Samlexpower SEC-2440UL Le manuel du propriétaire

Catégorie
Chargeurs de batterie
Taper
Le manuel du propriétaire
OWNER'S
MANUAL
Please read this
manual BEFORE
operating your
battery charger
Switch Mode,
Automatic, Lead
Acid Battery
Charger
MODELS:
SEC-1280UL
SEC-2440UL
2 | SAMLEX AMERICA INC.
OWNER'S MANUAL: Battery Chargers | Index
SECTION 1: Important Safety Precautions ...................................... 3
SECTION 2: Description & Features ................................................ 6
SECTION 3: Layout .........................................................................7
SECTION 4: Principles of Operation ...............................................8
SECTION 5: Protections ................................................................ 16
SECTION 6: Installation ................................................................18
SECTION 7: Preparing the Charger for Operation ........................20
SECTION 8: Operation ................................................................ 27
SECTION 9: Troubleshooting ........................................................ 29
SECTION 10: Internal Fuse Ratings .................................................30
SECTION 12: Specications ............................................................ 31
SECTION 13: Warranty ................................................................... 35
Disclaimer of Liability
UNLESS SPECIFICALLY AGREED TO IN WRITING, SAMLEX AMERICA INC.:
1. MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
2. ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF
ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK.
Samlex America reserves the right to revise this document and to periodically make changes to the content
hereof without obligation or organization of such revisions or changes.
Copyright Notice/Notice of Copyright
Copyright © 2020 by Samlex America Inc. All rights reserved. Permission to copy, distribute and/or modify this
document is prohibited without express written permission by Samlex America Inc.
2 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 3
SECTION 1 | Important Safety Precautions
SAVE THESE INSTRUCTIONS. This manual contains important safety and operating
instructions.
The following safety symbols will be used in this manual to highlight safety
and information:
WARNING!
Indicates possibility of physical harm to the user in case of non-compliance.
!
CAUTION!
Indicates possibility of damage to the equipment in case of non-compliance.
i
INFO
Indicates useful supplemental information.
Hazardous conditions may result if the charger is not installed or operated correctly.
Please read the following instructions to prevent personal injury or damage to the
charger.
1.1 BATTERY RELATED
• Working in the vicinity of a Lead-acid battery is dangerous. Batteries generate explo-
sive gases during normal battery operation. For this reason it is of the utmost impor-
tance that each time before using your charger, you read and follow the instructions
provided exactly.
• To reduce risk of battery explosion, follow these instructions and those marked on the
battery.
• Never smoke or allow an open spark or ame in the vicinity of the battery or engine.
• Use charger for charging a Lead-acid battery only. It is not intended to supply power
to an extra low voltage electrical system or to charge dry-cell batteries. Charging
dry-cell batteries may cause them to burst and cause injury to persons and damage to
property.
• Never charge a frozen battery
• If it is necessary to remove battery from vehicle to charge it, always remove grounded
terminal from battery rst. Make sure all accessories in the vehicle are off in order to
prevent an arc.
• Study all battery manufacturer's specic precautions such as removing or not remov-
ing cell caps while charging and recommended rates of charge.
4 | SAMLEX AMERICA INC.
• For a charger having an output voltage selector switch, refer to the car owner's
manual in order to determine the voltage of the battery and to make sure the output
voltage is set at the correct voltage. If an output voltage selector switch is not pro-
vided, do not use the battery chargner unless the battery voltage matches the output
voltage rating of the charger.
• Never place the charger directly above or below the battery being charged; gases or
uids from the battery will corrode and damage the charger. Locate the charger as far
away from the battery as DC cables permit
• Do not operate charger in a closed-in area or restrict ventilation in any way
• Connect and disconnect DC output clips only after setting any charger switches to the
off position and removing AC cord from the electric outlet. Never allow clips to touch
each other
• Follow these steps when battery is installed in vehicle. A spark near battery may cause
a battery explosion. To reduce risk of a spark near battery:
(i) Position AC and DC cords to reduce risk of damage by hood, door, or moving
engine part;
(ii) Stay clear of fan blades, belts, pulleys, and other parts that can cause injury to
persons;
(iii) Check polarity of battery posts. A Positive (POS, P, +) battery post usually has a
larger diameter than a Negative (NEG, N, –) post;
(iv) Determine which post of battery is grounded (connected) to the chassis. If Nega-
tive post is grounded to chassis (as in most vehicles), see item (v). If Positive post is
grounded to the chassis, see item (vi);
(v) For a Negative-grounded vehicle, connect the Positive (Red) clip from battery
charger to positive (POS, P, +) undergrounded post of battery. Connect the Nega-
tive (Black) clip to vehicle or engine block away from battery. Do not connect clip to
carburetor, fuel lines, or sheet-metal body parts. Connect to a heavy gauge metal
part of the frame or engine block.
(vi) For a Positive-grounded vehicle, connect the Negative (Black) clip from battery
charger to negative (NEG, N, –) ungrounded post of battery. Connect the Positive
(Red) clip to vehicle chassis or engine block away from battery. Do not connect
clip to carburetor, fuel lines, or sheet-metal body parts. Connect to a heavy gauge
metal part of the frame or engine block;
(vii) Connect charger AC supply cord to electric outlet; and
(viii) When disconnecting charger, turn switches to off, disconnect AC cord, remove
clip from vehicle chassis, and then remove clip from battery terminal.
• Follow these steps when battery is outside vehicle. A spark near battery may cause a
battery explosion. To reduce risk of a spark near battery:
(i) Check polarity of battery posts. A Positive (POS, P, +) battery post usually has a
larger diameter than a Negative (NEG, N, –) post;
SECTION 1 | Important Safety Precautions
4 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 5
(ii) Attach at least a 60cm 6-gauge (AWG) insulated battery cable to a Negative (NEG,
N, –) battery post;
(iii) Connect the Positive (Red) charger clip to the positive (POS, P, +) post of battery;
(iv) Position yourself and the free end of cable as far away from battery as possible,
then connect the Negative (Black) charger clip to free end of cable;
(v) Do not face battery when making nal connection;
(vi) Connect charger AC supply cord to electrical outlet; and
(vii) When disconnecting charger, always do so in reverse sequence of connecting
procedure and break rst connection while standing as far away from battery as
practical
1.2 CHARGER RELATED
• The maximum Ah capacities of the batteries must be limited as follows:
- SEC-1280UL: 800 Ah
- SEC-2440UL: 400 Ah
• Do not operate the charger in a closed-in area or restrict ventilation in any way.
Install in a well ventilated, cool, dry place.
• The charger must not be operated in a damp or wet environment. When mounting
in a boat, make sure it is not subjected to bilge water splash.
• Do not block the ventilation openings / openings for the cooling fan. There should
be at least 6 inches clearance all around the unit.
• Installation and wiring must comply with the local and the National Electrical Codes. It
is recommended that installation may be carried out by a certied electrician.
• Wrong installation on a boat may lead to corrosion of the boat. It is recommended
that installation on the boat must be carried out by a boat electrician.
• Disconnect the AC input power to the charger before connecting / disconnecting the
batteries or other DC loads or when working on the charger.
• Disconnect the AC input power before changing the setting of the Dip Switches.
• The chassis of the charger is connected to the Earth Ground Pin of the power cord
plug. Ensure that the Earth Ground Pin of AC receptacle feeding the charger is
connected to Earth Ground.
• Do not use an adapter. If a grounding type of receptacle is not available, do not use
this charger until proper outlet is installed by a qualied electrician.
• Do not operate the charger if the power cord is damaged.
SECTION 1 | Important Safety Precautions
6 | SAMLEX AMERICA INC.
SECTION 2 | Description & Features
2.1 GENERAL INFORMATION
SEC-1280UL (for 12V batteries) and SEC-2440UL (for 24V batteries) are high current, tem-
perature compensated 3 Stage Chargers that deliver Bulk Stage Currents of 80A and 40A
respectively ensuring a very fast, safe and complete charging of Lead Acid batteries. These
chargers can also be used as a Power Supply (Section 8.3) or as a DC UPS (Section 8.4).
2.2 FEATURES
• State-of-the-art Switch Mode Technology for high efciency, light-weight and quiet
operation.
• User congurable AC input voltage – 120 VAC or 230 VAC, 50 / 60 Hz
• Automatic operation for all types of Lead Acid Batteries - Flooded, AGM or Gel Cell
• User selectable 2 or 3-Stage automatic charging algorithm with timed Absorption
Stage and temperature compensation ensures rapid, safe and full return of capacity
for stand-alone and loaded batteries.
• Ability to reduce maximum charging current to approximately 1/2 of the rated capac-
ity during “Half Power Mode”. This allows safe charging of lower capacity batteries.
• Includes a Battery Temperature Sensor allowing temperature compensated charging,
if required.
• 2 banks of batteries can be charged simultaneously without the use of an external
battery isolator. The charging current will be shared between the two banks depend-
ing upon the depth of discharge of the connected batteries.
• Voltmeter and Ammeter for monitoring
• Fan cooled - fan ON/OFF based on output current.
• Protections against short circuit, over current, reverse battery connection and
over-temperature.
• Can be used as a power supply or as a DC UPS (Uninterruptible Power Supply)
when used in conjunction with a battery.
• Optional Remote LED Panel Model 900-RC with 10 Meters of wire for remote
ON/OFF control and indication of charging status.
• Conforms to UL Standard 1564 and certied to CSA STD. C22.2 No.107-2
• EMI compliant to FCC Part 15(B), Class B
2.3 MAXIMUM Ah CAPACITY OF BATTERY TO BE CHARGED
If the chargers are used to charge very high capacity batteries, they will be forced to sup-
ply their maximum rated charging current for longer time than the designed limit and
hence, the components will be overstressed and are likely to fail prematurely. To prevent
premature failure, the maximum Ah capacities of the batteries must be limited as follows:
- SEC-1280UL: 800 Ah
- SEC-2440UL: 400 Ah
6 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 7
SECTION 3 | Layout
NOTE: Both SEC-1280UL and SEC-2440UL have the same layout and dimensions
4 5 6 7 8
3 2 1
9
1
0
11
OUTPUT SIDE
INPUT SIDE
14B14A
12
13
LEGEND
1. Output Connector: +, Bank 1
2. Output Connector: +, Bank 2
3. Output Connector: , Common
4. Jack for Temperature Sensor Plug (14B)
5. Green LED: Indicates “Half Power
Mode” is ON
6. Jack for optional Remote LED
Panel Model No. 900-RC
7. DIP switches S1 to S4 for mode selection
8. Push Switch for Half Power Mode:
Pressed ON; Released OFF
9. Power ON/OFF switch
10. AC power cord with 15A NEMA5-20 Plug
11. Grill protected opening for
cooling fan
12. Voltmeter
13. Ammeter
14. Battery Temperature Sensor Model No. TF-500
with 5m cable
14A. Adhesive backed sensor (attach to battery
container wall)
14B. 3.5mm Plug (insert into Jack 4)
TOP VIEW
3
2
1
14
11
10
<
SEC-1280UL: 0-15V
SEC-2440UL: 0-30V
• Hole: 5/16” Dia.
