INSTRUCTION MANUAL
ENGLISH
FRANÇAIS pg. 33
ESPAÑOL pg. 17
2000A
Digital Clamp Meter
1000V
2000A
60M
Ω
True RMS
Measurement
Technology
NON-CONTACT
VOLTAGE TESTING
INRUSH CURRENT
LOW IMPEDANCE
DATA HOLD
RANGE HOLD
AUDIBLE
CONTINUITY
DIODE TEST
CAPACITANCE
FREQUENCY
2
m IP40
CL900
4007177
2
GENERAL SPECIFICATIONS
Klein Tools CL900 is an auto-ranging, true root mean square (TRMS)
digital clamp meter that measures AC/DC current via the clamp and
measures AC/DC voltage, resistance, continuity, frequency, duty-
cycle, capacitance, and tests diodes via test-leads. It features a Low
Impedance (LoZ) mode for identifying and eliminating ghost or stray
voltages, and has a dedicated mode for capturing Inrush Current.
Operating Altitude: 6562 ft. (2000m)
Relative Humidity: <80% non-condensing
Operating Temperature: 32° to 122°F (0° to 50°C)
Storage Temperature: 14° to 140°F (-10° to 60°C)
Accuracy: Values stated at 65° to 83°F (18° to 28°C)
Temp Coefcient: 0.1 x (Quoted Accuracy) per °C above
28°C or below 18°C, corrections are required when ambient
working temp is outside of Accuracy Temp range
Dimensions: 10.4" x 3.9" x 1.7" (265 x 99 x 43 mm)
Weight: 18.6 oz. (526 g) including batteries
Calibration: Accurate for one year
Standards: Conforms to UL STD 61010-1, 61010-2-032,
61010-2-033.
Certified to CSA STD C22.2 # 61010-1,
61010-2-032, 61010-2-033.
IEC EN 61010-1, 61010-2-032,
61010-2-033.
Pollution degree: 2
Accuracy: ± (% of reading + # of least significant digits)
Drop Protection: 6.6 ft. (2m)
Safety Rating: CAT IV 600V, CAT III 1000V, Class 2,
Double insulation
CAT III: Measurement category III is applicable to test and
measuring circuits connected to the distribution part of the
building’s low-voltage MAINS installation.
CAT IV: Measurement category IV is applicable to test and
measuring circuits connected at the source of the building’s
low-voltage MAINS installation.
Electromagnetic Environment: IEC EN 61326-1. This
equipment meets requirements for use in basic and controlled
electromagnetic environments like residential properties,
business premises, and light-industrial locations.
Specifications subject to change.
ENGLISH
3
ELECTRICAL SPECIFICATIONS
Function Range Resolution Accuracy (50/60 Hz)
AC Voltage
(V AC)
600.0mV 0.1mV ±(1.0% + 8 digits)*
6.000V 1mV ±(1.0% + 5 digits)
60.00V 10mV
±(1.2% + 5 digits)
600.0V 0.1V
1000V 1V ±(1.5% + 5 digits)
DC Voltage
(V DC)
600.0mV 0.1mV ±(0.9% + 8 digits)
6.000V 1mV
±(1.0% + 3 digits)60.00V 10mV
600.0V 0.1V
1000V 1V ±(1.2% + 3 digits)
Input Impedance:
10MΩ
Frequency Range:
50 to 400Hz
Maximum Input: 1000V AC RMS or 1000V DC
*Accuracy specified from 5% to 100% of the measuring range
AC Current
(A) TRMS
600.0A 0.1A ±(2.0% + 5 digits)
2000A 1A ±(2.5% + 8 digits)
DC Current (A)
600.0A 0.1A ±(2.0% + 5 digits)
2000A 1A ±(2.5% + 8 digits)
AC Frequency Range: 50 to 60Hz , >500mA
DC:
>200mA (low current requires use of DC ZERO function)
AC Current (A)
Inrush
600A 0.1A ±(2.5% + 5 digits)**
2000A 1A ±(3.0% + 8 digits)**
AC Frequency Range: 50 to 60Hz
when auto-ranging >3A detectable
(>2A if held in 600A range)
**Accuracy specified assumes AC sine wave
Resistance
600.0Ω 0.1Ω
±(1.5% + 5 digits)
6.000KΩ
60.00kΩ 10Ω
600.0kΩ 100Ω
6.000MΩ 1kΩ
60.00MΩ 10kΩ ±(2.0% + 10 digits)
Maximum Input: 600V AC RMS or 600V DC
Capacitance
60.00nF 10pF ±(5.0% + 35 digits)
600.0nF 0.1nF
±(3.0% + 5 digits)
6.000µF 1nF
60.00µF 10nF
600.0µF 0.1µF
6000µF 1µF ±(5.0% + 5 digits)
Maximum Input: 600V AC RMS or 600V DC
4
ENGLISH
WARNINGS
To ensure safe operation and service of the meter, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
Before each use, verify meter operation by measuring a known voltage
or current.
