Maico EKR 40 FU Mounting And Operating Instructions

Taper
Mounting And Operating Instructions

Ce manuel convient également à

Schallgedämmte Abluftbox
Sound-insulated ventilation box
Caisson d'air sortant insonorisé
EKR 20
EKR 25 EKR 25 FU
EKR 31 EKR 31 FU
EKR 35 EKR 35 FU
EKR 40 EKR 40 FU
Montage- und Betriebsanleitung
Mounting and Operating Instructions
Instructions de montage et Mode d'emploi
D GB F
www.maico-ventilatoren.com
de │ Inhaltsverzeichnis
2
Schallgedämmte Abluftbox
EKR 20 … EKR 40
EKR 25 FU … EKR 40 FU
Inhaltsverzeichnis
1. Lieferumfang ........................................................... 2
2. Verwendete Symbole .............................................. 2
2.1 Warnsymbole .................................................... 2
2.2 Sonstige Symbole ............................................ 2
3. Produktinformationen .............................................. 2
3.1 Geräteübersicht ................................................ 2
3.2 Produktbeschreibung ....................................... 3
3.3 Bestimmungsgemäße Verwendung ................. 3
3.4 Vorhersehbare Fehlanwendungen ................... 4
4. Technische Daten ................................................... 4
5. Umgebungsbedingungen und Grenzen
für den Betrieb ....................................................... 4
6. Grundlegende Sicherheitshinweise ........................ 4
6.1 Allgemeine Sicherheitshinweise ....................... 4
6.2 Sicheres und korrektes Verhalten
für den Betrieb ........................................................ 4
6.3 Betrieb mit raumluftabhängigen Feuerstätten .. 4
7. Montagevorbereitungen .......................................... 5
8. Montage .................................................................. 5
8.1 Umbau für 90°-Einbaulage ............................... 5
8.2 Gerätemontage Ausblasstutzen oben .............. 5
8.3 Gerätemontage Ausblasstutzen links/rechts ....... 6
8.4 Wetterschutzdach anbringen ............................ 6
8.5 Elektrischer Anschluss ..................................... 6
8.6 Inbetriebnahme................................................. 7
9. Wartung .................................................................. 7
10. Reinigung .............................................................. 7
11. Störungsbehebung ............................................... 8
12. Demontage ........................................................... 8
13. Entsorgung............................................................ 8
14. Schaltbilder ........................................................... 9
15. Abmessungen ..................................................... 11
1. Lieferumfang
Schallgedämmte Abluftbox, 2 Montageschienen,
4 Schwingungsdämpfer, Befestigungsmaterial,
Montage- und Betriebsanleitung.
EKR.. FU-Geräte mit Frequenzumrichter werden mit
einer zusätzlichen FU-Betriebsanleitung (für Motortype
siehe Typenschild auf dem Klemmenkasten) ausge-
liefert. Hier findet der Elektro-Fachinstallateur
detaillierte Frequenzumrichter-Informationen zum
Umgang, Einstellen oder zur Störungsbeseitigung.
2. Verwendete Symbole
2.1 Warnsymbole
GEFAHR
Lebensgefahr!
Eine Nichtbeachtung kann zum Tod
oder zu schweren Körperverletzungen
führen.
VORSICHT
Verletzungsgefahr!
Eine Nichtbeachtung kann zu leichten
bis mittleren Körperverletzungen
führen.
ACHTUNG
Sachschäden!
Eine Nichtbeachtung kann zu Sach-
schäden führen.
2.2 Sonstige Symbole
INFO-Symbol: Mit diesem Symbol
versehene Text-passagen geben Ihnen
wichtige Informationen und Tipps.
Aufzählungssymbol:
Liste mit wichtigen Informationen zum
jeweiligen Thema.
Handlungssymbol:
Liste mit durchzuführenden Tätigkeiten.
Führen Sie die angegebenen Anweisun-
gen der Reihe nach durch.
3. Produktinformationen
3.1 Geräteübersicht
1 Schwingungsdämpfer (Standfuß)
2 Montageschiene
3 Türstopper
4 Rampe
5 Halterung (2 Stück je Montageschiene)
5.1 Befestigungsschraube mit Unterlegscheibe
6 Unterlegscheibe mit Schraube
7 Revisionstür mit innenliegendem Laufrad
8 Türgriff
9 Motor
10 Klemmenkasten
11 Ausblasstutzen (Fortluft)
12 Türscharnier
13 Ansaugstutzen (Abluft)
14 Kondensat-Ablaufstutzen
i
Impressum
© Maico Elektroapparate-Fabrik GmbH.
Deutsche Originalanleitung. Druckfehler, Irrtümer
und technische Änderungen vorbehalten
.
3. Produktinformationen de
3.2 Produktbeschreibung
EKR-Abluftbox mit Radial-Rohrventilator, druck-
starke Ausführung.
Mit außenliegendem Motor, vom Luftstrom des
Fördermediums getrennt. Dadurch unempfindlich
gegen heiße, fettige oder verschmutzte Förder-
medien.
EKR-Standardausführung: Motorregelung erfolgt
mit externem Transformator, siehe Maico-Zubehör,
zum Beispiel 5-Stufentransformator TRE.
