Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual
CROUSE-HINDS
SERIES
Explosionsgeschützte Leergehäuse GBXE
Explosion-protected empty enclosure GBXE
Boîtier vide GBXE pour atmospres explosives
Betriebsanleitung
Operating instructions
Mode d’emploi
GHG 760 7001 P0001 D/GB/F (-)
CZ: "Tento návod k použití si m žete vyžádat
ve
svém mate ském jazyce u p íslušného
zastoupení spole nosti Cooper Crouse-
Hinds/CEAG ve vaší zemi."
DK: "Montagevejledningen kan oversættes til
andre EU-sprog og rekvireres hos Deres
Cooper Crouse-Hinds/CEAG leverandør"
E: "En caso necesario podrá solicitar de su
representante Cooper Crouse-Hinds/CEAG
estas instrucciones de servicio en otro idioma
de la Union Europea"
EST: "Seda kasutusjuhendit oma riigikeeles
võite küsida oma riigis asuvast asjaomasest
Cooper Crouse-Hindsi/CEAG esindusest."
FIN: "Tarvittaessa tämän käyttöohjeen käännös
on saatavissa toisella EU:n kielellä Teidän
Cooper
Crouse-Hinds/CEAG - edustajaltanne"
GR:
Cooper Crouse-
Hinds/CEAG"
H: "A kezelési útmutatót az adott ország
nyelvén a Cooper Crouse-Hinds/CEAG cég
helyi képviseletén igényelheti meg."
I: "Se desiderate la traduzione del manuale
operativo in un´altra lingua della Comunit à
Europea potete richiederla al vostro
rappresentante Cooper Crouse-Hinds/CEAG"
LT: Šios naudojimo instrukcijos, išverstos
J su
gimt
j kalb , galite pareikalauti atsakingoje
"Cooper Crouse-Hinds/CEAG" atstovyb
je savo
šalyje.
LV: "Šo ekspluat
cijas instrukciju valsts valod
varat piepras t j su valsts atbild gaj Cooper
Crouse-Hinds/CEAG p
rst vniec b ."
M: Jistg
u jitolbu dan il-manwal fil-lingwa
nazzjonali tag
hom ming and ir-rappre entant
ta' Cooper Crouse Hinds/CEAG f'pajji
hom.
NL: "Indien noodzakelijk kan de vertaling van
deze gebruiksinstructie in een andere EU-taal
worden opgevraagd bij Uw Cooper Crouse-
Hinds/CEAG - vertegenwoordiging"
P: "Se for necessária a tradução destas
instruções de operação para outro idioma da
União Europeia, pode solicita-la junto do seu
representante Cooper Crouse-Hinds/CEAG"
PL: Niniejsz
instrukcj obs ugi w odpowiedniej
wersji j
zykowej mo na zamówi
w
przedstawicielstwie firmy Cooper-Crouse-
Hinds/CEAG na dany kraj.
S: "En översättning av denna montage- och
skötselinstruktion till annat EU - språk kan vid
behov beställas från Er Cooper Crouse-
Hinds/CEAG- representant"
SK: "Tento návod na obsluhu Vám vo Vašom
rodnom jazyku poskytne zastúpenie spolo
nosti
Cooper Crouse-Hinds/CEAG vo Vašej krajine."
SLO: "Navodila za uporabo v Vašem jeziku
lahko zahtevate pri pristojnem zastopništvu
podjetja Cooper Crouse-Hinds/CEAG v Vaši
državi."
RUS:
"
При необходимости, вы можете запрашивать
перевод данного руководства на другом языке
ЕС или на русском от вашего
Cooper Crouse-Хиндс / CEAG - представителей."
2
Leergehäuse GBXE; Enclosures GBXE;
Inhalt: Contents: Contenu:
Konformitätsbescheinigung
separat beigelegt.
Attestation of conformity,
enclosed separately.
Attestation de conformité,
jointe séparément.