Never use the meter on a circuit with voltages that exceed the category
based rating of this meter.
Do not use the meter during electrical storms or in wet weather.
Do not use the meter or test leads if they appear to be damaged.
Use only with CAT III or CAT IV rated test leads.
Ensure meter leads are fully seated, and keep fingers away from the
metal probe contacts when making measurements.
Use caution when working with voltages above 25V AC RMS or
60V DC. Such voltages pose a shock hazard.
To avoid false readings that can lead to electrical shock, replace batteries
when a low battery indicator appears.
Do not attempt to measure resistance or continuity on a live circuit.
Do not hold meter above hand & finger guard during use.
ELECTRICAL SPECIFICATIONS
Frequency
9.999Hz 0.001Hz
±(1.0% + 5 digits)
99.99Hz 0.01Hz
999.9Hz 0.1Hz
9.999kHz 1Hz
99.99kHz 10Hz
500.0kHz 100Hz
Sensitivity: >8V RMS, Maximum Input: 600V DC or 600V AC RMS
Duty Cycle
0.1% – 99.9% 0.10%
±(1.2% + 2 digits)
Pulse width: 0.1ms – 100ms
Frequency width: 5Hz to 10kHz
Sensitivity: >8V RMS
Maximum Input: 600V AC RMS or 600V DC
OTHER MEASUREMENT APPLICATIONS
Diode Test: Max. 1.5mA, open circuit voltage ~ 3.0V DC
Continuity Check: Audible signal <50Ω, test current <0.35mA
Sampling Frequency: 3 samples per second
Low Impedence (Low Z): Input impedence: >3kΩ
Max input: 600V RMS
Auto Power off: After ~30 minutes of inactivity
Overload:
"OL" indicated on display, overload protection
1000V RMS in Voltage setting, 600V RMS in all other settings
Polarity: "-" on display indicates negative polarity
Non-Contact Voltage Detection:
>90V AC
Display: 3-5/6 digit, 6000 Count LCD
5
SYMBOLS ON METER
Alternating Current (AC) Direct Current (DC)
A
Amperage
V
Voltage
Audible Continuity
Hz
Frequency
Diode Test
%
Duty-Cycle
Capacitance Low Impedance
Resistance (Ohms) DC Current Zero Function
+ Positive Negative
COM
Common Ground
Double Insulated Class II
Warning or Caution:
To ensure safe operation and service of this
meter, follow all warnings and instructions detailed in this manual.
Risk of Electrical Shock:
I
mproper use of this meter can lead to risk of
electrical shock. Follow all warnings and instructions detailed in this manual.
SYMBOLS ON LCD
AC Measurement DC Measurement
Negative Reading Data Hold
AUTO
Auto Ranging
MAX
Maximum Value Hold
MIN
Minimum Value Hold Low Battery
Auto Power Off Audible Continuity
Diode Test Inrush Current
k
kilo (value x 10
3
)
m
mili (value x 10
-3
)
M
Mega (value x 10
6
)
n
nano (value x 10
-9
)
μ
micro (value x 10
-6
)
F
Farads
Ohms
A
Amps
V
Volts
LoZ
Low Impedence
Hz
Frequency (Hertz)
%
Duty Cycle
WARNINGS
Always adhere to local and national safety codes. Use personal
protective equipment to prevent shock and arc blast injury where
hazardous live conductors are exposed.
Usage of this meter in any way other than that specified by the
manufacturer can impair safe operation, resulting in severe injury or death.
To avoid risk of electric shock, disconnect leads from any voltage source
before removing battery door.
To avoid risk of electric shock, do not operate meter while battery door is
removed.
6
ENGLISH
FEATURE DETAILS
1
9
7
2
3
11
10
13
14
15
16
54
8
6
NOTE: There are no user-serviceable parts inside meter.
12
1.
6000 count
LCD display
2.
Function
selector
switch
3.
Clamp
4.
"COM" jack
5.
"VΩ" jack
6.
Data Hold /
Backlight
button
7.
"RANGE"
button
8.
"MAX/MIN"
button
9.
SEL (select) /
DC Zero button
10.
INRUSH button
11.
Clamp trigger
(press to open
clamp)
12.
Arrow markings
13.
N
on-contact
Voltage Testing
Button
14.
N
on-contact
Voltage Testing
Sensor
15.
N
on-contact
Voltage Testing
LED Indicator
16.
