red lion DA High Speed Rate Counter Module Manuel utilisateur

Taper
Manuel utilisateur
Installation HSRC - A
Drawing No. LP1148
Effective 09/2022
DA High Speed Rate Counter Module
Installation Guide
1
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
T4
C
C
US
US
UL
R
LISTED
IND.CONT. EQ.
E317425
MODULE PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DIN Rail Mount DA HSRC Module
- Installation Guide
GENERAL DESCRIPTION
The DA HSRC module features three counters designed for use
with the DA70 controllers. This module is an ideal choice to
monitor quadrature/direction encoders, count events, measure
pulse width, and measure rates.
The digital inputs accept standard DC inputs or contact
closures. Each counter has a software selectable input filter that
can be used to prevent contact bounce. 4 SSR outputs can
indicate the status of a count total or rate measurement.
Counting modes include quadrature/direction encoders, count
events on one input, sum events on two inputs, count with
direction, count SSR output activations, etc.
The SSR outputs are capable of switching up to one amp DC
each. For applications requiring large loads to be controlled or AC
voltages, several DIN rail mount interposing relays are available.
The modules connect and communicate via proprietary
backplane to the DA host device. The DA host device, equipped
with serial ports as well as an Ethernet port(s), allows the system
to share data with PCs, PLCs, and SCADA systems.
Internal power management circuits allow the module to be
replaced while power is applied, which reduces downtime in the
event of a module failure. All configuration information is stored
locally within the module, as well as in the Host, so replacement
modules do not need to be configured.
CONFIGURATION
The DA HSRC modules are configured with Windows®
compatible Crimson® software. The software is an easy to use,
graphical interface which provides a means of configuration and
commissioning of new systems, as well as routine module
re-calibration.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l’installation et
l’utilisation de l’appareil.
WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2
AVERTISSEMENT - DANGER D’EXPLOSION - LE
REMPLACEMENT DE COMPOSANTS PEUT NUIRE À
LAPTITUDE À LA CLASSE I, DIVISION 2
zAdds three counters to the DA70 products
zFour count inputs, four user inputs, four setpoint outputs, and
four digital outputs
zOffers complete isolation; inputs, outputs, power, and
communication
zDual channel counter inputs configurable for count, rate, or
quadrature counting modes
zOutputs are sinking with max of 1 A per channel
0.49
[12.51]
0.45 [11.50]
4.53 [114.97]
6.22
[157.91]
1.91
[48.51]
1.35
[34.32]
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
6.00
[152.40]
DIMENSIONS In inches [mm]
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx UL 20.0007X
UL22UKEX2576X
2
Drawing No. LP1148 Effective 09 2022
SPECIFICATIONS
1. POWER REQUIREMENTS:
Power is supplied by the DA host controller. Modules may be
hot-swapped (replaced while powered up) in non-hazardous
locations only.
Max Power: 2.0 W
2. LEDs: One LED indicator for each I/O point and a status LED.
3. MEMORY: Non-volatile memory retains all programmable
parameters. The Controller also stores the parameters in order
to reprogram any modules that need updates.
4. COUNTER INPUTS:
2 dual channel inputs, individual screw terminals for channel-
to-channel isolation and independent Sink/Source hardware
configuration
Maximum input voltage: 30 VDC, reverse polarity protected
Guaranteed ON voltage: 2.5 V
Guaranteed OFF voltage: 1.5 V
TTL compatible
Current draw: 10.5 mA @ 30 VDC, 4.5 mA @ 2.5 VDC,
nominal spec: 8 mA
Range: -2,147,483,648 to 2,147,483,647
Maximum Count Rates:
MODE COUNTER A COUNTER B
Count X1 500 KHz 500 KHz
Count X1 with Direction 50 KHz 50 KHz
Dual Input X1 Add/Add 50 KHz 50 KHz
Dual Input X1 Add/Subtract 50 KHz 50 KHz
Quad X1 50 KHz 50 KHz
Quad X2 500 KHz 50 KHz
Quad X4 500 KHz 500 KHz
Count X2 500 KHz 500 KHz
Count X2 with Direction 50 KHz 50 KHz
Pulse Width Fall/Fall Accuracy:
± 2.0 msec
Accuracy:
± 2.0 msec
Pulse Width Fall/Rise Accuracy:
± 2.0 msec
Accuracy:
± 2.0 msec
Pulse Width Rise/Fall Accuracy:
± 2.0 msec
Accuracy:
± 2.0 msec
Pulse Width Rise/Rise Accuracy:
± 2.0 msec
Accuracy:
± 2.0 msec
Software debounce filtering modes: None or Debounce.