• Set Screw:
5/16” x 24 TPI
<
SEC-1280UL: 0-80A
SEC-2440UL: 0-50A
NOTE: Meters shown are for SEC-1280UL
Fig. 3 Layout of SEC-1280UL and SEC-2440UL
8 | SAMLEX AMERICA INC.
SECTION 4 | Principles of Operation
i
INFO
For complete understanding of working of battery chargers, understanding of
operation of Lead Acid batteries is desirable.
For detailed information on construction, working and application of batteries,
please refer to White Paper titled "Batteries, Chargers and Alternators" at the
following link to Samlex America, Inc. website:
www.samlexamerica.com/support/whitepapers.aspx
4.1 SWITCH MODE POWER SUPPLY (SMPS) CHARGER
This unit is a Switched Mode Power Supply (SMPS) and charger that converts 120 / 230
VAC, 50 / 60 Hz to regulated DC voltages and limits the maximum output current equal
to the rated Bulk Stage Current (Current Limit Value) as shown in Table 4.1.
TABLE 4.1 CHARGING STAGE VOLTAGES AND CURRENTS
Model No.
Bulk Stage
Current
(Current
Limit Value)
Constant
Voltage in
Bulk Stage
Constant
Voltage in
Absorption
Stage
Constant
Voltage
in Float
Stage
Terminal
Voltage at
No Load
(See Table 4.2)
SEC-1280UL 80A 13.5 VDC
14.0 VDC or
14.4 VDC
13.5 VDC
13.7V to
13.8V
SEC-2440UL 40A 27 VDC
28 .0 VDC
or 28.8 VDC
27 VDC
27.2V to
27.3V
The specied output voltage of the charger during particular charging stage is held
constant till the Bulk Stage Current value is reached. When the battery or DC load tries
to draw current > the Bulk Stage Current value (80A for SEC-1280UL & 40A for SEC-
2440UL), the charger limits the current to the Bulk Stage Current value and the output
voltage of the charger drops and is no longer constant. When the charger is charging a
battery at current = the Bulk Stage Current, it will be in current limit condition and the
terminal voltage of the charger will drop but will be clamped to the actual lower intrin-
sic terminal voltage of the battery relative to its Stage of Charge at that time.
8 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 9
SECTION 4 | Principles of Operation
4.2 BATTERY IMPEDANCE AND CHARGING CURRENT
The internal impedance of a healthy battery is very low - in tens of milli Ohms. The
impedance is higher in discharged condition. Average impedance may be assumed as 20
milli Ohm or 0.02 Ohm.
When the charger is delivering a constant voltage under Absorption/ Float Stages (is
supplying current < its Bulk Stage Current value), the charging current drawn by the bat-
tery can be roughly calculated as follows:
Charging current = (Charger Voltage - Intrinsic battery voltage) ÷ Internal resistance (0.02 Ohm)
For example, when SEC-1280UL is in the Bulk Charge Stage 1 (Fig 4.1), its output voltage
is set at 13.5 VDC. When a battery discharged to say 10.5V is charged, it will try to draw
very large current = (13.5V - 10.5V) ÷ Internal resistance (0.02 Ω) = 150A. SEC-1280UL
will, however, limit this current to 80A.
4.3 CHARGING STAGES AND CHARGING CURVES
These chargers are designed to provide the following 3-Stage / 2-Stage charging algo-
rithms for Lead Acid Batteries (Flooded / AGM / Gel Cell types)
3-Stage Charging Algorithm: Bulk Stage " absorption Stage " Float Stage for Lead
Acid Batteries
2-Stage Charging Algorithm: Bulk Stage " Float Stage. When 2-Stage Charging
Algorithm is selected (Section 7.4), the Absorption Stage of the 3-Stage Charging
Algorithm is bypassed. This algorithm is suitable for operation as a Power Supply
(Section 8.3) or as a DC UPS (Uninterruptible Power Supply) in conjunction with a
battery (Section 8.4)
The type of Lead Acid Battery and the desired charging algorithm can be selected with
the help of DIP Switches S1 and S2 (7 in Fig 3). For details, please refer to Sections 7.4
Charging Curves for 3-Stage Charging Algorithm are given at Fig 4.1 for SEC-1280UL and
at Fig 4.2 for SEC-2440UL
Details of the 3 stages of charging operation are explained at Sections 4.3.1 to 4.3.3
10 | SAMLEX AMERICA INC.
SECTION 4 | Principles of Operation
(i) 4-Hr/ 8-Hr Timer runs out (Section 7.5) OR,
(ii) Current reduces to 10% of Bulk Stage
Current i.e. 8A+/-0.5A
NOTE: Please see “NOTES” for Fig 4.2
Voltage
curve
Voltage Curve shows voltage
at the Output Connectors
(Battery Connected)
Current Curve shows output
current
Current curve
80% of
current
capacity
of charger
(64 Amps)
Time, Hours
14.4V
13.5V
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
AMPS VOLTS
80A
64A
Stage 1
“Bulk Stage”
Stage 2 “Absorption Stage”
Start of Absorption Stage (See Section 4.3.2) and
Absorption Stage Timer (See Section 7.5)
Level
2
Stage 3
“Float Stage”
B1 C1
D1
E1
B2 C2 D2
E2
A1
A2
Level
1
100
80
60
40
20
10
Figure 4.1 Charging Curve - SEC-1280UL
28.8V
27V
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
B1 C1
D1
E1
B2 C2 D2
E2
40A
32A
A1
A2
Voltage
curve
Current curve
80% of
current
capacity
of charger
(32A)
AMPS VOLTS
Start of Absorption Stage (See Section 4.3.2) and
Absorption Stage Timer (See Section 7.5)
Voltage Curve shows voltage
at the Output Connectors
(Battery Connected)
Current Curve shows output
current
Time, Hours
NOTE: Please see “NOTES” for Fig 4.2
Stage 1
“Bulk Stage”
Stage 2 “Absorption Stage”
Level
2
Stage 3
“Float Stage”
Level
1
(i) 4-Hr/ 8-Hr Timer runs out (Section 7.5) OR,
(ii) Current reduces to 10% of Bulk Stage
Current i.e. 4A+/-0.5A
50
40
30
20
10
0
Fig. 4.2 Charging Curve for SEC-2440UL
10 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 11
SECTION 4 | Principles of Operation
NOTES FOR FIGS 4.1 & 4.2
Please note the following important information related to the Charging Curves
shown in Figs 4.1 and 4.2 above:
1. Terminal Voltage reading at charger Output Connectors on no load and on load:
(a) The Output Connectors of the charger consist of one common Negative Con-
nector (3, Fig 3) and two Red Positive Connectors (1, 2 in Fig 3) for charging
two banks of batteries. Each of the two Positive Connectors of the two banks
has Schottky Diodes in series for isolation. These isolating Schottky Diodes have
a current dependent forward voltage drop "Vf" ranging from 0.2 to 0.3V (at
0.1A) to 0.8V (at 80A). In addition, there will be additional forward drop "Vb"
across the bulk resistance of the Schottky Diodes and this drop will also increase
with increase in charging current. Please note that the forward voltage drops
"Vf" and "Vb" occur only when current ows through the Schottky Diode i.e.
when the charger is supplying current to the battery / load.
(b) The Float and Absorption voltages are tightly regulated before the isolating
Schottky Diodes. However, the voltages available at the terminals of the two
banks will vary with the value of the charging current because of the current
dependent forward voltage drop "Vf" and bulk resistance drop "Vb" of the
Schottky Diodes. The Float Voltage before the Schottky Diodes is, therefore,
set 0.2 to 0.3V higher to compensate for the forward drops during Float Stage
when the charging current would have dropped to less than 1A. Hence, the
output voltage at the Output Connectors of the two banks at no load (nothing
connected to the Connectors of the banks) will read 0.2 to 0.5V higher than the
Float Voltage of 13.5 / 27.0V because there is no forward voltage drop as there
is no current ow through the Schottky Diodes. The voltages are specied with
respect to charging / load current as follows:
Table 4.2 Terminal Voltages
Charging Stage Output Voltage Output Current
Absorption Stage - SEC-1280UL 14.4 / 14V for SEC-1280UL At 5A +/- 0.5A
Absorption Stage - SEC-2440UL 28.8 / 28V for SEC-2440UL At 3A +/- 0.5A
Float Stage - SEC-1280UL 13.5V At 0.1A
Float Stage - SEC-2440UL 27.0V At 0.1A
Open Circuit - SEC-1280UL 13.7 to 14.0V At 0A
Open Circuit - SEC-2440UL 27.2 to 27.5V At 0A
Bulk Stage - SEC-1280UL 13.5V (Internal voltage of charger) 70 - 80A
Bulk Stage - SEC-2440UL 27.0V (Internal voltage of charger) 35 - 40A
12 | SAMLEX AMERICA INC.
SECTION 4 | Principles of Operation
(c) Please also note that the output voltage at the two banks may differ between
0.2 to 0.8V depending upon the different values of the charging current being
delivered through each as a result of different values of voltage drops Vf and Vb
across the isolating Schottky Diodes.
2. Standard Temperature Conditions: The charging voltages shown pertain to bat-
tery electrolyte temperature of 77°F (25°C)
3. Charger / Battery Voltage / Current Values:
(a) During Constant Current "Stage 1 - Bulk Stage" (See Section 4.3.1), the output
voltage of the charger will be clamped to the actual battery voltage corre-
sponding to the intrinsic (internal) State of Charge of the battery. However,
during (i) Constant Voltage "Stage 2 - Absorption Stage" (Section 4.3.2) and (ii)
Constant Voltage "Stage 3 - Float Stage" (Section 4.3.3), the charger will output
constant voltage. During these stages, the intrinsic (internal) voltage of the bat-
tery will be lower than the rated Absorption and Float Voltages of the charger
and the charging current will taper down as the Stage of Charge of the battery
rises under constant voltage charging.