Schéma d'dimensions 3
Instructions de montage
Boulon de mise à la terre 3
1 Caractéristiques techniques 14
2 Legende 15
2.1 Consignes de sécurité 15
3 Conformité aux normes 15
4 Domaine d’utilisation 15
5 Utilisation/propriétés 16
6 Installation 16
7 Entretien / Maintenance 18
8 Réparations / Remise en état /
Modifications 18
9 Évacuation des déchets / Recyclage 18
10 Tableau de charge 19
Maßzeichnung 3
Montagehinweise
Erdungsanschluss 3
1 Technische Angaben 4
2 Legende 4
2.1 Sicherheitshinweise 4
3 Normenkonformität 5
4 Verwendungsbereich 5
5 Verwendung / Eigenschaften 5
6 Installation 5
7 Instandhaltung / Wartung 6
8 Reparatur / Instandsetzung /
Änderung 6
9 Entsorgung / Wiederverwertung 6
10 Zubehör / Ersatzteile 6
Dimension drawing 3
Mounting instruction
Earthing stud bolt 3
1 Technical data 7
2 Legende 7
2.1 Safety instructions 7
3 Conformity with standards 8
4 Field of application 8
5 Application / Properties 8
6 Installation 8
7 Maintenance / Servicing 9
8 Repairs / Overhaul /
Modifications 9
9 Disposal/Recycling 9
10 Accessories / Spare parts 9
Boîtier vide GBXE;
3
Leergehäuse GBXE Enclosures GBXE Boîtier vide GBXE
Maßangaben in mm
X = Befestigungsmaße
Dimensions in mm
X = fixing dimensions
Dimensions en mm
X = dimensions de fixation
B
Katalognummer /
Catalog number /
numéro de
catalogue
A B C Cu Co X Y
Gewicht /
Weight /
Poids
(g)
(mm) (mm) (mm) (mm) (mm) (mm) (mm)
GBX E 121209 122 120 90 65 25 106 82 543.5
GBX E 221209 220 120 90 65 25 204 82 811
GBX E 161609 160 160 90 70 20 140 110 959
GBX E 261609 260 160 90 70 20 240 110 1342
GBX E 361609 360 160 90 70 20 340 110 1727
GBX E 252512 255 250 120 95 25 235 200 2132
GBX E 402512 400 250 120 95 25 380 200 2971
GBX E 404012 400 405 120 95 25 380 355 4263
Maßzeichnung Dimension drawing Schéma d'dimensions
Fig. 1
A
C
1
Cu Co
Xd2
Xd1
X1
X1
Y
4
D
Explosionsgeschützte Leergehäuse GBXE
EU-Baumusterprüfbescheinigung: TÜV 18 ATEX 8239U
Gerätekennzeichnung nach 2014/34/EU
EN 60079-0
II 2 G
Ex e IIC Gb
II 2 D
Ex tb IIIC Db
IECEx Konformitätsbescheinigung: IECEx TUR 18.0033U
Gerätekennzeichnung
IEC60079-0 Ex e IIC Gb
Ex tb IIIC Db
Einsatztemperaturbereich: -50 °C ... +100 °C
Zul. Lagertemperatur in Originalverpackung: -50 °C ... +100 °C
Schlagfestigkeit nach IEC/EN 60079-0: 7 J
Schutzart nach EN/IEC 60529: IP66 (Listenausführung)
Schutzklasse nach EN/IEC 61140: II
Gehäusematerial: GRP (Glass fiber reinforced plastics / Glasfaserverstärkte Kunststoffe)
Gehäusefarbe: schwarz( vergleichbar RAL 9011)
Prüfdrehmomente:
Deckelschrauben: M4 1 - 2 Nm
M6 2- 4 Nm
1 Technische Angaben
1.1 Leergehäuse
2 Legende
Warnung
Dieses Symbol warnt von einer ernsten Gefahr. Diese Warnung nicht
zu beobachten kann Tod oder die Zerstörung von Einrichtungen zur
Folge haben.
Achtung
Dieses Symbol warnt von einem möglichen Ausfall. Wird diese
Warnung nicht beobachtet kann den Gesamtausfall der Vorrichtung
oder des Systems oder des Betriebes erfolgen, an die es angeschlos-
sen wird.
Hinweis
Dieses Symbol hebt wichtige Informationen hervor.
2.1 Sicherheitshinweise
Zielgruppe dieser Anleitung sind Elektrofachkräfte und
qualifizierte, unterwiesene Personen in Anlehnung an die
EN/IEC60079-14 und Projektierungs- Entwicklungsfach-
kräfte in Anlehnung an die EN/IEC 60079-0.
Die Anforderungen der EN/IEC 60079-31, u.a. in Bezug auf übermäßi-
ge Staubablagerungen und Temperatur, sind vom Anwender zu
beachten.
Diese Leergeuse GBXE dürfen ohne komplette Bescheinigung nicht
im Ex- Bereich eingesetzt werden. Sie sind auch komplett Beschei-
nigt nicht für den Einsatz in Zone 0 und Zone 20 geeignet.
Die Leergehäuse GBXE müssen nach erfolgter Bestückung von einer
Prüfstelle oder zur Prüfung berechtigter Personen geprüft und
komplett Bescheinigt werden.
Sie sind bestimmungsgemäß in unbeschädigtem und einwandfreiem
Zustand zu betreiben.
Nach der Installation nicht demontieren, außer für gelegentliche
Wartungsarbeiten.
Die Leergehäuse GBXE dürfen nur verwendet werden, wenn die
Temperatur an den Kabel- und Leitungseinführungen (KLE) zwischen
- 50 °C ... +100 °C liegt.
5
Vor Inbetriebnahme muss das Betriebsmittel entsprechend der im
Abschnitt 6 genannten Anweisung geprüft werden.
Beachten Sie die nationalen Sicherheits- und Unfallverhütungsvor-
schriften und die nachfolgenden Sicherheitshinweise in dieser
Betriebsanleitung, die wie dieser Text in Kursivschrift gefasst sind!
3 Normenkonformität
Die Leergehäuse entsprechen den aufgeführten Normen, in der separat
beigelegten Konformitätbescheinigung.
Verweise auf Normen und Richtlinien in dieser Betriebsanleitung beziehen
sich immer auf die aktuelle Version. Zusätzliche Ergänzungen
(z.B. Jahreszahlangaben) sind zu beachten.
4 Verwendungsbereich
Die nach der Prüfung durch eine Prüfstelle/berechtigter Person, komplett
bescheinigten Leergehäuse sind für den Einsatz in explosionsgefährdeten
Bereichen der Zone1 2 und Zone 21, 22 gemäß EN/IEC 60079-10-1
und EN/IEC 60079-10-2 geeignet.
Die eingesetzten Gehäusematerialien einschließlich der außenliegenden
Metallteile bestehen aus hochwertigen Werkstoffen, die einen anwen-
dungsgerechten Korrosionsschutz und Chemikalienresistenz in „norma-
ler Industrieatmosphäre“ gewährleisten:
- GRP
Bei einem Einsatz in extrem aggressiver Atmosphäre, können Sie
zusätzliche Informationen über die Chemikalienbeständigkeit der
eingesetzten Kunststoffe, bei Ihrer zuständigen EATON / Cooper
Crouse-Hinds GmbH Niederlassung erfragen.
5 Verwendung / Eigenschaften
Die nach der Prüfung durch eine Prüfstelle/berechtigte Person, komplett
bescheinigten Leergehäuse dienen zum Verteilen von elektrischer
Energie, z.B. Lichtstromkreise, Heizstromkreise, Steuerstromkreise, usw..
Umgebungstemperatur siehe technische Daten.
Das Leergehäuse GBXE kann für die Montage von elektrischen und
mechanischen Komponenten verwendet werden.
Das Leergehäuse GBXE besteht aus hochwertigem glasfaserverstärktem
Polyester mit Graphitzusatz. Deckel und Unterteil sind mit unverlierbaren
Edelstahlschrauben verschraubt.
Ein Nut-Feder-System mit eingelegter Dichtungsschnur zwischen Deckel
und Boden gewährleistet eine hohe Schutzart (siehe technische Daten).
Andere als die beschriebenen Anwendungen sind ohne schriftli-
che Erklärung der Fa. EATON / Cooper Crouse-Hinds GmbH nicht
zulässig.
Die Verantwortung hinsichtlich bestimmungsgemäßer Verwen-
dung der GBXE unter Bezugnahme der in der Anlage vorhandenen
Rahmenbedingungen (s. technische Daten) liegt allein beim
Betreiber.
Beim Betrieb sind die in der Betriebsanleitung unter Punkt 7
genannten Anweisungen zu beachten.
Das Produkt ist durch Patente geschützt. Weitere Hinweise hierzu
erhalten Sie bei Ihrer EATON / Cooper Crouse-Hinds GmbH Vertretung.
6 Installation
Für das Errichten / Betreiben sind die relevanten nationalen Vorschriften
(z.B. BetriSichV, Gerätesicherheitsgesetz für Deutschland) sowie die
allgemein anerkannten Regeln der Technik maßgebend.
Die Montage des Gehäuses erfolgt durch die außerhalb des Dichtraumes
liegenden Schraubenkanäle.
Bei der Bearbeitung der Gehäuse ist darauf zu achten, dass
zwischen den einzelnen Bohrungen und von der Dichtkante des
Gehäuses ein geeigneter Mindestabstand eingehalten wird, damit
das Gehäuse den Anforderungen einer Schlagprüfung standhalten
kann.
Der Mindestabstand ist abhängig von den geometrischen Abmessungen
der Einbauteile; ein längerer Hebel erfordert eine Vergrößerung des
Mindestabstandes und muss entsprechend festgelegt werden.
Bei Gehäusen, die im Freien aufgestellt werden müssen, kann es
erforderlich sein, Maßnahmen zu ergreifen, um den bestimmungsgemä-
ßen Betrieb sicherzustellen. Dazu gehören z.B. Dächer als Regenschutz
oder Außengehäuse mit ausreichender Schutzart.
Die Gehäuse sind horizontal an der Wand oder an den horizonta-
len Flächen anzubringen.
Die gewählte Schraube muss der Befestigungsöffnung angepasst sein
(siehe Maßbild) und sie darf die Öffnung nicht beschädigen (z.B.
Verwendung einer Unterlegscheibe).
Bei übermäßigem Anziehen der Befestigungsschrauben kann das
Betriebsmittel beschädigt werden.
6.1 Elektrischer Anschluss
Der elektrische Anschluss muss durch eine Elektrofachkraft
nach IEC/EN 60079-14 erfolgen.
D
Explosionsgeschützte Leergehäuse GBXE
6
6.2 Kabel-und Leitungseinführungen (KLE)
Der Mindestabstand der Bohrungen ist gemäß Tabelle, Bohrraum für
Kabelverschraubungen und Verschlussstopfen einzuhalten. Hierzu bitte
EATON / Cooper Crouse-Hinds GmbH kontaktieren.