Debounce limits input frequency to 50 Hz and input pulse
widths to 10 msec min.
Input isolation: 500 Vrms
5. RATE INPUTS:
Range: 0 to 999,999
Maximum Frequency: 500 KHz
Minimum Frequency: 0.001 Hz
Display Update Time: 0.1 to 999.9 seconds
Accuracy: ±0.01%
6. DIGITAL OUTPUT:
8 solid state N-channel open drain MOSFETs
Load Type: General purpose, resistive and Pilot Duty
All outputs share the same common
Rating: 1 ADC max
VDS ON: < 0.2 V @ 1 A
VDS MAX: 30 VDC
Offstate leakage current: 0.5 μA max
7. SIGNAL INPUTS (INPUT A and INPUT B):
Selectable inputs accept pulses from a variety of sources
including switch contacts, TTL outputs, and standard RLC
sensors. Inputs accept current sinking or current sourcing
outputs and provide software selectable input filtering for
low frequency signals or switch contact debounce.
8. USER INPUTS: Four programmable user inputs
Max. Continuous Input: 30 VDC
Channel-to-channel isolation
Response Time: 12 msec. max.
Independent Sink/Source hardware configuration
Guaranteed ON voltage: 2.5 V
Guaranteed OFF voltage: 1.5 V
TTL compatible
Current draw: 10.5 mA @ 30 VDC, 4.5 mA @ 2.5 VDC,
nominal spec: 8 mA
9. COMMUNICATIONS: Provided by the DA70 Controller
10. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -40 to 75 °C TAMB
Storage Temperature Range: -40 to 80 °C TAMB
Operating and Storage Humidity: 0 to 95% max. RH non-
condensing
Vibration to IEC 60068-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 60068-2-27: Operational 15 g
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/
EN 60664-1.
11. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
ATEX Approved
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx Approved
IECEx UL 20.0007X
UKEX Approved
UL22UKEX2576X
UL Hazardous: File # E317425
Rugged IP30 enclosure
12. CONNECTIONS: Removable wire clamp screw terminal blocks
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: 14 to 24 AWG (2.08 to 0.20 mm2)
copper wire only
Torque: 2 inch-lbs (0.23 N-m)
13. CONSTRUCTION: Plastic enclosure with IP30 rating. For
use only in an approved enclosure.
14. MOUNTING REQUIREMENTS: Mounts onto standard DIN
style top hat (T) profile mounting rails according to EN50022
– 35 x 7.5 mm and 35 x 15 mm.
15. WEIGHT: 10.2 oz (317.25 g)
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
WARNING - EXPLOSION HAZARD. NOT HOT
SWAPPABLE. DO NOT REMOVE OR REPLACE WHILE
CIRCUIT IS LIVE UNLESS THE AREA IS FREE OF
IGNITIBLE CONCENTRATIONS.
AVERTISSEMENT - RISQUE D’EXPLOSION. NON
ÉCHANGEABLE À CHAUD. NE PAS RETIRER OU
REMPLACER SOUS TENSION SAUF SI LA ZONE EST
EXEMPTE DE CONCENTRATIONS INFLAMMABLES.
3
Effective 09 2022 Drawing No. LP1148
HARDWARE INSTALLATION
Removing Module From Cradle
To remove the module from the cradle, push in the module
release button at the top of the cradle and pull the module out of
the cradle.
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
MODULE
1
CRADLE
2
Attaching the Module/Cradle to the DIN Rail
The DIN rail should be mounted
horizontally so that the unit’s
ventilation holes are vertical in
relation to installation orientation.
A minimum clearance of 1 inch
(25.4 mm) should be maintained
above and below the unit to
ensure proper thermal regulation.
The cradle can be installed on
the DIN rail with or without the
module attached. Ensure the DIN
rail lock latch is in the outward
most position (unlocked). Hook
the top back of the cradle DIN
rail clip over the DIN rail. Press
the cradle until flush with the rail and push the DIN rail lock latch
to the latched (in) position.
For hazardous location installation, the following shall be taken
into consideration:
The equipment shall only be used in an area of at least
pollution degree 2, as defined in EN/IEC 60664-1.
The equipment shall be installed in an enclosure that provides
a minimum ingress protection of IP54 in accordance with EN/
IEC 60079-0. The enclosure shall be accessible only with the
use of a tool.
