Amprobe TIC 300 PRO Non-Contact Voltage Detector Manuel utilisateur

Taper
Manuel utilisateur
TIC 300 PRO
High Energy Tic Tracer –
Non Contact
AC Voltage Detector
User Manual
TIC 300 PRO
High Energy Tic Tracer –
Non Contact
AC Voltage Detector
User Manual
10/2019, Rev006
©2019 Amprobe.
All rights reserved. Printed in China
English
Limited Warranty and Limitation of Liability
Your Amprobe product will be free from defects in material
and workmanship for 1 year from the date of purchase. This
warranty does not cover fuses, disposable batteries or damage
from accident, neglect, misuse, alteration, contamination, or
abnormal conditions of operation or handling. Resellers are not
authorized to extend any other warranty on Amprobe’s behalf.
To obtain service during the warranty period, return the product
with proof of purchase to an authorized Amprobe Test Tools
Service Center or to an Amprobe dealer or distributor. See Repair
Section for details. THIS WARRANTY IS YOUR ONLY REMEDY.
ALL OTHER WARRANTIES - WHETHER EXPRESS, IMPLIED OR
STAUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS FOR
A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY
DISCLAIMED. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES
OR LOSSES, ARISING FROM ANY CAUSE OR THEORY. Since some
states or countries do not allow the exclusion or limitation of an
implied warranty or of incidental or consequential damages, this
limitation of liability may not apply to you.
Repair
All test tools returned for warranty or non-warranty repair or
for calibration should be accompanied by the following: your
name, company’s name, address, telephone number, and proof of
purchase. Additionally, please include a brief description of the
problem or the service requested and include the test leads with
the meter. Non-warranty repair or replacement charges should be
remitted in the form of a check, a money order, credit card with
expiration date, or a purchase order made payable to Amprobe®
Test Tools.
In-Warranty Repairs and Replacement – All Countries
Please read the warranty statement and check your battery before
requesting repair. During the warranty period any defective test
tool can be returned to your Amprobe® Test Tools distributor
for an exchange for the same or like product. Please check the
“Where to Buy” section on www.amprobe.com for a list of
distributors near you. Additionally, in the United States and
Canada In-Warranty repair and replacement units can also be sent
to a Amprobe® Test Tools Service Center (see address below).
Non-Warranty Repairs and Replacement – US and Canada
Non-warranty repairs in the United States and Canada should be
sent to a Amprobe® Test Tools Service Center. Call Amprobe® Test
Tools or inquire at your point of purchase for current repair and
replacement rates.
In USA In Canada
Amprobe Test Tools Amprobe Test Tools
Everett, WA 98203 Mississauga, ON L4Z 1X9
Tel: 877-AMPROBE (267-7623) Tel: 905-890-7600
Non-Warranty Repairs and Replacement – Europe
European non-warranty units can be replaced by your Amprobe®
Test Tools distributor for a nominalv charge. Please check the
“Where to Buy” section on www.amprobe.com for a list of
distributors near you.
European Correspondence Address*
Beha-Amprobe® Test Tools Europe
In den Engematten 14
79286 Glottertal, Germany
Tel.: +49 (0) 7684 8009 - 0
*(Correspondence only – no repair or replacement available from
this address. European customers please contact your distributor.)
1) Voltage sensor
2) ON/OFF Button
3) Circuit TEST button
4) HIGH range switch
5) HIGH range LED
6) LOW range switch
7) LOW range LED
8) Battery compartment
9) HOT STICK attachment point
10)
Detection Blue LED indicators
TIC 300 PRO
1
CONTENTS
SYMBOLS .......................................................................... 2
UNPACKING AND INSPECTION ....................................... 3
INTRODUCTION ................................................................4
Features ........................................................................4
OPERATION ....................................................................... 5
ON/OFF Button ............................................................. 5
TEST Button .................................................................. 5
Voltage Detection ........................................................ 6
LOW Range ...................................................................6
HIGH Range .................................................................. 6
Locate breaks in insulated wire & heating elements
...... 7
Check Outlets and Switches ........................................8
MAINTENANCE AND REPAIR .......................................... 9
Cleaning ........................................................................9
Battery Replacement ...................................................9
SPECIFICATIONS ............................................................... 10
Sensitivity: LOW Voltage .............................................11
Sensitivity: HIGH Voltage .............................................11
2
SYMBOLS
Refer to the manual
X
Caution Dangerous Voltage
T
Double insulated
MSHA
United States Department of Labor
Mine Safety and Health Administration
In compliance with the United States
Department Of Labor Mine Safety and Health
Administration
Conforms to relevant Australian standards.
Conforms to relevant South Korean EMC standards.
Do not dispose of this product as unsorted
municipal waste.
For Use By Trained Personnel Only
Anyone using this instrument should be knowledgeable
and trained about the risks involved with measuring
medium and high voltage, especially in an industrial
setting, and the importance of taking safety precautions
and of testing the instrument before and after using it
to ensure that it is in good working condition.
WARNING and PRECAUTIONS
• Use extreme caution when testing live electrical
circuits due to risk of injury from electrical shock.
• Do not exceed the maximum overload limits
(see specifications) or the limits marked on the
instrument itself. Never test voltage more than
122 kV AC RMS.
• When using the HIGH range, the TIC 410A HOT
STICK or equivalent extension pole MUST be used.
• Comply with local and national safety
requirements.
• Use proper protective equipment as required by
local and national authorities.
=
3
• Observe the proper safety precautions when
working with voltages above 33 VAC RMS to avoid
electrical shock hazard.
• Before and after hazardous voltage measurements,
test the TIC 300 PRO by pressing the TEST button
and/or on a known source such as line voltage to
determine proper operation.
• Never ground yourself when taking measurements.
Do not touch exposed circuit elements.
• Do not operate the instrument in an explosive
atmosphere.
• Do not expose this product to rain or moisture. This
increases the risk of fire or electric shock.
Do not rely on the TIC 300 PRO for testing shielded wire.
• Do not let the unit make contact with a live line
with voltage higher than 20 kV.
• Three phase feeder cables with conductors close to
each other may self-cancel the electric field and
will not be detected by the TIC 300 PRO tracer.
Verify that the phase conductors are separated
by at least 15 in (38.1 cm) before testing for AC
voltage.
UNPACKING AND INSPECTION
Your shipping carton should include:
1 TIC 300 PRO
1 9 V Alkaline Battery
1 User Manual
1 Carrying Case
If any of the items are damaged or missing, return the
complete package to the place of purchase for an exchange.
4
INTRODUCTION
The TIC 300 PRO safely checks for the presence of AC
voltage without making any disconnection in cables,
wall sockets, fuses, circuit breakers, junction boxes, etc.
No current flow is needed for correct operation.
Rugged and reliable for utility, industrial and mine safety
applications, the TIC 300 PRO warns against dangerous
voltages in low and medium voltage applications up to
122 KV without contacting the energized conductor.
Features
Utility tool for checking transmission lines, power
distribution equipment, down power lines, fuses,
and load break connectors
Lower voltage setting for checking voltage
presence in breaker panels, breakers, power
outlets and wiring
Verifies presence of voltage from 30 VAC to
122,000 VAC (122 kV)
Non-contact AC voltage detection
Visual and audible voltage indication
Self-test for verifying that the tester is working properly
Ergonomic design with a convenient handle
Drop proof up to 6 ft (1.83 m)
Use with the Hot Stick 410A when voltage exceeds 1500 V
5
OPERATION
ON/OFF Button
When the TIC 300 PRO is activated, the blue LEDs and
beeper will pulse at a slow rate about twice a second.
The red LED of the range (HIGH) will turn ON.
TEST Button
The TEST button should be used prior to testing actual
power circuits. The TEST function will cause the blue
LEDs and beeper of the range selected (LOW or HIGH) to
pulse at a fast rate.
OSHA listed clearance distances for working with
voltage. National or local requirements may be
different.
Line voltage (kV) Phase to ground Phase to phase
phase to phase (ft-in) (m) (ft-in) (m)
0.03 to 1.0 Note1 Note1 Note1 Note1
1.1 to 15.0 2-1 0.64 2-2 0.66
15.1 to 36.0 2-4 0.72 2-7 0.77
36.1 to 46.0 2-7 0.77 2-10 0.77
46.1 to 72.5 3-0 0.90 3-6 1.05
72.6 to 121 3-2 0.95 4-3 1.29
Note1 – No contact necessary
Caution: If a three phase circuit is being checked and
one phase is open, the voltage from another phase
maybe detected and will give a faulty indication. Always
make sure that the phase cables are separated by at least
20 in (50.8 cm).
6
Voltage Detection
LOW Range
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A
beep will sound and the blue LEDs will flash twice
per second.
3. Push the LOW range push button. The unit is ready
for low voltage detection.
4. Place the probe tip of the TIC 300 PRO near, but not
touching, a low (<1000 V) voltage line (Fig. 1).
5. If voltage is present, the blue LEDs will blink and the
beeper will sound at an increased rate. Continuous
visual (blue LEDs) and audible indicators will increase
when the probe tip makes contact with or is very
close to the voltage line.
Fig. 1 Voltage detection in a line
HIGH Range (HOT STICK must be used)
(See Fig. 2)
1. Push the ON/OFF push button to turn the unit ON.
2. The high voltage detection circuit is activated. A
beep will sound and the blue LEDs will flash twice
per second.
3. Approach the probe tip near, but not touching, a
high voltage (>1500 V and <122 kV) conductor.
7
4. If voltage is present, the blue LEDs will blink and the
beeper will sound at an increased rate. Continuous
visual (blue LEDs) and audible indicators will increase
when the probe tip makes contact with or is very
close to the high voltage line.
TIC 300 PRO
Fig. 2 Voltage detection in transmission lines
Locate breaks in insulated wire and heating
elements (See Fig. 3)
1. Push the ON/OFF push button to turn the unit on.
2. Push the LOW range push button.
3. Make sure the wire or the heating element is energized.
4. Place the tip of the probe near the wire and start
tracing along it. When the fast or continuous beeping
stops, the point of the break or “open” is indicated.
HOT STICK
8
Fig. 3 Finding a break/open
Check Outlets and Switches (See Figs. 4 & 5)
1. Push the ON/OFF push button to turn the unit on.
2. Push the LOW range push button.
3. Place the probe tip of the TIC 300 PRO against the
hot prong of an outlet or switch contact.
4. Increased beeping indicates higher voltage presence.
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Fig. 4
Detecting voltage in an
outlet (Note: disconnect
all power cords from the
outlet before testing)
Fig. 5
Finding a breaker
9
MAINTENANCE AND REPAIR
If there appears to be a malfunction during the
operation of the voltage detector, the following steps
should be performed in order to isolate the cause of the
problem:
1. Check the battery.
2. Review the operating instructions for possible
mistakes in operating procedure.
Except for the replacement of the battery, repair of
the voltage detector should be performed only by a
Factory Authorized Service Center or by other qualified
instrument service personnel.
Cleaning
The front panel and case can be cleaned with a mild
solution of detergent and water. Apply sparingly with a
soft cloth and allow to dry completely before using. Do
not use aromatic hydrocarbons or chlorinated solvents
for cleaning.
Battery Replacement
Use a Phillips blade screwdriver to remove the battery
hatch screw. Lift the hatch. Remove the battery and
replace it with a 9 V alkaline battery. Make sure the seal
is in place. Close the battery hatch and replace the screw.
10
SPECIFICATIONS
Operating voltage
LOW Range: 30 to 1500 VAC; HIGH Range: 1500 VAC to
122 kVAC
Operating Temperature: 0°C to +52°C (32°F to +125°F);
RH < 90%
Storage Temperature: 0°C to +52°C (32°F to +125°F)
battery removed
Environment: < 2000 m (1.24 mi), outdoor operation
Power: 9 V alkaline battery
Power Consumption:
OFF: 60 uA
Low Detection mode: 39 mA
High Detection mode: 39 mA
Duty Cycle: Continuous
Frequency Response: 50/60 Hz
Response Time: Instantaneous
Dimensions: 345(L) x 75(W) x 47(H) mm (13.5 x 3.0 x 1.8 in)
Weight: 243 g (0.5 lb)
Optional Accessory: TIC 410A Hot Stick
Electromagnetic Compatibility (EMC): EN 61326-1
Korea (KCC): Class A Equipment (Industrial Broadcasting
& Communication Equipment)
[1]
[1]
This product meets requirements for industrial (Class
A) electromagnetic wave equipment and the seller or
user should take notice of it. This equipment is intended
for use in business environments and is not to be used
in homes.
