Regency F1100S Owners & Installation Manual

Catégorie
Cheminées
Taper
Owners & Installation Manual

Ce manuel convient également à

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
908-288e
MODELS: F1100S F3100L
Freestanding Woodstoves
03/11/14
Owners &
Installation Manual
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
www.regency- re.com
F1100 Video
French Manual: http://bit.ly/N4yDmr
2
Regency F1100/F3100 Freestanding Woodstove
Thank-you for purchasing a
REGENCY FIREPLACE PRODUCT.
The pride of workmanship that goes into each of our products will give you years of trouble-free enjoyment. Should you
have any questions about your product that are not covered in this manual, please contact the REGENCY DEALER
in your area.
Keep those REGENCY FIRES burning.
SAFETY NOTES:
If this woodstove is not properly installed, a house re may result. For your safety, follow the installation instructions,
contact local building or re of cials about restrictions and installation inspection requirements in your area.
This appliance needs fresh air for safe operation and must be installed with adequate combustion air available to the
room in which it is to be operating. Air starvation or icing of the chimney system may result.
F1100 Video
Modular Parts
Regency F1100/F3100 Freestanding Woodstove
33
TABLE OF CONTENTS
SAFETY LABEL
Copy Of Safety Label For F1100S .................................4
Copy Of Safety Label For F3100L .................................5
DIMENSIONS
F1100S Unit Dimensions ...............................................6
F3100L Unit Dimensions ...............................................7
INSTALLATION
Residential Installation...................................................8
Room Air .......................................................................8
Important .......................................................................8
Modular Installation Options ..........................................8
Minimum Clearance To Combustible Materials .............9
Stove Assembly Prior To Installation ...........................11
Step By Step Chimney And Connector Installation .....12
Masonry Chimney........................................................13
Masonry Fireplace .......................................................13
Factory built chimney...................................................13
Combustible Wall Chimney Connector
Pass-throughs .............................................................14
Recommended Heights For Woodstove Flue ..............15
Mobile Home Installation .............................................15
Listed Components For Mobile Home Installation .......16
Stainless steel smoke de ector
adjustment / replacement ............................................17
Brick Flue Baf e &
Secondary Air Tube Installation ...................................18
Brick Installation ..........................................................19
Door Handle ................................................................19
Glass Installation .........................................................19
Optional Accessories ...................................................19
Screen Door ................................................................19
Contemporary Door Handle.........................................19
Operating Instructions .................................................21
OPERATING INSTRUCTIONS
First Fire ......................................................................21
Draft Control ................................................................21
Ash Disposal................................................................22
Safety Guidelines And Warnings .................................22
Fan Operation..............................................................22
Creosote ......................................................................23
Latch Adjustment .........................................................23
Door Gasket ................................................................23
MAINTENANCE
Glass Maintenance ......................................................23
Maintenance ................................................................23
Maintenance Of Gold-plated Doors .............................23
PARTS LIST
Main Assembly with classic door .................................24
Main Assembly with contemporary door ......................25
Pedestal, Bottom Shield & Leg Options ......................26
Firebrick ....................................................................... 27
WARRANTY
Warranty ......................................................................27
4
Regency F1100/F3100 Freestanding Woodstove
SAFETY LABEL
This is a copy of the label that accompanies
each Regency Small Freestanding Woodstove
(F1100S).
We have printed a copy of the contents here
for your review.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
COPY OF SAFETY LABEL FOR F1100S
duplicate serial number
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT MAXIMUM ALCOVE DEPTH 915 MM / 36 IN.
MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18"
THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
F1100S WITHOUT
AIRMATE SHIELD
F1100S WITH
AIRMATE SHIELD
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT COMBUSTION
AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. RISK OF SMOKE AND FLAME SPILLAGE, OPERATE ONLY WITH DOORS FULLY OPEN OR FULLY CLOSED.
IF INSTALLED IN A MOBILE HOME OPERATE ONLY WITH DOORS FULLY CLOSED - OPEN FEED DOOR TO FEED FIRE ONLY. WHEN OPERATED WITH DOORS OPEN THE
MANUFACTURER SUPPLIED SCREEN MUST BE USED. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER
OR CHIMNEY CONNECTOR GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE
CREOSOTE BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH NEOCERAM
GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS INDICATED
OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENT: FAN, ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS, SCREEN DOOR
DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM: SECURITY MODEL
S2100, ICC EXCEL 2100.
IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA
VENT MODEL DVL, GSW SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS
SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR
METAL-FAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
AUTEUR MINIMALE DU PLAFOND DE L’ALCÔVE : 2.15 M / 7 PL PROFONDEUR MAXIMALE DE L’ALCÔVE : 915 MM / 36 PO
DÉGAGEMENT MINIMAL DU PLAFOND POUR UN CONNECTEUR HORIZONTAL : 455 MM / 18 PO.
L’ESPACE AU-DESSOUS DU POÊLE NE DOIT PAS ÊTRE OBSTRUÉ. UTILISER SEULEMENT AVEC LES BRIQUES RÉFRACTAIRES EN PLACE.
POUR UTILISATION AVEC BOIS SOLIDE SEULEMENT. L’UTILISATION D’AUTRES COMBUSTIBLES PEUT ENDOMMAGER LE POÊLE ET CRÉER UNE CONDITION DANGEREUSE.
NE PAS OBSTRUER LES OUVERTURES D’AIR DE COMBUSTION. UTILISER SEULEMENT AVEC LA PORTE FERMÉE – OUVRIR LA PORTE DE CHARGEMENT POUR ALIMENTER
LE FEU SEULEMENT. NE PAS UTILISER DE GRILLE À BÛCHES NI SURÉLEVER LE FEU. MONTER LE FEU DE BOIS DIRECTEMENT SUR L’ÂTRE. NE PAS SURCHAUFFER – SI
LE POÊLE OU LE CONNECTEUR DE CHEMINÉE SE MET À ROUGIR, VOUS SURCHAUFFEZ. INSPECTEZ ET NETTOYEZ FRÉQUEMMENT LA CHEMINÉE ET LE CONNECTEUREN
CERTAINES CONDITIONS D’UTILISATION, UN DÉPÔT DE CRÉOSOTE PEUT SE FORMER RAPIDEMENT. GARDEZ LES MEUBLES ET AUTRES MATÉRIAUX COMBUSTIBLES
ÉLOIGNÉS DU POÊLE. REMPLACEZ LA VITRE SEULEMENT PAR DU VERRE EN NEOCERAM. LE PLANCHER COMBUSTIBLE DOIT ÊTRE PROTÉGÉ PAR DES MATÉRIAUX NON
COMBUSTIBLES DÉPASSANT DU DESSOUS, DU DEVANT ET DES CÔTÉS DU POÊLE, TEL QU’INDIQUÉ, OU JUSQU’AU MATÉRIAU COMBUSTIBLE LE PLUS PRÈS PERMIS.
COMPOSANTS EN OPTION : VENTILATEUR, ALIMENTATION ÉLECTRIQUE : 115 VOLTS, 60 HZ, 2 AMP.
DANGER : RISQUE D’ÉLECTROCUTION. DÉCONNECTER L’ALIMENTATION ÉLECTRIQUE AVANT DE FAIRE L’ENTRETIEN DU POÊLE. NE PAS INSTALLER LE CORDON
ÉLECTRIQUE SOUS OU DEVANT L’APPAREIL.