Transient protection shall be provided that is set at a level not
exceeding 140% of the peak rated voltage value at the supply
terminals to the equipment.
Installing Module into Cradle
Push module into cradle until you hear an audible click
indicating it is properly latched.
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
MODULE CRADLE
4
DIN
rail
MODULE HOT SWAPPING
If the area is known to be non-hazardous (free of ignitable
concentrations), then a module can be removed and/or installed
into a cradle attached to the controller while power is applied.
However, it is NOT recommended to connect to or remove from
the controller, a module/cradle pair or group of modules/cradles,
while power is applied. The power should be turned off anytime
a cradle or group of cradles (with or without modules) is plugged
into or removed from the controller.
DIN RAIL LOCK LATCH
3
Unlock Lock
COUNT / RATE INPUT OPERATION
Reference the Crimson 3.2 Software Guide for more details.
MODE COUNTER X INPUT A COUNTER X INPUT B
Count X1 Adds Input A falling edge. Not Used.
Count X1 with Direction Adds Input A falling edge if Input B is high. Subtracts if Input B is low.
Dual Input X1 Add/Add Adds Input A falling edge. Adds Input B falling edge.
Dual Input X1 Add/Subtract Adds Input A falling edge. Subtracts Input B falling edge.
Quad X1 Adds Input A rising edge when Input B is high. Subtracts on reverse rotation.
Quad X2 Adds Input A rising edge when Input B is high and Input
A falling edge when Input B is low.
Subtracts on reverse rotation.
Quad X4 Adds Input A falling edge when Input B is high, Input A
rising edge when Input B is low, Input B rising edge
when Input A is high, and Input B falling edge when
Input A is low.
Subtracts on reverse rotation.
Count X2 Adds Input A rising and falling edges. Not Used.
Count X2 with Direction Adds Input A rising and falling edges if Input B is high. Subtracts if Input B is low.
Pulse Width Fall to Fall Measures the time between an Input A falling edge and
the next Input A falling edge.
Not Used.
Pulse Width Fall to Rise Measures the time between an Input A falling edge and
the next Input A rising edge.
Not Used.
Pulse Width Rise to Fall Measures the time between an Input A rising edge and
the next Input A falling edge.
Not Used.
Pulse Width Rise to Rise Measures the time between an Input A rising edge and
the next Input A rising edge.
Not Used.
4
Drawing No. LP1148 Effective 09 2022
WIRING
All power, input and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods and in accordance with
the authority having jurisdiction.
All conductors should meet voltage and current ratings for each
terminal. When wiring the module, use the numbers on the label
to identify the position number with the proper function. Strip
the wire, leaving approximately 0.3" (7.5 mm) of bare wire
exposed. Insert the wire into the terminal, and tighten.
I/O WIRING
The DA HSRC module offers 4 discrete count inputs, 4 discrete
user inputs, 4 discrete setpoint outputs, and 4 discrete digital
outputs. The discrete inputs and outputs operate on the same
voltage that powers the unit. Pluggable screw block terminals are
provided for the I/O wiring connections. Refer to the diagrams
below on how to make your I/O connections.
INPUT SIGNAL WIRING
Current Sourcing Output; Current Sinking Output
Switch; TTL Output
Rate; Quad/Direction
Dual Quad
USER INPUT WIRING
User Input terminals do not need to be wired in order to remain
in an inactive state
CAUTION: Only UL listed wiring with temperature
ratings greater than 90 °C permitted for Class I, Division
2, Zone 2 and ATEX, IECex and UKEX installations.
ATTENTION: Seul le câblage homologué UL avec des
températures nominales supérieures à 90°C est autorisé
pour les installations de classe I, Division 2 , zone 2 et
ATEX, IECex and UKEX.
Terminals
17 to 24
Terminals
25 to 32
Terminals
9 to 16
Terminals
1 to 8
DI3+
DI2+
DI3-
DI1-
DI1+
DI2-
DI4-
DI4+
DI8+
DI8-
DI7-
DI5+
DI6-
DI7+
DI6+
DI5-
DO4+
COM 3
DO1+
COM 2
DO3+
DO2+
COM 1
COM 4
COM 8
COM 5
DO6+
DO7+
COM 6
DO5+
COM 7
DO8+
01
02
03
06
04
05
08
07
14
09
11
10
13
12
16
15
20
17
19
18
21
22
24
23
29
28
26
25
27
32
31
30
DIGITAL OUTPUT 8
DIGITAL OUTPUT 6
DIGITAL OUTPUT 7
DIGITAL OUTPUT 5
SETPOINT 3
SETPOINT 2
SETPOINT 1
USER 4
USER 3
USER 2
USER 1
COUNTER B INPUT B
COUNTER B INPUT A
COUNTER A INPUT B
COUNTER A INPUT A
SETPOINT 4
OUTPUTINPUT
DI3+
DI2+
DI3-
DI1-
DI1+
DI2-
DI4-
DI4+
01
02
03
06
04
05
08
07
COUNTER B INPUT B
COUNTER B INPUT A
COUNTER A INPUT B
COUNTER A INPUT A
INPUT
+
-
+
-
PNP O.C.