Polarity markings
(for DC current)
7
FUNCTION BUTTONS
ON/OFF
To power ON the meter, rotate the Function Selector switch
2
from
the OFF setting to any measurement setting. To power OFF the meter,
rotate the Function Selector switch
2
to the OFF setting. By default,
the meter will automatically power OFF after aprox. 30 minutes of
inactivity. To deactivate the auto power OFF functionality, press and
hold the "SEL/DC ZERO" button
9
before powering ON from the OFF
setting. When auto power OFF is deactivated, the Auto Power Off icon
will not be visible in the display.
SEL (SELECT) / DC ZERO BUTTON (FOR SECONDARY FUNCTIONS)
The SEL/DC ZERO button
9
activates the secondary function for
each application accessible by the function selector switch
2
:
In Current
A
and Low Impedance modes, it toggles between
AC and DC measurements.
In Frequency/Duty Cycle
setting, it toggles between these
measurements
.
In Continuity/Resistance/Diode-Test
setting, it toggles
through these measurements in order
.
In DC current setting, pressing and holding for more than one
second initiates the DC ZERO function. Subsequent DC current
measurements automatically subtract the measurement that was
present as an offset correction.
The default function for each application is printed on the meter in
white, the secondary functions in orange. An icon on the LCD display
will indicate which function is active.
DATA HOLD
Press the Data Hold / Backlight button
6
to hold the measurement
on the display. Press again to release the display to return to live
measuring.
BACKLIGHT
Press and hold the Data Hold / Backlight button
6
for more than
one second to turn ON the backlight. The backlight will automatically
power OFF after 3 minutes of inactivity.
RANGE
The meter defaults to auto-ranging mode
AUTO
. This mode
automatically determines the most appropriate measurement range
for the testing that is being conducted. To manually force the meter to
measure in a different range, use the Range button
7
.
1. Press the "RANGE" button
7
to manually select measurement
range (AUTO is deactivated on the LCD). Repeatedly press the
"RANGE" button
7
to cycle through the available ranges, stopping
once the desired range is reached.
2. To return to auto-ranging mode, press and hold the "RANGE"
button
7
for more than one second (AUTO is reactivated).
8
ENGLISH
FUNCTION BUTTONS
MAX/MIN
When the "MAX/MIN" button
8
is pressed, the meter keeps track of
the Maximum and Minimum values as the meter continues to take
samples.
1. When measuring, press "MAX/MIN" button
8
to toggle between
the Maximum value (MAX) and Minimum value (MIN). If a new
Maximum or Minimum, the display will update with the new value.
2. Press "MAX/MIN" button
8
for more than one second to return to
normal measuring mode.
INRUSH CURRENT
Rotate the Function Selector switch
2
to the Current
A
setting
and
press INRUSH
10
prior to an inrush event to test for inrush
current. While the meter monitors current waiting for the inrush
event, "----" will be visible on the display.
NON-CONTACT VOLTAGE TESTING
Press and hold the "NCV" button
13
to test for AC voltage using the
integrated non-contact voltage tester. Approach the conductor under
test leading with the sensing antenna
14
. The meter delivers visual
warning signals via the LED indicator
15
and audible signals (beeps)
when AC voltage is detected. Release the "NCV" button to exit NCV
testing mode.
NOTE: It is not recommended to perform continuity and NCV testing
simultaneously, as both tests utilize the same audible signal, making
it difficult to resolve which test is responsible for the audible alarm.
NOTE: Only voltages of 90V AC or greater will be detected.
9
OPERATING INSTRUCTIONS
CONNECTING TEST LEADS
Do not test if leads are improperly seated. Results could cause
intermittent display readings. To ensure proper connection, firmly
press leads into the input jack completely.
TESTING IN CAT III / CAT IV MEASUREMENT LOCATIONS
Ensure the test lead shield is pressed firmly in place. Failure to use
the CATIII / CATIV shield increases arc-flash risk.
TESTING IN CAT II MEASUREMENT LOCATIONS
CAT III / CAT IV shields may be removed for CAT II locations. This
will allow testing on recessed conductors such as standard wall
outlets. Take care not to lose the shields.
5/32"
(4 mm)
.7" (18 mm)
INCORRECT
CORRECT
10
OPERATING INSTRUCTIONS
AC/DC CURRENT (LESS THAN 2000A)
AC Current is measured by pressing the
clamp trigger
11
to open the clamp
3
and placing it around a current-carrying wire.
When measuring, care should be taken to
ensure that the clamp
3
is completely
closed with trigger
11
fully released, and
that the wire passes perpendicularly through
the center of the clamp
3
in line with the
arrow markings
12
.
To measure current:
1. Rotate the Function Selector switch
2
to
the
Current
A
setting
.
2. The meter defaults to AC measurement.
To
measure DC, press the "SEL/DC ZERO"
button
9
to toggle between AC and DC
modes. The AC or DC icon on the LCD
indicates which mode is selected. Note
"AC" or "DC" on the display.