EKR .. FU-Ausführung mit integriertem Frequenz-
umrichter zur Motorregelung.
Motor für den Dauerbetrieb ausgelegt.
Durch doppelwandiges Gehäuse angenehm leise.
Ein-/Ausschalten des Gerätes mit externem Schalter.
3.3 Bestimmungsgemäße Verwendung
Als Abluftbox zur Förderung mittlerer bis großer
Luftmengen mit besonders hohen Widerständen.
Für den Einsatz mit Dunstabzugshauben, in Groß-
küchen, als Absauganlage für fettige oder ölige
Medien, als Arbeitsplatz- oder Maschinen-
absaugung geeignet.
Ventilator zur Förderung von feuchter, verschmutzter,
fetthaltiger oder heißer Luft im Bereich ihrer
Leistungskennlinien ausgelegt.
Bei Förderung von staubhaltige Medien ist ein
geeignetes Filter vorzuschalten.
Die Abluftbox ist ein Standgerät mit zulässiger Ein-
baulage mit Ausblasstutzen nach oben, rechts oder
links.
Der Betrieb ist nur zulässig, wenn Berührungsschutz
gemäß DIN EN 294 gewährleistet ist.
Durch Anschlussstutzen ist der direkte Einbau in
Lüftungsleitungen möglich. Je nach Geräteaus-
führung für Nennweiten DN 200 bis DN 400.
Eine Montage im Freien ist nur mit Wetterschutzdach
WSD 20-40 zulässig.
de 3. Produktinformationen
4
3.4 Vorhersehbare Fehlanwendungen
Maico haftet nicht für Schäden durch bestimmungs-
widrigen Gebrauch. Gerät auf keinen Fall einsetzen:
wenn ein Kondensatablauf bei Einbaulage mit
Ausblasstutzen nach rechts oder nach links benötigt
wird. Der Kondensatablauf wird nur bei Einbaulage
mit Ausblasstutzen nach oben gewährleistet.
in der Nähe von brennbaren Materialien, Flüssig-
keiten oder Gasen.
in explosionsfähiger Atmosphäre.
mit abgedecktem Motor (Überhitzungsgefahr).
4. Technische Daten
Bemessungs-
spannung
230 V
Netzfrequenz
50 Hz
Schutzart
IP 54 bei geschlossener
Revisionstür sowie saug-
und druckluftseitigem
Rohranschluss
Für weitere technische Daten siehe Typenschild oder
Internet. Für Gehäuseabmessungen siehe Kapitel 15.
5. Umgebungsbedingungen und
Grenzen für den Betrieb
Zulässige Umgebungstemperatur max. 50 °C,
für EKR..FU-Geräte max. 40 °C.
Zulässige Fördermitteltemperatur max. 120 °C.
Bei Betrieb mit raumluftabhängigen Feuerstätten
beträgt die maximal zulässige Druckdifferenz pro
Wohneinheit 4 Pa.
6. Grundlegende Sicherheitshinweise
6.1 Allgemeine Sicherheitshinweise
Sicherheitshinweise vor Inbetriebnahme aufmerksam
durchlesen.
Anleitung aufbewahren.
Das Gerät darf nicht als Spielzeug verwendet
werden.
Montage nur durch Fachkräfte zulässig.
Elektrischer Anschluss und Reparaturen nur durch
Elektrofachkräfte zulässig.
Gerät nur an fest verlegte elektrische Installation mit
Leitungen Typ NYM-O oder NYM-J (3 x 1,5 mm²)
anschließen. Zusätzlich ist eine Vorrichtung zur
Trennung vom Netz mit mindestens 3 mm Kontakt-
öffnung je Pol erforderlich.
Abluftbox nur mit auf Typenschild angegebener
Spannung und Frequenz betreiben.
Abluftbox nur auf den Montageschienen mit
Schwingungsdämpfern stehend montieren.
Bei starker Kondensatbildung im Ventilatorgehäuse
den ordnungsgemäßen Kondensatabfluss sicher-
stellen.
Abluftbox nur mit geschlossener Revisionstür
betreiben.
Vor dem Öffnen der Revisionstür das Gerät allpolig
vom Netz trennen.
Revisionstür nur bei Stillstand des Laufrades öffnen.
Vor dem Öffnen stets abwarten, bis das Laufrad still
steht.
Gerät nur in Betrieb nehmen, wenn der Berührungs-
schutz des Laufrades gemäß DIN EN 294 gewähr-
leistet ist. Hierzu muss abluft- und fortluftseitig
jeweils ein Lüftungsrohr mit mindestens 1 m Länge
oder ein Schutzgitter angebracht sein.
Veränderungen und Umbauten am Gerät sind nicht
zulässig und entbinden Maico von jeglicher Gewähr-
leistung und Haftung.
6.2 Sicheres und korrektes Verhalten für den
Betrieb
Bei Fehlverhalten besteht direkte Verletzungsgefahr
für das Bedien- oder Reinigungspersonal !
Die Revisionstür ist sehr schwer. Zur Vermeidung
von Verletzungen stets die herausgeschwenkte
Revisionstür mit Türstopper [3] fixieren.
Keine Gegenstände in das Gerät oder das
Schutzgitter stecken.
