Allen-Bradley 1746-NI8 Installation Instructions Manual

Taper
Installation Instructions Manual

Ce manuel convient également à

Publication 1746-IN006A-US-P
Installation Instructions
SLC 500™ Analog Input Module
(Catalog Number 1746-NI8)
Inside
Important User Information........................................................................... 2
For More Information ......................................................................................3
Hazardous Location Considerations............................................................. 4
Environnements dangereux.......................................................................... 4
Electrostatic Damage.................................................................................... 5
1746-NI8 Power Requirements..................................................................... 5
Module Location in Chassis.......................................................................... 6
Heat and Noise Considerations.................................................................... 7
Module Installation and Removal.................................................................. 7
Terminal Wiring........................................................................................... 10
Input Devices.............................................................................................. 15
Specifications.............................................................................................. 17
@JO"VTQQE@JO"VTQQE ".".
2
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Important User Information
Because of the variety of uses for the products described in this publication, those
responsible for the application and use of this control equipment must satisfy
themselves that all necessary steps have been taken to assure that each application
and use meets all performance and safety requirements, including any applicable
laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide
are intended solely for purposes of example. Since there are many variables and
requirements associated with any particular installation, Allen-Bradley does not
assume responsibility or liability (to include intellectual property liability) for actual
use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation
and Maintenance of Solid-State Control (available from your local Allen-Bradley
office), describes some important differences between solid-state equipment and
electromechanical devices that should be taken into consideration when applying
products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part,
without written permission of Rockwell Automation, is prohibited.
Attention statements help you to:
•identify a hazard
avoid the hazard
recognize the consequences
!
ATTENTION
Identifies information about practices or circumstances that
can lead to personal injury or death, property damage, or
economic loss.
IMPORTANT
Identifies information that is critical for successful application
and understanding of the product.
@JO"VTQQE@JO"VTQQE ".".
SLC 500™ Analog Input Module
3
Publication 1746-IN006A-US-P
For More Information
For detailed information on planning and installing your system, see the following
publications:
If you would like a manual, you can:
download a free electronic version from the internet:
www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting
www.theautomationbookstore.com
and placing your order
–calling
1.800.963.9548
(USA/Canada)
or
001.330.725.1574
(Outside USA/Canada)
Publication Publication
Number
Industrial Automation Wiring and Grounding Guidelines 1770-4.1
SLC 500™ Analog Input Modules User Manual 1746-6.8
SLC 500™ Modular Hardware Style Operation and Installation Manual 1747-6.2
SLC 500™ Fixed Hardware Style Operation and Installation Manual 1747-6.21
@JO"VTQQE@JO"VTQQE ".".
4
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use
in hazardous locations.
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
s’applique à une utilisation dans des environnements dangereux.
!
WARNING
!
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
All wiring must comply with N.E.C. article 501-4(b).
MISE EN GARDE
!
DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est
coupée.
Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée.
@JO"VTQQE@JO"VTQQE ".".
SLC 500™ Analog Input Module
5
Publication 1746-IN006A-US-P
Electrostatic Damage
Electrostatic discharge can damage semiconductor devices inside this module if you
touch backplane connector pins. Guard against electrostatic damage by observing
the following precautions.
1746-NI8 Power Requirements
The 1746-NI8 module receives its power through the SLC 500™ chassis backplane
from the fixed or modular +5V dc/+24V dc chassis power supply. The +5V dc
backplane supply powers the SLC circuitry and the +24V dc backplane supply
powers the module analog circuitry. The maximum current drawn by the module is
shown in the table below.
When you are using a modular system configuration, add the values shown in the
table above to the requirements of all other modules in the SLC chassis to prevent
overloading the chassis power supply.
!
ATTENTION
Electrostatic discharge can degrade performance or cause
permanent damage. Handle the module as stated below.
Wear an approved wrist strap grounding device when
handling the module.
