2524X/2525XCH
15
5. PROGRAMMVERSION 2.7
With the program version 2.7, the function possibilities of the presence detector - series Swiss Guard 360P KNX / KLR RA / EA expanded and existing features of program version 2.4, have been supplemented respectively adapted.
The standard values (default values) of the parameters compared to the settings in version 2.4 are partially modified.
These settings allow a simple and safe functionally check (initial start-up ) of the presence detector .
Older devices of software version 2.4 can also be programmed with the program version 2.7 ( backward compatibility ) .
However, supplemented functions and the additional communication objects are not all
supported.
5.1. Overview of the changes:
see 5.2.0
see 5.2.1
see 5.2.2
see 5.3.1
see 5.3.2
see 5.3.3
see 5.3.4
• Forced control Secondary detector-Mode
• Parameter changes via communication objects
• Dimming function with constant light control (clc)
• Power on characteristics
• Automatic lighting OFF threshold
• Delay time in semi-automatic mode
• Standby-function
• Light sensor adaption see 5.3.5
5.2. Communication objects
input objects
output objects
Object Function link application with Bit/Byte
0 Output - light (preset dimming) light group actuator 1 byte
0Output - light (switching) light group actuator. 1 bit
0Output - light (scene) light group actuator 1 bit
1Input external switch / status - light
(switching)
KNX switch, touch display, logic 1 bit
2Input external motion - light (switching) Output - light for secondary unit (object 0) 1 bit
3Input - light (forced control) • External logic module 2 bit
3Input - light (lock) KNX switch, touch display, logic module 1 bit
4Output - HVAC (switching) • Actuators for HVAC devices such as heating, ventilation and air conditioning
• Control of alarm logic modules
• Presence function
1 bit
5External switch / status - HVAC (switching) KNX switch, touch display, logic 1 bit
6External motion - HVAC (switching) Output HVAC for secondary unit (output object 4). 2 byte
7Input - HVAC (forced control) External logic module 2 bit
7Input - HVAC (lock) KNX switch, touch display, logic 1 bit
8Threshold switch brightness (switching) Logic, actuator 1 bit
9Brightness (lux value) Logic, touch display 2 byte
10 AD calibration value Read out and then set manually for calibration procedure 2 byte
16 Constant light control, switch on/off KNX switch , logic 1 bit
17 Constant light control, dimming relative 4 bit dimming object from KNX switch for ON/OFF, dimming up and down, touch display 4 bit
18 Constant light control, preset dimming Logic module 1 byte
20 Constant light control, forced control KNX button, logic 1 bit
21 Constant light control, scene selection Logic module 1 byte
22 Constant light control, channel 1 - output Dimming actuator for light group 1 1 byte
23 Constant light control, channel 2 - output Dimming actuator for light group 2 1 byte
24 Light - standby Switching of standby value sets 1 bit
5.2.1. COMMUNICATION OBJECTS with Secondary Detector- Mode
Object Function link application with Bit/Byte
0 Output (switching) Master presence -detector 1 bit
3Input (forced control) KNX switch, touch display, logic module 1 bit
Object forced control:
The object 3 as a forced control object knows 2 values ( 1 bit command ) which can be received :
If object forced control = 1: output ( Obj.0 ) remains locked when motion is detected , no telegrams are sent
If object forced control = 0: output ( Obj.0 ) AUTO ( normal operation )