Installation DAMIX - A
Drawing No. LP1149
Effective 09/2020
DA 4UI and 2UI MIX I/O Modules
Installation Guide
1
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
T4
C
C
US
US
U
L
R
LISTED
IND.CONT. EQ.
E317425
MODULE PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DIN Rail Mount DA Mix Module
- Installation Guide
GENERAL DESCRIPTION
The DA Mix modules are available in two configurations for use
with the DA70 controllers. The 4UI Mix module has 4 universal
inputs, 3 digital inputs/outputs, and 2 analog outputs. The 2UI
Mix module has 2 universal inputs, 8 digital inputs/outputs, and 2
analog outputs.
The design of the system provides a modular platform for
multi-zone control applications. The modules can accept a wide
range of thermocouple, RTD, 0-10 V, 0/4-20 mA signals, multiple
discrete inputs/outputs, and analog outputs.
The modules connect and communicate via proprietary
backplane to the DA host device. The DA host device, equipped
with serial ports as well as an Ethernet port(s), allows the system
to share data with PCs, PLCs, and SCADA systems.
Internal power management circuits allow the module to be
replaced while power is applied, in non-hazardous locations only,
which reduces downtime in the event of a module failure. All
configuration information is stored locally within the module, as
well as in the Host, so replacement modules do not need to be
configured.
CONFIGURATION
The DA Mix modules are configured with Windows
®
compatible
Crimson
®
software. The software is an easy to use, graphical
interface which provides a means of configuring and commissioning
new systems, as well as routine module re-calibration.
ALARMS
Each Universal Input channel has an alarm LED that illuminates
to indicate a fault.
SAFETY SUMMARY
All safety related regulations, local codes as well as instructions
that appear in this document or on equipment must be observed
to ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not consistent with these specifications.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l’installation et
l’utilisation de l’appareil.
WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2
AVERTISSEMENT - DANGER D’EXPLOSION - LE
REMPLACEMENT DE COMPOSANTS PEUT NUIRE À
LAPTITUDE À LA CLASSE I, DIVISION 2
z Two models offering mix of inputs and outputs
4UI Mix - 4 Universal Inputs, 3 DI/DO and 2 Analog Outputs
2UI Mix - 2 Universal Inputs, 8 DI/DO and 2 Analog Outputs
z Universal inputs accept TC, RTD, 0-10 V and 0/4-20 mA signals
z Digital inputs and outputs (software selectable)
z Analog outputs capable of multiple ranges
z Configured using Crimson
®
software (version 3.2 or later)
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx UL 20.0007X
0.49
(12.51)
0.45 (11.50)
4.53 (114.97)
6.22
(157.91)
1.91
(48.51)
1.35
(34.32)
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
6.00
(152.40)
DIMENSIONS In Inches (mm)
2
Drawing No. LP1149 Effective 09 2020
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
SPECIFICATIONS
1. POWER REQUIREMENTS:
Power is supplied by the DA host device. Modules may be
hot-swapped (replaced while powered up) in non-hazardous
locations only.
4UI Mix Max Power: 2.7 W
2UI Mix Max Power: 2.6 W
2. LEDs: (model dependent)
STS - A status LED to show general module status
Al1-Al4 - One alarm LED for each universal input channel
DIO1-DIO8 - One LED indicator for each Digital I/O point
3. MEMORY: Non-volatile memory retains all programmable
parameters. The controller also stores the parameters in order
to reprogram any modules that need updates.
4. UNIVERSAL INPUTS:
GENERAL:
Sample Time: 50 msec nominal; software configurable from
4 msec to 1200 msec
Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >50 dB, 50/60 Hz
Temperature Coefficient: 0.01%/
°
C
Step Response Time: 100 msec typ., 200 msec max
THERMOCOUPLE INPUT:
Types: T, E, J, K, R, S, B, N, C
Slope & Offset: Provides sensor error correction
Input Impedance: 20 M ohm
Lead Resistance Effect: 0.25 µV/ohm
Cold Junction Compensation: Less than ±1 °C typical (±1.5
°C max) over -40 to 75 °C ambient temperature
Resolution: 0.1
°
TYPE
MEASUREMENT
RANGE
WIRE COLOR
ANSI BS 1843
T
-200 to +400 °C
-328 to +752 °F
(+) Blue
(-) Red
(+) White
(-) Blue
E
-200 to +730 °C
-328 to +1346 °F
(+) Violet
(-) Red
(+) Brown
(-) Blue
J
-200 to +760 °C
-328 to +1400 °F
(+) White
(-) Red
(+) Yellow
(-) Blue
K
-200 to +1350 °C
-328 to +2462 °F
(+) Yellow
(-) Red
(+) Brown
(-) Blue
R
0 to +1768 °C
+32 to +3214 °F
No Standard
(+) White
(-) Blue
S
0 to +1768 °C
+32 to +3214 °F
No Standard
(+) White
(-) Blue
B
+149 to +1820 °C
+300 to +3308 °F
No Standard No Standard
N
-200 to +1300 °C
-328 to +2372 °F
(+) Orange
(-) Red
(+) Orange
(-) Blue
C W5/W6
0 to +2315 °C
+32 to +4199 °F
No Standard No Standard
mV 0 mV to 50 mV N/A N/A
Temperature Indication Accuracy: ± (0.3% of span, +1 °C).
