Platinum Pro/Platinum Touch/
Rotem One/Rotem Pro
Installation Manual
Revision: N1.6 of 12.2021
Product Software: Version 6.20/7.20
This manual for use and maintenance is an integral part of the apparatus together with the attached
technical documentation.
WARNING!
This document is destined for the user of the apparatus; it may not be reproduced in whole
or in part, committed to computer memory as a file or delivered to third parties without the
prior authorization of the assembler of the system.
Munters reserves the right to effect modifications to the apparatus in accordance with technical and legal
developments.
© Munters AB, 2018 3
Index
Chapter page
1
INTRODUCTION ------------------------------------------------------------------------------------------------------------------------------------------ 6
1.1
Disclaimer
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
6
1.2
Introduction
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
6
1.3
Notes
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
6
2
PRECAUTIONS ---------------------------------------------------------------------------------------------------------------------------------------------- 7
2.1
English
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
7
2.1.1
Grounding
................................................................................................................................................
7
2.1.2
Filtering
......................................................................................................................................................
7
2.1.3
Checking the Battery Level
.................................................................................................................
7
2.1.4
Frequency Inverters
...............................................................................................................................
7
2.2
French
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
8
2.2.1
Raccord à la Terre
................................................................................................................................
8
2.2.2
Filtrage
.......................................................................................................................................................
8
2.2.3
Vérification du Niveau de la Batterie
............................................................................................
8
2.2.4
Onduleurs de Fréquence
....................................................................................................................
9
3
SPECIFICATIONS -------------------------------------------------------------------------------------------------------------------------------------- 10
4
BEFORE USING ----------------------------------------------------------------------------------------------------------------------------------------- 11
4.1
Layout
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
11
4.1.1
Number of Relays
..............................................................................................................................
11
4.1.2
Platinum Pro Layout
...........................................................................................................................
12
4.1.3
Rotem One Layout
.............................................................................................................................
13
4.2
Typical Accessories
---------------------------------------------------------------------------------------------------------------------------------------------------------
14
4.3
Product Symbols
---------------------------------------------------------------------------------------------------------------------------------------------------------------
15
4.4
Rotem One/Rotem Pro: Normally Open/Closed Cards
-------------------------------------------------------------------------
16
5
MOUNTING THE UNITS ------------------------------------------------------------------------------------------------------------------------ 17
5.1
Installing the Platinum Pro
-------------------------------------------------------------------------------------------------------------------------------------------
17
5.1.1
Mounting the Platinum Pro
..............................................................................................................
17
5.1.2
Drilling
....................................................................................................................................................
17
5.2
Installing the Rotem One
---------------------------------------------------------------------------------------------------------------------------------------------
19
5.2.1
What comes in the Package
..........................................................................................................
19
5.2.2
Knockouts
..............................................................................................................................................
20
© Munters AB, 2018 4
5.2.3
Mounting
...............................................................................................................................................
20
6
HIGH VOLTAGE WIRING ---------------------------------------------------------------------------------------------------------------------- 22
6.1
Power Supply
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
22
6.2
RPLP Wiring
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------
22
6.3
Relay Wiring
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------
23
6.3.1
Platinum Pro Relay Wiring
..............................................................................................................
23
6.3.2
Rotem One Relay Wiring
................................................................................................................
24
6.3.3
Final Steps
.............................................................................................................................................
25
6.4
Winch Card Relay Wiring
------------------------------------------------------------------------------------------------------------------------------------------
25
6.4.1
Platinum Pro Winch Card Relay Wiring
....................................................................................
26
6.4.2
Rotem One Winch Card Relay Wiring
......................................................................................
27
6.5
Completing the Wiring
-------------------------------------------------------------------------------------------------------------------------------------------------
27
7
LOW VOLTAGE WIRING ------------------------------------------------------------------------------------------------------------------------ 28
7.1
Analog Input Wiring
------------------------------------------------------------------------------------------------------------------------------------------------------
28
7.1.1
Analog Card DIP Switches
.............................................................................................................
29
1.27.
Analog Input Wiring Diagram for Temperature Sensors
.....................................................
30
7.1.3
Analog Input Wiring Diagram for CO2 and Light Sensor
..................................................
31
7.1.4
Analog Input Wiring Diagram for Potentiometers
..................................................................
32
7.1.5
Analog Input Wiring Diagram for Humidity Sensors
............................................................
32
7.1.6
Analog Input Wiring Diagram for Ammonia Sensors
...........................................................
33
7.2
Weather Station Wiring
-----------------------------------------------------------------------------------------------------------------------------------------------
34
7.3
Digital Input Wiring
--------------------------------------------------------------------------------------------------------------------------------------------------------
36
7.4
Analog Output Wiring
--------------------------------------------------------------------------------------------------------------------------------------------------
37
7.5
Alarm Card Wiring
---------------------------------------------------------------------------------------------------------------------------------------------------------
38
7.6
Communication Card Wiring
-----------------------------------------------------------------------------------------------------------------------------------
39
7.7
RS-485 Termination
--------------------------------------------------------------------------------------------------------------------------------------------------------
40
7.7.1
Controllers and Comm-Box
.............................................................................................................
40
7.7.2
Controllers and Communicator
.....................................................................................................
41
7.7.3
Controller, Relay Expansion, RSU-2 and HUB
........................................................................
41
7.7.4
Placing the Terminator
......................................................................................................................
43
8
SCALE CARD WIRING ----------------------------------------------------------------------------------------------------------------------------- 45
8.1
Bird Scale Wiring
------------------------------------------------------------------------------------------------------------------------------------------------------------
45
8.2
Feed Scale Wiring
----------------------------------------------------------------------------------------------------------------------------------------------------------
46
8.3
Silo Scale Wiring
-------------------------------------------------------------------------------------------------------------------------------------------------------------
47
9
APPENDIX A: PLATINUM PRO METAL ASSEMBLY ------------------------------------------------------------------------- 48
9.1
Metal Assembly Precautions
-------------------------------------------------------------------------------------------------------------------------------------
48
9.2
Panels
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
49
© Munters AB, 2018 5
9.3
Back Panel Dimensions
-------------------------------------------------------------------------------------------------------------------------------------------------
50
9.4
Mounting the Panels
------------------------------------------------------------------------------------------------------------------------------------------------------
51
9.5
Connecting the Metal Panels
------------------------------------------------------------------------------------------------------------------------------------
52
9.5.1
Precautions
............................................................................................................................................
52
9.5.2
Panel Mount Cable Connections
.................................................................................................
53
10
APPENDIX B: ROTEM ONE WINCH CARD SET REPLACEMENT ---------------------------------------------- 58
10.1
General
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
59
10.2
In Practice
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
59
10.3
Relay Card Layout Considerations
------------------------------------------------------------------------------------------------------------------------
60
11
APPENDIX C: ELECTRICAL GROUNDING ---------------------------------------------------------------------------------------- 61
11.1
Ground Rods
----------------------------------------------------------------------------------------------------------------------------------------------------------------------
61
11.2
Ground Wire
----------------------------------------------------------------------------------------------------------------------------------------------------------------------
61
11.3
Ground Clamps
----------------------------------------------------------------------------------------------------------------------------------------------------------------
62
11.4
What Should Be Grounded?
------------------------------------------------------------------------------------------------------------------------------------
62
11.5
Lightening Protection
------------------------------------------------------------------------------------------------------------------------------------------------------
62
11.5.1
Power Line Protection
.....................................................................................................................
62
11.5.2
Communication Line Protection
..................................................................................................
62
12
APPENDIX D: ELECTROMAGNETIC NOISE SUPPRESSION CIRCUIT ------------------------------------- 63
12.1
English
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
63
12.2
Circuit de Suppression de Bruit Electromagnetique
------------------------------------------------------------------------------------
63
13
WARRANTY ------------------------------------------------------------------------------------------------------------------------------------------------- 65
© Munters AB, 2018 6
1 Introduction
Disclaimer
Introduction
Notes
1.1 Disclaimer
Munters reserves the right to make alterations to specifications, quantities, dimensions etc. for production
or other reasons, subsequent to publication. The information contained herein has been prepared by
qualified experts within Munters. While we believe the information is accurate and complete, we make no
warranty or representation for any particular purposes. The information is offered in good faith and with
the understanding that any use of the units or accessories in breach of the directions and warnings in this
document is at the sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing a Platinum Pro, Platinum Touch, Rotem Pro, or
Rotem One!