11
Sensitivity: LOW Voltage
Hold the TIC 300 PRO when making the detection range
measurement for LOW voltage range.
Voltage
(Phase to neutral with
890K Ohm load)
Detection Range
(From the TIP of probe to
the target line)
Average
30 V 3.8 cm (1.5 in)
75 V 16.5 cm (6.5 in)
100 V 21.6 cm (8.5 in)
120 V 25.4 cm (10 in)
220 V 33 cm (1 ft 1 in)
500 V 48.3 cm (1 ft 7 in)
1000 V 86.4 cm (2 ft 10 in)
Sensitivity: HIGH Voltage
The TIC 410A Hot Stick must be used when making
detection range measurement for HIGH voltage range.
Voltage
(Open Phase with no load)
Detection Range
(From the TIP of probe to
the target line)
Average
1.5 kV 12.7 mm (0.5 in)
2.0 kV 25.4 mm (1 in)
4.0 kV 5.1 cm (2 in)
10.0 kV 20.3 cm (8 in)
15.0 kV 35.6 cm (1 ft 2 in)
20.0 kV 50.8 cm (1 ft 8 in)
25.0 kV 66 cm (2 ft 2 in)
TIC 300 PRO
TIC Tracer haute tension –
Détecteur de tensions
alternatives sans contact
Mode d’emploi
10/2019, Rev006
©2019 Amprobe.
Tous droits réservés. Imprimé en Chine
Français
Limites de garantie et de responsabilité
Amprobe garantit l’absence de vices de matériaux et de
fabrication de ce produit pendant une période d’un an prenant
effet à la date d’achat. Cette garantie ne s’applique pas aux
fusibles, aux piles jetables ni à tout produit mal utilisé, modifié,
contaminé, négligé ou endommagé par accident ou soumis
à des conditions anormales d’utilisation et de manipulation.
Les revendeurs n’ont pas l’autorisation de prolonger toute autre
garantie au nom d’Amprobe. Pour bénéficier de la garantie,
renvoyez le produit accompagné d’un justificatif d’achat
auprès d’un centre de services agréé par Amprobe Test Tools ou
d’un distributeur ou d’un revendeur Amprobe. Voir la section
Réparation pour tous les détails. LA PRESENTE GARANTIE EST
LE SEUL ET EXCLUSIF RECOURS DE L’UTILISATEUR. TOUTES
AUTRES GARANTIES, EXPLICITES, IMPLICITES OU STATUTAIRES,
NOTAMMENT LES GARANTIES DE QUALITE MARCHANDE OU
D’ADAPTATION A UN OBJECTIF PARTICULIER SONT EXCLUES
PAR LES PRESENTES. LE FABRICANT NE SERA EN AUCUN CAS
TENU RESPONSABLE DE DOMMAGES PARTICULIERS, INDIRECTS,
ACCIDENTELS OU CONSECUTIFS, NI D’AUCUNS DEGATS OU
PERTES DE DONNEES, SUR UNE BASE CONTRACTUELLE, EXTRA-
CONTRACTUELLE OU AUTRE. Etant donné que certaines
juridictions n’admettent pas les limitations d’une condition
de garantie implicite ou l’exclusion ou la limitation de dégâts
accidentels ou consécutifs, il se peut que les limitations et les
exclusions de cette garantie ne s’appliquent pas à votre cas.
Réparation
Tous les outils de test renvoyés pour être réparés au titre de la
garantie doivent être accompagnés des éléments suivants : nom,
raison sociale, adresse, numéro de téléphone et justificatif d’achat.
Ajoutez également une brève description du problème ou du
service demandé et incluez les cordons de test avec l’appareil.
Les frais de remplacement ou de réparation hors garantie doivent
être acquittés par chèque, mandat, carte de crédit avec date
d’expiration, ou par bon de commande payable à l’ordre de
Amprobe
®
Test Tools.
Remplacements et réparations sous garantie – Tous pays
Veuillez lire la déclaration de garantie et vérifiez la pile avant
de demander une réparation. Pendant la période de garantie,
tout outil de test défectueux peut être renvoyé auprès de votre
distributeur Amprobe
®
Test Tools pour être échangé contre un
produit identique ou similaire. Consultez la section « Where to
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90

Amprobe TIC 300 PRO Non-Contact Voltage Detector Manuel utilisateur

Taper
Manuel utilisateur