Includes NIST conformity, cold junction effect, A/D
conversion errors, temperature coefficient and
linearization conformity at 23 °C after 20 minute warm up.
Probe Break Response: Upscale drive, Input Fault Alarm bit
set high, ALM LED illuminates.
RTD INPUT:
Type: 2 or 3 wire
Excitation: 150 µA
Lead Resistance: 15 ohms Max
Resolution: 1 or 0.1°
TYPE INPUT TYPE RANGE
385 100 ohm platinum, Alpha = 0.00385
-200 to +600 °C
-328 to +1100 °F
392 100 ohm platinum, Alpha = 0.003919
-200 to +600 °C
-328 to +1100 °F
672 120 ohm nickel, Alpha = 0.00672
-80 to +215 °C
-112 to +419 °F
Slope & Offset: Provides sensor error correction
Temperature Indication Accuracy: Includes NIST conformity,
A/D conversion errors, temperature coefficient and
linearization conformity at 23 °C after 20 minute warm up.
Probe Break Response: If channel is enabled: upscale drive,
Input
Fault Alarm bit set high, ALM LED illuminates
CURRENT INPUT:
Ranges: 0-20 mA or 4-20 mA
Programmable Scaling: ±30,000
Input Impedance: 10 Ohm
Max. Continuous Overload: 100 mA
Accuracy: ±0.1% of span
Input Fault Response: Upscale Drive, Input Fault Alarm bit
set high, ALM LED illuminates below -2 mA, and above
22 mA for 0-20 mA range; below +2 mA and above 22
mA for 4-20 mA signals.
VOLTAGE INPUT:
Ranges: 0-10 VDC
Programmable Scaling: ±30,000
Input Impedance: 1 M Ohm
Max. Continuous Overload: 50 V
Accuracy: ±0.1% of span
Input Fault Response: Upscale Drive, Input Fault Alarm bit
set high, ALM LED illuminates below -0.5 and above
+10.5 VDC.
5. DIGITAL INPUTS:
8 or 3 channels (model dependent)
Maximum input voltage: 30 VDC, reverse polarity protected
Guaranteed ON voltage: 3.8 V
Guaranteed OFF voltage: 1.2 V
Sinking Impedance: 20K Ohm
Selectable hardware Filter: 50 Hz or 500 Hz
6. DIGITAL OUTPUTS:
8 or 3 (model dependent) solid state N-channel open drain
MOSFETs
Rating: 1 ADC max
V
DS
ON: < 0.2 V @ 1 A
V
DS
MAX: 30 VDC
Offstate leakage current: 0.5 μA max
Isolation Level: 500 Vrms @ 50/60 Hz for 1 minute
7. AO – ANALOG OUTPUTS:
Two (2) independently configured. The outputs are not
isolated from each other, but are isolated from the power
supply and all other I/O.
Software programmable for 0-5 VDC, -10 VDC to 10 VDC,
0-20 mA, and 4-20 mA
Effective Resolution: Full 16-bit (Signed)
Voltage: 500 μV
Current: 1 μA
Accuracy: 0.2% of full scale (-40 to 70 °C)
Isolation Level: 500 Vrms @ 50/60 Hz for 1 minute
WARNING - EXPLOSION HAZARD. NOT HOT
SWAPPABLE. DO NOT REMOVE OR REPLACE WHILE
CIRCUIT IS LIVE UNLESS THE AREA IS FREE OF
IGNITIBLE CONCENTRATIONS.
AVERTISSEMENT - RISQUE D’EXPLOSION. NON
ÉCHANGEABLE À CHAUD. NE PAS RETIRER OU
REMPLACER SOUS TENSION SAUF SI LA ZONE EST
EXEMPTE DE CONCENTRATIONS INFLAMMABLES.
3
Effective 09 2020 Drawing No. LP1149
8. COMMUNICATIONS: Provided by the DA70 controller
9. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -40 to 75 °C
Storage Temperature Range: -40 to 85 °C
Operating and Storage Humidity: 0 to 85% max. RH non-
condensing
Vibration to IEC 60068-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 60068-2-27: Operational 15 g
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/
EN 60664-1.
10. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
ATEX Approved
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx Approved
IECEx UL 20.0007X
UL Hazardous: File # E317425
Rugged IP30 enclosure
11. CONNECTIONS: Removable wire clamp screw terminal
blocks
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: 14 to 24 AWG (2.08 to 0.20 mm
2
)
copper wire only
Torque: 2 inch-lbs (0.23 N-m)
12. CONSTRUCTION: Plastic enclosure with IP30 rating. For
use only in an approved enclosure.
13. MOUNTING REQUIREMENTS: Mounts onto standard DIN
style top hat (T) profile mounting rails according to EN50022
– 35 x 7.5 mm and 35 x 15 mm.
14. WEIGHT:
2UI Mix: 11.3 oz (320 g)
4UI Mix: 11.5 oz (326 g)
HARDWARE INSTALLATION
Removing Module From Cradle
To remove the module from the cradle, push in the module
release button at the top of the cradle and pull the module out of
the cradle.
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
MODULE
1
CRADLE
2
Attaching the Module/Cradle to the DIN Rail
The DIN rail should be mounted horizontally so that the unit’s
ventilation holes are vertical in relation to installation orientation.
A minimum clearance of 1 inch (25.4 mm) should be maintained
above and below the unit to ensure proper thermal regulation.
The cradle can be installed on the DIN rail with or without the
module attached. Ensure the DIN rail lock latch is in the outward
most position (unlocked). Hook the top back of the cradle DIN rail
clip over the DIN rail. Press the cradle until flush with the rail and
push the DIN rail lock latch to the latched (in) position.
For hazardous location
installation, the following shall be
taken into consideration:
The equipment shall only be
used in an area of at least
pollution degree 2, as
defined in EN/IEC 60664-1.
The equipment shall be
installed in an enclosure that
provides a minimum ingress
protection of IP54 in
accordance with EN/IEC
60079-0. The enclosure
shall be accessible only with
the use of a tool.
Transient protection shall be provided that is set at a level
not exceeding 140% of the peak rated voltage value at the
supply terminals to the equipment.
Installing Module into Cradle
Push module into cradle until you hear an audible click
indicating it is properly latched.
MODULE HOT SWAPPING
If the area is known to be non-hazardous (free of ignitable
concentrations), then a module can be removed and/or installed
into a cradle attached to the controller while power is applied.
However, it is NOT recommended to connect to or remove from
the controller, a module/cradle pair or group of modules/cradles,
while power is applied. The power should be turned off anytime
a cradle or group of cradles (with or without modules) is plugged
into or removed from the controller.
DIN RAIL LOCK LATCH
3
Unlock Lock
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
MODULE CRADLE
4
DIN
rail
4
Drawing No. LP1149 Effective 09 2020
WIRING
All power, input and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods and in accordance with
the authority having jurisdiction.
All conductors should meet voltage and current ratings for each
terminal. When wiring the module, use the numbers on the label
to identify the position number with the proper function. Strip
the wire, leaving approximately 0.3" (7.5 mm) of bare wire
exposed. Insert the wire into the terminal, and tighten.
WIRING CONNECTIONS
Universal Input Wiring
THERMOCOUPLE VOLTAGE
RTD CURRENT
Digital I/O Wiring
The DA Mix Module offers either 8 or 3 digital inputs/NFET
outputs. The digital inputs and outputs operate on the same
voltage that powers the unit. Pluggable screw block terminals are
provided for the I/O wiring connections. Refer to the following
diagrams on how to make your I/O connections. These diagrams
show the 2UIN terminal numbers. Reference the full unit label
shown for 4UIN terminal numbers.
Analog Output Wiring
CAUTION: Only UL listed wiring with temperature
ratings greater than 90 °C permitted for Class I, Division
2, Zone 2 and ATEX/IECex installations.
ATTENTION: Seul le câblage homologué UL avec des
températures nominales supérieures à 90°C est autorisé
pour les installations de classe I, Division 2 , zone 2 et
ATEX/IECex.