In order to realize the full benefit from this product it is important that it is installed, commissioned and
operated correctly. Before installation or using the fan, this manual should be studied carefully. It is also
recommended that it is kept safely for future reference. The manual is intended as a reference for
installation, commissioning and day-to-day operation of the Munters Controllers.
1.3 Notes
Date of release: May 2009
Munters cannot guarantee to inform users about the changes or to distribute new manuals to them.
All rights reserved. No part of this manual may be reproduced in any manner whatsoever without the
expressed written permission of Munters. The contents of this manual are subject to change without notice.
© Munters AB, 2018 7
2
Precautions
CAUTION
Protection provided by the equipment can be impaired if the equipment is used in a manner
not specified by the manufacturer!
CAUTION
There is a risk of explosion if the lithium battery is replaced with an incorrect type. Replace
the battery using the same type and manufacturer only.
English
French
2.1 English
Grounding
Filtering
Checking the Battery Level
Frequency Inverters
2.1.1 G
ROUNDING
Always connect temperature and sensor shields to earth ground.
Avoid mixing high voltage
wiring with sensor and low voltage wiring
.
Keep the controller as far as possible from heavy contactor boxes and other sources of
electrical interference
.
Do not connect communication wire shields, which go from one house to another at both ends.
Connect them at one end only. Connection at both ends can cause ground loop currents to
flow, which reduce reliability
.
The COM connection for communications is not the shield wire. The COM, RX and TX wires
must connect to each other at all controllers
.
2.1.2 F
ILTERING
If this installation includes a power inverter to drive variable speed fans, install an EMI filter in front of the
inverter, according to the specifications provided by the inverter manufacturer. Refer to the inverter
documentation.
2.1.3 C
HECKING THE
B
ATTERY
L
EVEL
Check the battery once a year. The output must be 2.7 volts (minimum). Authorized personnel only must
replace the battery if the output is below the minimum required level or every five years.
2.1.4 F
REQUENCY
I
NVERTERS
Frequency inverters can cause severe electrical and electromagnetic interference. Therefore, when
employing a frequency inverter, it is critical that you carefully follow the manufacturer's installation
instructions.
In particular verify:
© Munters AB, 2018 8
That the cable shielding between the inverter and any motor meets industry standards
Proper grounding of the inverter's chassis and motor power cable
Proper grounding of low voltage cable shield wire
That the controller and inverter cables are kept in separate conduits or wire bundles
1. Controller
2. Inverter
3. Place the controller at least five meters from the inverter.
2.2 French
Raccord à la Terre
Filtrage
Vérification du Niveau de la Batterie
Onduleurs de Fréquence
2.2.1 RACCORD À LA TERRE
Raccordez toujours à la terre les protections thermiques et du capteur. Evitez de mélanger les
fils à haute tension avec les fils du capteur et les fils à basse tension.
Maintenez le contrôleur aussi loin que possible du boîtier lourd de contacteur et des autres
sources d’interférences électriques.
Ne connectez les protections des fils de communication, allant d’une maison à une autre aux
deux extrémités. Connectez-les à une seule extrémité uniquement. La connexion aux deux
extrémités peut entraîner la circulation de courants dans la boucle de terre, et risquer ainsi de
réduire la fiabilité.
La connexion COM pour les communications n’est pas le fil blindé. Les fils COM, RX et TX
doivent être connectés les uns aux autres au niveau de tous les contrôleurs.
2.2.2 FILTRAGE
Si cette installation comprend un onduleur de puissance capable d’actionner les ventilateurs à vitesse
variable, installez un filtre EMI en amont de l’onduleur selon les spécifications fournies par le fabricant de
l’onduleur. Référez-vous à la documentation de l’onduleur.
2.2.3 VÉRIFICATION DU NIVEAU DE LA BATTERIE
Vérifiez la batterie une fois par an. La sortie doit être 2.7 volts (minimum). Seul le personnel autorisé est
en droit de remplacer la batterie si la sortie est inférieure au niveau minimum ou tous les cinq ans.
© Munters AB, 2018 9
2.2.4 ONDULEURS DE FRÉQUENCE
Les onduleurs de fréquence peuvent causer de sévères interférences électriques et électromagnétiques.
Par conséquent, lorsque vous utilisez un onduleur de fréquence, il est essentiel de suivre scrupuleusement
les instructions du fabricant.
Vérifiez en particulier :
Que la protection des câbles entre l’onduleur et le moteur réponde aux normes industrielles.