(b) The voltage curve shows the voltage at the charger Output Connectors, which
will be the same as the voltage at the battery terminals (assuming that there is
no voltage drop along the wires connecting the charger to the batteries)
(c) The Current Curve shows the current being drawn by the battery
4.3.1 Stage 1 - Bulk Stage
4.3.1.1 The Bulk Stage is a Constant Current Stage where the battery is charged at “Bulk
Stage Current” rating of (i) 80A for SEC-1280UL or, (ii) 40A for SEC-2440UL. During this
stage, the charger’s open circuit voltage will be (i) 13.5V for SEC-1280UL or, (ii) 27.0V for
SEC-2440UL. However, when discharged battery is connected and charging is initiated
under this stage, the terminal voltage of the charger will get clamped to the battery
voltage - see Section 4.3.1.2 for details.
4.3.1.2 Let us assume that SEC-1280UL is being used to charge a 12V battery bank that
has been discharged to 10.5V. When the charger is switched on, the 12V battery will
initially try to draw very large current = (13.5V - 10.5V) " Internal Resistance of dis-
charged battery (say 0.02 Ohm) = 150A. As the Bulk Current rating of SEC-1280UL is 80A,
the charger will enter current limit condition at 80A (Point A2 in Fig 4.1) and its voltage
will drop but will get clamped at the initial battery voltage of 10.5V (Point A1 in Fig 4.1).
The battery will start charging at constant current of 80A (Section A2-B2 in Fig 4.1) and
its intrinsic (internal) voltage will ramp up almost linearly (Section A1-B1 in Fig 4.1). When
the battery’s intrinsic voltage approaches 13.5V (Point B1 in Fig 4.1) and the current
drawn by the battery reduces to < 80A (Point B2 in Fig 4.1), the charger will exit Constant
Current Bulk Stage and enter Constant Voltage Absorption Stage described further at
Section 4.3.2.
12 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 13
SECTION 4 | Principles of Operation
4.3.1.3 Charging Characteristics during Bulk Stage
• Battery is charged at
constant current
equal to Bulk Stage Current rating of 80A
for SEC-1280UL and 40A for SEC-2440UL
• Battery voltage rises slowly and almost linearly till 13.5V for SEC-1280UL and till
27.0V for SEC-2440UL
• The entire charging current is used to convert (i) Lead Sulfate to Sponge Lead at
the Negative plates and (ii) Lead Sulfate to Lead Dioxide at the Positive plates
• There is minimal gassing and the charging efciency is high - around 91%
• The restored capacity in this stage is inversely proportional to the Charging Rate
(due to Peukert’s Effect). This means that as the charging rate is increased, the
capacity restored in this stage will also be reduced. This Bulk Stage will restore (i)
60% capacity at Charging Rate of C/5, (ii) 70%-75% capacity at Charging Rate of
C/10 and (iii) 85% to 90% capacity at Charging Rate of C/20
• Red LED marked "Bulk"/“I Phase” on the optional Remote Model 900-RC will be
lighted
4.3.2 Stage 2 - Absorption Stage
Refer to the Charging Curves at (i) Fig 4.1 for SEC-1280UL and (ii) Fig 4.2 for SEC-2440UL
4.3.2.1 General Information: The charger enters Absorption Stage at points “B1” (Voltage
Curve) and “B2” (Current Curve) after completion of Bulk Stage (Section 4.3.1). Absorption
Stage is carried out at constant voltage at 2 voltage levels - (i) Absorption Voltage Level 1
at 13.5V for SEC-1280UL or, 27.0V for SEC-2440UL and then, (ii) Absorption Voltage Level
2 at (i) 14.0/14.4 V for SEC-1280UL (selected through DIP Switches S1 and S2 - See Section
7.4 and Table 7.1) or, (ii) 28.0/28.8V for SEC-2440UL (selected through DIP Switches S1 and
S2 - See Section 7.4 and Table 7.2)
4.3.2.2 Absorption Stage Timer: When the charger enters Absorption Stage Level 1 (Sec-
tion 4.3.2.3.1), a 4 Hr / 8 Hr Absorption Stage Timer (Selected by DIP Switches “S3” and
“S4”- See Section 7.5, Table 7.3) is activated. When this Timer runs out, the charger will
transition from Absorption Stage to Float Stage (Section 4.3.3).
4.3.2.3.1 Absorption Stage Level 1: Charging is carried out at constant voltage of 13.5V
for SEC-1280UL or, 27.0V for SEC-2440UL (Section B1 to C1 of Voltage Curve in Figs 4.1
and 4.2). The intrinsic (internal) voltage of the battery rises further and its current starts
to taper down (Section B2 to C2 of Current Curve in Figs 4.1 and 4.2). The charging cur-
rent tapers down because the intrinsic (internal) battery voltage is rising and the differ-
ential voltage between 13.5/27.0V of the charger and the intrinsic (internal) voltage of
the battery is reducing, thereby, lesser current is driven into the battery. Tapering charge
at 13.5V / 27.0V is provided in this Absorption Stage Level 1 to reduce surface charge ef-
fect and to ensure that the charge slowly diffuses to the internal thickness of the plates
and prevents overcharging. When the charging current tapers down to 80% of the Bulk
Stage Current value of the charger (64A for SEC-1280UL or, 32A for SEC-2440UL) at point
14 | SAMLEX AMERICA INC.
