GE AW15ES2VHB Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation
31-5000587 Rev. 1 02-23 GEA
Ductless Single Zone with Highwall Indoor Unit
Zone simple sans conduit avec unité intérieure en hauteur
Unidad Interna para Pared Alta sin Conducto y de Zona Única
Design may vary by model number.
This installation manual is only
printed in English. For French or
Spanish version, please visit
GEAppliancesairandwater.com
L’aspect peut varier selon le numéro de
modèle.
Ce manuel d’installation est uniquement
imprimé en anglais. Pour la version française
ou espagnole, visitez le site
GEAppliancesairandwater.com
El diseño puede variar según el número de model.
Este manual de instalación sólo fue impreso en
inglés. Para acceder a la versión en francés o
español, por favor visite
GEAppliancesairandwater.com
Installation Manual
Manuel d’installation
Instrucciones de instalación
231-5000587 Rev. 1
ENGLISH
Thank you for purchasing this Haier product. This installation manual
will help you get the best performance from your new heat pump.
For future reference, record the model and serial number located on
the label on the side of your air conditioner/heat pump, and the date
of purchase.
Staple your proof of purchase to this manual to aid in obtaining
warranty service if needed.
_______________________________________
Model number
_______________________________________
Serial number
_______________________________________
Date of purchase
To register your new Haier Duct Free System go to
https://www.haierductless.com/product-registration and input the
model/serial number information on this page. To receive a 10-year
compressor and parts warranty, registration is required within 60
days of installation.
TABLE OF CONTENTS
RECORD KEEPING
IMPORTANT SAFETY INFORMATION .....................................................................................3
INSTALLATION INSTRUCTIONS ..........................................................................................4
Step 1 - Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 2 - Installation of Indoor Unit ....................................................................................7
Step 3 - Installation of Outdoor Unit .................................................................................10
Step 4 - Final Check ................................................................................................14
LIMITED WARRANTY ................................................................................................... 15
31-5000587 Rev. 1 3
ENGLISH
WARNING For your safety; the information in this manual must be followed to minimize the risk of fire, electric
shock, or personal injury.
Use this equipment only for its intended purpose as
described in this manual.
This heat pump must be properly installed in accordance
with these instructions before it is used.
All wiring should be rated for the amperage value listed on
the rating plate. Use only copper wiring.
All electrical work must be completed by a qualified
electrician and completed in accordance with local and
national building codes.
Any servicing must be performed by a qualified individual.
All air conditioners contain refrigerants, which under
federal law must be removed prior to product disposal.
If you are getting rid of an old product with refrigerants,
check with the company handling disposal.
These R-410A heat pumps systems require that
contractors and technicians use tools, equipment and
safety standards approved for use with this refrigerant.
DO NOT use equipment certified for R22 refrigerant only.
WARNING RISK OF ELECTRIC SHOCK. Could cause injury or death.
An adequate ground is essential before connecting the
power supply.
Disconnect all connected electric power supplies before
servicing.
Repair or replace immediately all electrical wiring that has
become frayed or otherwise damaged. Do not use wiring
that shows cracks or abrasion damage along its length or
at either end.
READ AND SAVE THESE INSTRUCTIONS
WARNING
RISK OF FIRE. Could cause injury or death.
Do not store or use combustible materials, gasoline or
other flammable vapors or liquids in the vicinity of this or
any other appliance.
For any service which requires entry into the
refrigerant sealed system, Federal regulations require
that the work is performed by a technician having a
Class II or Universal certification.
IMPORTANT SAFETY INFORMATION
WARNING
- This product is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the product
- Ensure that the unit shall be installed in accordance with local and national wiring codes
- Ensure the dimensions of the space necessary for correct installation of the appliance including the minimum
permissible distances to adjacent structures
- Ensure only approved units are connected together and that all refrigerant line dimensions and refrigerant charging
requirements are followed to prevent exceeding the maximum operating pressure
- ONLY connect units that are labeled with the same refrigerant.
- Any damage of electrical supply must be replaced by the manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
431-5000587 Rev. 1
ENGLISH
FOR MORE HELP, VISIT HAIERAPPLIANCES.COM OR CALL THE CONSUMER HELP LINE AT 877-337-3639.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT – Save these instructions for
local inspector’s use.
IMPORTANT – Observe all governing
codes and ordinances.
Note to installer – Be sure to leave these instructions
with the Consumer.
Note to consumer – Keep these instructions for future
reference.
Skill level – A licensed certified technician (to handle
refrigerant R-410A, recovery, etc) and a qualified
electrician are required for installation and service of
this split heat pump system.
Proper installation is the responsibility of the installer.
Product failure due to improper installation is not
covered under the limited warranty.
For personal safety, this system must be properly
grounded.
Protective devices (fuses or circuit breakers)
acceptable for installation are specified on the
nameplate of each unit.
Make sure to minimize wiring or plumbing inside the
wall when installing.
CAUTION
Aluminum building wiring may present special
problems - consult a qualified electrician.
When the unit is in the STOP position, there is still
voltage to the electrical controls.