COMPOSANTS EXIGÉS POUR INSTALLATION DANS UNE MAISON MOBILE : KIT DE PRISE D’AIR EXTÉRIEUR ET L’UN DES CONNECTEURS DE CHEMINÉE À DOUBLE PAROI
SUIVANTS :
AU CANADA : CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI : SECURITY MODÈLE DP, OU OLIVER MACLEOD PRO-VENT PV, AVEC SYSTÈME DE CHEMINÉE
HOMOLOGUÉ : SECURITY MODÈLE S2100, ICC EXCEL 2100, SUPER VENT 2100.
AUX ÉTATS-UNIS : CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI : SECURITY MODÈLE DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV,
SIMPSON DURA VENT MODÈLE DVL, GSW SUPER PIPE 6, METAL-FAB À DOUBLE PAROI. CONNECTÉ À L’UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS :
SECURITY MODÈLE S2100 OU MODÈLE ASHT, SELKIRK MODÈLE SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODÈLE SC OU METAL-FAB TEMP/
GUARD, AMERI-TECHS, ICC EXCEL 2100, SIMPSON DURA PLUS HTC. UTILISER LES COMPOSANTS DE CHEMINÉE SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION.
.
100
CERTIFIED TO COMPLY WITH JULY 1990
PARTICULATE EMISSION STANDARDS.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
ATTENTION
CHAUD DURANT LE FONCTIONNEMENT. NE TOUCHEZ PAS.
ÉLOIGNEZ LES ENFANTS, LES VÊTEMENTS ET LES MEUBLES.
LE CONTACT PEUT CAUSER DES BRÛLURES DE LA PEAU.
LISEZ LA PLAQUE SIGNALÉTIQUE ET LES INSTRUCTIONS
MADE IN CANADA / FAIT AU CANADA
MANUFACTURED BY/ FABRIQUÉ PAR:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
6988 VENTURE ST.
DELTA, BC V4G 1H4
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO
SUITABLE FOR MOBILE HOME INSTALLATION /
APPAREIL DE CHAUFFAGE AMBIANT HOMOLOGUÉ
À COMBUSTIBLE SOLIDE, CONVENANT AUSSI
POUR INSTALLATION DANS UNE MAISON MOBILE
FLOOR PROTECTION*
PROTECTION DE PLANCHER*
* Au Canada, la protection de plancher doit dépasser de
18 po (457 mm) à l’avant et de 8 po (200 mm) de chaque
côté du poêle et derrière le
poêle.
* In Canada, fl oor protection must extend 18" (450mm)
to the front and 8" (200mm) to each side and back of
the stove.
DO NOT REMOVE THIS LABEL/
NE RETIREZ PAS CETTE ÉTIQUETTE
100
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA.
USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK OR 26 MSG BLUED STEEL CONNECTOR WITH LISTED UL103 HT
FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUELS OR MASONRY CHIMNEY.
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A
CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE
WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
INSTALLER ET UTILISER SEULEMENT SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION DU FABRICANT.
CONTACTER LES RESPONSABLES DU BÂTIMENT OU DU SERVICE-INCENDIE DE VOTRE RÉGION POUR CONNAÎTRE
LES RESTRICTIONS ET EXIGENCES D’INSPECTION DANS VOTRE RÉGION. UTILISER UN CONNECTEUR D’UN DIAMÈTRE
MINIMAL DE 150 MM (6 PO) 24 MSG EN ACIER NOIR OU 26 MSG EN ACIER BRONZÉ AVEC CHEMINÉE PRÉFABRIQUÉE
HOMOLOGUÉE UL103 HT CONÇUE POUR UTILISATION AVEC COMBUSTIBLES SOLIDES OU UNE CHEMINÉE DE MAÇON-
NERIE.
VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT CONCERNANT LES PRÉCAUTIONS
EXIGÉES POUR INSTALLER UNE CHEMINÉE TRAVERSANT UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES.
NE FAITES PAS TRAVERSER LE CONNECTEUR DE CHEMINÉE DANS UN MUR OU PLAFOND EN MATÉRIAUX COMBUS-
TIBLES. NE RACCORDEZ PAS CE POÊLE À BOIS À UN CONDUIT DE CHEMINÉE DESSERVANT UN AUTRE APPAREIL.
908-281b
MODEL: REGENCY SMALL FREESTANDING STOVE - F1100S
TESTED TO: ULC S627-00 / UL 1482-2011 / UL 737 REPORT NO.6621
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX COMBUSTIBLES
F1100S WITH AIRMATE SHIELD F1100S WITHOUT AIRMATE SHIELD
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
MEASURE FLUE
FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
SIDEWALL A 380 mm /15 in D 685 mm / 27 in
BACKWALL B 265 mm / 10.5in E 430 mm / 17 in
CORNER C 280 mm / 11 in F 585 mm / 23 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
SIDEWALL A 330 mm / 13 in D 635 mm / 25 in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNER C 230 mm / 9 in F 535 mm / 21 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
SIDEWALL A 345 mm / 13.5in D 650 mm / 25.5 in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNER C 125 mm / 5 in F 430 mm / 17 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
SIDEWALL A 330 mm / 13 in D 635 mm / 25 in
BACKWALL B 280 mm / 11 in E 445 mm / 17.5 in
CORNER C 205 mm / 8 in F 510 mm / 20 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
SIDEWALL A 280 mm / 11 in D 585 mm / 23 in
BACKWALL B 150 mm / 6 in E 320 mm / 12.5 in
CORNER C 150 mm / 6 in F 460 mm / 18 in
SIDEWALL A 230 mm / 9 in D 535 mm / 21 in
BACKWALL B 125 mm / 5 in E 290 mm / 11.5in
CORNER C 75 mm / 3 in F 380 mm / 15 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
SIDEWALL G 280 mm / 11 in I 585 mm / 23 in
BACKWALL H 180 mm / 7 in J 345 mm / 13.5 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
SIDEWALL G 330 mm / 13 in I 635 mm / 25 in
BACKWALL H 125 mm / 5 in J 290 mm / 11.5in
MEASURE FLUE
FROM HEATER CENTER-LINE
K 405 mm / 16 in
L 200 mm / 8 in
M 200 mm / 8 in
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
DATE OF MANUFACTURE
2014 20162015
Regency F1100/F3100 Freestanding Woodstove
5
SAFETY LABEL
This is a copy of the label that accompanies
each Regency Large Freestanding Woodstove
(F3100L).
We have printed a copy of the contents here
for your review.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
COPY OF SAFETY LABEL FOR F3100L
MODEL: REGENCY LARGE FREESTANDING STOVE - F3100L
TESTED TO: ULC S627-00 / UL 1482-2011 / UL 737 REPORT NO.6623
duplicate serial number
MINIMUM ALCOVE CEILING HEIGHT: 2.15 M / 7 FT MAXIMUM ALCOVE DEPTH 915 MM / 36 IN.
MINIMUM CLEARANCES FOR HORIZONTAL CONNECTOR TO CEILING: 455 MM / 18"
THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
F3100L WITHOUT
AIRMATE SHIELD
F3100L WITH
AIRMATE SHIELD
FOR USE WITH SOLID WOOD FUEL ONLY. USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION. DO NOT OBSTRUCT COMBUSTION
AIR OPENINGS. OPERATE ONLY WITH FIREBRICKS IN PLACE. RISK OF SMOKE AND FLAME SPILLAGE, OPERATE ONLY WITH DOORS FULLY OPEN OR FULLY CLOSED.