Touch a grounded object to rid yourself of electrostatic charge
before handling the module.
Handle the module from the front, away from the backplane
connector. Do not touch backplane connector pins.
Keep the module in its static-shield bag when not in use, or
during shipment.
5V dc Amps 24V dc Amps
200 mA 100 mA
@JO"VTQQE@JO"VTQQE ".".
6
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Module Location in Chassis
Modular Chassis Considerations
Place your 1746-NI8 module in any slot of an SLC 500 modular, or modular
expansion chassis, except for the extreme left slot (slot 0) in the first chassis. This slot
is reserved for the processor or adapter modules.
Fixed Expansion Chassis Considerations
IMPORTANT
For applications using the upper limit of the operating
temperature range, the 1746-NI8 module (or multiple modules)
should be placed in the right-most slot(s) of the chassis.
Operating Temperature Range
Temperature Chassis Location
+0
°
C to +55
°
C (+32
°
F to +131
°
F) Any slot except slot 0.
0°C to +60°C (32°F to 140°F) In right most slot of chassis
IMPORTANT
The 2-slot, SLC 500 fixed I/O expansion chassis (1746-A2)
supports only specific combinations of modules. If you are using
the 1746-NI8 module in a 2-slot expansion chassis with another
SLC I/O or communication module, refer to the 1746-NI8
user
manual to determine whether the combination can be
supported.
@JO"VTQQE@JO"VTQQE ".".
SLC 500™ Analog Input Module
7
Publication 1746-IN006A-US-P
Heat and Noise Considerations
Most applications require installation in an industrial enclosure to reduce the effects
of electrical interference. Analog inputs are highly susceptible to electrical noise.
Electrical noise coupled to the analog inputs reduces the performance (accuracy) of
the module.
Group your modules to minimize adverse effects from radiated electrical noise and
heat. Consider the following conditions when selecting a slot for the analog input
module. Position the module:
in a slot away from sources of electrical noise such as hard-contact switches,
relays, and AC motor drives
away from modules which generate significant radiated heat, such as the 32-point
I/O module (series C or earlier)
In addition, route shielded twisted-pair analog input wiring away from any
high-voltage I/O wiring.
Module Installation and Removal
When installing the module in a chassis, it is not necessary to remove the terminal
block from the module. However, if the terminal block is removed, use the write-on
label (shown below) located on the side of the terminal block to identify the module
location and type.
!
ATTENTION
Remove power before removing or inserting this module. When
you remove or insert a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
sending an erroneous signal to your systems field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
SLOT
RACK
MODULE
@JO"VTQQE@JO"VTQQE ".".
8
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Terminal Block Removal
To remove the terminal block:
1. Loosen the two terminal block release screws.
.
2. Grasp the terminal block at the top and bottom and pull outward and down.
Switch Settings to Select Voltage or Current Input
Before installing the module in the chassis, use the DIP switches on the module
circuit board to select between voltage and current inputs for channels 0 through 7.
The switch settings are
OFF = VOLTAGE INPUT
ON = CURRENT INPUT.
Terminal Block Release
Screws
Maximum Torque =
0.7 to 0.9 Nm (6 to 8 in-lbs)
O
2
1
N
O
2
1
N
O
2
1
N
O
2
1
N
VOLTAGE
CURRENT
CH7CH0
@JO"VTQQE@JO"VTQQE ".".
SLC 500™ Analog Input Module
9
Publication 1746-IN006A-US-P
Module Installation Procedure
1. Align the circuit board of the analog input module with the card guides located at
the top and bottom of the chassis.
2. Slide the module into the chassis until both top and bottom retaining clips are
secured. Apply firm even pressure on the module to attach it to its backplane
connector. Never force the module into the slot.
3. Cover all unused slots with the Card Slot Filler, catalog number 1746-N2.
Module Removal Procedure
1. Press the releases at the top and bottom of the module and slide the module out
of the chassis slot.
