Input Configurations 1 Phase, 2 wire
1 or 2 Phase, 3 wire
Supply Voltage Range
(L1 or L2 to Neutral)
Min. 102 VAC Max. 138 VAC
Maximum Input Power 8 VA
Maximum Rated Current
1
220 A primary for 200 A models
110 A primary for 100 A models
0.11 A secondary for 0.1 A secondary models
0.22 A secondary for 0.2 A secondary models
Line Frequency 50-60 Hz
Power Factor Range 0.5 to 1.0, leading or lagging
Accuracy +/- 0.5% of registration @ 1.0pf. 2 to 200 A
+/- 0.75% of registration @ 0.5pf, 2 to 200 A
Operating Temperature Range -30 to +70 degrees C
Rated Pollution Degree
2
2
Rated Relative Humidity 80%
Branch Fuse Holder
Klemsan ASK2 or equiv.
500 V, 6.3 A, 6 mm2
Branch Fuses
Large/XL Enclosure: Littlefuse, Inc.
0235003.HXP or equiv.
Medium Enclosure: Littlefuse, Inc.
0235001.HXP or equiv.
250 V, 3 A, fast acting, short time lag
250 V, 1 A, fast acting, short time lag
Terminal Blocks Mini Meter
Dinkle/International Connector
EK508-11P or equiv.
MMU: Molex 0387800105 or Cinch Barrier
Block Series 141 or equiv.
4.4 in-lb of torque maximum
12 in-lb of torque maximum
3 TECHNICAL SPECIFICATIONS
8
Table 1 - Electrical and Environmental Specifications
1
Product approved for use with included Leviton Current Transformers, as follows:
• 200A:
Part Numbers CDA02-x12 (CDA02-B12, CDA02-R12, CDA02-L12, CDA02-212,
CDA02-312) for Solid Core, 0.72" Diameter CTs or CTD02-K16 for Split Core 1" CTs
• 100A:
Part Numbers CDA01-x12 (CDA01-B12, CDA01-R12, CDA01-L12, CDA01-212,
CDA01-312) for Solid Core, 0.72" Diameter CTs or CTD01-K16 for Split Core 1" CTs
2
Pollution Degree 2: normally only non-conductive pollution occurs. Occasionally, however,
a temporary conductivity caused by condensation must be expected.
3.2 Electrical and Environmental Specifications
Mini Meters fall under UL Circuit Category III: a device for measurements performed
in the building installation. The electrical and environmental specifications for Mini
Meters are given in the table below