IF INSTALLED IN A MOBILE HOME OPERATE ONLY WITH DOORS FULLY CLOSED - OPEN FEED DOOR TO FEED FIRE ONLY. WHEN OPERATED WITH DOORS OPEN THE
MANUFACTURER SUPPLIED SCREEN MUST BE USED. DO NOT USE GRATE OR ELEVATE FIRE. BUILD WOOD FIRE DIRECTLY ON HEARTH. DO NOT OVERFIRE - IF HEATER
OR CHIMNEY CONNECTOR GLOWS YOU ARE OVERFIRING. INSPECT AND CLEAN CHIMNEY AND CONNECTOR FREQUENTLY. UNDER CERTAIN CONDITIONS OF USE
CREOSOTE BUILDUP MAY OCCUR RAPIDLY. KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIAL AWAY FROM HEATER. REPLACE GLASS ONLY WITH NEOCERAM
GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS INDICATED
OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENT: FAN, ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS, SCREEN DOOR
DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM: SECURITY MODEL
S2100, ICC EXCEL 2100.
IN USA: LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA
VENT MODEL DVL, GSW SUPER PIPE 6, METAL-FAB DOUBLE WALL. CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS
SECURITY MODEL S2100 OR MODEL ASHT, SELKIRK MODEL SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODEL SC OR
METAL-FAB TEMP/GUARD, AMERI-TEC HS, ICC EXCEL 2100 . USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION INSTRUCTIONS.
AUTEUR MINIMALE DU PLAFOND DE L’ALCÔVE : 2.15 M / 7 PL PROFONDEUR MAXIMALE DE L’ALCÔVE : 915 MM / 36 PO
DÉGAGEMENT MINIMAL DU PLAFOND POUR UN CONNECTEUR HORIZONTAL : 455 MM / 18 PO.
L’ESPACE AU-DESSOUS DU POÊLE NE DOIT PAS ÊTRE OBSTRUÉ. UTILISER SEULEMENT AVEC LES BRIQUES RÉFRACTAIRES EN PLACE.
POUR UTILISATION AVEC BOIS SOLIDE SEULEMENT. L’UTILISATION D’AUTRES COMBUSTIBLES PEUT ENDOMMAGER LE POÊLE ET CRÉER UNE CONDITION DANGEREUSE.
NE PAS OBSTRUER LES OUVERTURES D’AIR DE COMBUSTION. UTILISER SEULEMENT AVEC LA PORTE FERMÉE – OUVRIR LA PORTE DE CHARGEMENT POUR ALIMENTER
LE FEU SEULEMENT. NE PAS UTILISER DE GRILLE À BÛCHES NI SURÉLEVER LE FEU. MONTER LE FEU DE BOIS DIRECTEMENT SUR L’ÂTRE. NE PAS SURCHAUFFER – SI
LE POÊLE OU LE CONNECTEUR DE CHEMINÉE SE MET À ROUGIR, VOUS SURCHAUFFEZ. INSPECTEZ ET NETTOYEZ FRÉQUEMMENT LA CHEMINÉE ET LE CONNECTEUREN
CERTAINES CONDITIONS D’UTILISATION, UN DÉPÔT DE CRÉOSOTE PEUT SE FORMER RAPIDEMENT. GARDEZ LES MEUBLES ET AUTRES MATÉRIAUX COMBUSTIBLES
ÉLOIGNÉS DU POÊLE. REMPLACEZ LA VITRE SEULEMENT PAR DU VERRE EN NEOCERAM. LE PLANCHER COMBUSTIBLE DOIT ÊTRE PROTÉGÉ PAR DES MATÉRIAUX NON
COMBUSTIBLES DÉPASSANT DU DESSOUS, DU DEVANT ET DES CÔTÉS DU POÊLE, TEL QU’INDIQUÉ, OU JUSQU’AU MATÉRIAU COMBUSTIBLE LE PLUS PRÈS PERMIS.
COMPOSANTS EN OPTION : VENTILATEUR, ALIMENTATION ÉLECTRIQUE : 115 VOLTS, 60 HZ, 2 AMP.
DANGER : RISQUE D’ÉLECTROCUTION. DÉCONNECTER L’ALIMENTATION ÉLECTRIQUE AVANT DE FAIRE L’ENTRETIEN DU POÊLE. NE PAS INSTALLER LE CORDON
ÉLECTRIQUE SOUS OU DEVANT L’APPAREIL.
COMPOSANTS EXIGÉS POUR INSTALLATION DANS UNE MAISON MOBILE : KIT DE PRISE D’AIR EXTÉRIEUR ET L’UN DES CONNECTEURS DE CHEMINÉE À DOUBLE PAROI
SUIVANTS :
AU CANADA : CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI : SECURITY MODÈLE DP, OU OLIVER MACLEOD PRO-VENT PV, AVEC SYSTÈME DE CHEMINÉE
HOMOLOGUÉ : SECURITY MODÈLE S2100, ICC EXCEL 2100, SUPER VENT 2100.
AUX ÉTATS-UNIS : CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI : SECURITY MODÈLE DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV,
SIMPSON DURA VENT MODÈLE DVL, GSW SUPER PIPE 6, METAL-FAB À DOUBLE PAROI. CONNECTÉ À L’UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS :
SECURITY MODÈLE S2100 OU MODÈLE ASHT, SELKIRK MODÈLE SSII, OLIVER MACLEOD PRO JET 3103, SIMPSON DURA PLUS, GSW MODÈLE SC OU METAL-FAB TEMP/
GUARD, AMERI-TECHS, ICC EXCEL 2100, SIMPSON DURA PLUS HTC. UTILISER LES COMPOSANTS DE CHEMINÉE SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION.
.
102
CERTIFIED TO COMPLY WITH JULY 1990
PARTICULATE EMISSION STANDARDS.
UNITED STATES ENVIRONMENTAL
PROTECTION AGENCY
CAUTION
HOT WHILE IN OPERATION DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.
ATTENTION
CHAUD DURANT LE FONCTIONNEMENT. NE TOUCHEZ PAS.
ÉLOIGNEZ LES ENFANTS, LES VÊTEMENTS ET LES MEUBLES.
LE CONTACT PEUT CAUSER DES BRÛLURES DE LA PEAU.
LISEZ LA PLAQUE SIGNALÉTIQUE ET LES INSTRUCTIONS
MADE IN CANADA / FAIT AU CANADA
MANUFACTURED BY/ FABRIQUÉ PAR:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
6988 VENTURE ST.
DELTA, BC V4G 1H4
LISTED SPACE HEATER, SOLID FUEL TYPE, ALSO
SUITABLE FOR MOBILE HOME INSTALLATION /
APPAREIL DE CHAUFFAGE AMBIANT HOMOLOGUÉ
À COMBUSTIBLE SOLIDE, CONVENANT AUSSI
POUR INSTALLATION DANS UNE MAISON MOBILE
FLOOR PROTECTION*
PROTECTION DE PLANCHER*
* Au Canada, la protection de plancher doit dépasser de
18 po (457 mm) à l’avant et de 8 po (200 mm) de chaque
côté du poêle et derrière le
poêle.