Required Tools for Installation
14/4 AWG stranded wire
5/8” (16mm), 7/8” (22mm), 1” (25mm) or adjustable
wrench
R-410A refrigerant*
Adhesive tape
Conduit cable clamp ½”*
Copper line set (refer to indoor specification for line set
size)
#2 phillips screwdriver
Drill
R-410A flaring tool
Hex wrench
Hole saw 2 1/4
Insulation*
• Refrigerant scale
Level
Manifold gauge set
Measuring tape
Micron gauge
Mini-split adapter (5/16”F to 1/4”M)
Nitrogen*
Pipe cutter
PVC pipe (optional)
Razor knife
Reamer
Saddle clamp (L.S.) w/ screws
Sealant, non-expanding (for lineset hole)
Soap/water solution* or gas leakage detector
Stud finder
Torque wrench
Vacuum pump
Wire strippers
All usual and customary HVAC hand and power tools,
meters, and testing devices
* consumable
INSTALLATION INSTRUCTIONS
31-5000587 Rev. 1 5
ENGLISH
INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES
(Appearance may vary)
This picture is for reference only. Your product may look different. Read your manual before installation. Explain
the operation of the unit to the user according to this manual.
Wrap the insulation pipe with
÷ëèĤñìöëìñê÷äóèéõòð÷ëè
bottom to top.
Cut thermal insulation pipe to an
appropriate length and wrap it with tape,
making sure that no gap is left in the
insulation pipe’s cut line.
Arrangement of
piping directions
Condensate
piping must have a
downward slope of
at least 1/4” per foot
for proper drainage.
Rear Left
Rear Right
Right
Below
Left
More than 4 inches
More than 4 inches
LOW AMBIENT INSTALL
- If the outdoor unit is installed in a region that is affected by strong wind or snow accumulation, it is recommended
to install wind baffle or/and snow hood accessories. Corresponding snow hood and wind baffle model number can
be found in product catalog. The installation instructions can be found in the manual shipped with each accessory or
on-line at GEAppliancesairandwater.com.
SALTWATER COAST INSTALL
The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland
waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland
waterways, please follow the installation instruction below.
Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can
damage the outdoor unit.
If you cannot avoid installing the outdoor unit by the seashore, construct a
protection wall around it to block the sea breeze.
A protection wall should be constructed with a solid material to block the sea
breeze. The height and the width of the wall should be 1.5 times larger than the
size of the outdoor unit. Also, allow at least 28“ (700mm) between the protection
wall and the outdoor unit for air circulation to ventilate.
Install the outdoor unit in a place where water can drain freely.
If the above conditions cannot be met, contact Haier for assistance.
Protection Walls
Sea Breeze
Sea ODU
ODU
Sea Breeze
Sea
ODU
Sea Breeze
Sea ODU
ODU
631-5000587 Rev. 1
ENGLISH
Step 1 - Preparation
Select the Outdoor location:
Choose a level place solid enough to bear the weight
and vibration of the OD unit and where the operation
noise will not be amplified.
Choose a location where the hot air discharge and/or
noise will not create a nuisance for neighbors.
Ensure there is sufficient space to maneuver the OD
unit into place.
Ensure there is sufficient space and no obstructions
for the air inlet and outlet.
• I nstall the unit’s power/communication wiring at
least 10 feet away from television and radio sets to
prevent interference.
Ensure any moisture sensitive items are kept away
from the condensate drain path of the OD unit.
NOTES:
OD unit cannot hang from a ceiling or be stacked.
Ensure that accumulated snow and debris will not
block the air inlet or the coil if installing the outdoor
unit with a fence or guard rail around it.
Ensure ventilation in case of refrigerant leakage.
R-410A is a safe, nontoxic, and nonflammable
refrigerant.
Avoid installing the OD unit where corrosive gases,
such as sulfur oxides, ammonia, and sulfurous gas
are produced. Consult with an installation specialist
about using a corrosion-proof or anti-rust additive to
protect the unit coils.
INSTALLATION INSTRUCTIONS
(3) Installation and maintenance space
Selection of installation location of outdoor
Above
12(300)
Above 40 (1000)
Above
16(400) Above
16(400) Above
16(400)
Above16(400) Above16(400)
Above80(2000) Above12(300)
Above 40(1000)
Above 177(4500)
Above
24(600) If wall is half the height of the unit, 8 (250).
If wall is between half the height of the unit and
the same height of the unit, 12 (300)
If wall is half the height of the unit, 8 (250).
If wall is between half the height of the unit and the same
height of the unit, 12 (300)
31-5000587 Rev. 1 7
ENGLISH
INSTALLATION INSTRUCTIONS
B. Install the Mounting Plate
Remove plastic bag, tape, and mounting plate from
the back of the indoor unit.
Place the mounting plate on the wall in the
desired location taking into account the minimum
clearances necessary for proper operation.
Using a level, verify that the mounting plate is
horizontal and mark the screw locations.
Attach the mounting plate to the wall with the
supplied screws.
Wall anchors are supplied if not able to align all
screw holes with studs.