Terminals 17 to 24
Terminals 25 to 32
Terminals 9 to 16
Terminals 1 to 8
01
02
03
06
04
05
08
07
14
09
11
10
13
12
16
15
20
17
19
18
21
22
24
23
0-10V
4-20mA
INPUT COM
TC/RTD+
RTD +EXC
INPUT COM
TC/RTD+
RTD +EXC
0-10V
4-20mA
V+
I+
COM
COM
V+
I+
30
25
27
26
29
28
32
31
DI/DO6+
DI/DO7-
DI/DO6-
DI/DO7+
DI/DO8-
DI/DO8+
DI/DO5+
DI/DO5-
DI/DO2+
DI/DO3-
DI/DO2-
DI/DO3+
DI/DO4-
DI/DO4+
DI/DO1+
DI/DO1-
8
7
6
INPUT
ANALOG
OUTPUT
3
2
1
4
5
DIGITAL I/O
1
2
1
2
01
02
03
06
04
05
08
07
14
09
11
10
13
12
16
15
20
17
19
18
21
22
24
23
0-10V
4-20mA
INPUT COM
TC/RTD+
RTD +EXC
INPUT COM
TC/RTD+
RTD +EXC
0-10V
4-20mA
V+
I+
COM
COM
V+
I+
0-10V
4-20mA
INPUT COM
TC/RTD+
RTD +EXC
3
INPUT COM
TC/RTD+
RTD +EXC
0-10V
4-20mA
4
30
25
27
26
29
28
32
31
DI/DO1+
DI/DO2-
DI/DO1-
DI/DO2+
DI/DO3-
DI/DO3+
3
2
1
INPUTINPUT
1
2
ANALOG
OUTPUT
1
2
DIGITAL I/O
2UI MIX 4UI MIX
0-10V
4-20 mA
INPUT COM
TC/RTD+
RTD +EXC
+
0-10V
4-20 mA
INPUT COM
TC/RTD+
RTD +EXC
VDC-
VDC+
0-10V
4-20 mA
INPUT COM
TC/RTD+
RTD +EXC
LOAD
POWER
+
+
_
0-10V
4-20 mA
INPUT COM
TC/RTD+
RTD +EXC
+
-
+
-
20
17
19
18
21
22
24
23
25
DI/DO5-
DI/DO2+
DI/DO3-
DI/DO2-
DI/DO3+
DI/DO4-
DI/DO4+
DI/DO1+
DI/DO1-
3
2
1
4
DIGITAL I/
Input Connections - 2UI shown
20
17
19
18
21
22
24
23
25
DI/DO5-
DI/DO2+
DI/DO3-
DI/DO2-
DI/DO3+
DI/DO4-
DI/DO4+
DI/DO1+
DI/DO1-
3
2
1
4
DIGITAL I/
+
-
Load
+
-
Solid State NFET Output Connection - 2UI shown
Recorder,
Controller,
Valve, etc
+
-
14
11
10
13
12
16
15
4-20mA
V+
I+
COM
COM
V+
I+
ANALOG
OUTPUT
1
2
Voltage Analog Output
Recorder,
Controller,
Valve, etc
+
-
14
11
10
13
12
16
15
4-20mA
V+
I+
COM
COM
V+
I+
ANALOG
OUTPUT
1
2
Current Analog Output
5
Effective 09 2020 Drawing No. LP1149
LEDS
Status LED
LED
COLOR(S)
LED STATE MEANING
Blue 3 quick flashes Module is booting.
Green Solid Module is configured and running.
Green/Off Flashing Module is running but is not
configured.
Green/
Purple
Flashing Module is performing calibration.
Red/Green Flashing Module is running but
communication with the controller
is inactive. If status persists, contact
technical support.
Red/Off Flashing An internal error has occurred. If
status persists, contact technical
support.
Yellow/Off Flashing Module position is unassigned. If
status persists, contact technical
support.
Off Solid Module application is not running or
the module is not powered. If status
persists, contact technical support.
Alarm LEDs
Each universal analog input has an alarm LED that is factory
configured to indicate an input value that is out of range. A red
LED is lit when an alarm condition is present. Otherwise the LED
is off.
RED LION CONTROLS TECHNICAL SUPPORT
If for any reason you have trouble operating, connecting, or
simply have questions concerning your new DA Module, contact
Red Lion’s technical support.
Support: support.redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.
20 Willow Springs Circle York, PA 17406
ORDERING INFORMATION
PART NUMBER DESCRIPTION
DAM00I0IN4DA0000
DA Series I/O Mix Module with 4UI
DAM00I0IN2DA0000
DA Series I/O Mix Module with 2UI
A listing of the entire DA Series family of products and accessories
can be found at www.redlion.net.
6
Drawing No. LP1149 Effective 09 2020
This page intentionally left blank.
7
Effective 09 2020 Drawing No. LP1149
This page intentionally left blank.
8
COPYRIGHT
©2020 Red Lion Controls, Inc. All rights reserved. Red Lion and the Red Lion logo are trademarks of Red Lion Controls, Inc. All other
company and product names are trademarks of their respective owners.
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and
workmanship under normal use for the period of me provided in “Statement of Warranty Periods” (available at
www.redlion.net) current at the me of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE
ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR
A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY
RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE
OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a
Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a
result of Customer’s failure to store, install, commission or maintain the Product according to specicaons; (ii)
Customer alters or repairs such Product without the prior wrien consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discreon, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that,
if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET
FORTH IN PARAGRAPH (a).
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL OTHER
DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT.