Installation Instructions
Original Instructions
POINT I/O Source Input Modules
Catalog Numbers 1734-IV2, 1734-IV4, 1734-IV8, 1734-IV8K, Series C
Catalog numbers with the suffix ‘K’ are conformal coated and their specifications are the same as non-conformal coated catalogs.
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic Page
Summary of Changes 1
Before You Begin 5
Install the Mounting Base 5
Install the Module 5
Install the Removable Terminal Block 6
Remove a Mounting Base 7
Wire the Module 7
Communicate with the Module 10
Interpret Status Indicators 10
Specifications 11
Topic Page
Updated IEC Hazardous Location Approval 3
Updated UK and European Hazardous Location Approval 4
Updated Special Conditions for Safe Use 4
Updated General Specifications 12
Updated Environmental Specifications 12
Updated Certifications 13
2Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or
maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable
code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
󴎥󲼒󽴼󱲉󲔞󷠴󸞂󶔩󳕽󰽳󱠥󶑷󳇢󳦦󰹢󱡸󱑹󼵼󷸽󸾔󷹁󳦦󳛓󳮔󰻅󱛻 󽶴 󱌧󰺮󸀵󴙃 󽶵 󸛉󱐕󱐪󱐁󵒹󳥤󱌣󷸄󱾋󲔞󷠴󸞂󶔩󱠥󳕽󰽳󵒹󵕲󲪿󳛓󳮔󹀒󰸬󳄿󳥤󸓔󵈾󷨟󶲵󴎂󲲓󱠥󳫼󱎦󵒹
󵕲󱌣󷦴󴊡󰷔󱾫󼵼󵈾󳄫󸑯󲳴󹏣󴰀󲸫󲔞󷠴󱠥󳍺󶑂󷸺󳟉
󲔞󷠴󷹉󳚯󳇐󸑙󰾫󵈾󶑇󷠴󳈓󱙹󱠥󶑷󳇢󵴞󱝑󹏡󳕽󰽳󲳴󹏣󵉌󶑒󸑃󸓔󲰳󷷳󶑆󵒹󰶂󰶍󰺄󱟘󳉾󴮒󸓔󵈾󵒹󳕽󰽳󷨟󶲵󲕋󳜷
󲁶󳩔󳦣󳉾󴮒󱑗󸔤󱥂󳉸󲕂󵒹󳜱󲮮󰾫󵈾󷸫󷸄󱾋󼵼󱐮󱜴󶡋󰼕󳌁󲕳󷸄󱾋󳏀󰿙󵒹󱁃󳇢
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca
de la instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares
vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el
código de práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este
produto. Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de
acordo com o código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы,
перечисленные в разделе «Дополнительные ресурсы». В этих документах изложены сведения об установке, настройке и эксплуатации данного оборудования.
Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требованиями всех применимых норм, законов и
стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться
обученным персоналом в соответствии с применимыми нормами и правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
󴎤󲼑 : 󳦥󷢢󱡸󷫤󶔨󳸔󳃮󵫪󱕜󱁃󲔛󱑹󳦥󳥆󳦥󳼤󱬼󷫤󶔨󷫤󲕁󳕽󰽳󱛬󶙌󷽺󳛲󷭪󲰳󵶙󳄾󷪹󸋺󳛒󳥆󵕢󸔑
󷭪󲰳󳧵󰾾󴎁󲲓󷧊󳭔󷦳󰻞󱔈󷫤󶔨󸞂󶊁󳅜󹌬󶗠󴯿󲳴󷦳
󷫤󶔨󷰄󳚮󸖋󸋅󸻛󲄤󰾫󵈾󶅉󵰨󷩒󰽥󱁃󲔛󱞎󷲀󰽳󳵠󷭪󲰳󲕌󳜶󷧊󱑲󲲟󷪯󶊻󱜍󸗞󱐗󰽳󳵠󱢟󲕌󷝥󲳴󷦳
󳦥󳼤󱬼󷢢󸔢󳉸󲕁󳜰󴎁󰾫󵈾󱸦󱝖󳼤󱬼󳏀󰿙󱁃󷶋󳐧󲷋
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Weitere Informationen“aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten,
bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den
Installations- und Verdrahtungsanweisungen vertraut machen.
Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit
den anwendbaren Ausführungsvorschriften vorgenommen werden.
Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer,
configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en
vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
󻷋󻰧 : 󻇇󽴔󻳫󼥗󽴔󻗳󼌧 , 󻗳󻳤 , 󻱠󺢨󽴔󺫟󺝣󽴔󻯯󻺏󽴔󻇃󻛧󼨧󺋿󽴔󻳓󻪟󽴔󻇇󽴔󻀇󻗫󺹋󽴔󼢻󼨷󼨧󻪻󽴔󻗳󼌧 , 󻗳󻳤󽴔󻃞󽴔󻱠󺢨󻪟󽴔󺇏󼨫󽴔󼄇󺆯󽴔󻱟󺶛󽴔󻘈󻘧󻰧󽴔󻀇󻗫󺦳󻰓󽴔󻃧󺦫󻞫󽴔󻱌󺆯󽴔󻛨󻺏󼨧󻞼󻞫󻫳 . 󻕻󻭸󻱟󺝣󽴔󺽷󺦯󽴔󺇏󺳷󽴔󺊫󻳤 ,
󻅤󺊫󽴔󻃞󽴔󼤫󻷏󻪟󻗫󽴔󻭣󺈻󼨧󺝣󽴔󻕻󼨼󻪟󽴔󺟏󼩃󽴔󻃧󺦫󻞫󽴔󻗳󼌧󽴔󻃞󽴔󻃿󻗯󽴔󻺏󼌷󻰓󽴔󻛨󻺏󼩃󻩋󽴔󼨸󺞗󺞳 .
󻗳󼌧 , 󻴿󻳤 , 󺃏󺢨 , 󻕻󻭸 , 󻴿󺺌 , 󻉓󼩃 , 󻯯󻺏󻇃󻛧󽴔󺧀󽴔󺽷󺦯󽴔󻱠󻪔󻰏󽴔󺇏󺳷󽴔󺊫󻳤󻪟󽴔󺧿󺱋󽴔󻳐󻳗󼨫󽴔󺈟󻯰󻰓󽴔󻃪󻰏󽴔󻕻󻭸󻱟󺹋󽴔󼚄󼩃󻗫󺺛󽴔󻛧󼩘󼩃󻩋󽴔󼨸󺞗󺞳 .
󻇇󽴔󻱴󻌓󺹋󽴔󻳫󻴿󻕻󺃏󽴔󺽔󻞫󼨧󻺏󽴔󻨙󻰏󽴔󻃸󻅤󻰋󺴫󽴔󻕻󻭸󼨧󺽃󽴔󻱴󻌓󻰧󽴔󻇃󼬇󽴔󺋿󺝴󻱃󽴔󻙟󻖐󺣯󽴔󻛧󽴔󻱗󻞄󺞗󺞳 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre
risorse”, riguardanti l’installazione, la configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti
dalle leggi, codici e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş
dokümanları okuyun. Kullanıcılar yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun
şekilde yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
岤䠑✲갪㖈㸞酤鏤㹁乽⡲䧴笞隌劥欴ㅷ⵹锞⯓ꠗ隡姽俒⟝⟃⿻⴪倴 չⰦ➮须彂պ畎眏⚥剤ꡠ㸞酤鏤㹁莅乽⡲姽鏤⪔涸俒⟝⢪欽罏䗳갭擿䜫㸞酤ㄤꂂ箁䭸
爚⚛痘ざ䨾剤岁鋊岁䖒ㄤ垦彋銴宠
⺫䭍㸞酤锅侮❜➰⢪欽⢪欽穉酤䬓⽹ㄤ笞隌瘞⹛⡲鿪䗳갭❜歋䊺竤麕黠殹鎯箻涸➃㆞鹎遤⟃痘ざ黠欽涸㻜⡲岁鋊
㥶卓㼟鏤⪔欽倴ꬌ醢鸤㉂䭸㹁涸欽鸁儘〳腋剚鸤䧭鏤⪔䨾䲿⣘涸⥃隌⸆腋「䴦
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace,
konfigurace a provozu tohoto zařízení. Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů anorem nutně seznámit také s pokyny pro instalaci a elektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła
omawiające instalację, konfigurację i procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z
obowiązującymi kodeksami, prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z
obowiązującym kodeksem postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda
eller utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product
installeert, configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en
normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en
in overeenstemming met de geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 3
POINT I/O Source Input Modules Installation Instructions
Environment and Enclosure
North American Hazardous Location Approval
IEC Hazardous Location Approval
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in
EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure
must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for
the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements.
NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this
equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring
instructions in addition to requirements of all applicable codes, laws, and standards.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained
personnel in accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module
should be returned to the manufacturer for repair. Do not dismantle the module.
The Following Information Applies When Operating This Equipment In
Hazardous Locations. Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division
2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each
product is supplied with markings on the rating nameplate indicating the
hazardous location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number) may be used to
help determine the overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the local Authority
Having Jurisdiction at the time of installation.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements dangereux. Lorsque
plusieurs produits sont combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons d'équipements dans le
système sont sujettes à inspection par les autorités locales qualifiées au moment de
l'installation.
WARNING:
Explosion Hazard –
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment
by using screws, sliding latches, threaded connectors, or other
means provided with this product.
Substitution of components may impair suitability for Class I,
Division 2.
AVERTISSEMENT:
Risque d’Explosion –
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les
connecteurs externes reliés à cet équipement à l'aide de vis,
loquets coulissants, connecteurs filetés ou autres moyens fournis
avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à
une utilisation en environnement de Classe I, Division 2.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that
complies with the governing electrical codes.
The following applies to products marked with IECEx certification:
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
The type of protection is Ex eC IIC T4 Gc according to IEC 60079-0 and IEC 60079-7.
Comply to Standards IEC 60079-0, Explosive atmospheres Part 0: Equipment General requirements, Edition 7, Revision Date 2017 and IEC 60079-7, 5.1 Edition revision date
2017, Explosive atmospheres - Part 7: Equipment protection by increased safety "e", reference IECEx certificate number IECEx UL 20.0072X.
May have catalog numbers followed by a "K" to indicate a conformal coating option.
4Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
UK and European Hazardous Location Approval
Special Conditions for Safe Use
Prevent Electrostatic Discharge
Electrical Safety Considerations
The following applies to products marked II 3 G:
Are intended for use in potentially explosive atmospheres as defined by UKEX regulation 2016 No. 1107 and European Union Directive 2014/34/EU and has been found to
comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive
atmospheres, given in Schedule 1 of UKEX and Annex II of this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN IEC 60079-7, and EN IEC 60079-0.
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment
given in Schedule 1 of UKEX and Annex II of EU Directive 2014/34/EU. See the UKEx and EU Declaration of Conformity at rok.auto/certifications for details.
The type of protection is Ex ec IIC T4 Gc according to EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, and
CENELEC EN IEC 60079-7:2015+A1:2018, Explosive atmospheres. Equipment protection by increased safety "e".
Comply to Standard EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, and CENELEC EN IEC 60079-
7:2015+A1:2018 Explosive atmospheres. Equipment protection by increased safety "e", reference certificate number DEMKO 04 ATEX 0330347X and UL22UKEX2478X.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification according to UKEX regulation 2016 No. 1107 and ATEX directive 2014/34/EU.
May have catalog numbers followed by a “K” to indicate a conformal coating option.
WARNING:
This equipment is not resistant to sunlight or other sources of UV radiation.
This equipment shall be mounted in an UKEX/ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance
with EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments.
The enclosure must be accessible only by the use of a tool.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when
applied in Zone 2 environments.
The instructions in the user manual shall be observed.
This equipment must be used only with UKEX/ATEX/IECEx certified Rockwell Automation backplanes.
Earthing is accomplished through mounting of modules on rail.
Devices shall be used in an environment of not more than Pollution Degree 2.
ATTENTION:
This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of
other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. See
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more information.
Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage at the supply terminals to the equipment.
Do not remove or replace an adapter while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in
equipment damage or injury from electric shock.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION:
This equipment is certified for use only within the surrounding air temperature range of -20…+55 °C (-4…+131 °F). The equipment must not be used outside
of this range.
Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 5
POINT I/O Source Input Modules Installation Instructions
Before You Begin
You can use these Series C POINT I/O™ Input modules with DeviceNet® and PROFIBUS adapters. If you are using Studio 5000 Logix Designer® application version 20 or higher, you
can also use the modules with ControlNet® and EtherNet/IP™ adapters. See Figure 1 to identify the external features of the module.
Figure 1 - POINT I/O Input Module with 1734-TB or 1734-TBS Base
Install the Mounting Base
To install the mounting base on the DIN rail, proceed as follows:
1. Position the mounting base vertically above the installed units (adapter, power supply, or existing module).
2. Slide the mounting base down allowing the interlocking side pieces to engage the adjacent module or adapter.
3. Press firmly to seat the mounting base on the DIN rail. The mounting base snaps into place. Be sure that the orange DIN rail locking screw is in the horizontal position and
that it has engaged the DIN rail.
Install the Module
The module can be installed before or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition,
make sure that the mounting base locking screw is positioned horizontal referenced to the base.
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number required for the type of module being installed aligns with the notch in
the base.
2. Verify that the DIN rail locking screw is in the horizontal position. You cannot insert the module if the locking mechanism is unlocked.
3. Insert the module straight down into the mounting base.
4. Press to secure. The module locks into place.
Description Description
1 Module locking mechanism 6 1734-TB or 1734-TBS mounting base
2 Slide-in writable label 7 Interlocking side pieces
3 Insertable I/O module 8 Mechanical keying (orange)
4 Removable terminal block (RTB) handle 9 DIN rail locking screw (orange)
5 Removable terminal block with screw (1734-RTB) or spring clamp (1734-RTBS) 10 Module wiring diagram
ATTENTION: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is non-hazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure
to do so could result in equipment damage or injury from electric shock.
Module
Status
Network
Status
NODE:
0
1
2
3
1
10
9
8
7
2
4
5
6
3
The wiring base assembly includes terminal base, 1734-TB, or 1734-TBS, which consists of a
mounting base, 1734-MB, and removable terminal block, 1734-RTB, or 1734-RTBS.
6Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
Install the Removable Terminal Block
A Removable Terminal Block (RTB) is supplied with your wiring base assembly. To remove, pull up on the RTB handle. This allows the mounting base to be removed and replaced as
necessary without removing any of the wirings. To reinsert the Removable Terminal Block, proceed as follows.
1. Insert the end opposite the handle into the base unit. This end has a curved section that engages with the wiring base.
2. Rotate the terminal block into the wiring base until it locks itself in place.
3. If an I/O module is installed, snap the RTB handle into place on the module.
WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field-side power applied, an electrical arc can occur. This can cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: For 1734-RTBS and 1734-RTB3S, to latch and unlatch the wire, insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter blade)
into the opening at approximately 73° (blade surface is parallel with top surface of the opening) and push up gently.
WARNING: For 1734-TOPS and 1734-TOP3S, to latch and unlatch the wire, insert a bladed screwdriver (catalog number 1492-N90 – 3 mm diameter) into
the opening at approximately 97° (blade surface is parallel with top surface of the opening) and press in (do not push up or down).
0
1
Hook the RTB end into the
mounting base end, and rotate
until it locks into place.
73° 85°
97°
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 7
POINT I/O Source Input Modules Installation Instructions
Remove a Mounting Base
To remove a mounting base, you must remove any installed module and the module that is installed in the base to the right. Remove the removable terminal block, if wired.
1. Unlatch the RTB handle on the I/O module.
2. Pull on the RTB handle to remove the removable terminal block.
3. Press the module lock on the top of the module.
4. Pull on the I/O module to remove from the base.
5. Repeat steps 1, 2, 3 and 4 for the module to the right.
6. Use a small bladed screwdriver to rotate the orange base locking screw to a vertical position. This releases the locking mechanism.