Alle Kabeleinführungen und Blindverschraubungen müssen für die
Schutzarten "e" und "tb" zertifiziert sein und mindestens die Schutzart
IP 66 erfüllen.
Alle nicht benutzten Gehäuseöffnungen müssen mit zertifizierten
Verschlussstopfen der Schutzarten "e" und "tb" verschlossen
werden und mindestens die Schutzart IP 66 erfüllen.
Die Eignung aller Verschlussstopfen und KLEs sollte vor der Inbe-
triebnahme überprüft werden.
Bei Einführungen mit parallelen Gewinden müssen Kabelver-
schraubungen, Verschlussstopfen und eine zusätzliche Dichtung
verwendet werden.
6.3 Schließen des Gerätes
Alle Fremdkörper sind aus dem Gerät zu entfernen.
Gehäusedeckel auf dem Unterteil ausrichten.
Die Gehäuseschrauben anschrauben und diagonal anziehen
(Prüfdrehmoment siehe Technische Daten).
6.4 Inbetriebnahme
Vor Inbetriebnahme des Betriebsmittels sind die in den einzelnen
nationalen Bestimmungen genannten Prüfungen durchzuführen.
Außerdem ist vor der Inbetriebnahme die korrekte Funktion und
Installation des Betriebsmittels in Übereinstimmung mit dieser Betriebs-
anleitung und anderen anwendbaren Bestimmungen zu überprüfen.
Elektrische Anlagen müssen vor der ersten Inbetriebnahme und
regelmäßig in bestimmten Zeitabständen von einem qualifizierten
Fachmann überprüft werden.
IUnsachgemäße Installation und Betrieb kann zum Verlust der
Garantie führen.
7 Instandhaltung / Wartung
Die für die Wartung / Instandhaltung von elektrischen Betriebs-
mitteln in explosionsgefährdeten Bereichen geltenden nationalen
Bestimmungen sind einzuhalten EN/IEC 60079-17.
Vor dem Öffnen des Gehäuses sicherstellen, dass das Gehäuse von
der Spannung getrennt ist, oder entsprechenden Schutzmaßnahmen
treffen.
Bei eigensicheren Stromkreisen ist das Arbeiten unter Spannung zulässig.
Die erforderlichen Wartungsintervalle sind anwendungsspezifisch und
daher in Abhängigkeit von den Einsatzbedingungen vom Betreiber
festzulegen.
Im Rahmen der Wartung sind vor allem die Teile, von denen die Zünd-
schutzart abhängt, zu prüfen (z.B. Unversehrtheit und Dichtheit des
Gehäuses).
Sollte bei einer Wartung festgestellt werden, dass Instandsetzungsarbei-
ten erforderlich sind, ist Abschnitt 8 dieser Betriebsanleitung zu beachten.
8 Reparatur / Instandsetzung / Änderung
Instandsetzungsarbeiten / Reparaturen dürfen nur unter Verwendung von
EATON / Cooper Crouse-Hinds GmbH Originalersatzteilen vorgenommen
werden.
Reparaturen, die den Explosionsschutz betreffen, dürfen nur von
EATON / Cooper Crouse-Hinds GmbH oder einer qualifizierten
Elektrofachkraft in Übereinstimmung mit national geltenden Regeln
durchgeführt werden (EN/IEC 60079-19).
Für Austausch und Reparatur dürfen nur Originalteile von EATON
/ Cooper Crouse-Hinds GmbH verwendet werden.
Umbauten oder Änderungen am Betriebsmittel die den Explosionsschutz
betreffen sind nicht gestattet.
9 Entsorgung / Wiederverwertung
Bei der Entsorgung des Betriebsmittels sind die jeweils geltenden
nationalen Abfallbeseitigungsvorschriften zu beachten.
Zusätzliche Informationen zur Entsorgung des Produktes können Sie bei
Ihrer zuständigen EATON / Cooper Crouse-Hinds GmbH Niederlassung
erfragen.
Programmänderungen und -ergänzungen sind vorbehalten.
10 Zubehör / Ersatzteile
Zubehör / Ersatzteile finden Sie im EATON / Cooper Crouse-Hinds GmbH
Katalog
D
Explosionsgeschützte Leergehäuse GBXE
7
Explosion-protected empty enclosure GBXE
GB
1 Technical data
1.1 Empty enclosure
2 Legende
Warning
This symbol warns of a serious hazard. Failure to observe this
warning may result in death or the destruction of property.
Attention:
This symbol indicates a possible failure. Ignoring this warning can
lead to the total failure of the device, system or operation to which it
is connected.
Note:
This symbol stresses important information.
2.1 Safety instructions
The operations shall be carried out
by qualified, instructed electricians or qualified personnel
according to IEC/EN 60079-14 and engineering/develop-
ment specialists according to IEC/EN 60079-0.
The requirements of the IEC/EN 60079-31 regarding excessive dust
deposits and temperature to be considered from the user.
These empty enclosures GBXE may not be used in hazardous areas
without full certification. Even if they are fully certified, they are not
suitable for use in Zone 0 and Zone 20.
After apparatus/terminals have been installed in the empty enclo-
sure, it shall be tested and fully certified by a testing authority or
authorized person.
They shall be used for their intended purpose and in perfect and
clean condition.
Once Installed do not dismantle except for occasional inspection.
The empty enclosures GBXE shall only be used where temperature
at the point of entry is between (- 50 °C to +100 °C).
EU type examination certificate: TÜV 18 ATEX 8239U
Marking acc. to 2014/34/EU and standard:
EN 60079-0
II 2 G
Ex e IIC Gb
II 2 D
Ex tb IIIC Db
IEC Ex type examination certificate IECEx TUR 18.0033U
Marking:
IEC60079-0 Ex e IIC Gb
Ex tb IIIC Db
Perm. service temperature: -50 °C ... +100 °C
Perm. storage temperature in original packing: -50 °C ... +100 °C
Impact resistance acc. to IEC/EN 60079-0: 7 J
Protection category acc. to IEC/EN 60529: IP66 (catalogue version)
Insulation class acc. to IEC/EN 61140: II
Enclosure material: GRP (Glass fiber reinforced plastics)
Enclosure color: Black ( Similar to RAL 9011)
Test torques:
Cover screws: M4 1 - 2 Nm
M6 2- 4 Nm
8
Prior to being put into operation, the apparatus shall be checked in
accordance with the instructions as per section 6.
The national safety rules and regulations for the prevention of
accidents, as well as the safety instructions included in these
operating instructions, that, like this text, are set in italics, shall be
observed!
3 Conformity with standards
They are conform to the standards specified in the attestation of
conformity, enclosed separately.
References to standards and directives in these operating instructions
always relate to the latest version. Other additions (e.g. details relating to
the year) shall be observed.
4 Field of application
Fully certified empty enclosures that have been tested by a testing
authority or authorized person are suited for use in hazardous areas in
Zone 1, 2 and Zone 21, 22 in accordance with IEC/EN60079-10-1 and
IEC/EN60079-10-2.
The enclosure materials used, including any external metal parts, are high
quality materials which ensure a corrosion protection and resistance to
chemical substances corresponding to the requirements in a “normal
industrial atmosphere”:
- GRP
In case of use in an extremely aggressive atmosphere, you can obtain
information concerning the chemical resistance of the materials used
from your Cooper Crouse-Hinds branch.
5 Application / Properties
The empty enclosures GBXE have been fully certified by a testing station/
authorized individual after inspection are used, within the limitations of
the permissible power loss, to distribute electrical energy, e.g. for lighting,
heating and control circuits, etc..
Service temperature see technical data.
The empty enclosure GBXE may be used for fitting electrical and
mechanical components.
The empty enclosure GBXE consists of high-quality Glass Reinforced
Polyester with graphite added . Lid and base are screwed together with
stainless steel captive screws.
A groove and tongue system with inserted sealing cord between the lid
and base assures the high protection class (see technical data).
Applications other than those described are not permitted
without Cooper Crouse-Hinds’s / EATON prior written consent.
The user alone is responsible for the appropriate use of this
empty enclosure GBXE in consideration of the basic conditions exist-
ing at the plant (see technical data).
The instructions stated in section 7 of the operating instructions
shall be observed during operation.
The product is protected by patents. For more information, please contact
your local EATON / Cooper Crouse-Hinds GmbH representative.
6 Installation
For the mounting and operation, the respective national regulations as
well as the general rules of engineering will have to be observed
(IEC/EN 60079-14).
The enclosure is mounted through the screw channels lying outside the
sealing space.
When processing the enclosures, attention must be paid to
ensuring that there is suitable minimum spacing between individual
boreholes and from the sealing edge of the enclosure so that the
enclosure with the fittings will be able to withstand an impact test.
The minimum spacing depends on the geometrical dimensions of the
built-in components; a longer lever will require an increase in the
minimum spacing and accordingly must be determined specifically.
In the case of enclosures that have to be set up outside, it may be
necessary to take measures to ensure that operation is in accordance
with the intended use. This would include, for example, roofs as
protection against rain or outer housings with an adequate protection
class.
Enclosures shall be mounted horizontally over the wall or on the
horizontal surfaces.
The chosen screw shall match the fastening hole (see dimensional
drawing) and it must not damage the hole (e. g. use of a washer).
If the screws are overtightened, the apparatus can be damaged.
6.1 Electrical connection
The electrical connection may only be carried out by skilled
staff accordance to IEC/EN 600479-14.
Explosion-protected empty enclosure GBXE
GB
9
Explosion-protected empty enclosure GBXE
GB
8 Repairs / Overhaul / Modifications
Overhaul and repairs may only be carried out with genuine EATON /
Cooper Crouse-Hinds GmbH spare parts.