Be sure that the mounting plate has been attached
firmly and that applied weight is evenly distributed
by each screw. (At least one screw in wall stud,
others can use wall anchors.)
The piping for the indoor unit may be routed to and
from the unit in one of several directions: left, left
rear, right, right rear, or right below.
Knockouts are provided on the unit case for Left,
Right, and Right Below usage.
Step 2 - Installation of the Indoor Unit
A. Select the Indoor location:
Do not allow any heat or steam near the unit.
Select a location where there are no obstacles in
front of the unit.
Make sure that condensate drainage can be
conveniently routed away.
Do not install near a doorway.
Ensure that the space around the left and right
of the unit is more than 4”. The unit should be
installed as high on the wall as possible but allow a
minimum of 4” from the ceiling.
Use a stud finder to locate and mark stud locations
for mounting and to prevent unnecessary damage
to the wall.
Install in a location that is strong enough to
withstand the full weight and vibration of the unit.
Leave enough space to allow access for routine
maintenance.
Select a location that gives easy access to
removing and cleaning air filters.
Install in a location that is 3 ft. or more away from
other electrical appliances, such as televisions and
audio devices.
C. Install the Tubing
Measure and mark the location where the piping hole is
to be drilled.
Follow these steps to move the drain pipe if the pipe
location will be on the left side of the unit.
1. Remove the stopper in the left drain hole and knockout
the molded plug inside the port.
2. Transfer the corrugate drain hose from the right side to
the left side.
3. Insert stopper into right side drain port. Using soap as
a lubricant and a small screwdriver will allow for easier
seating of the stopper.
Drill the lineset hole using a 2 1/4” hole saw. Angle
the drill with a downward pitch to the outside wall so
that the outside wall hole will be at least a ¼” lower
than the inside hole. This allows for proper drainage of
condensate.
Install the lineset hole flange at the hole opening on the
inside wall.
NOTE: The flange is prescored. It may be necessary to
modify the flange to fit properly behind the wall unit housing.
831-5000587 Rev. 1
ENGLISH
F. Condensate Drainage Pipe
Verify the condensate drain line has a constant
pitch downward for proper water flow. There
should be no kinks or rises in the tubing which
may cause a trapping effect of the water (see
illustration).
Optional: Can use PVC pipe by connecting a 1” ID
PVC pipe to the drain line coming out of the wall
and running to desired location.
D. Electrical Connections for the Indoor Unit
NOTE: Be certain all wiring complies with local building
codes and NEC and that the supply voltage for this
system is correct.
Place the indoor unit on a solid work surface before
making electrical connections.
Both the outer plastic and inner galvanized steel
cover plates must be removed to make the electrical
connections for the indoor unit.
Raise the front cover to access the screws for
removing these covers.
Route the 14/4 AWG wiring through the slot in the
back of the unit and into the front access panel.
Using a wire stripper, remove the insulation and
separate the 4 wires.
Make wiring connections at each terminal according
to wiring diagram. Take note of the color of the wire
at each terminal and ensure the wires are connected
to the outdoor unit accordingly.
Ensure each wire is under the screw terminal plate
and the plate is tightened.
Ensure the 14/4 cable is secured under the strain
relief bracket.
After the terminal block wiring is completed, replace
both cover plates and lower the front casing.
mounting plate
Step 2 - Installation of the Indoor Unit (Cont.)
E. Mount Indoor Unit to Mounting Plate
Bundle the refrigerant piping, drain piping, and
wiring with tape and carefully rout the bundle
through the piping hole.
With the top of the indoor unit closer to the wall,
hang the indoor unit on the upper hooks of the
mounting plate. Slide the unit slightly side to side
to verify proper placement.
Rotate the lower portion of the indoor unit to the
mounting plate, and lower the unit onto the lower
hooks of the mounting plate. (see illustration)
Verify the unit is secured and flush to the wall.
Indoor Unit installation is finished at this time.
G. To Remove the Indoor Unit
Slightly raise the entire unit.
Pull the lower portion of the unit off the lower
hooks and pull slightly away from the wall.
Lift the upper portion of the unit off the upper
hooks.
It becomes
high midway. The gap with the
ground is too small There is the bad
smell from a sewer
It waves.
The end is imm-
ersed in water.
Less than
5cm
INSTALLATION INSTRUCTIONS
*NextGen Arctic Series
Outdoor unit
Power Wirin
g
3
2
1)
(C
L2
L1
Indoor unit
Control Wiring
4 Wire - 14 AWG
Stranded
1
2
3
=White
=Black
=Red
=Green
Sugested Colors
Strain Relief
Brackets
*Tempo 230V series
31-5000587 Rev. 1 9
ENGLISH
INSTALLATION INSTRUCTIONS
Wall Brackets
A cardboard template for the mounting plate is included with many of the indoor units. It serves as an easier way of
determining where to mount the wall bracket and where to cut the hole for piping.
NOTE: Some models may not have a cardboard template, in this case, a manual measurement is needed to determine the
piping hole location.
When mounting the unit, use a stud finder to secure the upper-most holes to the structure of the building. Use load rated
anchors to attach other portions of the bracket to the wall.
EXAMPLE
10 31-5000587 Rev. 1
ENGLISH
Step 3 - Installation of the Outdoor Unit
INSTALLATION INSTRUCTIONS
Proper Installation for Drainage
Set the unit on mount or pad using team lift.
Do not install the drain elbow if the unit is
located in an area where freezing can occur.
31-5000587 Rev. 1 11
ENGLISH
B. Prepare the Outdoor Unit for Installation
Remove all packaging.
Place supplied vibration pads onto outdoor unit’s
feet.
Attach the supplied drain elbow to the outdoor
unit if required. Connect extension piping as
needed (not supplied). (see illustration)
NOTE: The drain elbow is designed with an
air gap and will not sit flush to bottom of the
outdoor unit.
NOTE: 1U09AP*, 1U12AP*, 1U15AP*, 1U18AP*
and 1U24AP* models will not use a drain
elbow. A 3rd party pan is needed if condensate
management is required by code.
Remove the cover plate of the outdoor unit to
expose the terminal block connections.
C. Electrical Connections for the Outdoor Unit
WARNING RISK OF ELECTRIC SHOCK.
Could cause injury or death.
Make sure power is off before touching wires.
NOTE: Be certain all wiring complies with local
building codes and NEC and that the supply
voltage for this system is correct.
Connect the wiring for both the power source
and the indoor wiring using a conduit cable
bracket on the side of the outdoor unit.
Using a wire stripper, remove the insulation and
separate the wires.
Verify that the wiring connections match the
indoor connections wire for wire.
Ensure each wire is under the screw terminal
plate and the plate is tightened.
Ensure the 14/4 control cable is secured under
the strain relief bracket.
Verify that all connections are secured
1. Remove Screw 2. Slide the panel down to
release the clips and pull
away.
Step 3 - Installation of the Outdoor Unit
NOTE: Failure to follow the wiring guidelines can result in control board damage and communication issues (E7 error
code). This includes improper wire size, use of solid core wire, midline splicing and poor terminal connections.
INSTALLATION INSTRUCTIONS
Outdoor unit
Power Wirin
g
3
2
1)
(C
L2
L1
Indoor unit
Control Wiring
4 Wire - 14 AWG
Stranded
1
2
3
=White
=Black
=Red
=Green
Sugested Colors
Strain Relief
Brackets
*Tempo 230V series
*NextGen Arctic Series
12 31-5000587 Rev. 1
ENGLISH
Step 3 - Installation of the Outdoor Unit (Cont.)
D. Install Copper Lineset
The standard line set length is 25 feet. If
the installation length is different, adjust the
refrigerant charge by adding 0.2 oz/ft if the liquid
line is 1/4”, or 0.5 oz/ft if the liquid line is 3/8”.
Cut the line set to length.
Place nut over the pipe and then flare with the
R-410A flaring tool.
NOTE: Follow standard practices for creating
pipe flares. When cutting and reaming the
tubing, use caution to prevent dirt or debris from
entering the tubing. Remember to place nut over
the tubing before flaring.
To join the line set, directly align the tubing flare
to the fitting on the other pipe. Slide the nut
onto the fitting and hand tighten.
Torque the fittings according to the
specifications shown in the torque chart below.
Two wrenches are required
to join the flare connection;
one standard wrench and one
torque wrench adjusted to the
proper settings.
Repeat the process for
attaching the other end of the
line set.
E. Leak Test
Remove the cap on the service valve.
Using a tank of dry nitrogen and approved
regulator, charge the system with 150 psig of dry
nitrogen using mini split adapter to connect the
valve.
Check for leaks at the flare fittings using soap
bubbles or another detection device. If a leak
is detected, make repairs to the fittings and
recheck. If no leaks are detected within 3
minutes, proceed.
Using the same tank/regulator, charge the
system to 300 psig.
Check for leaks as earlier. If no leaks are
detected within 3 minutes, proceed.
Using the same tank/regulator, charge the
system to 500 psig.
Check for leaks as earlier. Keep system
pressurized for at least 20 minutes.
WARNING Do not use acetylene, oxygen,
compressed air or any mixture containing anything
other than dry nitrogen. Use only dry nitrogen for
pressure testing. Do not use mixtures of hydrogen
containing refrigerant and air above atmospheric
pressure for pressure testing, as they may become
flammable and could result in an explosion.
Refrigerant, when used as a trace gas, should only
be mixed with dry nitrogen for pressurizing units.
Failure to follow these recommendations could
result in death or serious injury as well as equipment
or property damage.
Half union Flare nut
Torque wrench
Spanner
INSTALLATION INSTRUCTIONS
Forced fastening without careful centering may
damage the threads and cause a refrigerant leak.
Pipe Diameter ( ø ) Fastening torque
1/4” 18N.m/13.3Ft.lbs
3/8” 42 N.m/30.1Ft.lbs
1/2” 55N.m/40.6Ft.lbs
5/8” 60 N.m/44.3Ft.lbs
31-5000587 Rev. 1 13
ENGLISH
F. System Evacuation
NOTE– Do not open service valve.
Attach a manifold gauge, micron gauge, and
vacuum pump to the suction line port using
adapter AD-87 (see illustration).
Evacuate the system to at least 350 microns.
Close the vacuum pump valve and check the
micron gauge. If the gauge rises 150 microns
in 60 seconds, the evacuation is incomplete
or there is a leak in the system. If the gauge
does not rise 150 microns in 60 seconds, the
evacuation is complete.
Once evacuation is complete, remove the
adapter and hose connection from the suction
line port and replaced the cap.
Step 3 - Installation of the Outdoor Unit (Cont.)
G. Refrigerant Charging
Add any additional refrigerant after evacuation
using a digital scale.
NOTE: Charge liquid only.
Fill out the refrigerant charge label using indelible
ink.
Place the factory refrigerant charge found on the
outdoor nameplate in box number 1.
Place the amount of additional refrigerant added
in box number 2.
Add boxes 1 and 2 together and place the value
in the sum box (D).
Adhere the filled out label in the proximity of the
product charging port and under the outside
units valve cover.
Write amounts on outdoor unit with permanent
marker above the charging port if the label is
missing.
Remove the cap from the liquid line valve. Using
a hex wrench, open the valve, then replace and
tighten the cap securly to avoid leaks.
Remove the cap from the suction line valve.
Using a hex wrench, open the valve, then replace
and tighten the cap securly to avoid leaks.
Wrap the line set, drain line, and 14/4 AWG wiring
starting at the bottom of the bundle with an
overlap type wrap until you reach the piping hole.
Use a sealant to seal the piping on both sides of
the wall in order to prevent drafts, weather, or
pests from entering the building.
This product contains fluorinated greenhouse
gases covered by the Kyoto Protocol. Do not vent
into the atmosphere.
Refrigerant type: R-410A
GWP* value: 2088
GWP = global warming potential
11+2= oz
R410A
2oz
2=
1=
B
C
D
FE
oz
A
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
INSTALLATION INSTRUCTIONS
14 31-5000587 Rev. 1
ENGLISH
Step 4 - Final Check
Check Items for Test Run
No gas leak from linesets?
Are the linesets insulated properly?
Are the connecting wirings of indoor and outdoor
firmly inserted to the terminal block?
Is the connecting wiring of indoor and outdoor
fixed?
Is condensate draining correctly?
Is the ground wire securely connected? Is the
indoor unit securely fixed?
Is power source voltage correct according to local
code?
Is there any odd noise?
Does the cooling temperature drop between
20-30°F?
Does the heating temperature raise between
35-40°F?
Is the room temperature display accurate?
Explaining Operation To the End User
Using the User Manual, explain to the user how to
use the air conditioner/heat pump, (the remote
controller, adding/removing the air filters, placing
or removing the remote controller from the remote
control holder, cleaning methods, precautions for
operation, etc.)
Review precautions for operation.
Recommend that the user read the Operating
Instructions carefully.
INSTALLATION INSTRUCTIONS
31-5000587 Rev. 1 15
ENGLISH
LIMITED WARRANTY
For The Period Of: Haier Will Replace:
5 year limited parts
warranty
From the date of the
original purchase
This Standard Base. Limited Warranty covers all defects in workmanship or material for the
mechanical and electrical parts (including the compressor) contained in the Product (“Defective
Parts”) for a period of 5 years from the Date of Purchase. GE Appliances will provide new or
refurbished parts, or a replacement for all or part of the unit, at its sole discretion, to your licensed
HVAC technician installer. This warranty also covers all defects in workmanship or material for the
unit controller for a period of 1 year. The remote controller is covered by 1-year accessory warranty.
The ductless system is covered by Standard Base Limited Warranty. GE Appliances will provide a
new or refurbished controller, at its sole discretion.
For the product models listed on Attachment 1 (the “Product”), this Standard Base Limited Warranty is provided to the Original
Owner of the Product:
Damage from improper service or installation.
Damage in shipping.
Defects other than manufacturing defects (i.e., other than
workmanship or materials).
Damage from misuse, abuse, accident, alteration, lack of proper
care and/or regular maintenance, or incorrect electrical voltage or
current.
Damage resulting from floods, fires, wind, lightning, accidents or
similar conditions.
Product that was not installed or serviced by a licensed HVAC
technician.
Labor and related services for repair or installation of the Product.
A product purchased from an unauthorized online retailer.
Damage as a result of subjecting Product to an atmosphere with
corrosives or high levels of particulates (such as soot, aerosols,
fumes, grease).
A Product sold and/or installed outside of the 50 United States, the
District of Columbia, or Canada.
Batteries for the controller and other accessories provided with
the Product for installation (e.g., plastic hose).
Normal maintenance, such as cleaning of coils, cleaning filters, and
lubrication.
For Product installed in non-owner occupied applications, Product
that has not been maintained annually by a licensed HVAC
technician (proof required).
Damage caused by a used or unapproved component or part by
GE Appliances, a Haier company (e.g., a used and/or unapproved
condenser / air handler).
Component or parts are not provided by GE Appliances, a Haier
Company
Product that has been moved from its original installation to a new
residence or building.
THIS WARRANTY DOES NOT COVER
Owner occupied: The “Original Owner” of this product means the original owner (and his or her spouse) of the residence where
the Product was originally installed. Non-owner occupied: The “Original Owner” of the Product means the original owner of
the building where the Product was originally installed, and for new construction, the purchaser of the building from the builder.
“Non-owner occupied” is defined as a a) single family or multi-family non-owner-occupied residential building, or b) non-
industrial commercial application, (such as office buildings, retail establishments, hotels/motels), but for non-owner-occupied
Original Owners, this limited warranty requires that the product be installed and maintained annually by a licensed HVAC
technician (proof of annual maintenance is required). Subject to the law of the state or province where the Product is installed,
the remainder of this Standard Base Warranty is transferable to subsequent owners of the residence or building.
WHO IS COVERED
The “Date of Purchase” is the date that the original installation is complete and all product start-up procedures have been
properly completed and verified by the installer’s invoice. Registration is strongly recommended. If the installation date cannot
be verified, then the Date of Purchase will be sixty (60) days after the manufacture date, as determined by the Product’s serial
number. You should keep and be able to provide your original sales receipt from the installer as proof of the Date of Purchase.
For new construction, the Date of Purchase will be the date of purchase of the residence by the Owner from the builder.
WHAT IS THE DATE OF PURCHASE
Contact your licensed HVAC technician installer. All installation and service must be performed by a licensed HVAC technician.
Failure to use a licensed HVAC technician for installation of this Product voids all warranty on this Product.
HOW CAN YOU GET SERVICE
The following components are not covered by this warranty: cabinets, cabinet pieces, air filters, driers, refrigerant, refrigerant line sets, belts,
wiring, fuses, oil nozzles, unit accessories and any parts not affecting unit operation.
EXCLUDED COMPONENTS
16 31-5000587 Rev. 1
ENGLISH
LIMITED WARRANTY
10 YEAR STANDARD REGISTERED LIMITED WARRANTY
ATTACHMENT 1
THIS LIMITED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
All “Indoor and Outdoor Products,” identified in Attachment 1, registered by the installer or the Original Owner within 60 days
of the Date of Purchase shall receive a Standard Registered Limited Warranty, which shall be identical to the Standard Base
Warranty, except that the Limited Parts Warranty shall be for a term of 10 Years. All Product not registered within 60 days of
the Date of Purchase shall be subject to the Standard Base Warranty. Some states and provinces do not allow warranty terms
to be subject to registration; in those states and provinces the longer terms for Limited Parts Warranty apply. Except in Texas
or where otherwise required by law, this Standard Registered Limited Warranty is not transferable to a subsequent purchaser
(other than the purchaser of a new building), but subsequent purchases will receive the remainder of the Standard Base
Warranty.
The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies. This warranty does not cover
incidental or consequential damages. Some states and provinces do not allow the exclusion of incidental or consequential
damages, so this limitation may not apply to you. Some states and provinces do not allow limitations on how long an implied
warranty lasts, so this limitation may not apply to you. This warranty gives you specific legal rights and you may also have other
rights which vary by state and province. This warranty covers units within the 50 United States, the District of Columbia and
Canada. This warranty it provided by GE Appliances a Haier company, Louisville, KY 40225.
The “Product” is defined as Haier brand and GE Appliances brand Ductless Split Units and Side-discharge Units. The “Product”
contains 2 sub-categories of goods: “Indoor and Outdoor Products” and “Selected Installation Products,” which are further
defined below: “Indoor and Outdoor Products” can further be identified by the following model number descriptions: 1U*,
2U*, 3U*, 4U*, 5U*, AB*, AD*, AL*, AM*, AW*, AF*, ASY*, USY*, ASH*, AUH*, UUC*, UUY*, “Selected Installation Products”,
identified by the following model number descriptions: PB-*, PAD-*.
31-5000587 Rev. 1 17
FRANÇAIS FRANÇAIS
Nous vous remercions de votre achat de ce produit Haier. Ce manuel
d’installation vous aidera à obtenir le meilleur rendement de votre
nouvelle unité.
Pour référence ultérieure, inscrivez les numéros de modèle et de série qui
figurent sur l'étiquette apposée sur le côté de votre thermopompe avec
la date de l’achat.
Brochez votre preuve d’achat sur ce manuel pour faciliter le service sous
garantie le cas échéant.
_______________________________________
Numéro de modèle
_______________________________________
Numéro de série
_______________________________________
Date de l'achat
Pour enregistrer votre nouveau système sans conduit Haier, allez sur
http://www.haierductless.com/product-registration
et saisissez les numéros de série et de modèle sur cette page. Pour
recevoir une garantie de 10 ans sur le compresseur et les pièces,
l’enregistrement est requis dans les 60 jours suivant l’installation.
CONSERVER DANS VOS DOSSIERS
TABLE DES MATIÈRES
CONSIGNES DE SÉCURITÉ IMPORTANTES ..............................................................................18
INSTRUCTIONS D’INSTALLATION ......................................................................................19
Étape 1 - Préparation ...............................................................................................21
Étape 2 - Installation de l’unité intérieure ............................................................................22
Étape 3 - Installation de l’unité extérieure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ŭ÷äóè$¡߯õìĤæä÷ìòñĤñäïè .........................................................................................29
GARANTIE LIMITÉE ..................................................................................................... 30
18 31-5000587 Rev. 1
FRANÇAIS
AVERTISSEMENT Pour votre sécurité, les renseignements dans ce manuel doivent être observés afin de minimiser le risque
d’incendie, de décharge électrique ou de blessure.
Utilisez cet équipement uniquement aux fins auxquelles il est fait
mention dans ce manuel d’utilisation.
Avant son utilisation, ce climatiseur doit être installé
correctement en conformité avec les instructions d’installation.
Tout le câblage doit présenter des valeurs nominales compatibles
avec l’alimentation électrique spécifiée sur la plaque signalétique.
Utilisez seulement du fil de cuivre.
Toute la partie électrique de l’installation doit être exécutée
par un électricien agréé selon les codes de l’électricité local et
national.
Toute réparation doit être effectuée par une personne qualifiée.
Tous les climatiseurs contiennent un frigorigène qu’il faut retirer
avant de disposer du produit en vertu de la loi fédérale. Si vous
vous débarrassez d’un produit qui contient un frigorigène,
informez-vous auprès de l’organisme responsable d’en disposer.
Ces systèmes de climatisation R-410A exigent que les
entrepreneurs et les techniciens utilisent des outils, des
équipements et des normes de sécurité approuvés pour ce type
de frigorigène. N’utilisez PAS un équipement certifié pour le
frigorigène R22 seulement.
AVERTISSEMENT
RISQUE DE CHOC ÉLECTRIQUE. Peut occasionner une blessure ou la mort.
Une mise à la terre est essentielle avant de brancher l’alimentation
électrique.
Coupez l’alimentation électrique à la source avant de procéder à
une réparation ou un entretien.
Réparez ou remplacez immédiatement tout câblage électrique usé
ou autrement endommagé. N’utilisez pas un câblage qui présente
des fissures ou des marques d’abrasion sur sa longueur ou l’une de
ses extrémités.
AVERTISSEMENT
RISQUE D’INCENDIE. Peut occasionner une blessure ou la mort.
Abstenez-vous d’entreposer ou d’utiliser des matières
combustibles, de l’essence ou d’autres vapeurs ou liquides
inflammables à proximité de cet appareil ou de tout autre.
LISEZ ET CONSERVEZ CES INSTRUCTIONS
Si une réparation exige de pénétrer dans le système
de frigorigène étanche, la réglementation fédérale
impose de faire réaliser le travail par un technicien de
Classe II ou détenant une certification universelle.
CONSIGNES DE SÉCURITÉ IMPORTANTES
AVERTISSEMENT
- Ce produit n’est pas destiné à être utilisé par des personnes (y compris des enfants) dont les capacités physiques, sensorielles ou
mentales sont réduites, ou qui manquent d’expérience et de connaissances, à moins qu’elles n’aient reçu une surveillance ou des
instructions concernant l’utilisation de l’appareil par une personne responsable de leur sécurité.
- Les enfants doivent être surveillés afin qu’ils ne jouent pas avec ce produit
- Assurez-vous que l’appareil est installé conformément aux codes de câblage électrique locaux et nationau.
- Assurez-vous que les dimensions d’espacement nécessaires pour l’installation adéquate de l’appareil respectent les distances
minimales requises aux structures adjacentes.
- Assurez-vous que seuls les appareils approuvés sont raccordés ensemble et que les dimensions de toutes les conduites de
frigorigène ainsi que les exigences de charge de frigorigène sont respectées pour éviter une surcharge de la pression de service.
- Raccordez SEULEMENT les appareils comportant une étiquette de frigorigène identique.
- Tout dommage d’alimentation électrique doit être remplacé par le fabricant, son agent gestionnaire ou des personnes possédant une
qualification semblable pour éviter les risques.
31-5000587 Rev. 1 19
FRANÇAIS
POUR OBTENIR DE LAIDE SUPPLÉMENTAIRE, VISITEZ HAIERAPPLIANCES.COM OU COMMUNIQUEZ AVEC
LASSISTANCE AU CONSOMMATEUR AU 877-337-3639.
AVANT DE COMMENCER
Veuillez lire toutes ces instructions attentivement.
IMPORTANT – Conservez ces instructions
à l’usage de l’inspecteur local.
IMPORTANT – Observez tous les codes et
ordonnances en vigueur.
Note à l’installateur – Assurez-vous de laisser ces
instructions au consommateur.
Note au consommateur - Conservez ces instructions pour
référence ultérieure.
Temps d’exécution – Environ 3 heures.
L’exactitude de l’installation est la responsabilité de
l’installateur.
La garantie ne couvre pas les défectuosités du produit
causées par une installation inadéquate.
Pour votre sécurité, ce produit doit être correctement mis à
la terre.
Les dispositifs de protection (fusibles ou disjoncteurs)
admissibles pour l’installation sont spécifiés sur la plaque
signalétique de chaque unité.
. • Si une réparation exige de pénétrer dans le système de
frigorigène étanche, la réglementation fédérale impose
de faire réaliser le travail par un technicien de Classe II ou
détenant une certification universelle.
ATTENTION
N’utilisez pas un cordon de rallonge avec ce système.
Le câblage de bâtiment en aluminium peut présenter des
problèmes particuliers, veuillez consulter un électricien agréé.
Outils nécessaires pour l’installation
OUTILS DONT VOUS AUREZ BESOIN
• Fil torsadé 14/4
• 5/8» (16mm), 7/8» (22mm), 1» (25mm) ou clé réglable
• Frigorigène R-410A*
• Ruban adhésif*
• Bride de câble de conduit ½ po*
Tuyauterie en cuivre (consultez les spécifications d’intérieur
pour connaître la dimension de conduit)
• Tournevis à tête cruciforme no 2
• Perceuse
• Outil à évaser R-410A°
• Clé hexagonale
• Scie-cloche 2 1/4 po
• Isolant*
• Balance de réfrigérant
• Niveau
• Manomètre de pression d’admission définir
• Ruban à mesurer
• Microvacuomètre
• Adaptateur « mini-split » (5/16 po F à 1/4 po M)
• Azote*
• Coupe-tube
• Tube PVC (facultatif)
• Couteau utilitaire
• Alésoir
• Bride de tube (L.S.) et vis
• Scellant, non expansif (pour orifice de tuyauterie)
• Solution d’eau savonneuse* ou détecteur de fuite de gaz
• Localisateur de montants
• Clé dynamométrique
• Pompe à vide
• Pinces à dénuder
• Tous les outils, les appareils de mesure et les appareils d’essai
HVAC habituels et usuels
* consommables
INSTRUCTIONS D'INSTALLATION
20 31-5000587 Rev. 1
FRANÇAIS
INSTRUCTIONS D'INSTALLATION
DÉGAGEMENTS MINIMAUX
(L’aspect peut varier)
Cette illustration est pour référence seulement. Laspect de votre produit peut être différent. Lisez votre manuel avant l’installation.
Expliquez le fonctionnement de l’appareil à l’utilisateur selon ce manuel.
Plus de 4 pouces
Directions des
tuyauteries
Arrière gauche
Arrière droite
droite
Dessous
gauche
Plus de 4 pouces
Envelopper le tuyau
d’isolation avec du ruban
definition de bas en haut. Le tuyau de
condensat doit avoir
une inclinaison vers
le bas d’au moins
1/4 po par pied pour
une évacuation
appropriée.
Couper le tuyau d’isolant thermique à une
longueur appropriée et l’envelopper avec du
ruban, en s’assurant qu’aucun espace n’est laissé
dans la ligne de coupe du tuyau d’isolation.
INSTALLATION POUR LITTORAL SALIN
L’unité extérieure doit être installée à un minimum de 1/2 mille (0,8 km) d’un plan d’eau salée telle que bord de mer et voies
navigables intérieures. Si l’unité est installée entre 1/2 mille et 5 milles (0,8 et 8 km) d’un plan d’eau salée (y compris bord de mer et
voies navigables intérieures), alors veuillez suivre les instructions d’installation ci-dessous).
Installez l’unité intérieure à un endroit (p.ex. près de bâtiments, etc.) où elle peut être protégée de la brise marine qui peut
l’endommager.
Si vous ne pouvez pas éviter d’installer l’unité extérieure en bord de mer, construisez un mur de protection autour d’elle afin de
bloquer la brise marine.
Le mur de protection doit être composé d’un matériau solide tel que le béton afin
de bloquer la brise marine. La hauteur et la largeur du mur doivent être 1,5fois
plus importantes que celles de l’unité extérieure. Allouez au moins 28 po (700
mm) entre le mur de protection et l’unité extérieure pour la ventilation de l’air
d’évacuation.
Installez l’unité extérieure à un endroit où l’eau peut s’évacuer en douceur.
Si les conditions ci-dessus ne peuvent pas être respectées, contactez Haier pour
de l’assistance.
Murs de protection Unité ext.
Unité ext.
Brise marine
Mer
Unité ext.
Unité ext.
Unité ext.
Brise marine Brise marine
Mer
Mer
INSTALLATION DANS UN CLIMAT FROID
- Si une unité extérieure est installée dans une région qui est affectée par des vents forts ou une accumulation de neige, il est
recommandé d’installer une bâche coupe-vent et/ou un capot de protection contre la neige. Le numéro de modèle correspondant
au capot de protection contre la neige et à la bâche coupe-vent se trouve dans le catalogue de produits. Il est possible de trouver les
instructions d’installation dans le manuel expédié avec chaque accessoire ou en ligne au GEAppliancesairandwater.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

GE AW15ES2VHB Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation

dans d''autres langues