Que le raccord à la terre pour le châssis de l’onduleur et le câble d’alimentation du moteur soit
correct
Que le raccord à la terre du fil de protection du câble à basse tension soit correct
Que les câbles du contrôleur et de l’onduleur soient conservés dans des conduites séparées ou
des faisceaux de fils
1. Manette
2. Onduleur
3. Placez le contrôleur à au moins 5 mètres de l'onduleur.
© Munters AB, 2018 10
3
Specifications
Description
Specification
Input Power Voltage
100 240 VAC
Platinum Touch: 1A, 50/60 Hz
Platinum Pro: 0.6A, 50/60 Hz
Rotem One: 1.2A, 50/60 Hz
Rotem Pro: 0.8A, 50/60 Hz
Normally Open Relays
Non Fused
70% of relays can operate simultaneously (maximum)
200 240 VAC max load: 2HP (7A during continual
operation, up to 30A at startup)
100 130 VAC max load: 1HP (7A during continual
operation, up to 30A at startup)
Normally Close Relays
Non Fused
70% of relays can operate simultaneously (maximum)
200 240 VAC max load: 1HP (4A during continual
operation, up to 20 Amp at startup)
100 130 VAC max load: 0.5HP (4A during continual
operation, up to 20A at startup)
CAUTION
Switching loads over 10A reduces a relay’s life span (from 100,000 operations to
~10,000 operations).
Analog Inputs 0 - 5 Volts, 5VDC maximum
Analog Output 0 - 10 Volts; maximum load: 20 mA
Digital Inputs 5 Volts, 1.5 mA, dry contact
Operating Temperature
Range
0° to +50° C (32° to 125° F)
Enclosure
Water and dust tight
indoor use only
Fuses Fuse F1 on PS card: 5A, 250V
Certification
Disconnection device/overcurrent protection: In the building installation, use a certified 2-
pole circuit breaker rated 10A, certified in accordance with the IEC standard 60947-2 (in the
US and Canada uses a Listed Brach Circuit protective circuit breaker). This step is required to
provide overcurrent protection and mains disconnection. The circuit breaker must be easily
accessible and marked as the controller disconnect device.
Main Supply Voltage: Permanently connect the controller to the mains in accordance with the
relevant national code. Provide fixed wiring inside a flexible conduit. Relays must be suitably
protected against overcurrent, using a circuit breaker rated at 10A.
© Munters AB, 2018 11
4
Before Using
NOTE
Platinum Pro refers to the Platinum Pro and Platinum Touch units unless specified. Rotem One
refers to the Rotem One and Rotem Pro units unless specified.
Layout
Typical Accessories
Product Symbols
Rotem One/Rotem Pro Normally Open/Closed Cards
4.1 Layout
Number of Relays
Platinum Pro Layout
Rotem One Layout
4.1.1 N
UMBER OF
R
ELAYS
Platinum Pro/Platinum Touch supports 30 relays
Rotem Pro/Rotem One supports 50 relays
Panel Mounts support 30 or 50 relays
© Munters AB, 2018 12
4.1.2 P
LATINUM
P
RO
L
AYOUT
This illustration displays the main elements found in the Platinum Pro and Platinum Touch.
Figure 1: Platinum Pro /Platinum Touch Layout
Figure 1 key
1 Backup screen and keyboard (Touch only) 6 Communication card
2 Main CPU card 7 Power supply
3 Communication card to Expansion unit/RLED 2.0
8 Normally Open, Normally
Closed, Winch, Current
Sense cards
4 Analog Input/Output and Digital Input cards 9 Switch cards
5 Alarm card
© Munters AB, 2018 13
4.1.3 R
OTEM
O
NE
L
AYOUT
The following illustration displays the main elements in Rotem One units.
Figure 2: Rotem Pro /Rotem One Layout
Figure 2 key
1 Backup screen and keyboard (Touch only) 6 Communication card
2 Main CPU card 7 Power supply, high voltage
3 Pressure sensor 8 Normally Open, Normally Closed,
Winch, Current Sense cards
4 Analog Input/Output and Digital Input cards 9 Switch cards
5 Alarm card 10 Internal communication card
NOTE
Figure 1 and Figure 2 are example layouts. Each installation can differ.