Das Gerät ist nicht dafür bestimmt, durch Menschen
benutzt zu werden, deren physische, sensorische
oder geistige Fähigkeiten nicht genügen, die
Sicherheits-hinweise dieser Anleitung zu verstehen
und umzusetzen. Diese Einschränkung bezieht sich
auch auf Kinder.
Das Gerät kann dennoch von diesen Menschen
gefahrlos benutzt werden, sofern sie von einer für
ihre Sicherheit zuständige Person beaufsichtigt oder
in geeigneter Weise unterwiesen werden.
6.3 Betrieb mit raumluftabhängigen
Feuerstätten
Bei Betrieb mit raumluftabhängigen Feuerstätten
muss für ausreichende Zuluftnachströmung gesorgt
werden.
7. Montagevorbereitungen de
7. Montagevorbereitungen
Hinweise
Für Geräteabmessungen siehe Kapitel 15.
Einbauort so wählen, dass sich die Revisionstür weit
öffnen lässt, damit Sie an das Laufrad gelangen und
den Innenbereich der Abluftbox reinigen können.
Ausgeliefert wird die Abluftbox für eine Einbaulage
mit Ausblasstutzen nach oben.
Bei um 90° gedrehtem Einbau der Abluftbox müssen
die Scharniere und auch der Türgriff an der
Revisionstür umgebaut werden. Die Revisionstür
wird dabei nicht gedreht, sie bleibt in ihrer
ursprünglichen Position.
Für die Wand- oder Deckenmontage ist eine geeig-
nete Halterung anzubringen, um die Abluftbox als
Standgerät aufstellen zu können. Decke, Wand und
Halterung müssen eine ausreichende Tragkraft für
das Gesamtgewicht aufweisen. Geeignetes
Befestigungsmaterial ist bauseitig bereitzustellen.
Wenn mit erhöhter Kondensatbildung zu rechnen ist,
unbedingt den Kondensatabfluss sicherstellen. Dazu
ist eine Abflussleitung mit Siphon am Kondensatab-
laufstutzen [14] anzuschließen.
Die Installation mit Kondensatablauf ist nur bei
Geräte-Einbaulage mit Ausblasstutzen nach
oben zulässig. Nur dann befindet sich Ablaufstutzen
[14] unten und der sichere Kondensatabfluss ist
gewährleistet.
8. Montage
8.1 Umbau für 90°-Einbaulage
Bei um 90° gedrehter Abluftbox werden die Tür-
scharniere gegenüberliegend dem Ausblasstutzen
montiert.
Der Türgriff wird ummontiert.
Gerät vorsichtig auf die Rückseite (Ansaugstutzen)
legen.
Schraube/Unterlegscheibe [6] ummontieren
(je nach Einbaulage, siehe Pfeile oben).
Beide Türscharniere [12] entfernen.
Revisionstür nicht drehen, sie bleibt in ihrer
ursprünglichen Position.
Beide Türscharniere an der Geräteunterseite und
der Revisionstür ( Kreisausschnitte) anbringen und
fest anziehen.
Türgriff [2] entfernen und an der seitlichen Montage-
position (Abbildungen oben) anbringen.
Kondensat-Ablaufstutzen [14] mit Dichtmaterial
verschließen.
8.2 Gerätemontage Ausblasstutzen oben
Gerät vorsichtig auf die Rückseite (Ansaugstutzen)
legen.
Beide Montageschienen [2] an den Halterungen [5]
mit dem Gehäuse (Pos. A) verschrauben. Beigefügte
Schrauben und Unterlegscheiben [5.1] verwenden.
Die 4 Schwingungsdämpfer [1] mit beigefügten
Hutmuttern auf die Montageschienen schrauben.
Gerät aufstellen und waagerecht am Montageort
abstellen. Darauf achten, dass dieses sicher auf
den Schwingungsdämpfern steht.
Bodenunebenheiten mit bauseitig bereitzustellenden
Distanzstücken ausgleichen.
Lüftungsleitungen abluft- und fortluftseitig an der
Abluftbox anschließen. Dazu saug- und druck-
luftseitig eine elastische Befestigungsmanschette
ELR.. verwenden, um Schwingungsübertragungen
auf das Rohrsystem zu verhindern.
i
i
de 8. Montage
6
8.3 Gerätemontage Ausblasstutzen links/rechts
Abluftbox wie in Kapitel 8.2 beschrieben aufstellen.
Jedoch die beiden Montageschienen [2] an den
Positionen „B“ oder „C“ anbringen:
Ausblas nach links = Pos. B / nach rechts = Pos. C
8.4 Wetterschutzdach anbringen
Wird die EKR-Abluftbox im Freien aufgestellt, ist
die Montage des Wetterschutzdaches WSD 20-40
vorgeschrieben.
Wetterschutzdach mit beigefügtem Befestigungs-
material an den 4 Montagepositionen fest mit der
Revisionstür verschrauben.
8.5 Elektrischer Anschluss
GEFAHR
Lebensgefahr durch Stromschlag.
Netzsicherung ausschalten.
Warnschild gegen Wiedereinschalten
anbringen.
ACHTUNG
Kurzschluss durch Nässe bei nicht
ordnungsgemäßer Einführung der
Anschlussleitungen in den Klemmen-
kasten.
Anschlussleitungen durch die PG-Ver-
schraubungen in den Klemmenkasten
führen. Darauf achten, dass die
Gummidichtungen die Leitungen
dicht umschließen.
EKR 20 ... EKR 40
Gerät allpolig vom Netz trennen. Dazu Netz-
sicherung im Sicherungskasten ausschalten.
Unbedingt auch den TK-Stromkreis der Thermo-
kontakte vom Netz trennen.
Abluftbox an der Klemmleiste im Klemmenkasten
[10] gemäß Schaltbild ( Kapitel 14) elektrisch
verdrahten.
Die Thermokontakte des Motors sind auf Klemmen
geführt zur Kombination mit Steuerschütz oder
Motorvollschutzschalter MVE 10. Die Verdrahtung
ist so vorzunehmen, dass keine automatische
Anschaltung erfolgen kann (Selbsthaltung).
EKR 25 FU … EKR 40 FU
ACHTUNG
Sachschäden bei fehlerhaftem
elektrischem Anschluss.
Beachten Sie unbedingt die zusätz-
lichen Instruktionen der Zusatz-
Motorenanleitung „Grundfos“!
Hinweise
Der Motor kann über einen externen, potenzialfreien
Kontakt über das Netz ein- bzw. ausgeschaltet wer-
den, siehe Schaltbild in Kapitel 14, Klemme 2 und 3.
Verwenden Sie abgeschirmte Leitungen, insbeson-
dere für den externen Ein-/Aus-Schalter, die Digi-
taleingänge und die Sollwert- bzw. Sensorsignale.
Der Motor läuft nach ca. 5 Sekunden an, wenn
dieser über das Netz eingeschaltet wird. Über den
externen Ein-/Aus-Schalter darf der Motor maximal
3 bis 4-mal pro Stunde ein-/ausgeschaltet werden.
Gerät allpolig vom Netz trennen. Dazu Netz-
sicherung im Sicherungskasten ausschalten.
Abluftbox an der Klemmleiste im Klemmenkasten
[10] gemäß Schaltbild ( Kapitel 14) elektrisch
verdrahten.
i
8. Montage de
8.6 Inbetriebnahme
Übereinstimmung mit den technischen Daten
kontrollieren, siehe Kapitel 4 und Typenschild.
Vor dem Öffnen der Revisionstür das Gerät allpolig
vom Netz trennen. Dazu Netzsicherung im Siche-
rungskasten ausschalten! Unbedingt auch den TK-
Stromkreis der Thermokontakte vom Netz trennen.
VORSICHT
Einklemm- bzw. Quetschgefahr durch
Zurückschwenken der schweren
Revisionstür.
Revisionstür unbedingt mit Türstopper
[3] sichern.
Revisionstür öffnen. Dazu beide Schrauben/Unter-
legscheiben [6] entfernen, Revisionstür über die
2. Montageschiene hinausschwenken und sichern.
Gehäuse-Innenbereich und auch das Laufrad gemäß
Kapitel 10 reinigen. Dafür sorgen, dass sich keine
Fremdkörper (z. B. Schrauben) im Innenbereich
befinden.
Revisionstüre vorsichtig schließen. Rampe [4] muss
dabei so eingestellt sein, dass sich die Revisionstüre
leicht und ohne Spannungen verschließen lässt.
Darauf achten, dass die Tür auch dicht schließt.
Beide Unterlegscheiben auflegen und Revisionstür
mit Schrauben [6] fest verschrauben.
Sicherstellen, dass die Ansaug- und Ausblas-
öffnungen des Lüftungssystems offen sind.
Netzsicherung einschalten. Funktionstest durch-
führen.
9. Wartung
Die Abluftbox ist wartungsfrei.
10. Reinigung
Die Reinigung darf nur von autorisierten Fachkräften
vorgenommen werden
GEFAHR
Gefahr durch elektrischen Schlag.
Gerät allpolig vom Netz trennen und
gegen Inbetriebnahme sichern.
Unbedingt auch den TK-Stromkreis der
Thermokontakte allpolig vom Netz
trennen.
VORSICHT
Verletzungsgefahr durch sich
drehendes Laufrad.
Vor dem Öffnen der Revisionstür
unbedingt den Stillstand des Laufrades
abwarten.
Reinigungsintervalle
Alle 3 Monate. Bei starker Verschmutzung kürzere
Reinigungsintervalle wählen.
Reinigen
Durch mitgeführten Staub, Fett oder ähnliche
Stoffe können Ablagerungen im Ventilator-
gehäuse und auf dem Laufrad entstehen. Diese
Ablagerungen können eine Unwucht, einen
unruhigen Lauf und sogar eine Beschädigung
des Motorlagers verursachen.
Revisionstür öffnen. Dazu die beiden Schrauben [6]
entfernen und die Revisionstür herausschwenken.
VORSICHT
Einklemm- bzw. Quetschgefahr
durch schwere Revisionstür.
Revisionstür mit Türstopper [3] gegen
Zurückschwenken sichern.
Laufrad und den Gehäuse-Innenbereich kontrollieren
(Sichtkontrolle).
Laufrad mit einem angefeuchteten Tuch reinigen,
dazu kein fließendes Wasser verwenden.
Zum Reinigen keine scharfen, gesundheits-
schädlichen und niemals leicht entflammbare
Reinigungsmittel verwenden.
Revisionstür schließen, mit beiden Schrauben [6]
verschrauben.
Netzsicherungen einschalten.
i
i
de 11. Störungsbehebung
8
11. Störungsbehebung
Eine Störung kann z. B. durch erhöhte Fördermittel-
temperaturen oder durch Blockieren des Ventilator-
motors auftreten. Der Überlastungsschutz reagiert und
der Ventilator schaltet aus.
Wird kein Motorvollschutzschalter oder ein als
Selbsthalter verkabeltes Steuerschütz verwen-
det, läuft der Ventilator nach Abkühlendes
Ventilatormotors automatisch wieder an.
GEFAHR
Gefahr durch elektrischen Schlag.
Vor Arbeiten an der Elektrik oder im
Störungsfall das Gerät allpolig vom
Netz trennen und gegen Inbetrieb-
nahme sichern.
Unbedingt auch den TK-Stromkreis der
Thermokontakte allpolig vom Netz
trennen.
VORSICHT
Verletzungsgefahr durch sich
drehendes Laufrad.
Vor dem Öffnen der Revisionstür den
Stillstand des Laufrades abwarten.
EKR 20 ... EKR 40
Bei einer Störung generell prüfen, ob die
Netzsicherung eingeschaltet ist.
Ventilator auf korrekte Verkabelung prüfen.
Wird ein Motorvollschutzschalter als Sicherheits-
einrichtung verwendet, muss der Motorvollschutz-
schalter bei einer Störung ansprechen. Vor dem
Starten des Ventilators den Ventilatormotor abkühlen
lassen und den Motorvollschutzschalter entriegeln.
Der Ventilator läuft wieder an.
Wird ein als Selbsthalter verkabeltes Steuerschütz
als Sicherheitseinrichtung verwendet, muss das
Steuerschütz bei einer Störung ansprechen. Vor
dem Starten des Ventilators den Ventilatormotor
abkühlen lassen und das Steuerschütz entriegeln.
Der Ventilator läuft wieder an.
Besteht die Störung weiterhin oder tritt diese wieder-
holt auf, ist das Gerät spannungsfrei zu schalten und
eine Elektrofachkraft hinzuziehen.
EKR 25 FU … EKR 40 FU
Motorschutz: Der Motor benötigt keinen
externen Motorschutz. Er ist sowohl gegen
langsam auftretende Überlastung als auch
gegen Blockierung geschützt ( IEC 34-11:
TP 211).
Impulsüberspannungsschutz: Der Motor
ist gegen Impulsüberspannungen geschützt
( EN 61800-3).
Detaillierte Informationen zu Störungsmeldungen
finden Sie in der zusätzlichen Motorenanleitung
„Grundfos“!
Bei einer Störung generell prüfen, ob die Netz-
sicherung eingeschaltet ist.
Ventilator auf korrekte Verkabelung prüfen.
Besteht die Störung weiterhin oder tritt diese wieder-
holt auf, ist das Gerät spannungsfrei zu schalten und
eine Elektrofachkraft hinzuziehen.
12. Demontage
GEFAHR
Gefahr durch elektrischen Schlag.
Gerät allpolig vom Netz trennen und
gegen Inbetriebnahme sichern.
Die Demontage darf nur von Elektrofachkräften
vorgenommen werden.
13. Entsorgung
Entsorgen Sie das Gerät nach Ablauf seiner
Lebensdauer nach den in Ihrem Land geltenden
Bestimmungen.
Nicht in den Restmüll ! Das Gerät enthält teils
wiederverwertbare Stoffe, teils Substanzen, die
nicht in den Restmüll gelangen dürfen.
i
i
i
i
14. Schaltbilder de
14. Schaltbilder
EKR ..
EKR .. mit MVE 10 und TRE
de 14. Schaltbilder
10
EKR .. FU: Standardanschluss
EKR .. FU: Optionen
EKR .. FU: Optionen
15. Abmessungen de
15. Abmessungen
gb Table of contents
12
Sound-insulated ventilation air box
EKR 20 … EKR 40
EKR 25 FU … EKR 40 FU
Table of contents
1. Scope of delivery .................................................. 12
2. Symbols used ....................................................... 12
2.1 Warning symbols ............................................ 12
2.2 Other symbols ................................................ 12
3. Product information ............................................... 12
3.1 Equipment overview ....................................... 12
3.2 Product description ......................................... 13
3.3 Intended use ................................................... 13
3.4 Foreseeable cases of misuse ......................... 14
4. Technical data ...................................................... 14
5. Environmental conditions and operating limits ..... 14
6. Essential safety instructions ................................. 14
6.1 General safety instructions ............................. 14
6.2 Safe and correct practices during operation .. 14
6.3 Operation with air-ventilated fireplaces .......... 14
7. Installation preparations ........................................ 15
8. Assembly .............................................................. 15
8.1 Conversion for 90° installation position .......... 15
8.2 Device installation, exhaust socket on the top... 15
8.3 Device installation, exhaust socket left/right ...... 16
8.4 Installing the weather protection roof ............. 16
8.5 Electrical connection ...................................... 16
8.6 Start-up ........................................................... 17
9. Maintenance ......................................................... 17
10. Cleaning .............................................................. 17
11. Fault rectification ................................................. 18
12. Dismantling ......................................................... 18
13. Disposal .............................................................. 18
14. Wiring diagrams .................................................. 19
15. Dimensions ......................................................... 21
1. Scope of delivery
Sound-insulated ventilation box, 2 Mounting tracks,
4 Vibration dampers, Mounting material, Mounting
and Operating instructions
EKR... FU devices with frequency converter are
supplied with additional FU Operating instructions
(please refer to rating plate on the terminal box for
the motor type). Here, the specialist installer will
find detailed information about handling and adjusting
the frequency converter and about fault rectification.
2. Symbols used
2.1 Warning symbols
DANGER
Danger to life.
Non-observance can lead to death or
serious bodily injuries.
CAUTION
Danger of injury
Non-observance can lead to minor or
more serious bodily injuries.
NOTICE
Property damage.
Non-observance can lead to damage to
property.
2.2 Other symbols
INFO symbol: Text passages marked
with this symbol contain important
information and tips.
List symbol:
List with important information about
the corresponding subject.
Action symbol:
List of work to be carried out. Follow the
instructions given in the order stated.
3. Product information
3.1 Equipment overview
1 Vibration damper (Support foot)
2 Mounting tracks
3 Door stopper
4 Ramp
5 Holder (2 pieces per mounting track)
5.1 Fixing screws with washers
6 Washer with screw
7 Service door with internal impeller
8 Door handle
9 Motor
10 Terminal box
11 Exhaust socket (outgoing air)
12 Door hinge
13 Intake socket (exhaust air)
14 Condensate discharge outlet
i
Acknowledgements
© Maico Elektroapparate-Fabrik GmbH. This is a
translation of the German original operating
instructions. We are not responsible for mistakes or
printing errors and retain the right to make technical
modifications without giving prior notice.
3. Product information gb
3.2 Product description
EKR ventilation box with centrifugal duct fan, high
pressure model.
With external motor, separated from the air flow of
the air medium. Therefore, it is not sensitive to hot,
greasy and polluted air streams.
EKR standard model: The motor is controlled by
an external transformer, see Maico accessories,
e.g. the TRE 5-step transformer.
EKR... FU Model with integrated frequency
converter for motor control.
Motor designed for continuous operation.
Pleasantly quiet thanks to double-wall housing.
Unit is switched on/off with an external switch.
3.3 Intended use
As an exhaust air box for the transport of medium to
larger air volumes with particularly high resistances.
For deployment with extractor hoods, in large
kitchens, as an air extraction system for greasy or
oily air. Suitable for workplace or machine air
extraction.
Fan for the transport of damp, polluted, greasy or
hot air within the scope of its performance
characteristics.
A suitable filter should be installed upstream when
transporting dusty air.
The ventilation box is a floor-mounted unit with
permitted installation position such that the exhaust
socket is directed up, to the right or to the left.
The unit may only be operated, if protection against
accidental contact is guaranteed in accordance with
DIN EN 294.
Direct installation on ventilation ducts is possible
through the connection socket. For nominal sizes of
Ø 200 to Ø 400 mm depending on the unit housing.
External installation is only permitted with a
WSD 20-40 weather protection roof.
gb 3. Product information
14
3.4 Foreseeable cases of misuse
Maico is not liable for damages caused by usage not
for the intended purpose. The fan unit should not
be used:
if a condensation drain to is needed to the right or
left with an installation position with exhaust socket.
Condensation drain is only guaranteed with an
installation position where the exhaust socket is
directed upwards.
close to flammable materials, liquids or gasses.
in potentially explosive atmospheres
with covered motor (danger of overheating)
4. Technical data
Rated voltage
230 V
Power frequency
50 Hz
Degree of protection
IP 54 degree of
protection with closed
service door as well as
duct connections fitted on
the inlet and outlet sides.
For more technical data, see rating plate or Internet.
Refer to Chapter 15 for housing dimensions.
5. Environmental conditions and
operating limits
Permitted max. ambient temperature 50 °C, for
EKR..FU units, max. 40 °C.
Permitted max. airstream temperature: 120 °C
When operating with air-ventilated fireplaces,
the maximum permitted pressure difference per
living unit is 4 Pa.
6. Essential safety instructions
6.1 General safety instructions
Read the safety instructions through carefully before
commissioning.
Keep the instructions.
The device must not be used as a toy.
Mounting is only permitted when carried out by
trained specialists.
Electrical connections and repairs only permitted
when carried out by trained specialists.
Only connect device to permanently wired electrical
installations with NYM-O or NYM-J, (3 x 1.5 mm²)
type cables. Additionally, a mains isolation device
is required with contact openings of at least 3 mm
at each pole.
The ventilation box may only be operated using the
voltage and frequency shown on the rating plate.
Only floor-mount the ventilation box on the mounting
tracks with vibration dampers.
If there is a heavy build of condensation on the fan
housing, make sure there is sufficient condensation
run-off.
Only operate the ventilation box when the service
door is closed.
Disconnect the unit completely from the power
supply before opening the service door.
Only open the service door when the impeller has
come to a complete stop. Wait until the impeller is
stationary before opening.
The device may only be operated if the protection
against accidental contact with the impeller is
guaranteed to be in accordance with DIN EN 294.
For this purpose, a ventilation duct at least 1 meter
long on both the exhaust air and outgoing air side
or a protective grille must be installed.
Modifications and alterations to the unit are not
permitted and release Maico from any guarantee
obligations and liability.
6.2 Safe and correct practices during
operation
In the case of incorrect use, there is a direct risk of
injury to operational or cleaning personnel.
The service door is very heavy. In order to avoid
injuries, always fix the opened service door in place
with door stoppers [3].
Do not insert any objects in the unit or the protective
grille.
The unit is not intended to be used by people whose
physical, sensory or mental capabilities are not
sufficient for them to understand and put into
practice the safety information provided in these
instructions. This limitation also applies to children.
The unit may however be safely used by such
persons if they are supervised by someone
responsible for their safety or if they are instructed
in a suitable way.
6.3 Operation with air-ventilated fireplaces
Sufficient supply air intake must be ensured during
operation with air-ventilated fireplaces.
7. Installation preparations gb
7. Installation preparations
Notes
Refer to Chapter 15 for housing dimensions.
Select the installation location such that the service
door can be opened wide, so that you can get to the
impeller and clean the inside of the ventilation box.
The ventilation box is supplied for an installation
position with the exhaust socket directed upwards.
If the ventilation box is to be turned through 90° for
installation, the hinges and the door handle on the
service door must be adjusted. The service door is
not turned for this purpose. It stays in its original
position.
A suitable holder must be used for wall or ceiling
mounting, in order to be able to install the ventilation
box as a floor-mounted unit. Ceiling, wall and holder
must have sufficient load-bearing capacity for the
total weight. Suitable mounting material is to be
supplied by the customer.
If an increased build-up of condensation is expected,
the condensation run-off must be ensured. To do
this, connect a drain tube with siphon to the
condensation discharge outlet [14].
Installation with condensation run-off is only
permitted with a device installation position
where the exhaust socket is directed upwards.
Only in this case is the discharge outlet [14] at the
bottom and the secure run-off of condensation is
guaranteed.
8. Assembly
8.1 Conversion for 90° installation position
When the ventilation box is turned through 90°, the
door hinges are installed opposite the exhaust
socket.
The door handle is repositioned.
Carefully lay the device on its back (intake sockets).
Reposition the screw/washer [6] (depending on the
installation position, see arrow above).
Remove both door hinges [12].
Do not turn the service door. It stays in its
original position.
Mount both door hinges on the underside of the
device and the service door (→ circular cut-out) and
screw securely into place.
Remove the door handle [2] and mount it at the side
installation position (→ figure above).
Close off the condensate discharge outlet [14] with
sealing material.
8.2 Device installation, exhaust socket on the
top
Carefully lay the device on its back (intake sockets).
Screw both mounting tracks [2] at the holders [5] to
the housing (Pos. A). Use the supplied screws and
washers [5.1].
Screw the 4 vibration dampers [1] to the mounting
tracks with the supplied cap nuts.
Install the device and locate it horizontally at the
installation location. Make sure that it is securely
located on the vibration dampers.
Provide spacers to compensate for any unevenness
in the floor.
Connect ventilation ducts to the ventilation box on
the exhaust air and outgoing air sides. Use an ELR
flexible fixing cuff on both the suction and pressured
air side, to avoid the transmission of vibrations to the
duct system.
i
i
gb 8. Assembly
16
8.3 Device installation, exhaust socket left/right
Installation of the ventilation box as described in
Chapter 8.2. In this case however, install both
mounting tracks [2] in positions "B" or "C":
Air outlet to the left = Pos. B / to the right = Pos. C.
8.4 Installing the weather protection roof
If the EKR ventilation box is to be installed outdoors,
the WSD 20-40 Weather protection roof must be
installed.
Screw the weather protection roof firmly to the 4
installation positions on the service door, with the
mounting material supplied.
8.5 Electrical connection
DANGER
Danger to life from electric shock.
Switch the mains fuse off.
Position a warning notice to avoid the
unit being switched back on.
NOTICE
Danger of short-circuits caused by
damp if the connection cables are not
inserted correctly into the terminal
box.
Feed the connection cables into the
housing through the PG screw-
connections. Ensure that the rubber
seals fit tightly round the cables.
EKR 20 ... EKR 40
Disconnect the unit completely from the mains power
supply. Switch the mains fuse in the fuse box off.
Also make sure that the TC power circuit to the
thermal contacts is disconnected from the power
supply.
Connect the electric cables of the ventilation box to
the terminal block in the terminal box [10] in
accordance with the wiring diagram (→ Chapter 14).
The motor's thermal contacts are connected to
terminals, to allow combination with control contactor
or MVE 10 motor protection switch. The wiring must
be done so that switch-on cannot happen
automatically (locking).
EKR 25 FU … EKR 40 FU
NOTICE
Material damage can result from
incorrect electrical connections.
The additional instructions
contained in the "Grundfos"
Motor manual must be followed.
Notes
The motor can be switched on or off through an
external potential-free contact, see wiring diagram
in Chapter 14, terminals 2 and 3.
Use screened cables, especially for the external
on/off switch, the digital inputs and the setpoint
and/or sensor signals.