* In Canada, fl oor protection must extend 18" (450mm)
to the front and 8" (200mm) to each side and back of
the stove.
DO NOT REMOVE THIS LABEL/
NE RETIREZ PAS CETTE ÉTIQUETTE
102
INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA.
USE 150 MM (6 IN.) DIAMETER MINIMUM 24 MSG BLACK OR 26 MSG BLUED STEEL CONNECTOR WITH LISTED UL103 HT
FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUELS OR MASONRY CHIMNEY.
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A
CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE
WALL OR CEILING. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
INSTALLER ET UTILISER SEULEMENT SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION DU FABRICANT.
CONTACTER LES RESPONSABLES DU BÂTIMENT OU DU SERVICE-INCENDIE DE VOTRE RÉGION POUR CONNAÎTRE
LES RESTRICTIONS ET EXIGENCES D’INSPECTION DANS VOTRE RÉGION. UTILISER UN CONNECTEUR D’UN DIAMÈTRE
MINIMAL DE 150 MM (6 PO) 24 MSG EN ACIER NOIR OU 26 MSG EN ACIER BRONZÉ AVEC CHEMINÉE PRÉFABRIQUÉE
HOMOLOGUÉE UL103 HT CONÇUE POUR UTILISATION AVEC COMBUSTIBLES SOLIDES OU UNE CHEMINÉE DE MAÇON-
NERIE.
VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT CONCERNANT LES PRÉCAUTIONS
EXIGÉES POUR INSTALLER UNE CHEMINÉE TRAVERSANT UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES.
NE FAITES PAS TRAVERSER LE CONNECTEUR DE CHEMINÉE DANS UN MUR OU PLAFOND EN MATÉRIAUX COMBUS-
TIBLES. NE RACCORDEZ PAS CE POÊLE À BOIS À UN CONDUIT DE CHEMINÉE DESSERVANT UN AUTRE APPAREIL.
908-351b
JAN FEB MAR APR MAY JUN JUL AUG SEPT OCT NOV DEC
DATE OF MANUFACTURE
2014 20162015
K 405 mm / 16 in
L 200 mm / 8 in
M 200 mm / 8 in
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX COMBUSTIBLES
F3100L WITH AIRMATE SHIELD
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
SIDEWALL A 460 mm / 18 in D 810 mm / 32 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5in
CORNER C 215 mm / 8.5 in F 560 mm / 22 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
SIDEWALL A 460 mm / 18 in D 810 mm / 32 in
BACKWALL B 240 mm / 9.5 in E 405 mm / 16 in
CORNER C 255 mm / 10 in F 595 mm /
23.5in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
SIDEWALL A 405 mm / 16 in D 760 mm / 30 in
BACKWALL B 240 mm / 9.5 in E 405 mm / 16 in
CORNER C 215 mm / 8.5 in F 560 mm / 22 in
SIDEWALL G 405 mm / 16 in I 760 mm / 30 in
BACKWALL H 240 mm / 9.5 in J 405 mm / 16 in
MEASURE FLUE
FROM HEATER CENTER-LINE
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - ALCOVE
F3100L WITHOUT AIRMATE SHIELD
MEASURE FLUE
FROM HEATER CENTER-LINE
RESIDENTIAL INSTALLATION USING
SINGLE WALL CONNECTOR
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 355 mm / 14 in E 520 mm / 20.5 in
CORNER C 265 mm / 10.5in F 610 mm / 24 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - MOBILE HOME
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5 in
CORNER C 255 mm / 10 in F 595 mm / 23.5 in
INSTALLATION USING LISTED DOUBLE WALL
CONNECTOR - RESIDENTIAL CLOSE CLEARANCE
SIDEWALL A 510 mm / 20 in D 860 mm / 34 in
BACKWALL B 305 mm / 12 in E 470 mm / 18.5 in
CORNER C 215 mm / 8.5 in F 560 mm / 22 in
ALCOVE INSTALLATION
REQUIRES AIRMATE SHIELD
6
Regency F1100/F3100 Freestanding Woodstove
DIMENSIONS
F1100S UNIT DIMENSIONS
Contemporary Door
Classix Door
Regency F1100/F3100 Freestanding Woodstove
7
INSTALLATION
F3100L UNIT DIMENSIONS
Contemporary Door
Classix Door
8
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
RESIDENTIAL
INSTALLATION
1) Read all instructions before installing your
Regency Stove. Install and use only in ac-
cordance with these installation and operating
instructions. Be aware that local Codes and
Regulations may override some items in this
manual. Check with your local inspector.
2) Select a position for your Regency Stove.
Consult the minimum clearance chart for your
model and set the stove in place. For close
clearance installation use listed double wall
connector systems (refer to Combustible Wall
Chimney Connector Pass - Throughs).
3) To insure vertical alignment, suspend a plumb
bob from the ceiling over the exact center of
your stove ue and mark a spot on the ceiling
to indicate the center of the chimney.
4) Check that the area above the ceiling is clear
for cutting. Re-con rm the clearance from the
stove to combustibles to insure that they are
within the prescribed limits.
5) Install chimney according to chimney manu-
facturers instructions. The performance of your
woodstove is governed to a very large part by
the chimney system. Too short a chimney can
cause dif cult start-up, dirty glass, backsmok-
ing when door is open, and even reduced heat
output. Too tall a chimney may prompt exces-
sive draft which can result in very short burn
times and excessive heat output. The use of an
inexpensive ue pipe damper may be helpful
in reducing excessive draft.
CAUTION: The chimney should be the same
size as the ue outlet on the stove. The chimney
must be listed as suitable for use with solid
fuels. For other types of chimneys check with
your local building code of cials. Do not con-
fuse a chimney with a type “B” Venting System
used for gas appliances as suitable for a wood
burning appliance (refer to the Mobile Home
installations section).
6) Mark the location of the pedestal base or legs
on the oor, then move the stove aside and
mark the position of the oor protector.
7) The oor protector must be of non-combustible
material and must extend 16" in front of the
door opening and 8" to the sides and rear of
the unit. Some areas may require a larger size
oor protector. See your local inspector. For
outside air installation refer to Mobile Home
section.
8) When the oor protection is complete, position
the stove with the ue collar centered under
the installed chimney.
9) In seismically active areas, Regency recom-
mends that your unit is secured to the oor by
using the bolt down holes inside the pedestal
(the same ones used in Mobile Home instal-
lations).
10) For residential installations using "C" Vent
(single wall) the chimney connector must be
at least 24 gauge steel. Do not use galvanized
pipe. For Mobile Home installation refer to the
Mobile Home installation section.
11) Do not connect this unit to a chimney serving
another appliance unless approved by your
local building authority.
12) A chimney connector cannot pass through an
attic or roof space, closet or similar concealed
space, or a oor, ceiling, wall or partition of
combustible construction. In Canada, if pas-
sage through a wall, or partition of combustible
construction is desired, the installation shall
conform to CAN/CSA-B365, Installation Code
for Solid-Fuel-Burning Appliances and Equip-
ment.
13) Your Regency Woodstove is not to be connected
to any air distribution duct.
ROOM AIR
IMPORTANT
For installation using room air for combustion,
remove knockout from the pedestal, and/or from
the bottom if using a heat shield.
Mobile home installations require the use of out-
side air.