2. Cover all unused slots with the Card Slot Filler, catalog number 1746-N2.
Card
Guide
Top and Bottom Module
Release(s)
@JO"VTQQE@JO"VTQQE ".".
10
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Terminal Wiring
The 1746-NI8 module contains an 18-position, removable terminal block. The
terminal pin-out is shown below.
T
erminal Block
!
ATTENTION
Disconnect power to the SLC before attempting to install,
remove, or wire the removable terminal wiring block.
To avoid cracking the removable terminal block, alternate the
removal of the slotted terminal block release screws.
Shield
Channel 0 (-)
Channel 1 (-)
Channel 2 (-)
Channel 3 (-)
Channel 4 (-)
Channel 5 (-)
Channel 6 (-)
Channel 7 (-)
Channel 0 (+)
Channel 1 (+)
Channel 2 (+)
Channel 3 (+)
Channel 4 (+)
Channel 5 (+)
Channel 6 (+)
Channel 7 (+)
Shield
(Terminal Block Spare Part Catalog Number 1746-RT25G)
Terminal Block Release Screw
Maximum Torque=0.7 to 0.9 Nm
(6 to 8 in-lbs.)
@JO"VTQQE@JO"VTQQE ".".
SLC 500™ Analog Input Module
11
Publication 1746-IN006A-US-P
Wiring Single-Ended Inputs
The following diagram shows typical wiring for the 1746-NI8 module.
Use shielded communication cable (Belden™ 8761) and keep length as short as
possible.
Connect only one end of the cable shield to earth ground.
Connect the shield drain wires for channels 0 to 3 to the top shield terminal.
Shield terminals are internally connected to chassis ground which is connected to
earth ground via the SLC backplane.
Single-ended source commons may be jumpered together at the terminal block.
Channels are not isolated from each other.
If a different signal source has an analog common, it cannot and must not be
connected to the module.
Common mode voltage range is ±10.5 volts. The voltage between any two
terminals must be less than 15 volts.
The module does not provide power for the analog inputs.
Use a power supply that matches the transmitter (sensor) specifications.
IMPORTANT
Follow these guidelines when wiring the module.
@JO"VTQQE@JO"VTQQE ".".
12
SLC 500™ Analog Input Module
Publication 1746-IN006A-US-P
Typical 1746-NI8 Wiring
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
+
+
Power
Supply
Connections
single-end
signal source
single-end
signal source
single-end
signal source
single-end
signal source
differential
signal source
differential
signal source
differential
signal source
differential
signal source
shield
shield
shield
shield
shield
shield
shield
shield
Shield
Channel 0
Channel 7
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Shield
@JO"VTQQE@JO"VTQQE ".".
SLC 500 Analog Input Module
13
Publication 1746-IN006A-US-P
When wiring single-ended analog input devices to the analog input module, the
number of total wires necessary can be limited by jumpering all “IN” terminals
together. Note that differential inputs are more immune to noise than single-ended
inputs.
IMPORTANT
The module does not provide loop power for analog inputs. Use
a power supply that matches the transmitter specifications.
+
+
+
-
+
+
Wiring Schematic for Single-Ended Analog Input Connections
Power
Supply
Transmitter
Signal
Transmitter
Transmitter
Signal
Signal
Transmitter
SignalSupply
Ground
1746-NI8
IN 0+
IN 1-
IN 2+
IN 2-
IN 3-
IN 3+
IN 0-
IN 1+
@JO"VTQQE@JO"VTQQE ".".
14
SLC 500 Analog Input Module
Publication 1746-IN006A-US-P
IMPORTANT
The module does not provide loop power for analog inputs. Use
a power supply that matches the transmitter specifications.