Repairs may only be carried out by EATON / Cooper Crouse-Hinds
GmbH or a qualified electrician (Competent person) in compliance
with the applicable national rules
(IEC/EN 60079-19).
For replacement and repair only original parts from EATON /
Cooper Crouse-Hinds GmbH may be used.
Modifications to the apparatus or changes of its design are not permitted,
except for the mounting of additional cable entries and the installation of
supply terminals in accordance with the approval of the apparatus.
9 Disposal/Recycling
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
In case of disposal you can obtain additional information from your EATON
/ Cooper Crouse-Hinds GmbH branch.
Subject to modifications or supplement of the product range.
10 Accessories / Spare parts
For accessories and spare parts, see EATON / Cooper Crouse-Hinds
GmbH catalogue.
6.2 Cable Entry
The minimum distance of the drillings is to be kept in accordance with the
table, drilling space for cable glands and stopping plugs.
Please contact EATON / Cooper Crouse-Hinds GmbH
All cable entry devices and blanking elements must be certified
for protection types e’ and ‘tb’ and must have a minimum IP 66
rating.
All unused device openings must be fitted with a certified close-up
plug of protection types ‘e’ and ‘tb’ and must have a minimum IP 66
rating
The suitability of all entries should be considered in the end use
application.
For entries with parallel threads, cable glands, stop plugs must
be should be used along with additional seal or gasket.
6.3 Closing the device
Any foreign matter shall be removed from the apparatus.
Align the cover with the base.
Screw in the enclosure screws and tighten them diagonally
(test torque see technical data).
6.4 Taking into operation
Prior to taking the apparatus into operation, the tests specified in the
relevant national regulations will have to be carried out.
Apart from that, the correct functioning and installation of the enclosure /
equipment in accordance with these operating instructions and other
applicable regulations will have to be checked.
Electric plants must be examined by a qualified specialist before first
commissioning and regularly at specific intervals.
Incorrect installation and use can invalidate the guarantee.
7 Maintenance / Servicing
The relevant national regulations which apply to the maintenance/
repair of electrical apparatus in explosive atmospheres, will have to
be observed (IEC/EN 60079-17).
Before opening the enclosure make sure that the equipment is
disconnected from the voltage, or take the appropriate protective
measures.
In case of intrinsically safe circuits, working is permitted while voltage
applies.
The required maintenance intervals depend on the specific application and
will therefore have to be determined by the user dependent on the
conditions of use.
When servicing the apparatus, particularly those parts that are decisive for
the type of protection against explosion, will have to be checked (e.g.
intactness and tightness of the enclosure, efficacy of the gaskets and the
cable entries).
If during servicing, repairs prove to be necessary, section 8 of these
operating instructions will have to be observed.
10
Boîtier vide GBXE pour atmosphères explosives
F
1 Caractéristiques techniques
1.1 Boîtier vide
Attestation d’examen CE: TÜV 18 ATEX 8239U
Marquage selon 2014/34/UE et directive:
EN 60079-0
II 2 G
Ex e IIC Gb
II 2 D
Ex tb IIIC Db
IECEx Certificat de Conformité: IECEx TUR 18.0033U
Marquage selon:
IEC60079-0 Ex e IIC Gb
Ex tb IIIC Db
Température fonctionnement admissible: -50 °C ... +100 °C
Temp. de stockage dans l’emballage d’origine: -50 °C ... +100 °C
Impact resistance acc. to IEC/EN 60079-0: 7 J
Indice de protection selon CEI/EN 60529: IP66 (Versions standard)
Classe d’isolation selon CEI/EN 61140: II
Matèries de l’enveloppe: GRP ( polyester renforcé en fibre de verre)
Enclosure color: noir (comparable à RAL 9011)
Couples de serrage testés:
Vis du couvercle M4 1 - 2 Nm
M6 2- 4 Nm
2 Légende
Avertissement
Ce symbole avertit d'un risque grave. Cet avertissement peut pas
observer la mort ou la destruction des installations ont abouti.
Attention
Ce symbole met en garde contre un éventuel échec. Si cet avertisse-
ment est pas observé l'échec total de l'appareil ou système ou
l'opération peut avoir lieu, à laquelle il est connecté.
Référence
Ce symbole met en évidence des informations importantes.
2.1 Consignes de sécurité
Pour le personnel électricien qualifié et le personnel instruit
suivant la règlementation légale, y compris les normes
respectives ainsi que, le cas échéant,
CEI/EN 60079-14 pour appareils électriques utilisables
en atmosphère explosive et ingénierie / développement-profession-
nels, conformément aux CEI/EN 60079-0.
Les exigences des CEI/EN 60079-31 en ce qui concerne des dépôts de
poussière démesurés et une température doivent être considérées
par I’utilisateur.
Ces enveloppes GBXE ne doivent pas être utilisées en atmosphère
explosive sans attestation complète. Même avec attestation
complète, elles ne sont pas conçues pour l’utilisation en zone 0 ou
en zone 20.