On pedestal units there are two locations where
outside air may be adapted to the unit. If using the
bottom of the pedestal, do not remove knockout from
the rear of the pedestal. Only remove rear knockout
if outside air will be brought in from the rear.
On leg units outside air can only be brought in from
the bottom of the heat shield.
Note: Once the knockout is removed there are
two tabs remaining. Bend both tabs out
for ease of installation when attaching
outside air.
MODULAR INSTALLATION OPTIONS
Modular Part
Things to consider when choosing options:
OPTIONS: These can be installed at time of installation or added later:
F1100 & F3100 only:
Airmate OR
Rear Heat De ector
(all units)
Pedestal OR
Legs
The following items are required when assembling your Regency Stove. F1100 and F3100 units - the Rear Heat De ector is supplied with the
stove, but if you choose not to use it you must use the Airmate instead.
Clearances are different. See chart on pages 7 and 8. Generally you can get closer clearances with the airmate than
with the rear heat de ector.
Convection heat with Airmate vs. Radiant Heat with Rear Heat De ector. The airmate pushes heat forward and into
the room, the rear heat de ector de ects the heat upward. See installation instructions.
There are no performance differences with either the pedestal or legs. It is primarily a personal preference. Legs can
be either painted cast or gold plated cast.
Leg installation requires the bottom shield. See installation instructions.
Emissions from burning wood or gas could
contain chemicals known to the State of Cali-
fornia to cause cancer, birth defects or other
reproductive harm.
NOTE: In Canada, oor protection must ex-
tend 18" to the front and 8" to each
side of the stove.
Modular Option
Blower/Fan
Ash Drawer Kit
Screen Door
Things to consider when choosing options
Adding the blower will increase the area heated by the stove, it can move warm air beyond the room where the stove
is installed. Installation instructions.
Adding the Ash Drawer Kit makes cleaning ashes out of the stove easier and cleaner. Installation instructions.
A simple add-on option that will allow you to enjoy the sound, warmth and view of an open re.
Regency F1100/F3100 Freestanding Woodstove
9
INSTALLATION
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Please read the section below carefully as clearances depend on whether the airmate or the rear heat de ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit From Unit From Corner From Flue Center-line
A B C D E F
Small F1100S with Airmate 11" 6" 6" 23" 12.5" 18"
with Rear De ector 13" 5" 9" 25" 11.5" 21"
Large F3100L with Airmate 18" 9.5" 10" 32" 16" 23.5"
with Rear De ector 20" 12" 10" 34" 18.5" 23.5"
NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.
Residential Installation “C” Vent (Single Wall)
Unit From Unit From Corner From Flue Center-line
A B C D E F
Small F1100S with Airmate 13" 11" 8" 25" 17.5" 20"
with Rear De ector 15" 10.5" 11" 27" 17" 23"
Large F3100L with Airmate 18" 12" 8.5" 32" 18.5" 22"
with Rear De ector 20" 14" 10.5" 34" 20.5" 24"
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove
collar to the ceiling level.
Unit From Unit From Corner From Flue Center-line
A B C D E F
Small F1100S with Airmate 9" 5" 3" 21" 11.5" 15"
with Rear De ector 13.5" 5" 5" 25.5" 11.5" 17"
Large F3100L with Airmate 16" 9.5" 8.5" 30" 16" 22"
with Rear De ector 20" 12" 8.5" 34" 18.5" 22"
10
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
8
8
8
8
Minimum Alcove Clearance and Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
Minimum Overall Width (X) of Floor
Protector for all installations:
Small Stove F1100S 38"
Large Stove F3100L 42"
*The rear clearance to combustibles is less than 6" (152mm), for corner installations the rear corners may be angled to take advantage of the
closer clearances.
Floor Protection
A combustible oor must be protected by a non-combustible material (like tile,
concrete board, or certi ed to UL-1618 or as de ned by local codes) extend-
ing beneath the heater and a minimum of 8" from each side and minimum
16" from the front face of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.
NOTE: In Canada, oor protection must extend 18" to the front and 8" to each side of the stove.
From From Flue Min. Min.Hearth
Unit Unit Center-line Width to Rear Wall
G H I J K L
Small F1100S with Airmate 11" 7" 23" 13.5" 46" 39"
with Rear De ector 13" 5" 25" 11.5" 50" 37"
Large F3100L with Airmate 16" 9.5" 30" 16" 60" 46.5"
with Rear De ector (not approved for Alcove)
Minimum Overall Depth (Y) of Floor Protector
Residential Residential Mobile Home Alcove
Unit "C" Vent Close Clearance Close Clearance
Y Z Y Z Y Z Y Z
Small F1100S with Airmate 38" 6" 37"* 5" 38" 6" 38" 6"
with Rear De ector 38" 6" 37"* 5" 37"* 5" 37"* 5"
Large F3100L with Airmate 43" 6" 43" 6" 43" 6" 43" 6"
with Rear De ector 43" 6" 43" 6" 43" 6" n/a n/a
Regency F1100/F3100 Freestanding Woodstove
11
INSTALLATION
Diagram 4
Diagram 2
Diagram 3
STOVE ASSEMBLY
PRIOR TO
INSTALLATION
All units require either the pedestal or 4 legs at-
tached to the base. The F1100 and F3100 stoves
require either the Airmate or Rear Heat De ector
on top of the stove. Clearances to combustible
materials vary depending on whether the airmate
or rear heat de ector is installed, so be sure to
check the Minimum Clearance to Combustible
Materials section.
Airmate Assembly
for F1100 & F3100
Small 850-105
Large 850-305
1) The airmate sits on top of the stove with
the slots in the sides tting over the curved
de ector on the rear stove top. See diagram
1. Discard the Rear Heat De ector that is
supplied with the unit, it is not required if the
airmate is installed.
2) Center the airmate and push it forward to the
front of the stove. The back of the airmate
should be level with the back and sides of
the rear heat shield. See Diagrams 2 & 3.
Diagram 1
Shown with classic door
Shown with classic door
Shown with contemporary door
Rear Heat De ector Assembly
for F1100 & F3100
Small 815-555
Large 815-556
The rear heat de ector is supplied with the stove
and must be installed unless the optional airmate
has been selected. It stops the heat radiated from
the ue collar from overheating the rear wall. The
rear heat de ector is installed on top of the rear
heat shield, as shown in Diagram 4.
Pedestal Assembly
Small 850-115
Large 850-315
1) For easier assembly, tip the stove on its
back (onto a soft surface to prevent scratch-
ing).
Hint: If you have chosen the Ash Drawer
option, remove the ash dump cover plates
before attaching the pedestal (refer to the
Ashdrawer Kit Installation section).
2) Remove the blanking plate if:
a) you are not installing outside combustion
air or
b) outside air is to be brought in from the
rear of the stove.
3) Unscrew the 4 bolts in the under-side of the
stove. Align the holes in the corners of the
pedestal top with the corresponding holes
in the base of the stove. Fasten using a bolt
and washer for each corner.
4) Push the Regency logo
into the two holes in
the front bottom
left corner of
the pedestal
cover plate.
Note: Any paint touch up should be done
prior to placing logo on pedestal.
5) If not using ash drawer, then the knockout
must remain in place. If using ash drawer,
then remove knockout.
12
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
Horizontal Installation
Standard Ceiling Installation
8) To complete your chimney installation, install
the double wall connector pipe from the
stove’s ue collar to the chimney support
device.