7. Lift straight up to remove.
Wire the Module
To wire the module, see the diagrams and tables.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Input 0
NC
C
NC
Input 1
C
VV
Input = 0 and 1
NC = No connection (2 and 3)
C = Common (4 and 5)
V = Supply (6 and7)
Input 0 Input 1
1734-IV2 1734-IV4 1734-IV8, 1734-IV8K
24VDC
Source
Input
Module
Status
Network
Status
1734
IV2
NODE:
0
1
24VDC
Source
Input
Module
Status
Network
Status
1734
IV4
NODE:
0
1
2
3
24VDC
Source
Input
Module
Status
Network
Status
1734
IV8
NODE:
0
1
2
3
4
5
6
7
Input 3
Input 5
Input 7
Input 2
Input 4
Input 6
Input 0 Input 1
Input 3Input 2
C
V
C
V
Input 0, 1, 2, and 3
C = Common (4 and 5)
V = Supply (6 and7)
Input 0, 1, 2, 3, 4, 5, 6, and 7
Note: V and C are daisy chained from either the adapter, 1734-FPD,
1734-EP24DC, or from a user supplied auxiliary terminal block.
8Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
Figure 2 - POINT I/O Source Input Module Wiring – 1734-IV2
Figure 3 - POINT I/O Source Input Module Wiring – 1734-IV4
Figure 4 - POINT I/O Source Input Module Wiring – 1734-IV8, 1734-IV8K
Channel Input Terminal Common Terminal Power
0046
1157
Connect power on 3-wire proximity switches.
12/24V DC is provided by the internal field power bus.
Channel Input Terminal Common Terminal Power
0046
1157
2246
3357
Connect power on 3-wire proximity switches.
12/24V DC is provided by the internal field power bus.
Channel Input Terminal Channel Input Terminal
00 44
11 55
22 66
33 77
Daisy chain common and power connections from 1734 adapter, 1734-FPD, 1734-EP24DC, or from user supplied external auxiliary terminal block.
In 0
10
32
54
76
In 1
NC
CC
VV
2-wire
C = Common
V = 12/24V DC supply
Note: Not protected, 0.3A max
3-wire
NC ProxProx
In 0
10
32
54
76
In 1
CC
VV
2-wire
C = Common
V = 12/24V DC supply
Note: Not protected, 0.3A max
3-wire
Prox ProxProx Prox In 2 In 3
In 0
10
32
54
76
In 1
2-wire
C = Common
V = 12/24V DC supply
3-wire
In 2 In 3
In 4 In 5
In 6 In 7
Prox
Prox
Prox
Prox
2-wire
3-wire
CV
2-wire
3-wire
Prox
Prox
Prox
Prox
2-wire
3-wire
VC
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 9
POINT I/O Source Input Modules Installation Instructions
Figure 5 - Wiring Example of 1734-IV8, 1734-IV8K Using 2-Wire Proximity Switches
Figure 6 - Wiring Example of 1734-IV8, 1734-IV8K Using 3-Wire Proximity Switches
System
Power
DeviceNet
Power
Network
Status
Module
Status
1734
OB8E
3
2
0
1
7
6
4
5
Network
Status
Module
Status
1734
IV8
3
2
0
1
7
6
4
5
Prox
Prox
Prox
Prox
Prox
Prox
Prox
Prox
System
Power
DeviceNet
Power
Network
Status
Module
Status
1734
OB8E
3
2
0
1
7
6
4
5
Network
Status
Module
Status
1734
IV8
3
2
0
1
7
6
4
5
Prox
Prox
Prox
Prox
Prox
Prox
Prox
Prox
DeviceNet
24V DC return (C)
24V DC (V)
Terminal block with bus
connector strip
Terminal block with bus
connector strip
10 Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
Communicate with the Module
POINT I/O modules send (produce) and receive (consume) I/O data (messages). You map this data into the memory of the processor.
The 1734-IV2, 1734-IB4, and 1734-IV8 modules produce 1 byte of input data (scanner Rx). The modules do not consume I/O data (scanner Tx).
Interpret Status Indicators
See Figure 7 and Table 1 for information on how to interpret the status indicators.