Après l’assemblage, les enveloppes doivent être contrôlées par un
organisme de contrôle ou par un personnel autorisé à effectuer le
contrôle et recevoir une attestation complète.
Seuls des boîtier vide intactes et sans défaut de fabrication devront
être employés pour la fonction qui leur est dévolue.
Once Installed do not dismantle except for occasional inspection.
The empty enclosures GBXE shall only be used where temperature
at the point of entry is between (- 50 °C to +100 °C).
11
Avant toute mise en service, il est nécessaire de contrôler le matériel
selon les instructions données au point 6.
Respectez les prescriptions nationales de sécurité et de prévoyance
contre les accidents ainsi que les consignes de sécurité de ce mode
d’emploi en italique comme ce texte.
3 Conformité aux normes
Les enveloppes à jonction sont conformes aux normes reprises dans la
Attestation de conformité.
References to standards and directives in these operating instructions
always relate to the latest version. Other additions (e.g. details relating to
the year) shall be observed.
4 Domaine d’utilisation
Les enveloppes contrôlées par un organisme de contrôle ou par un
personnel autorisé à effectuer le contrôle et pourvues d’une attestation
complète ont été conçues pour l’utilisation dans des atmosphères
explosives de zone1, 2 et de zone 21, 22 CEI/EN 60079-10-1 et
CEI/EN 60079-10-2.
Les matériaux utilisés pour le boîtier et les pièces métalliques extérieures
sont de haute qualité et garantissent une protection anticorrosion et une
résistance aux produits chimiques adaptées à une « atmosphère
industrielle normale »
- GRP
En cas d‘utilisation dans une atmosphère extrêmement agressive, vous
pouvez obtenir des informations supplémentaires sur la résistance aux
produits chimiques des plastiques utilisés auprès de la filiale Cooper
Crouse Hinds compétente.
5 Utilisation/propriétés
Les enveloppes GBXE contrôlées par un organisme de contrôle ou par un
personnel autorisé à effectuer le contrôle et pourvues d’une attestation
complète servent à la distribution d’énergie électrique p.e. des circuits
d’éclairage, des circuits de chauffage, des circuits de commande, des
circuits à sécurité intrinséque etc. (quant à la classe de température, le
groupe d’explosion et la température ambiante admissible, voir les
caractéristiques techniques).
Température de fonctionnement admissible, voir les caractéristiques
techniques.
Le boîtier vide GBXE peut être utilisé pour le montage de composants
électriques et mécaniques.
Le boîtier vide GBXE est constitué d'un polyester renforcé de verre de
haute qualité avec ajout de graphite. Le couvercle et la base sont vissés
ensemble avec des vis imperdables en acier inoxydable.
Un système de rainure et languette avec cordon d'étanchéité inséré
entre le couvercle et la base assure une haute classe de protection (voir
caractéristiques techniques).
Toute utilisation autre que celle décrite ci-dessus est interdite,
sauf accord écrit de Cooper Crouse-Hinds’s / EATON.
Seul l’utilisateur est responsable de l’emploi comme prévu de
cette enveloppes GBXE, en tenant compte des conditions générales
existant dans l’établissement (voir Caractéristiques techniques).
Pour l'utilisation, respecter les instructions décrites au point7 du
mode d'emploi.
Le produit est protégé par des brevets. Pour plus d'informations, s'il vous
plaît contacter votre représentant Cooper Crouse-Hinds / EATON local.
6 Installation
Pour l’installation de ces appareils, la règlementation nationale en vigueur
(en Allemagne par ex. Betr.Si.V réglementation de sécurité des appareils,
ainsi que les règles de la technique généralement reconnues devront
être respectées (CEI/EN 60079-14).
Le boîtier est monté à travers les canaux de vis situés à l'extérieur de
l'espace d'étanchéité.
Lors de l'usinage des boîtiers, il faut veiller à ce qu'il y ait un
espacement minimal adéquat entre les différents trous de forage et
par rapport au bord d'étanchéité du boîtier afin que le boîtier avec
les raccords puisse résister à un essai de choc.
L'espacement minimum dépend des dimensions géométriques des
composants intégrés ; un levier plus long nécessitera une augmentation
de l'espacement minimum et doit donc être déterminé spécifiquement.
Dans le cas d'enceintes qui doivent être installées à l'extérieur, il peut
être nécessaire de prendre des mesures pour s'assurer que le fonction-
nement est conforme à l'utilisation prévue. Il peut s'agir, par exemple, de
toitures comme protection contre la pluie ou de boîtiers extérieurs avec
une classe de protection adéquate.
Les enceintes doivent être montées horizontalement au-dessus
du mur ou sur les surfaces horizontales.
La vis choisie doit correspondre à l'orifice de fixation (voir plan coté) sans
l'endommager (p.ex. utilisation d'une rondelle).
Le matériel peut être endommagé en cas de serrage excessif des
vis de fixation.
6.1 Raccordement électrique
Le raccordement électrique doit être effectué par un électricien
qualifié selon la norme CEI/EN 60079-14.