NPN O.C.
DI3+
DI2+
DI3-
DI1-
DI1+
DI2-
DI4-
DI4+
01
02
03
06
04
05
08
07
COUNTER B INPUT B
COUNTER B INPUT A
COUNTER A INPUT B
COUNTER A INPUT A
INPUT
+5V
COMM
+
-
DI3+
DI2+
DI3-
DI1-
DI1+
DI2-
DI4-
DI4+
01
02
03
06
04
05
08
07
COUNTER B INPUT B
COUNTER B INPUT A
COUNTER A INPUT B
COUNTER A INPUT A
INPUT
DATA
COMMON
Rate
+8-28 VDC
DATA B
COMMON
+8-28 VDC
DATA A
Count
DI3+
DI2+
DI3-
DI1-
DI1+
DI2-
DI4-
DI4+
01
02
03
06
04
05
08
07
COUNTER B INPUT B
COUNTER B INPUT A
COUNTER A INPUT B
COUNTER A INPUT A
INPUT
DATA B
COMMON
+8-28 VDC
DATA A
Count
DATA B
COMMON
+8-28 VDC
DATA A
Count
DI8+
DI8-
DI7-
DI5+
DI6-
DI7+
DI6+
DI5-
14
09
11
10
13
12
16
15
USER 4
USER 3
USER 2
USER 1
INPUT
+
+
-
-
+
-
+
-
5
Effective 09 2022 Drawing No. LP1148
SETPOINT/DIGITAL OUTPUT WIRING
STATUS LED
LED
COLOR(S) LED STATE MEANING
Blue 3 quick flashes Module is booting.
Green Solid Module is configured and running.
Green/Off Flashing Module is running but is not
configured.
Green/
Purple
Flashing Module is performing calibration.
Red/Green Flashing Module is running but
communication with the controller
is inactive. If status persists, contact
technical support.
Red/Off Flashing An internal error has occurred. If
status persists, contact technical
support.
Yellow/Off Flashing Module position is unassigned. If
status persists, contact technical
support.
Off Solid Module application is not running or
the module is not powered. If status
persists, contact technical support.
RED LION CONTROLS TECHNICAL SUPPORT
If for any reason you have trouble operating, connecting, or
simply have questions concerning your new product, contact Red
Lion’s technical support.
Support: support.redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.
35 Willow Springs Circle York, PA 17406
COPYRIGHT
©2022 Red Lion Controls, Inc. All rights reserved. Red Lion
and the Red Lion logo are trademarks of Red Lion Controls,
Inc. All other company and product names are trademarks of
their respective owners.
ORDERING INFORMATION
DESCRIPTION PART NUMBER
DA Series I/O Module High-Speed Rate Counter DAM00I02C0000000
+
-
+
-
Load
-+
DO4+
COM 3
DO1+
COM 2
DO3+
DO2+
COM 1
COM 4
COM 5
COM 6
DO5+
20
17
19
18
21
22
24
23
26
25
27
DIGITAL OUTPUT 6
DIGITAL OUTPUT 5
SETPOINT 3
SETPOINT 2
SETPOINT 1
SETPOINT 4
OUTPUT
Load
-+
6
Drawing No. LP1148 Effective 09 2022
This page intentionally left blank.
7
Effective 09 2022 Drawing No. LP1148
This page intentionally left blank.
8
Drawing No. LP1148 Effective 09 2022
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and
workmanship under normal use for the period of me provided in “Statement of Warranty Periods” (available at
www.redlion.net) current at the me of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE
ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR
A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY
RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE
OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a
Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a
result of Customer’s failure to store, install, commission or maintain the Product according to specicaons; (ii)
Customer alters or repairs such Product without the prior wrien consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discreon, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that,
if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET
FORTH IN PARAGRAPH (a).
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL OTHER
DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT.