KPS TP3500LCD Le manuel du propriétaire

Catégorie
Multimètres
Taper
Le manuel du propriétaire
IT
EN Voltage Tester Instruction Manual VTB
Probador de tensión
Testeur de tension
Spannungsprüfer
Tester di tensione Manuale di istruzioni
VTB
LIMITED
WARRANTY
YEARS
User Manual / MANUAL DEL USUARIO /
Manuel d'utilisation / Benutzerhandbuch /
Manuale Utente
TP3500LCD
EN
TP3500LCD
!Safety Information
To ensure safe operation and service of the Tester,
follow these instructions. Failure to observe warnings
can result in severe injury or death.
- This meter is designed to be used by skilled
persons and in accordance with safe methods of
work.
- Avoid working alone so assistance can be
rendered. If the operators safety can not be
guaranteed, the Tester must be removed from
service and protected against use.
- Prior to usage ensure perfect instrument function
(e.g. on known voltage source) before and after the
test.
- Do not connect the instrument to voltages higher
than 750V.
- Do not open the battery cover before take off from
voltage source.
- The safety can no longer be insured if the
Tester :
• shows obvious damage • does not carry out the
desired measurements • has been stored for too
long under unfavorable conditions • has been
subjected to mechanical stress (i.e. during
transport).
- All relevant statutory safety regulations must be
adhered to when using this instrument.
- The Tester may no longer be used if one or several
functions fail or if no functionality is indicated or the
Tester looks damaged.
- When using this Tester, only the handles of the
probes may be touched do not touch the probe tips
(metal part).
- Do not use the Tester if the Tester is not operating
properly or if it is wet.
- Use the Tester only as specified in the Instruction
card including environmental conditions and the
usage in dry environments must be followed or the
protection by the Tester might be impaired.
- Use extreme caution when working around bare
conductors or bus bar. Contact with the conductor
could result in an electric shock.
- Use caution with voltages above 50V AC rms or
110V DC. These voltages pose a shock hazard.
- The voltage marked on this meter are nominal
voltages or nominal voltage ranges and that this
meter is only to be used on installations with the
specified nominal voltage or nominal voltage ranges.
- ELV indicator and internal sounder are not to be
used for measuring purposes.
- Verify the meter operation by measuring a known
voltage and by connecting the test probes together,
before use it. If no response, replace the battery
first or have the meter services.
1. Safety
1
EN
TP3500LCD
Depending on the internal impedance of the voltage
detector there will be a different capability of
indicating the presence or absence of operating
voltage in case of the presence of interference
voltage.
When in contact with the parts to be tested, the
voltage detector may discharge temporar-ily the
interference voltage to a level below the ELV, but it
will be back to the original value when the voltage
detector is removed.
When the indication “voltage present” does not
appear, it is highly recommended installing earthing
equipment before work.
When the indication “voltage present” appears on a
part that is expected to be disconnected of the
installation, it is highly recommended confirming by
another means (e.g. use of an adequate voltage
detector, visual check of the disconnecting point of
the electric circuit, etc.) that there is no operating
voltage on the part to be tested and to conclude that
the voltage indicated by the voltage detector is an
interference voltage.
SAFETY ADVICES
2. Symbols and Features
Symbols as marked on the Tester and
Instruction manual
!
Risk of electric shock
+ DC or –DC measurement
Battery
Earth
Equipment protected by double or
reinforced insulation
AC measurement
Conforms to EU directives
See instruction manual
+ or -
High Voltage Detection
ELV Indication
Continuity
Phase indicator see “Phase Rotation Test”
section for more Information.
2
EN
TP3500LCD
– AC Voltage
– DC Voltage
– Continuity
– Resistance
– Single pole phase test
– Phase rotation of a three-phase mains
– Frequency test
– Auto test
– Probe tip torch
– Drop proof 1 meter
– IP 65 Protection
Auto Power On/Off
– Selectable probe tips 2/4 mm
Symbols and Features
AC V
DC V
3. AC / DC V Measurements
The ELV indicator can report a dangerous
voltage > 50 V AC and 120 V DC.
If the tester is used in a noisy background, you
need to ensure that the soundlevel of the tester is
perceptible here.
3
EN
TP3500LCD
Continuity Tests
4. Continuity / Diode Test
Diode Test
The Continuity / test is only possible
when batteries are installed and in good condition.
4
EN
TP3500LCD
5. Resistance Measurements
ȍ
6. Single-Pole Phase Test
Single-Pole Phase
The Resistance test is only possible when
batteries are installed and in good condition.
)LUPO\ĺ
5
EN
TP3500LCD
)LUPO\ĺ
The single-pole phase test is only possible
when batteries are installed and in good condition.
The single-pole phase test is not always
appropriate for testing whether a circuit is not live.
For this purpose, the bipolar test is required.
To determine external conductors during
phase tests the display function may be impaired
(e.g. for insulating body protection or insulating
sites).
Firmly grasp the insulated grips of the Tester
probe L2 it is better for increase the sensitivity of
single-pole phase test.
7. Phase Rotation Test
Rotary phase of a three-phase mains
• Right rotary field
6
EN
TP3500LCD
• Left rotary field
)LUPO\ĺ
Testing of phase-sequence direction is
possible from 100V AC voltage (phase to phase)
provided the neutral is earthed.
On making contact with both test electrodes
(probe tips) to two phases of the three-phase
power supply which are connected in clockwise
rotation, a symbol appears in the LCD Display.
If the rotation is anticlockwise, then a symbol
is displayed. In this case both phases of the unit
should be switched around.
!Note :
Testing the phase rotation always requires a
negative phase rotation test!
To ensure a connect test, it is better to test on a
known source.
!Attention :
Please ensure that the test electrodes (probe tips)
make good contact with two phases of a three-phase
mains while testing the phase rotation. For absolute
determination of a clock-wise phase rotation it is
necessary to make a negative phase rotation test
after changing the phases. The indication or
can be affected by unfavorable light conditions, by
protective clothing or in insulated locations.
7
EN
TP3500LCD
Firmly grasp the insulated grip of the Tester
probe L2, it is better for the sensitivity of the phase
rotation test.
8. RCD Voltage Test
Voltage Test with RCD Trip Test
During voltage tests in systems equipped with RCD
circuit breakers, a RCD switch can be tripped at a
nominal residual current of 10mA or 30mA by
measuring the voltage between L and PE.
This Tester is equipped with an internal load
enabling the tripping of an RCD protection device of
10mA or 30mA.
To avoid RCD tripping, a test has to be carried out
between L and N during approx. 5sec. Immediately
afterwards, voltage testing between L and PE can be
carried out without RCD tripping.
8
EN
TP3500LCD
9. Illumination
Probe tip torch
10. Frequency Tests
9
EN
TP3500LCD
12. Battery Replacement
If the symbol “ ” is displayed
- Completely disconnect from the measurement
circuit.
- Unscrew the screw by a cross screw driver,
then open the battery cover.
- Remove discharged batteries.
- Replace by new batteries, type 1.5V
IEC LR03 by respecting correct polarity.
- Close the battery cover and re-screw the screw.
If the instrument shows failue, please don’t
use it and send it to our service department for
repair.
11. Auto Tests
Remain
1 Sec.
10
EN
TP3500LCD
13. 4mm Tips Replacement
14. Cleaning
Prior to cleaning, remove the instruments from all
measurement circuits.
If the instruments are dirty after daily usage, it is
advisable to clean them by using a damp cloth
and a mild household detergent. Never use acid
detergents or dissolvent for clean-ing. After
cleaning, do not use the voltage tester till it is
dried completely.
15. Transport and Storage
In order to avoid instrument damage, it is
advised to remove batteries when not using the
instrument over a longer period.
The tester must be stored in dry and closed areas.
In the case of an instrument being transported in
extreme temperatures, a recovery time of
minimum 2 hours is required prior to instrument
operation.
11
EN
TP3500LCD
16. Maintenance
Unauthorized persons shall not disassemble the
tester and the supplementary equipment.
When using tester in compliance with the
instruction manual, no particular maintenance is
required.