The motor starts up after approx. 5 seconds, if it is
switched on through the mains power. The motor
may be switched on/off a maximum of 3 to 4 times
an hour, using the external on/off switch.
Disconnect the unit completely from the mains power
supply. Switch the mains fuse in the fuse box off.
Connect the electric cables of the ventilation box to
the terminal block in the terminal box [10] in accor-
dance with the wiring diagram (→ Chapter 14).
i
8. Assembly gb
8.6 Start-up
Check that the technical data has been adhered to,
by reference to Chapter 4 and the rating plate.
Disconnect the unit completely from the power
supply before opening the service door. Switch the
mains fuse in the fuse box off. Also make sure that
the TC power circuit to the thermal contacts is
disconnected from the power supply.
CAUTION
Danger of trapping or crushing if the
heavy service door swings back.
The service door must be secured
using door stopper [3].
Open the service door. To do this, remove both
screws and washers [6], swing the service door
out over the second mounting track and secure it.
Clean the inside of the housing and the impeller as
described in Chapter 10. Make sure that there are no
loose foreign bodies, e.g. screws inside the housing.
Close the service door carefully, The ramp [4] must
be adjusted such that the service door can be closed
easily and without any tension. Make sure that the
door also closes tightly.
Position the two washers and screw the service door
firmly closed with the screws [6][.
Ensure that the ventilation system suction and outlet
openings are open.
Switch the mains fuse on. Carry out a function test.
9. Maintenance
The ventilation box is maintenance-free.
10. Cleaning
Cleaning may only be undertaken by authorised
specialist personnel.
DANGER
Risk of electric shock.
Disconnect the device completely from
the power supply and secure it against
being started up.
Also make sure that the TC power
circuit to the thermal contacts is
disconnected from the power supply.
CAUTION
Danger from rotating impeller.
Make sure the impeller has come to a
complete stop before opening the
service door.
Cleaning intervals
Every 3 months. Select shorter cleaning intervals in
the case of heavy contamination.
Cleaning
Deposits can build up on the fan housing and
the impeller through the intake of dust, grease or
similar materials. These build-ups can cause an
imbalance, noisy operation or even damage the
motor bearing.
Open the service door. To do this, remove both
screws [6] and swing the service door outwards.
CAUTION
Danger of trapping or crushing
because of heavy service door.
Secure the service door against
swinging back with door stopper [3].
Carry out a visual check of the impeller and the
inside of the housing.
Clean the impeller with a damp cloth. Do not use
running water.
Do not use aggressive, harmful or easily
flammable cleaning agents for cleaning work.
Close the service door and secure it with both
screws.
Switch the mains fuse on.
i
i
gb 11. Fault rectification
18
11. Fault rectification
A fault can occur if, for example, the airstream
temperature increases or if the fan motor is blocked.
The overload protection kicks in and the fan switches
off.
If no motor protection switch or self-holding,
cabled control contactor is used, the fan starts
up again automatically after the fan motor has
cooled down.
DANGER
Risk of electric shock.
Disconnect the device completely from
the mains power supply and protect it
against be started up before starting
work on the electrical system or in the
case of a fault.
Also make sure that the TC power
circuit to the thermal contacts is
completely disconnected from the
power supply.
CAUTION
Danger from rotating impeller.
Make sure the impeller has come to a
complete stop before opening the
service door.
EKR 20 ... EKR 40
If the fan fails to operate, always check whether the
mains fuse is switched on.
Check that the cabling of the fan is correct.
If a motor protection switch is used as a safety
device, the motor protection switch must be activated
in the case of a fault. Before starting the fan, let the
fan motor cool down and release the motor
protection switch. The fan starts up again.
If a self-holding, cabled control contactor is used as
a safety device, the control contactor must be
activated in the case of a fault. Before starting the
fan, let the fan motor cool down and release the
control contactor. The fan starts up again.
If the fault still continues or occurs again, disconnect
the device from the mains and call on the services of
a trained electrician.
EKR 25 FU … EKR 40 FU
Motor protection: The motor does not require
any external motor protection. It is protected
against slowly developing overload as well as
blocking (IEC 34-11: TP 211).
Voltage surge protection: The motor is
protected against pulse overvoltage
(→ EN 61800-3).
You will find detailed information about fault
messages in the in the additional "Grundfos"
Motor manual.
If the fan fails to operate, always check whether the
mains fuse is switched on.
Check that the cabling of the fan is correct.
If the fault still continues or occurs again, disconnect
the device from the mains and call on the services of
a trained electrician.
12. Dismantling
DANGER
Risk of electric shock.
Disconnect the device completely from
the power supply and secure it against
being started up.
Dismantling may only be undertaken by a specialist
electrician.
13. Disposal
Dispose of the unit once it has reached the end of its
working life according to the regulations valid where
you are.
Do not dispose of it in domestic waste!
The unit contains in part material that can be
recycled and in part substances that should
not end up as domestic waste.
i
i
i
i
14. Wiring diagrams gb
14. Wiring diagrams
EKR...
EKR .. with MVE 10 and TRE
gb 14. Wiring diagrams
20
EKR... FU: Standard connection
EKR... FU: Options
EKR... FU: Options
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Maico EKR 40 FU Mounting And Operating Instructions

Taper
Mounting And Operating Instructions
Ce manuel convient également à

dans d''autres langues