6.0 INSTALLATION INSTRUCTIONS
The ProStar is installed in 10 steps. Follow the
procedure in section 6.2 for a proper installation and
best performance.
6.1 GENERAL INSTALLATION NOTES
• The ProStar uses stainless steel fasteners, an anodized
heat sink, and conformal coating to protect from harsh
conditions. However, for acceptable service life extreme
temperatures and marine environments should be
avoided.
• The ProStar prevents reverse current leakage at night, so
a blocking diode is not required in the system.
• The ProStar is designed to regulate ONLY solar
(photovoltaic) power. Do not connect it to any other type
of power generator. Do not attempt to regulate a wind
turbine. However, other power sources can be connected
directly to the battery.
• The connector terminals will accept a maximum wire
size of AWG #6 / 16 mm2 (solid/multistrand) or AWG
#8 / 10 mm2 (fine strand). Use a flathead insulated
screwdriver, and torque tightly up to 35 in-lb.
• Stranded wires to be connected to the ProStar
terminals should be prepared first with e.g. clamped
copper heads, etc. to avoid the possibility of one
conductor free out of the connection screw, and possible
contact with the metal enclosure.
• Solar and Battery fuses or DC disconnects are not part of
the ProStar controller.
WARNING: Solar and battery fuses or DC break -
ers are required in the system. These protection
devices are external to the Prostar PWM controller, and must
be a maximum of 18 amps for the PS-PWM-15/M and 37.5
amps for the PS-PWM-30/M.
AVERTISSEMENT: Solaire et batterie fusibles ou
disjoncteurs DC sont nécessaires dans le système.
Ces dispositifs de protection sont externes au contrôleur
PS-PWM et doivent être un maximum de 18 ampères pour
le PS-PWM-25/M et 37.5 ampères pour le PS-PWM-40/M.
WARNING: Installation must comply with all
NEC requirments. All breakers must be properly
rated for wire ampacity, which may require less than the
maximum breaker sizes referenced above.
AVERTISSEMENT: Installation doit être conforme
à toutes les requirments NEC. Tous les disjonc-
teurs doivent être correctement classifiés pour fil courant
admissible, susceptible d’exiger moins que les tailles
maximales disjoncteur référencés ci-dessus.
WARNING: Minimum over-current protection
device interrupt ratings must be 2000A for 12V
systems, and 4000A for 24V systems.
AVERTISSEMENT: Protection contre les
surintensités minimum cotes d’interruption de
périphérique doivent être de 2000 a 12V systèmes et 4000 a
pour les systèmes de 24V.
NOTE:
Carefully observe the LEDs at each connection. The
LEDs will indicate proper polarity and a good connection.