© Munters AB, 2018 14
Figure 3: Rotem One External Parts
4.2 Typical Accessories
Platinum Pro and Rotem One support:
Analog input, digital input, analog output cards
1 x Rotem One Expansion unit
5 x RLED 2.0
1 X RDT-5 (Software version X.20 supports two RDT-5 units)
2 x RSU-2 (Software version X.18 supports five RSU-2 units)
1 x HUB-4
NOTE
This manual provides wiring instructions for the cards. Refer to the products respective manuals
for installation instructions.
Figure 4: Expansion units
Figure 5: RLED 2.0
© Munters AB, 2018 15
Figure 6: RDT-5
Figure 7: RSU-2
Figure 8: HUB
Figure 9: Accessories
4.3 Product Symbols
The following labels appear on your controller:
:
Caution! Hazardous voltage
:
Caution: Refer to the manual
:
Main Protective Earthing Terminal
CAUTION
IF THE UNIT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE
PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
© Munters AB, 2018 16
4.4 Rotem One/Rotem Pro: Normally Open/Closed Cards
Normally Open (only) sets include ten relays: Two (2) 5 x Normally Open relay cards along
with a 10 relay switch card.
Normally Closed relays come included in sets made up of:
o
One 5 x Normally Closed relay card. This card must be installed on the left side of the
unit. See Figure 4.
o
One 5 x Normally Open relay card.
o
A switch card having five Normally Open relays and five Normally Closed relays.
Figure 10: Normally Closed Card Installation
To order replacements:
Rotem One / Rotem Pro - Combined Normally Close/Open Switch Card (P/N: P4-NC&NO-
SC): 900-99-00336
Rotem One / Rotem Pro - Combined Normally Close/Open Set 30A (P/N: P4-NC&NO-S-
30A): : 900-99-00337 (
sets include relay cards and a switch
)
© Munters AB, 2018 17
5
Mounting the Units
The following sections detail the initial steps required when installing the controllers. Users installing the
Panel Mounts, refer to Appendix A: Platinum Pro Metal Assembly.
Installing the Platinum Pro
Installing the Rotem One
5.1 Installing the Platinum Pro
Mounting the Platinum Pro
Drilling
5.1.1 M
OUNTING THE
P
LATINUM
P
RO
1. Remove the mounting plates (x4) and
screws (x8) from the plastic bag.
2. Fasten the mounting plates to the corners of
the controller using four screws.
3. Place the controller box on the wall and make sure it is leveled (use a spirit level).
4. Using the remaining screws, secure the controller to the wall.
5.1.2 D
RILLING
Drill holes on the side and bottom of controller box according to the steps defined below. Use these
holes to route the low and high voltage cables.
CAUTION
Make sure not to damage cards when drilling holes. Locate holes properly before
drilling!
© Munters AB, 2018 18
1. Drill a hole on the right side of the controller box. Verify that the low voltage cables being used
go through the hole properly.
Figure 11: Drilling on the Side
2. Drill a hole on the bottom side of the controller box. Verify that the high voltage cables being
used fit through the hole properly.
NOTE
Munters recommends drilling at least two (2) holes, placed as close to the front edge as
possible (to avoid crowding the wiring).
Figure 12: Drilling on the Bottom
3. Clean the holes from plastic shards. Verify that rims of holes are smooth.
© Munters AB, 2018 19
Figure 13: Hole locations
5.2 Installing the Rotem One
What comes in the Package
Knockouts
Mounting
5.2.1 W
HAT COMES IN THE
P
ACKAGE
One Rotem One unit
Two hanging brackets
12 screws
© Munters AB, 2018 20
5.2.2 K
NOCKOUTS
On the bottom and side of the Rotem One are knockouts used to route the low and high voltage cables.
Figure 14: Low Voltage Knockouts
Figure 15: High Voltage Knockouts
Using a screwdriver and a hammer, gently apply pressure to the knockouts.
Only open up the holes that you require.
Munters recommends removing the knockouts before mounting the unit.
5.2.3 M
OUNTING
Rotem One comes with two hanging brackets.
Hang the Rotem One on a wall capable of supporting the unit’s weight!
1. Use the supplied screws to attack the bracket to the wall.
Figure 16: Wall bracket
2. Attach to the Rotem One:
o
the second hanging bracket
o
the securing brackets
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67

Munters PP Rotem1 Guide d'installation

Taper
Guide d'installation

dans d''autres langues