Boîtier vide GBXE pour atmosphères explosives
F
6.2 Passe-câbles
La distance minimale des perçages doit être respectée conformément au
tableau, l'espace de perçage pour les presse-étoupes et les bouchons
d'obturation doit être respecté.
Veuillez contacter EATON / Cooper Crouse-Hinds GmbH
Tous les dispositifs d'entrée de câble et les éléments d'obturation
doivent être certifiés pour les types de protection'e' et'tb' et doivent
avoir un indice de protection IP 66 minimum.
Toutes les ouvertures non utilisées de l'appareil doivent être munies
d'un bouchon de fermeture certifié de type de protection'e' et'tb' et
doivent avoir un indice de protection IP 66 minimum.
La pertinence de toutes les entrées doit être prise en compte dans
l'application d'utilisation finale.
Pour les entrées avec filetage parallèle, les presse-étoupes, les
bouchons d'arrêt doivent être utilisés avec un joint d'étanchéité
supplémentaire.
6.3 Fermeture de l’appareil
Tout corps étranger doit être ôté de l’appareil.
Aligner le couvercle avec le fond du boitier.
Vissez les vis du couvercle et serrez les en diagonale (voir couples de
serrage dans les caractéristiques techniques).
6.4 Mise en service
Avant la mise en service du produit, les tests mentionnés dans les
spécifications nationales sont à effectuer.
Le bon fonctionnement et la conformité de l'installation du matériel et
équipement au présent mode d'emploi, ainsi que d'autres dispositions
applicables doivent également être contrôlés avant la mise en service.
Electric plants must be examined by a qualified specialist before first
commissioning and regularly at specific intervals.
L'installation et l'utilisation non conformes entraînent la nullité de
la garantie.
7 Maintien/Entretien
La règlementation nationale en vigueur pour le maintien et l’entre-
tien du matériel électrique pour atmosphère explosive doit être
respectée. (en Allemagne par ex. CEI/EN 60079-17).
Avant d’ouvrir l’enveloppe, débrancher l’appareil de la tension ou
prendre des mesures préventives appropriées.
In case of intrinsically safe circuits, working is permitted while voltage
applies.
Les intervalles d´entretien sont spécifiques aux applications et sont donc
déterminées en fonction des conditions d´utilisation.
Lors de l’entretien des appareils et surtout des composants qui sont
essentiels à la protection contre l’explosion, devront être vérifiés (par ex.
intégrité des composants antidéflagrants, de l’enveloppe, des joints
d’étanchéité et des entrées de câble).
Si des travaux de remise en état sont jugés nécessaires, on se reportera
au chapitre 8 de ce mode d’emploi.
8 Réparations / Remise en état / Modification
Des réparations ne doivent être exécutées qu’à l’aide des pièces de
rechange d’origine EATON / Cooper Crouse-Hinds GmbH.
Des réparations qui portent sur la protection contre l’explosion,
ne devront être exécutées que par EATON / Cooper Crouse-Hinds
GmbH ou par un électricien qualifié en conformité avec la règlemen-
tation nationale en vigueur (CEI/EN 60079-19).
Des réparations ne doivent être exécutées qu’à l’aide de pièces de
rechange d’origine COOPER CROUSE-HINDS / EATON.
Des réparations qui portent sur la protection contre l’explosion, ne
devront être exécutées que par COOPER CROUSE-HINDS / EATON ou
par un électricien qualifié en conformité avec la règlementation nationale
en vigueur (CEI/EN 60079-19).
9 Disposal/Recycling
Lors de l’évacuation de ce matériel électrique, la règlementation nationale
respective en vigueur devra être respectée.
En cas d'élimination, vous pouvez obtenir des informations supplémen-
taires auprès de votre branche Cooper Crouse-Hinds / EATON.
Sous réserve de modification ou de supplément de cette série de
produits.
10 Accessories / Spare parts
For accessories and spare parts, see EATON / Cooper Crouse-Hinds
GmbH catalogue.
Boîtier vide GBXE pour atmosphères explosives
F
Publication No.
GHG 760 7001 P0001 / (-) /
Auflage / 19.19 / MS
Cooper Crouse-Hinds GmbH
Neuer Weg-Nord 49
69412 Eberbach
www.crouse-hinds.de
© 2019 Eaton
All Rights Reserved
Printed in Germany
dd
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Eaton is dedicated to ensuring that reliable, efficient and safe power is available when
it’s needed most. With unparalleled knowledge of electrical power management across
industries, experts at Eaton deliver customized, integrated solutions to solve our cus-
tomers’ most critical challenges.
Our focus is on delivering the right solution for the application. But, decision makers
demand more than just innovative products. They turn to Eaton for an unwavering
commitment to personal support that makes customer success a top priority. For more
information, visit
www.eaton.com/electrical.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Eaton Crouse-hinds series Operating Instructions Manual

Taper
Operating Instructions Manual

dans d''autres langues