales-us@prelectronics.com
www.prelectronics.cn
sales-cn@prelectronics.com
www.prelectronics.be
sales-be@prelectronics.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

PR 2204V104-UK Manuel utilisateur

Taper
Manuel utilisateur

dans d''autres langues