The Instruments
Voltage range 12….750V AC/DC
LED/Bargraph
resolution ± 12,24,50,120,230,400,
750V
LCD voltage range 12V…750V AC/DC
LCD resolution 1V
Accuracy AC ± (1.3%+5d)
DC ± (1.0%+2d)
Voltage detection Automatic
Acoustic signal sound AC 50V
DC 120V
Polarity detection Full range
Range detection Automatic
Response time <0.1s/BAR
<2s/RDG
Frequency range DC, 45…65Hz
Automatic load (RCD) Yes
Peak current Is <0.2A / Is(5s) <3.5mA
Operation time 30sec
Recovery Time 240sec
Auto Power On >12 VAC / DC
Single- pole Phase Test
Voltage range 100…750V AC
Frequency range 45…65Hz
Resistance Test
Resistance Range 0…2
Accuracy ± (2%+10d)
Resolution ȍ
Frequency Test
Frequency range 30Hz~999Hz
Accuracy ±(0.3%+5d)
Resolution 1Hz
Vmin (61Hz~999Hz) 20VAC
17. Specification
12
EN
TP3500LCD
Continuity Test
Threshold < 200ȍ
Diode Test 0.1~1.0V
Resolution 0.1V
Overvoltage
protection 1000V AC/DC
Rotary Field Indication
Voltage range (LEDs) 100…750V
Frequency range 50…60Hz
Measurement
principle Double-pole and firmly
hold the grip (L2)
Power supply 2 x 1.5V IEC LR03 AAA
size
Power consumption Max. 32mA / approx.
94mȍ
Operating Temperature -15ºC ~ 4C
Storage Temperature -2C ~ 60ºC
Temperature Coefficient 0.2x(Spec.Accuracy/ºC
<18ºC >28ºC
Humidity Max. 85% relative
humidity
Height above sea level Up to 2000m
Pollution Degree 2
Type of protection IP65
CE EN61326
Safety EN61010 -1
EN61010 -2-030
EN61010 -031
IEC61243 -3
UTE 18 -510
EN60529
GS38
Weight 240g (incl. Batteries)
Dimensions 239x68x29mm
Overvoltage category
Overvoltage class CAT III 1000V/CAT IV 600V
CAT. Application field
CAT II The circuits directly
connected to Low -voltage
Installation.
CAT III The building installation
CAT IV The source of the Low
voltage installation.
13
EN
TP3500LCD
18. Warranty
The Instruments are subject to strict quality
control. However, should the instrument function
improperly during normal use, you are protected
by our two years warranty.
We will repair or replace free of charge any
defects in workmanship material, provided the
instrument is returned unopened and unhampered
with.
Damage due to dropping or incorrect handling is
not covered by the warranty.
If the instrument shows failure following expiry of
warranty, our service depart-ment can offer you a
quick and economical repair.
14
ES
TP3500LCD
!Información de seguridad
Para garantizar un funcionamiento y uso seguros del
probador, siga estas instrucciones.
La inobservancia de estas advertencias puede tener
como consecuencia graves daños de salud.
- Este medidor está diseñado para que lo utilicen
personas cualificadas y de acuerdo a las
advertencias de seguridad.
- Evite trabajar solo por si necesita ayuda. Si no se
puede garantizar la seguridad de los operarrios,
debe retirarse del servicio el dispositivo y evitar que
se use.
- Antes de su uso, asegúrese de que el instrumento
funciona correctamente (p.ej., con una fuente de
tensión conocida) antes y después de la prueba.
- No conecte el instrumento a tensiones superiores a
750V.
- No abra la tapa de las pilas antes de desconectar
la fuente de tensión.
- No se está garantizada si el probador:
• muestra daños evidentes • no realiza las
mediciones deseadas • se ha almacenado durante
demasiado tiempo en condiciones desfavorables •
ha sido sometido a estrés mecánico (es decir,
durante el transporte).
- Deben respetarse todas las normativas de
seguridad pertinentes al usar el instrumento.
- No debe utilizarse si fallan una o varias funciones o
si no muestra funcionalidad o el probador parece
dañado.