“C2” (Current Curve in Figs 4.1 and 4.2), the charger transitions to Absorption Stage
Level 2 (See Section 4.3.2.3.2)
4.3.2.3.2 Absorption Stage Level 2: After completion of Absorption Stage Level 1 (Sec-
tion 4.3.2.3.1), the Absorption Voltage is raised to Level 2 as follows:
i. SEC-1280UL:
o Absorption Voltage is raised from 13.5V to 14.4 for Flooded /AGM or,
o Absorption Voltage is raised from 13.5V to 14.0 V for Gel Cell
NOTE: The desired voltage is selected through DIP Switches S1 and S2 (See Section 7.4
and Table 7.1).
ii. SEC-2440UL:
o Absorption Voltage is raised from 27.0V to 28.8V for Flooded /AGM or,
o Absorption Voltage is raised from 27.0V to 28.0 V for Gel Cell
NOTE: The desired voltage is selected through DIP Switches S1 and S2 (See Section
7.4 and Table 7.2).
At voltage transition point “C1” (Voltage Curve in Fig 4.1 and Fig 4.2), the internal out-
put voltage of the charger will be raised from (i) 13.5 V to 14.0 / 14.4V for SEC-1280UL
or, (ii) from 27.0V to 28.0 / 28.8V for SEC-2440UL.
However, this increased voltage will not be seen as constant voltage immediately
(Section C1 to D1 in Voltage Curves in Figs 4.1 and 4.2 shows voltage becomes constant
only after point D1) because the battery will try to draw current higher than the Bulk
Stage Current rating of the charger (80A for SEC-1280UL or, 40A for SEC-2440UL) due
to sudden rise in voltage of the charger. The charger will deliver current limited to the
rated Bulk Stage Current (Section “C2-D2” in the Current Curves in Figs 4.1 and 4.2),
its voltage will drop due to loss of regulation due to "current limit condition" and will
get clamped to the intrinsic (internal) battery voltage. The battery will start charging
further at the rated Bulk Stage Current (Section C2 to D2 in the Current Curves in Figs
4.1 and 4.2) and its voltage will start rising (Section C1 to D1 in Voltage Curves in Figs
4.1 and 4.2). At point “D2” (Current Curves in Figs 4.1 and 4.2), the charging current will
reduce to less than the Bulk Stage Current limit value of 80A for SEC-1280UL / 40A for
SEC-2440UL and the charger will then exit the current limited constant current mode
and will enter constant voltage mode of 14V/14.4 V for SEC-1280UL or, 28.0 / 28.8V for
SEC-2440UL. (Please note that voltage of 14V/14.4 V for SEC-1280UL or, 28.0 / 28.8V for
SEC-2440UL is the constant Absorption Voltage Level 2 being put out by the charger.
The intrinsic (internal) voltage of the battery will still be lower than these voltages
because the battery will still not be fully charged at this transition). As the intrinsic
(internal) voltage of the battery rises further, the charging current will start tapering
down (Section D2 to E2 in the Current Curves in Figs 4.1 and 4.2). Tapering charge is
provided at this transition to reduce surface charge effect to ensure that the charge
slowly diffuses to the internal thickness of the plates and prevents overcharging.
The charger will transition to the next “Stage 3- Float Stage” (Section 4.3.3) at point
“E2” (Current Curves in Figs 4.1 and 4.2) under the following 2 conditions (whichever
occurs earlier):
SECTION 4 | Principles of Operation
14 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 15
SECTION 4 | Principles of Operation
a) When the 4 Hr / 8 Hr Absorption Stage Timer (Selected by DIP Switches “S3” and
“S4”- See Section 7.5, Table 7.3) runs out OR,
b) When the charging current tapers down to 10% of the rated “Bulk Current Capac-
ity” of the charger;
8A +/- 0.5A for SEC-1280UL
4A +/- 0.5A for SEC-2440UL
4.3.2.3.3 Thresholds of Charger Currents for Change over Between Absorption and
Float Stages: The thresholds of charger current for change over between the Absorption
Stage (Displayed as "Absorption"/“U0 Phase" in optional Remote Control 900-RC) and
Float Stage (Displayed as "Float"/“U Phase" in optional Remote Control 900-RC) are
shown below:
Change Over SEC-1280UL SEC-2440UL
From Absorption Stage (Level 2) to Float Stage 8A +/- 0.5A 4A +/- 0.5A
From Float Stage to Absorption Stage (Level 1) 15A +/- 0.5A 8A +/- 0.5A
4.3.2.3.4 Charging Characteristics during Absorption Stage
Absorption Stage Levels 1 and 2 (Displayed as "Absorption"/“U0 Phase" in op-
tional Remote Control 900-RC) feed additional 35% to 55% of the capacity that
adds to the total charged capacity of around 115% to take care of around 15%
loss due to charger efciency
There will be moderate gassing during this Absorption Stage
Orange LED marked "Absorption"/“U0 Phase” on the optional Remote Control
Model No.900-RC will be lighted
4.3.2.4 Thresholds of Charger Currents for Change over Between Absorption and Float
Stages: The thresholds of charger current for change over between the Absorption
Stage (Displayed as "Absorption"/“U0 Phase" in optional Remote Control 900-RC) and
Float Stage (Displayed as "Float"/“U Phase" in optional Remote Control 900-RC) are
shown below:
Change Over SEC-1280UL SEC-2440UL
From Absorption Stage (Level 2) to Float Stage 8A +/- 0.5A 4A +/- 0.5A
From Float Stage to Absorption Stage (Level 1) 15A +/- 0.5A 8A +/- 0.5A
4.3.3 Stage 3 - Float Stage
4.3.3.1 During this stage, the charger outputs a constant Float Voltage of (i) 13.5V for
SEC-1280UL or, (ii) 27.0V for SEC- 2440UL. This helps in maintaining full capacity of the bat-
tery and also provides replacement charge to overcome self discharge of the battery. The
battery can remain connected in this stage indenitely without the risk of discharging.