+-
+
-
+
-
+
-
+
-
+
-
Transmitter
Transmitter
Transmitter
Power
Supply
Power
Supply
Power
Supply
Supply
Signal
GND
Supply
Module
Module
Module
IN +
IN -
IN +
IN -
IN +
IN -
2-Wire Transmitter
3-Wire Transmitter
4-Wire Transmitter
Wiring Schematics for 2, 3, and 4-Wire Analog Input Devices
@JO"VTQQE@JO"VTQQE ".".
SLC 500 Analog Input Module
15
Publication 1746-IN006A-US-P
Wiring Guidelines
Follow the guidelines below when planning your system wiring.
To limit noise, keep signal wires as far away as possible from power and load lines.
To ensure proper operation and high immunity to electrical noise, always use
Belden™ 8761 (shielded, twisted-pair) or equivalent wire.
Connect the shield drain wire to the shield terminal on the 1746-NI8 module.
Up to four shield wires may be connected to each shield screw terminal that
provides a connection to chassis ground.
Tighten terminal screws using a screwdriver. Each screw should be turned tight
enough to immobilize the wires end. Excessive tightening can strip the terminal
screw. The torque applied to each screw should not exceed 0.9 Nm (8 in-lb) for
each terminal.
Follow system grounding and wiring guidelines found in your SLC 500 Modular
Hardware Style Installation and Operation Manual, publication 1747-6.2.
Input Devices
Transducer Source Impedance
If the source impedance of the input device and associated cabling is too high, it
affects the accuracy of the channel data word. Source impedance of 500 ohms
produces up to 0.05% of module error over and above the specified accuracy of the
module.
You can compensate for device impedance error by implementing the following
equation in your ladder program:
!
ATTENTION
To prevent shock hazard, care should be taken when wiring the
module to analog signal sources. Before wiring any analog
module, disconnect power from the SLC 500 system and from
any other source to the analog module.
V
S
V
measured
(
R
s
R
in
)
R
in
where:
Vs = input device voltage
Rs = input device impedance
Rin = 1746-NI8 input impedance (See Specifications on page 17.)
@JO"VTQQE@JO"VTQQE ".".
16
SLC 500 Analog Input Module
Publication 1746-IN006A-US-P
Wiring Input Devices to the 1746-NI8
After the analog input module is properly installed in the chassis, follow the wiring
procedure below using Belden 8761 cable.
To wire your 1746-NI8 module follow these steps.
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 50 mm (2 inch) lengths. Strip about 5 mm (3/16 inch) of
insulation away to expose the end of the wire.
3. At one end of the cable, twist the drain wire and foil shield together. This end of
the cable is connected to one of the shield terminals on the 1746-NI8 module.
Connect shields for channels 0 through 3 to the upper shield terminal and shields
for channels 4 through 7 to the lower shield terminal.
4. At the other end of the cable, cut the drain wire and foil shield back to the cable.
5. Connect the signal wires and shield drain wire to the 1746-NI8 terminal block or
interposing terminal block.
6. Connect the other end of the cable to the voltage or current transmitter terminals.
7. Repeat steps 1 through 6 for each channel on the module.
!
ATTENTION
Care should be taken to avoid connecting a voltage source to a
current input module. Improper module operation or damage to
the voltage source can occur.
Cable
(Cut foil shield
and drain wire.)
Signal Wire
Signal Wire
Signal Wire
Signal Wire
Foil Shield
Drain Wire
(Twist the drain wire and foil shield together
and connect to earth ground or to the shield
terminal on the 1746-NI8 module.)
@JO"VTQQE@JO"VTQQE ".".