- Cuando se utiliza este probador, solo se pueden
tocar el mango de las sondas; no toque la punta de
la sonda (parte metálica).
- No utilice el probador si no funciona correctamente
o si está mojado.
- Utilice el probador según lo especificado en la
tarjeta de instrucciones, incluidas las condiciones
ambientales y el uso en entornos secos, o la
protección del probador podría verse afectada.
- Extrema la precaución cuando trabaje cerca de
conductores desnudos o embarrados. El contacto
con el conductor podría provocar una descarga
eléctrica.
- Tenga cuidado con las tensiones por encima de
50V CA rms o 110V CC. Estas tensiones
representan un peligro de electrocutación.
- Las tensións marcadas en este medidor son
tensiones nominales o rangos de tensión
nominales por lo que este medidor sólo debe
utilizarse en instalaciones con la tensión nominal o
rangos de tensión nominales especificados.
- El indicador ELV y la sonda interna no deben
utilizarse para medir.
- Verifique el funcionamiento del medidor midiendo
un tensión conocida y conectando las sondas de
prueba juntas, antes de usarlo. Si no hay respuesta,
reemplace primero las pilas o repare el medidor.
1. Seguridad
15
ES
TP3500LCD
Dependiendo de la impedancia interna del detector
de tensión habrá una diferencia de capacidad al
indicar la presencia o ausencia de tensión de
funcionamiento en caso de presencia de tensión de
interferencia.
Cuando esté conectado a las piezas a probar, este
detector de tensión puede descargar temporalmente
la tensión de interferencia a un nivel por debajo del
ELV, pero volverá al valor original cuando se retire el
detector de tensión.
Cuando no aparezca la indicación "tensión
presente", se recomienda encarecidamente instalar
equipos de puesta a tierra antes del trabajo.
Cuando aparezca la indicación "tensión presente" en
una pieza que está desconectada de la instalación,
se recomienda encarecidamente confirmar por otro
medio (por ejemplo, el uso de un detector de tensión
adecuado, comprobación visual del punto de
desconexión del circuito eléctrico, etc.) que no haya
tensión de funcionamiento en la pieza a probar y
concluir que la tensión indicada por este medidor es
una tensión de interferencia.
CONSEJOS DE SEGURIDAD
2. Símbolos y
Símbolos según se encuentran en el probador
y manual de instrucciones
!
Riesgo de descarga eléctrica
Medición + CC o - CC
Pila
Tierra
Equipos protegidos por aislamiento
doble o reforzado
Medición CA
Se ajusta a las directivas de la UE
Consulte el manual de instrucciones
+ or -
Detección de alta tensión
Indicación de ELV
Continuidad
Indicador de fase vea la sección "Prueba
de rotación de fase" para obtener más
información.
16
ES
TP3500LCD
– Tensión CA
– Tensión CC
– Continuidad
– Resistencia
– Prueba de fase de polo único
– Rotación de fase de una red trifásica
– Prueba de frecuencia
– Prueba automática
– Linterna de punta de sonda
– Prueba de caída de 1 metro
– Protección IP 65
– Encendido/apagado automático
– Puntas de sonda seleccionables 2/4 mm
Lista de características
CA V
CC V
3. Mediciones CA/CC V
El indicador ELV puede reportar una tensión
peligrosa > 50 V CA y 120 V CC.
Si el probador se utiliza en entornos ruidos,
debe asegurarse de que el nivel de sonido del
probador es perceptible ahí.
17
ES
TP3500LCD
Pruebas de continuidad
4. Pruebas de continuidad / diodos
Pruebas de diodos
La prueba de continuidad / sólo es posible
con las pilas instaladas y en buen estado
18
ES
TP3500LCD
5. Mediciones de resistencia
ȍ
6. Prueba de fase de polo únic
Fase de polo único
La prueba de resistencia sólo es posible con
las pilas instaladas y en buen estado.
)LUPHPHQWHĺ
19
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71

KPS TP3500LCD Le manuel du propriétaire

Catégorie
Multimètres
Taper
Le manuel du propriétaire