16 | SAMLEX AMERICA INC.
SECTION 4 | Principles of Operation
4.3.3.2 Charging characteristics during this stage are as follows:
• Float Stage is used to maintain the battery's charge without losing electrolyte
through gassing and also, to compensate for self-discharge. For example, a bat-
tery not under charge and sitting idle with no load will self discharge at around
1% of its remaining Ah capacity every day.
• Float Stage current is around 0.1% of the Ah capacity of the battery
• During this stage, Green LED marked "Float"/“U Phase" on the optional Remote
Control Model 900-RC will be lighted
4.3.3.3 Thresholds of Charger Currents for Change over Between Absorption and Float
Stages: The thresholds of charger current for change over between the Absorption
Stage (Displayed as “U0” Phase in optional Remote Control 900-RC) and Float Stage
(Displayed as “U” Phase in optional Remote Control 900-RC) are shown below:
Change Over SEC-1280UL SEC-2440UL
From Absorption Stage to Float Stage 8A +/- 0.5A 4A +/- 0.5A
From Float Stage to Absorption Stage 15A +/- 0.5A 8A +/- 0.5A
SECTION 5 | Protections
The charger has the following protections:
5.1 SHORT CIRCUIT SHUT DOWN
In case of a short circuit on the output side, the output of the charger will be shut down.
Another symptom of short circuit shut down is that the fan will be ON till the unit is
reset or switched OFF. On the optional Remote Control 900-RC, Green LED marked
"Power" and Red LED marked "Bulk"/ "I Phase" will be lit. The charger will be latched
in this shut down condition and will NOT recover automatically even after the short
circuit condition is removed. To reset, the AC input power ON/ OFF switch at the back of
the unit has to be switched OFF and ON again.
5.2 OVER LOAD CURRENT LIMITING
The current drawn by the load is automatically limited to a maximum of 80A for
SEC-1280UL (40A +/- 1A in “Half Power Mode”) and 40A for SEC-2440UL (20A +/- 1A
when in “Half Power Mode”). If the load tries to draw a higher current than these lim-
its, the output voltage of the unit will start to drop. The unit will automatically recover
when the overload condition is removed.
5.3 REVERSE BATTERY CONNECTION – DC SIDE FUSES WILL BLOW
The output is internally fused on the DC side - 3 x 30A fuses for SEC-1280UL and 3 X
15A fuses for SEC-2440UL. In case, the polarity of the battery connection is reversed, the
16 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 17
SECTION 5 | Protections
fuse(s) will blow. Another symptom of blown fuse on DC side is that the fan will be ON
till the unit is switched OFF. On the optional Remote Control 900-RC, Green LED marked
"Power" and Red LED marked "Bulk"/“I Phase" will be lit.
5.4 COOLING
The charger is cooled by convection and in addition, has a fan for forced air-cooling.
The operation of the fan is controlled by the current supplied by the charger and will be
switched ON and OFF automatically as follows:
SEC-1280UL SEC-2440UL
Switch ON current 15A +/- 1A 8A +/- 1A
Switch OFF current 8A +/- 0.5A 4A +/- 0.5A
NOTE: Once the fan switches on at the specied current threshold, it will switch off at
a lower threshold. For example, the fan in SEC-1280UL switches ON at 15A but switches
OFF at 8A. This is to prevent the fan from oscillating between ON and OFF conditions
due to minor uctuations in load current
5.5 OVER TEMPERATURE SHUTDOWN
!
CAUTION!
Keep the charger in a well ventilated, cool and open area. DO NOT BLOCK THE
VENT HOLES on the sides or the discharge openings of the cooling fan. Keep at
least 6” clearance on all sides
In case the fan fails or if the cooling is not adequate due to higher ambient tempera-
ture, inadequate air circulation or blockage of air ventilation openings, the temperature
inside the unit will rise. A temperature sensor is mounted in the windings of the power
transformer. At 105° C +/- 5° C the thermal sensor will activate and shut down the out-
put voltage of the charger. The fan will be ON. On the optional Remote Control
900-RC, Green LED marked "Power" and Red LED marked "Bulk"/"I Phase" will be lit.
The charger will be latched in this shut down condition and will NOT reset automatically
even after the unit has cooled down. To reset, the AC input power ON/OFF switch at the
back of the unit has to be switched OFF and ON again.
5.6 PROTECTION AGAINST TRANSIENTS / SURGES IN THE AC INPUT
In a number of locations, the AC line input is not clean and may contain high volt-
age transients / surges. To prevent damage to the internal components against these
unwanted high voltages, the charger uses a MOV (Metal Oxide Varistor) for protection.
If surge / transient voltage higher than approximately 170 VAC in 120V Mode / 340 VAC
in 230 VAC Mode appear in the AC input, the MOV will conduct and will blow the AC
side fuse.
18 | SAMLEX AMERICA INC.
SECTION 6 | Installation
6.1 INSTALLATION DIMENSIONS
Installation dimensions are given below. Dimensions are same for SEC-1280UL and
SEC-2440UL.