9) If you are using a horizontal connector,
the chimney connector should be as high
as possible while still maintaining the 18"
(457mm) minimum distance from the hori-
zontal connector to the ceiling.
10) NOTE: Residential Close Clearance and
Alcove installations require a listed dou-
ble wall connector from the stove collar
to the ceiling level.
The diagrams below illustrate one way to in-
stall your unit into a standard ceiling or with a
horizontal connector. Check with your dealer
or installer for information on other options
available to you.
STEP BY STEP
CHIMNEY AND
CONNECTOR
INSTALLATION
Note: These are a generic set of chimney
installation instructions. Always fol-
low the manufacturers own instruc-
tions explicitly. Check the Minimum
Recommended Flue Heights section
(Table 1).
1) With your location already established, cut
and frame the roof hole. It is recommended
that no ceiling support member be cut for
chimney and support box installation. If it is
necessary to cut them, the members must
be made structurally sound.
2) Install radiant shield and support from
above.
3) Stack the insulated pipe onto your nish
support to a minimum height of 3 feet above
the roof penetration, or 2 feet above any
point within 10 feet measured horizontally.
There must be at least 3 feet of chimney
above the roof level.
Note: Increasing the chimney height above
this minimum level will sometimes
help your unit to “breathe” better
by allowing a greater draft to be cre-
ated. This greater draft can decrease
problems such as, dif cult start-ups,
back-smoking when door is open, and
dirty glass. It might be suf cient to
initially try with the minimum required
height, and then if problems do arise
add additional height at a later date.
4) Slide the roof ashing over your chimney
and seal the ashing to the roof with roo ng
compound. Secure the ashing to your roof
with nails or screws.
5) Place the storm collar over the ashing,
sealing the joints with a silicone caulking.
6) Fasten the raincap with spark screens (if
required) to the top of your chimney.
7) For optimum ef ciency when installing into
a masonry chimney, size accordingly, i.e.
the 6" (152mm) ue dia. is 28.28 sq.in.
Leg and Bottom Shield Assembly
Bottom Shield
Small 850-121
Large 850-321
Legs (set of 4)
Cast - Painted Black 850-126
Cast - Gold Plated 850-127
The instructions below apply to the painted cast
leg and the gold plated cast leg. It will be easier
to attach the legs to the stove if the stove is
tipped on its back (preferably on a soft surface
to prevent scratching). Ensure to be extremely
careful when tipping stove.
1) Remove the 4 bolts from underside of the
base of the pedestal and discard. Also
remove cover plate and put to the side.
2) Line up the heat shield with the bottom of
the unit.
3) Start threading the bolt and washer (supplied
with the bottom shield) for about 1/4 of the
way through the leg with the washers being
underneath the legs. Ensure that the legs
are properly aligned with heat shield and
tighten the bolts.
4) Level the stove by adjusting the levelling
bolts in the bottom of each leg.
5) Reinstall cover plate.
6) Install logo plate onto heat shield by placing
in 2 holes as shown in diagram.
If you are installing outside combustion air, bend
the tabs out 90 degrees. Pipe fresh air into the
bottom shield by using a minimum 4" duct pipe
with a mesh grill at the outside termination. At-
tach the pipe to the 2 tabs with screws.
Regency F1100/F3100 Freestanding Woodstove
13
INSTALLATION
FACTORY
BUILT CHIMNEY
When a metal prefabricated chimney is used, the manufacturer's installation instructions must be followed. You must also purchase and install the
ceiling support package or wall pass-through and "T" section package, restops (where needed), insulation shield, roof ashing, chimney cap, etc.
Maintain proper clearance to the structure as recommended by the manufacturer. The chimney must be the required height above the roof or other
obstructions for safety and proper draft operation. The space heater is to be connected to a factory-built chimney conforming to CAN/ULC-S629,
Standard for 650
0
C Factory-Built Chimneys.
MASONRY
CHIMNEY
Ensure that a masonry chimney meets the mini-
mum standards of the National Fire Protection
Association (NFPA) by having it inspected by
a professional. Make sure there are no cracks,
loose mortar or other signs of deterioration and
blockage. Have the chimney cleaned before
the stove is installed and operated. When
connecting the stove through a combustible
wall to a masonry chimney, special methods
are needed.
Ensure that an effective vapour barrier at the
location where the chimney or other component
penetrates to the exterior of the structure.
MASONRY
FIREPLACE
There are listed kits available to connect a stove
to a masonry replace. The kit is an adapter
that is installed at the location of the replace
damper. The existing damper may have to be
removed to allow installation.
Ensure that an effective vapour barrier at the
location where the chimney or other component
penetrates to the exterior of the structure.
Liner
Listed
When referencing installation or connec-
tion to masonry replaces or chimneys, the
masonry construction must or shall be code
complying.
When referencing installation or connec-
tion to masonry replaces or chimneys, the
masonry construction must or shall be code
complying.
14
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
Method A: 12" (304.8 mm) Clearance to Combustible Wall Member:
Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm)
minimum wall thickness clay liner, construct a wall pass-through. The
clay liner must conform to ASTM C315 (Standard Speci cation for
Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8
mm) of brick masonry between the clay liner and wall combustibles.
The clay liner shall run from the brick masonry outer surface to the
inner surface of the chimney ue liner but not past the inner surface.
Firmly grout or cement the clay liner in place to the chimney ue liner.
Method B: 9" (228.6 mm) Clearance to Combustible Wall Member:
Using a 6" (152.4 mm) inside diameter, listed, factory-built Solid-Pak
chimney section with insulation of 1" (25.4 mm) or more, build a wall
pass-through with a minimum 9" (228.6 mm) air space between the
outer wall of the chimney length and wall combustibles. Use sheet metal
supports fastened securely to wall surfaces on all sides, to maintain the
9" (228.6 mm) air space. When fastening supports to chimney length,
do not penetrate the chimney liner (the inside wall of the Solid-Pak
chimney). The inner end of the Solid-Pak chimney section shall be
ush with the inside of the masonry chimney ue, and sealed with a
non-water soluble refractory cement. Use this cement to also seal to
the brick masonry penetration.
Minimum
12 in. (304.8mm)
to combustibles
Masonry chimney
Chimney Flue
Minimum chimney clearance to brick
and combustibles 2 in. (50.8mm)
Minimum clearance
12 in. (304.8mm)
of brick
Chimney
connector
Fire clay
liner
Method C: 6" (152.4 mm) Clearance to Combustible Wall Member:
Starting with a minimum 24 gage (.024" [.61 mm]) 6" (152.4 mm) metal
chimney connector, and a minimum 24 gage ventilated wall thimble
which has two air channels of 1" (25.4 mm) each, construct a wall
pass-through. There shall be a minimum 6" (152.4) mm separation area
containing berglass insulation, from the outer surface of the wall thimble
to wall combustibles. Support the wall thimble, and cover its opening
with a 24-gage minimum sheet metal support. Maintain the 6" (152.4
mm) space. There should also be a support sized to t and hold the
metal chimney connector. See that the supports are fastened securely
to wall surfaces on all sides. Make sure fasteners used to secure the
metal chimney connector do not penetrate chimney ue liner.
Method D: 2" (50.8 mm) Clearance to Combustible Wall Member:
Start with a solid-pak listed factory built chimney section at least 12"
(304 mm) long, with insulation of 1" (25.4 mm) or more, and an inside
diameter of 8" (2 inches [51 mm] larger than the 6" [152.4 mm] chimney
connector). Use this as a pass-through for a minimum 24-gage single
wall steel chimney connector. Keep solid-pak section concentric with
and spaced 1" (25.4 mm) off the chimney connector by way of sheet
metal support plates at both ends of chimney section. Cover opening
with and support chimney section on both sides with 24 gage minimum
sheet metal supports. See that the supports are fastened securely to
wall surfaces on all sides. Make sure fasteners used to secure chimney
ue liner.
COMBUSTIBLE WALL CHIMNEY
CONNECTOR PASS-THROUGHS
Regency F1100/F3100 Freestanding Woodstove
15
INSTALLATION
TABLE 1
MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET
(Measured from the top of the unit)
# OF ELBOWS
ELEVATION (FT)
ABOVE SEA LEVEL 0 2 x 15
o
4 x 15
o
2 x 30
o
4 x 30
o
2 x 45
o
4 x 45
o
0-1000 12.0 13.0 14.0 15.0 18.0 16.0 20.0
1000-2000 12.5 13.5 14.5 15.5 19.0 16.5 21.0
2000-3000 13.0 14.0 15.0 16.0 19.5 17.0 21.5
3000-4000 13.5 14.5 15.5 17.0 20.0 18.0 22.5
4000-5000 14.0 15.0 16.0 17.5 21.0 18.5 23.0
5000-6000 14.5 15.5 17.0 18.0 21.5 19.0 24.0
6000-7000 15.0 16.0 17.5 18.5 22.5 20.0 25.0
7000-8000 15.5 16.5 18.0 19.0 23.0 20.5 25.5
8000-9000 16.0 17.0 18.5 20.0 24.0 21.0 26.5
9000-10000 16.5 17.5 19.0 20.5 24.5 22.0 27.0
NOTE: No more than two offsets (four elbows) allowed. Two 45
o
elbows equal one 90
o
elbow.
MOBILE HOME INSTALLATION
RECOMMENDED
HEIGHTS FOR
WOODSTOVE FLUE
Simple rules on draft. See Table 1.
1) At sea level minimum height is 12'
straight.
2) Add the following vertical height to compen-
sate for:
45 deg. elbow = 1 ft.
90 deg. elbow = 2 ft.
"T" = 3 ft.
Each foot of horizontal run = 2 ft.
3) Add 4% overall for each 1000' above sea
level.
Example: a)
1-1/2 ft. of horizontal run = 3 ft.
one "T" = 3 ft.
Total Addition (at sea level) = 6 ft.
Example: b)
One 90 deg. elbow = 2 ft.
2 ft. of horizontal run = 4 ft.
one "T" = 3 ft.
Total Addition (at sea level) = 9 ft.
Recommended Flue Height
Elevation Example a) Example b)
0' 18' 21'
1000' 18.72' 21.84'
2000' 19.44' 22.68'
5000' 21.60' 25.20'
8000' 23.76' 27.72'
Once you have properly marked the position
of your unit and the oor protection as outlined
in the Residential Installation items #1 through
#8, a supply of fresh air has to be supplied to
your unit. Cut a minimum 4 inch diameter hole
through your oor protector and the oor directly
under your pedestal base to the outside. Use
4" duct pipe with a mesh grill to pipe fresh air
into the pedestal area. Block off the hole in the
back of the pedestal with the square plate and
the two 1/2" screws provided.
Place your unit in position and secure it to the
oor using two lag bolts 3/8" x 3-1/2" through
the two holes inside the pedestal base. It is
important to maintain the structural integrity
of the Mobile Home oor, walls and roof when
installing your unit.
For Mobile Home units installed in the U.S. the
unit must be grounded using a #8 ground wire
with approved termination and star washer.
WARNING:
Minimum height requirements
must be met. Safe removal of
the chimney system must be
adhered to when transporting the
mobile home.
WARNING: Operate only with door fully
closed - open feed door to feed re only.
16
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
SIMPSON DURA-PLUS
Qty.Part # Description
1 6DVL8693 Connector Kit
1 6DP-MH9096 Mobile Home Kit
ICC EXCEL 2100
Qty.Part # Description
1 6CL48 48" Chimney length (also in
12",18", 24" lengths.
1 6RC Rain Cap
1 6RCS Spark Screen (for rain cap)
1 6RDS/SQS Round/Square support box
1 6VF Flashing
1 6UBA "Ultrablack" Close Clearance
Connector
Canadian Installations*
SECURITY S2100 (see above for details)
ICC EXCEL 2100 (see above for details)
*The use of alternate pitch ashings, support
box extensions, additional chimney lengths,
and additional chimney bracing, may be used
on each of the previously listed systems. These
parts though must be from the same system
as listed, and must be a similar and/or compli-
mentary part.
CAUTION: At no time use unlabelled
parts, or substitute parts made for
another chimney system.
Install as per chimney manufacturer's installa-
tion instructions.
LISTED COMPONENTS FOR
MOBILE HOME INSTALLATION
The Regency Small and Large Freestanding pedestal units are approved for installation in a Mobile Home if one of the following pipe systems is
used.
U.S. Installation*
METALBESTOS SSII
Qty. Part # Description
1 6DS-VK Connector Kit
1 6TMH Shield/Support
1 6TAF-6 Flashing
1 6T-36 Chimney Length
1 6T-18 Chimney Length
1 6T-CT Rain Cap
PRO-JET 3103
Qty.Part # Description
1 PV06-TK Connector
1 CSB Shield/Support
1 RRS Radiation Shield
1 LFR03 Flashing
1 SL3 Chimney Length
1 SL1 Chimney Length
1 RCSA Rain Cap
SECURITY ASHT
Qty.Part # Description
1 DL42A-6 Connector Kit
1 6SS Shield/Support
1 6FAMH Flashing
1 6L3 Chimney Length
1 6L1 Chimney Length
1 CPE Rain Cap
SECURITY S2100
Qty.Part # Description
1 DL42A-6 Connector Kit
1 6XSF Support
1 6XFA Flashing
1 6XL3 Chimney Length
1 6XL18 Chimney Length
1 6XCPE Rain Cap
METAL-FAB TEMP/GUARD 2100
Qty.Part # Description
1 6DWBK Connector
1 6TGRS Roof Support
1 6TGG36 Chimney Length
1 6TGG12 Chimney Length
1 6TGF Flashing
1 6TGC Rain Cap
AMERI-TEC HS
Qty.Part # Description
1 6DCC Connector
1 6HSRS-12 Roof Support (6PLRS-12-BK)
1 6F Flashing
1 6HS-36 Chimney Length
1 6HS-18 Chimney Length
1 6HS-RCS Rain Cap (6PL-MPC)
Regency F1100/F3100 Freestanding Woodstove
17
INSTALLATION
STAINLESS STEEL SMOKE DEFLECTOR ADJUSTMENT / REPLACEMENT
The stainless smoke defl ector is located in the upper front area of the fi rebox. The defl ector is held in place with 2 bolts
Prior to the fi rst fi re, ensure defl ector is seated properly and secured with 2 hand tightened bolts.
To replace the defl ector, loosen off both bolts and slide defector upward and out. Install new defector and hand tighten bolts. Ensure positive location of
the defector prior to hand tightening.
WARNING: Operation of the unit with out proper installation of smoke defl ector will void warranty.