SLC 500 Analog Input Module
17
Publication 1746-IN006A-US-P
Specifications
Electrical Specifications
Description Specification
Backplane Current Consumption 200 mA at 5V dc
100 mA at 24V dc
Backplane Power Consumption 3.4W maximum (1.0W at 5V dc, 2.4W at 24V dc)
Number of Channels 8 (backplane isolated)
I/O Chassis Location Any I/O module slot except slot 0
A/D Conversion Method Successive appoximation, switched capacitor
Input Filtering Low-pass digital filter with programmable filter
frequencies
Normal Mode Rejection
(between [+] input and Analog Com
Provided by low-pass filter
Common Mode Rejection
(between inputs and chassis
ground)
Greater than or equal to 75 dB at DC
Greater than or equal to 100 dB at 50/60 Hz
Input Filter Frequencies 1 Hz
2 Hz
5 Hz
10 Hz
20 Hz
50 Hz
75 Hz
Calibration The module performs continuous autocalibration
Isolation 500V dc continuous between the analog inputs and the
backplane
530V ac and 750V dc pulse withstand for one second
Common-Mode Voltage Range
±
10.5V (15V maximum between any two terminals)
@JO"VTQQE@JO"VTQQE ".".
18
SLC 500 Analog Input Module
Publication 1746-IN006A-US-P
Physical Specifications
Environmental Specifications
Description Specification
LED Indicators 9 green status indicators
one for each of 8 channels and one for module status
Module ID Code Class 1 Interface: 3526
Class 3 Interface: 12726
Recommended Cable Belden #8761 or equivalent
Maximum Wire Size Two 14 AWG wires per terminal
Maximum Cable
Impedance
Voltage Source (with less than 10
impedance):
40
maximum loop impedance, for <1LSB error
Current Source (transmitter properly wired to its power supply):
250
maximum loop impedance, to meet common-mode voltage
requirements
Terminal Block Removable, Allen-Bradley spare part Catalog Number 1746-RT25G
Description Specification
Operating Temperature 0°C to +55°C (32°F to 133°F) in any slot except 0
0°C to 60°C (32°F to 140°F) in right most slot of chassis
Storage Temperature
-40
°
C to
+
85
°
C (-40
°
F to
+
185
°
F)
Relative Humidity 5% to 95% (without condensation)
Agency Certification UL listed
CSA approved
CE compliant for all applicable directives
Hazardous Environment
Classification
Class 1 Division 2 Hazardous Environment
@JO"VTQQE@JO"VTQQE ".".
SLC 500 Analog Input Module
19
Publication 1746-IN006A-US-P
Input Specifications
Description Specification
Type of Input (Selectable) ±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0 to 20 mA
4 to 20 mA
±20 mA
0 to 1 mA
Type of Data (Selectable) Engineering Units
Scaled-for-PID
Proportional Counts (-32,768 to +32,767 range)
Proportional Counts (User Defined Range, Class 3 only)
1746-NI4 Data Format
Input Impedance 1 M
Voltage Input (maximum)
±
30V between any two signal terminals
Current Input (maximum) 30 mA
Time to Detect Open Circuit 1 module scan
Input Step Response
(1)
(1)Depends on filter selected. Refer to the 1746-NI8 User Manual, publication 1746-6.8.
Input Resolution 1 mV or 1
µ
A
Display Resolution 1 mV or 1
µ
A
Overall Module Accuracy
(0
°
C to +60
°
C, +32
°
F to +140
°
F)
Voltage input types
(
±
10V dc, 1 to 5V dc, 0 to 5V dc, 0 to 10V dc):
±
0.1%
Current Input Types
(0 to 20 mA, 4 to 20 mA, ±20 mA):±0.05%
Current Input Type (0 to 1 mA): ±0.5%
Overall Module Drift Voltage input type: ±6 ppm/°C
Current Input Type: ±12 ppm/°C
@JO"VTQQE@JO"VTQQE ".".
Publication 1746-IN006A-US-P - February 2000 PN 40071-081-01 (A)
© 2006 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
SLC 500 is a trademark of Rockwell Automation.
Belden is a trademark of Belden, Inc.
@JO"VTQQE@JO"VTQQE ".".
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Allen-Bradley 1746-NI8 Installation Instructions Manual

Taper
Installation Instructions Manual
Ce manuel convient également à

dans d''autres langues