Figure 7 - Status Indicators for POINT I/O 2 Current Output and 2 Voltage Output Analog Modules
Message Size: 1 Byte
765 43210
Produces (Rx) I1 I0
Consumes (Tx) No consumed data
Where: I0 = Channel 0, I1 = Channel 1
Message Size: 1 Byte
765 43210
Produces (Rx) I3 I2 I1 I0
Consumes (Tx) No consumed data
Where: I0 = Channel 0, I1 = Channel 1, I2 = Channel 2, I3 = Channel 3
Message Size: 1 Byte
765 43210
Produces (Rx) I7 I6 I5 I4 I3 I2 I1 I0
Consumes (Tx) No consumed data
Where: I0 = Channel 0, I1 = Channel 1, I2 = Channel 2, I3 = Channel 3,
I4 = Channel 4, I5 = Channel 5, I6 = Channel 6, I7 = Channel 7
Module status
Network status
Status of input 0
Status of input 1
1734-IV2 1734-IV4 1734-IV8, 1734-IV8K
Status of input 2
24VDC
Source
Input
Module
Status
Network
Status
1734
IV2
NODE:
0
1
24VDC
Source
Input
Module
Status
Network
Status
1734
IV4
NODE:
0
1
2
3
24VDC
Source
Input
Module
Status
Network
Status
1734
IV8
NODE:
0
1
2
3
4
5
6
7
Status of input 0 and 4
Status of input 1 and 5
Status of input 2 and 6
Status of input 3 and 7
Status of input 3
Module status
Network status
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 11
POINT I/O Source Input Modules Installation Instructions
Specifications
Table 1 - Indicator Status for Modules
Status Description
Module status
Off No power applied to device.
Green Device operating normally.
Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration.
Flashing red Recoverable fault.
Red Unrecoverable fault – may require device replacement.
Flashing red/green Device is in self-test mode.
Network status
Off Device is not online:
– Device has not completed dup_MAC-id test.
– Device not powered – check module status indicator.
Flashing green Device is online but has no connections in the established state.
Green Device is online and has connections in the established state.
Flashing red One or more I/O connections are in timed-out state.
Red Critical link failure – failed communication device. Device detected error that prevents it from
communicating on the network.
Flashing red/green Communication faulted device – the device has detected a network access error and is in communication
faulted state. Device has received and accepted an Identity Communication Faulted Request – long protocol
message.
Channel status Off Input is in the Off state.
Yellow Input is in the On state.
POINT I/O Source Input Modules – 1734-IV2, 1734-IV4, 1734-IV8, 1734-IV8K
Attribute 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K
Number of inputs, sourcing 2 (1 group of 2) 4 (1 group of 4) 8 (1 group of 8)
Voltage, on-state
Min
Nom
Max
10V DC
24V DC
28.8V DC
Current, on-state
Min
Nom
Max
2 mA
4 mA @ 24V DC
5 mA
Voltage, off-state, max 5V DC
Current, off-state, min 1.5 mA
Impedance, input,
Nom
Max 3.6 kΩ
4.7 kΩ
Input filter time(1)
Off to On
On to Off
(1) Input Off-to-On filter time is the time from a valid input signal to recognition by the module. Input On-to-Off time is the time from a valid input signal to recognition by the
module.
0.5 hardware plus 0…63 ms (user selectable)
0.5 hardware plus 0…63 ms (user selectable)
Field wiring terminations
0 – Input 0
1 – Input 1
2 – No connection
3 – No connection
4 – Common
5 – Common
6 – User supply
7 – User supply
0 – Input 0
1 – Input 1
2 – Input 2
3 – Input 3
4 – Common
5 – Common
6 – User supply
7 – User supply
0 – Input 0
1 – Input 1
2 – Input 2
3 – Input 3
4 – Input 4
5 – Input 5
6 – Input 6
7 – Input 7
General Specifications
Attribute 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K
Terminal base screw torque 0.8 N•m (7 lb•in)
Indicators
1 green/red – module status indicator, logic side
1 green/red – network status indicator, logic side
2 yellow – input status indicators, logic side 4 yellow – input status indicators, logic side 8 yellow – input status indicators, logic side
Module location 1734-TB or 1734-TBS wiring base assembly
12 Rockwell Automation Publication 1734-IN052H-EN-E - September 2022
POINT I/O Source Input Modules Installation Instructions
POINTBus™ current, max 75 mA @ 5V DC
Power dissipation, max 0.7 W @ 28.8V DC 1.0 W @ 28.8V DC 1.6 W @ 28.8V DC
Thermal dissipation, max 2.4 BTU/h
@ 28.8V DC 3.4 BTU/h
@ 28.8V DC 5.5 BTU/h
@ 28.8V DC
Isolation voltage 50V continuous
Tested to withstand 2500V DC for 60 s
Field power bus
Supply voltage, nom
Voltage range 24V DC
10...28.8V DC
Dimensions, approx (H x W x D) 56 x 12 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Wiring category(1) 2 – on signal ports
Wire size 0.25…2.5 mm2 (22…14 AWG) solid or stranded shielded copper wire rated at 75 °C (167 °F) or greater 1.2 mm (3/64 in.) insulation max
Weight, approx. 31.2 g (1.10 oz) 31.8 g (1.12 oz) 32.3 g (1.14 oz)
Enclosure type rating None (open-style)
North American temp code T4A
IECEx temp code T4
UKEX/ATEX temp code T4
Keyswitch position 1
(1) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual. Also see Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1, for more information.