SEC-1280-2440UL Top View Dimensions
2
244
381
350
5
75
2
75
200
244
97
9
Fig. 6.1 Dimensional Drawing of SEC-1280UL & SEC-2440UL
18 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 19
SECTION 6 | Installation
6.2 LOCATION, MOUNTING AND SAFETY
The charger is required to be installed in a safe, well ventilated and dry location.
Please see the details given under “Important Safety Precautions”. The charger can be
mounted horizontally or vertically. When mounting vertically on a wall or a bulkhead,
please ensure that the axis of the fan rotor is horizontal i.e. the fan exhaust opening
should face left or right but NOT face up or down.
WARNING!
Mounting the unit vertically on a vertical surface with the fan opening facing
up or down is NOT allowed for safety. This is to prevent falling of objects into
the unit through the fan grille when the fan opening faces up. If fan opening
faces down, hot damaged components may fall out.
6.3 OUTPUT CONNECTORS
Connectors with tubular, screw down type of terminals are used for output connection
(1,2 & 3 in Fig 3). The diameter of the tubular hole of the connector is 5/16". Set screw
size is 5/16" x 24 TPI. Two Positive output connectors (1, 2 in Fig 3) are provided for con-
necting to the Positive terminals of the 2 banks of batteries. One common connector (3
in Fig 3.1) is provided for the Negative connection.
6.4 TERMINAL LUGS FOR CONNECTION TO THE CHARGER
For rm connection when using stranded wire, crimp / solder “pin” style terminal lugs on
the charger end of the DC wires used for connecting to the battery / other DC loads. 3 pieces
of “pin” style terminal lugs have been provided as follows for charger to battery distance of
up to 10ft:
For SEC-1280UL: 3 x Pin Type Terminal Lugs, Type PTNB 35-20. Will accommodate up to
AWG #4 wire
For SEC-2440UL: 3 x Pin Type Terminal Lugs, Type PTNB 10-12. Will accommodate up to
AWG #8 wire
6.5 WIRES
To avoid polarity errors and possible damage, never use wires of only one color. Use Red
insulated wire(s) for Positive connection(s) and Black for Negative connection(s).
Recommended DC wire sizes are given below (Based on a voltage drop of 2%). The
length in feet is the length of the pair of the positive and negative DC wires from the
charger to the battery / other DC loads.
Distance From Battery SEC-1280UL SEC-2440UL
Up to 6 ft. AWG #2 AWG #8
6 to 10 ft AWG #1/0 AWG #6
10 to 20 ft. AWG #3/0 AWG #4
6.6 TERMINATION OF WIRE ENDS
For rm connection when using stranded wire, wire ends for the connection to the
charger should be terminated with pin types of lugs that have been provided (See Section 6.4).
20 | SAMLEX AMERICA INC.
7.1 SELECTING AC INPUT VOLTAGE
The charger is pre-set to operate from input AC voltage of 120 VAC, 60 Hz. To operate the
charger from AC input voltage of 230 VAC, 50 Hz, change the internal setting as follows:
1. Remove the side plate that has the power cord entry by unscrewing 4 screws
2. Remove the Voltmeter and the Ammeter on the top central plate by prying up the
bottom edges of the meters with a broad, at screw driver and by pushing the meters
up from the bottom of the plate (these are snap tted). Remove the connecting wires
and mark them. Note the polarity for connecting back in proper polarity. The meter
terminals are marked Positive (+) and Negative (-). Thicker wires are for the Ammeter
and thinner are for the Voltmeter
3. Gently slide the center top cover plate out. Note and mark its orientation for
correct re-tting
4. Locate Yellow loop of jumper wire with quick female disconnect. In the pre-set
120 VAC condition, this jumper wire is shorting the male vertical pins marked “C” and
“D” and “115V”. Pull any one end of this female disconnect upwards to disconnect
shorting between “C” and “D”. Insulate this end with insulating tape. The unit is now
set for “230 VAC”
5. The 120 VAC version has a soldered 20A fuse on the AC side. When converting
120 VAC version unit for 230 VAC operation, there is no need to replace the 20A fuse
6. Replace the AC plug of the power cord with a suitable 3 pin grounded plug to mate
with the 230 VAC outlet.
!
CAUTION!
The new plug should have 3 poles i.e. Line (L), Neutral (N) and Earth ground.
Color code for the power cord conductors is:
- Line (L) - Black
- Neutral (N) - White
- Earth ground - Green
7.2 CONNECTING BATTERIES OR OTHER DC LOADS
As shown in Fig. 7.1 and 7.2, the output of the charger has a common Negative (-) con-
nector and 2 Positive connectors for connection of 2 banks of batteries. Each Positive
connector has its own internal Isolating Diode, which works as a battery isolator. If more
than one bank of batteries is connected, these will be charged at the same time as long
as the AC power is available to the charger. The maximum charging current of 80A (Full
Power Mode)/ 40A (Half Power Mode) for SEC-1280UL and 40A (Full Power Mode)/ 20A
(Half Power Mode) current for SEC-2440UL will be shared among the connected banks
of the batteries depending upon their discharged states. In case the AC power fails or
if there is no output from the charger, the Isolating Diodes will prevent charging / dis-
charging among the batteries connected to the banks.
SECTION 7 | Preparing the Charger for Operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Samlexpower SEC-2440UL Le manuel du propriétaire

Catégorie
Chargeurs de batterie
Taper
Le manuel du propriétaire

dans d''autres langues