Smoke de ector is installed through the door
opening in location shown in diagram
Smoke de ector
Ensure defector is seated so bolts are situated
at the top of the keyhole before tightening.
18
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
Side View
Front View
Front View
4) Install the third air tube into the holes on the
side channels. The notch goes on the right
hand side with the air holes facing forward
toward the door opening. If the tube will
not slide in easily, simply use a pair of vise
grips or pliers and tap it into place with a
hammer. A tighter t will ensure the tube
will not move when the unit is burning.
Note: When cleaning the chimney reverse
the above procedures, removing
the air tube and baf e bricks and
then replace them when cleaning is
completed.
Large Stove F3100L
The unit arrives with the third air tube (from the
front) and the 2 baf e bricks on the oor of the
rebox. The baf e bricks are positioned rst and
then the air tubes are installed.
1) Slide the left baf e brick over the two rear
air tubes and then push it all the way to the
left side of the rebox.
Front View
2) Tilt the rst Baf e Brick down and then slide
the 2nd Baf e Brick up and back. Reposition
both baf e bricks at on the air tubes.
3) Important: push both baf e bricks so
they are tight against the side walls.
Side View
BRICK FLUE BAFFLE &
SECONDARY AIR TUBE
INSTALLATION
The ue baf e system located in the upper area
of the rebox is removable to make cleaning
your chimney system easier. The brick baf es
must be installed prior to your rst re. Smoke
spillage and draft problems may occur if the
baf es are improperly positioned. Check the
position of the brick baf es on a regular basis as
they can be dislodged if too much fuel is forced
into the rebox.
The Large Stoves F3100L and S3100L are
shipped with one of the secondary air tubes
loose inside the rebox. It needs to be installed
after the brick baf e are installed. Follow the
directions below.
Small Stove F1100S
1) If the two air tubes are installed continue on
to Step 2), if not, follow the instructions below.
Install the air tube into the holes in the side
channels. The notch goes on the right hand
side with the air holes facing toward the door.
Slide the tube into the left hand side, as far
as possible and then bring it back into the
hole on the right hand side until it locks into
position. If the tube will not slide in easily
simply use a pair of vise grips or pliers and
tap it into place with a hammer. A tighter t
will ensure the tube will not move when the
unit is burning. Refer to the Mobile Home
Installation section, though there are only
two air tubes in the small units.
2) Slide the left baf e brick over the front air
tube and then slide it back over the rear air
tube.
3) Tilt the left baf e brick up on top of the side
channel and it will leave enough room to
position the right baf e brick in the same
manner as Step 1 above. Then reposition
the left baf e brick at on the air tube.
4) Important: push both baf e bricks so
they are tight against the side walls.
Note: When getting the chimney cleaned,
remove the baf e bricks for access
to the ue, then replace them when
cleaning is completed.
Regency F1100/F3100 Freestanding Woodstove
19
INSTALLATION
OPTIONAL ACCESSORIES
The pieces listed below can be purchased and
installed during the initial installation or added
on later.
Freestanding - Large F3100
CLASSIC DOOR
HANDLE
Attach spring handle by rotating counter
clockwise onto rod. Ensure that the rod ts
into the entire length of the spring handle. See
Diagram below.
GLASS INSTALLATION
Your Regency stove is supplied with 5 mm
Neoceram ceramic glass that will withstand
the highest heat that your unit will produce. In
the event that you break your glass by impact,
purchase your replacement from an authorized
Regency dealer only.
Remove the door from the stove and remove
the glass retainer. Position the glass in the door,
make sure that the glass gasketing will properly
seal your unit, and replace the retainer, it should
rest on the gasket not the glass. Tighten securely,
but do not wrench down on the glass as this may
cause the glass to break.
Freestanding - Small F1100
BRICK INSTALLATION
Firebrick is included to extend the life of your
stove and radiate heat more evenly. Check to
see that all rebricks are in their correct posi-
tions and have not become misaligned during
shipping.
The "AD" brick in the drawings above is the
brick covering the Ash Dump hole that is used
when the Ash Drawer Kit is installed (refer to
the Listed Components for Mobile Home Instal-
lation section).
SCREEN DOOR
Hook screen to the inside on the right side
of the rebox door opening. Lock in place by
turning handle.
Back Side of Screen Shown
Handle Lock
Hooks
NOTE: The handle must be positioned at 10
o'clock when closed to avoid the handle from
getting hot and to ensure the screen stays in
place.
Handle at 10 o'clock position.
Shown with classic door
CONTEMPORARY DOOR
HANDLE
The cool to touch door handle is designed to be
inserted from the bottom up and slide off when not
held in place. Once in position, the door can be
opened. After use, store the door handle on the
storage hook located on the left side of the faceplate
Handle
Hook
WARNING: FAILURE TO USE RE-
MOVABLE HANDLE AS PER IN-
STRUCTIONS MAY CAUSE
SERIOUS BURNS.
20
Regency F1100/F3100 Freestanding Woodstove
INSTALLATION
Blower/Fan (846-515)
1) Remove the two screws from the top of the fan
housing.
2) Slide the fan up into the rear heat shield.
3) After aligning holes, secure the fan to the rear
heat shield using the two screws removed
earlier.
CAUTION: The connection cord should not be
in contact with any hot surfaces. Do
not route cord under or in front of unit.
Read the Fan Operation instructions before using.
Ground
Fan Fan
Ground
Green
Neutral
Live
White
Fan
Switch
Manual/
Auto
Switch
Black Black
High (Black)
Low (Red)
Black
Fan Thermodisc
(normally open)
120V AC
60 Hz
Blower/Fan Wiring Diagram
CAUTION: Label all wires prior to disconnec-
tion when servicing controls. Wiring errors
can cause improper and dangerous operation.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged
(grounding) plug for your protection against shock
hazard and should be plugged directly into a prop-
erly grounded three-prong receptacle. Do not cut or
remove the grounding prong from this plug.
Refer to the Ash Drawer Operating section.
Bottom Shield Ash Drawer Kit
(850-101 )
1) Remove the bricks from the oor of the
rebox.
2) Remove and discard the cover plate by
removing the two screws on the front of the
Bottom Shield.
3) Remove the ash dump cover plates (one
inside the rebox and one on the underside
of the rebox) by removing the two nuts
and bolts holding the 2 plates together from
inside the rebox.
4) Push the ash plug into the hole inside the
rebox and replace all the bricks except
for the brick over the ash plug. See brick
diagrams.
5) Place the ash plug tool beside the lid, then
slide the ash drawer inside.
Refer to the Ash Drawer Operating section.
Pedestal Ash Drawer Kit (850-100)
1) Remove the bricks from the oor of the
rebox.
2) If using ashdrawer, discard cover plate.
3) Remove the ash dump cover plates (one
inside the rebox and one on the underside
of the rebox) by removing the two nuts
and bolts holding the 2 plates together from
inside the rebox.
4) Push the ash plug into the hole inside the
rebox and replace all the bricks except
for the brick over the ash plug. See brick
diagrams.
5) Place the ash drawer lid inside the pedestal,
and the ash plug tool beside the lid, then
slide the ash drawer inside so it sits on top
of the lid.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Regency F1100S Owners & Installation Manual

Catégorie
Cheminées
Taper
Owners & Installation Manual
Ce manuel convient également à

dans d''autres langues