Environmental Specifications
Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, operating cold),
IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock):
-20 °C Ta +55 °C (-4 °F Ta + 131 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, unpackaged nonoperating cold),
IEC 60068-2-2 (Test Bb, unpackaged nonoperating dry heat),
IEC 60068-2-14 (Test Na, unpackaged nonoperating thermal shock):
-40…+85 °C (-40…+185 °F)
Temperature, surrounding air, max 55 °C (131 °F)
Relative humidity IEC 60068-2-30 (Test Db, unpackaged damp heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, operating):
5 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, unpackaged shock): 30 g
Shock, nonoperating 50 g
Emissions IEC 61000-6-4
ESD immunity IEC6100-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…6000 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
Surge transient immunity IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF immunity IEC61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
General Specifications (Continued)
Attribute 1734-IV2 1734-IV4 1734-IV8, 1734-IV8K
Rockwell Automation Publication 1734-IN052H-EN-E - September 2022 13
POINT I/O Source Input Modules Installation Instructions
Certifications
Certification (When Product Is Marked)(1)
(1) See the Product Certification link at rok.auto/certifications for Declaration of Conformity, Certificates, and other certification details.
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
UK and CE
UK Statutory Instrument 2016 No. 1091 and European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Measurement/Control/Laboratory use, Industrial requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
UK Statutory Instrument 2012 No. 3032 and European Union 2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical documentation
Ex
For 1734-IV2 and 1734-IV4 only
UK Statutory Instrument 2016 No. 1107 and European Union 2014/34/EU ATEX Directive, compliant with:
EN IEC 60079-0; General Requirements
EN IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
DEMKO 04 ATEX 0330347X
UL22UKEX2478X
IECEx
For 1734-IV2 and 1734-IV4 only
IECEx System, compliant with:
IEC 60079-0; General Requirements
IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
IECEx UL 20.0072X
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions.
Morocco Arrêté ministériel n° 6404-15 du 29 ramadan 1436
CCC
For 1734-IV2 and 1734-IV4 only
CNCA-C23-01 󲰃󱑗󲶎󰹢󱡸󷷪󷸇󲕋󳜷󷨟󱐮 󸿉󴳙󵉐󴉟
CNCA-C23-01 CCC Implementation Rule Explosion-Proof Electrical Products
CCC: 2020122309111607
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
Publication 1734-IN052H-EN-E - September 2022 | Supersedes Publication 1734-IN052G-EN-E - January 2021
Copyright © 2022 Rockwell Automation, Inc. All rights reserved.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur
Allen-Bradley, expanding human possibility, FactoryTalk, POINT I/O, POINTBus, Rockwell Automation, Studio 5000 Logix Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Waste Electrical and Electronic Equipment (WEEE)
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product notification updates. rok.auto/support
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Technical Documentation Center Quickly access and download technical specifications, installation instructions, and user manuals. rok.auto/techdocs
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center (PCDC) Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes. rok.auto/pcdc
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Allen Bradley Allen-Bradley 1734-IV2 POINT I-O Source Input Modules Manuel utilisateur

Taper
Manuel utilisateur