3. Place the clamp
3
around the wire. When measuring DC current,
align the polarity markings
16
on the clamp with the polarity of
the wire to avoid negative readings. The current measurement will
be shown in the display.
The meter will auto-range to display the
measurement in the most appropriate range.
To measure inrush current:
1. Rotate the Function Selector switch
2
to the Current
A
setting.
Place the clamp
3
around the wire and press "INRUSH"
10
. The
Display
1
will show "----". Initiate the Inrush event and the inrush
current will be captured and presented in the display. A second press of
"INRUSH"
10
will reset the Inrush measurement, "----" will be presented
on the display and the meter will wait for the next Inrush event.
NOTE: The Inrush measurement period is 100 milliseconds, with a 20
millisecond sampling rate.
2. P
ress and hold
"INRUSH"
10
for more than one second to return to
normal measuring mode.
Disconnect test leads when measuring with the clamp.
NOTE: If non-zero values are displayed prior to measuring in DC
current mode, an offset correction may be required to improve
accuracy. With meter in DC current mode, press and hold the
"SEL/DC ZERO" button
9
for more than one second to initiate the
DC current ZERO function. Subsequent DC current measurements
automatically subtract the measurement that was initially present as
an offset correction.
ENGLISH
WIRE
11
OPERATING INSTRUCTIONS
AC/DC VOLTAGE (LESS THAN 1000V)
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
AC voltage V or DC voltage V setting. The AC or DC icon on
the LCD indicates which setting is selected.
2. Apply test leads to the circuit to be tested to measure voltage.
The meter will auto-range to display the measurement in the
most appropriate range.
NOTE: If "" appears on the LCD, the test leads are being applied to
the circuit in reverse. Swap the position of the leads to correct this.
NOTE: When in a voltage setting and the test leads are open,
readings of order mV may appear on the display. This is noise and
is normal. By touching the test leads together to close the circuit
the meter will measure zero volts.
Do not attempt to measure voltages greater than 1000V
in any Voltage setting.
AC/DC LoZ VOLTAGE (LESS THAN 600V)
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
AC/DC LoZ voltage
setting.
The meter defaults to AC
measurement.
To measure DC, press the "SEL/DC ZERO" button
9
to toggle between AC and DC modes. The AC or DC icon on
the LCD indicates which mode is selected. Note "AC" or "DC" on
the display.
2. Apply test leads to the circuit to be tested to measure voltage.
The meter will auto-range to display the measurement in the
most appropriate range.
Do not attempt to measure voltages greater than 600V
in LoZ setting.
Black lead Red lead
Black lead Red lead
-or-
12
ENGLISH
RESISTANCE MEASUREMENTS
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
Continuity/Resistance/Diode-Test
setting.
NOTE: The meter defaults to Continuity testing in this mode. Press
the SEL/DC ZERO" button
9
once to enter Resistance testing
mode. The Resistance icon
will appear on the display.
2. Remove power from circuit.
3. Measure resistance by connecting test leads to circuit. The
meter will auto-range to display the measurement in the most
appropriate range.
NOTE: When in a Resistance setting and the test leads are open
(not connected across a resistor), or when a failed resistor is under
test, the display will indicate O.L. This is normal.
DO NOT attempt to measure resistance on a live circuit.
CONTINUITY
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
Continuity/Resistance/Diode-Test
setting.
NOTE: The meter defaults to Continuity testing in this setting.
Ensure that the Continuity Testing icon
is visible on the display.
If not, press the "SEL/DC ZERO" button
9
repeatedly until the
icon is shown.
2. Remove power from circuit.
3. Test for continuity by connecting conductor or circuit with test
leads. If resistance is measured less than 50Ω, an audible signal
will sound and display will show a resistance value indicating
continuity. If circuit is open, display will show "OL".
DO NOT attempt to measure continuity on a live circuit.
OPERATING INSTRUCTIONS
Black lead Red lead
Black lead Red lead
13
DIODE TEST
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
Continuity/Resistance/Diode-Test
setting.
NOTE: The meter defaults to Continuity testing in this mode. Press
the SEL/DC ZERO" button
9
twice to enter Diode testing mode. The
Diode icon will appear on the display.
2. Touch test leads to diode. A reading of 200-800mV on display
indicates forward bias, "OL" indicates reverse bias. An open
device will show "OL" in both polarities. A shorted device will
show approximately 0mV.
FREQUENCY / DUTY-CYCLE
1. Insert RED test lead into VΩ jack
5
and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
Frequency/Duty-Cycle
setting.
OPERATING INSTRUCTIONS
NOTE: : The meter defaults to Frequency testing. To test Duty-Cycle,
press the "SEL/DC ZERO" button
9
once. Ensure that the appropriate
icon (either Hz or %) appears on the display.
1. Measure by connecting test leads across the circuit.
Black lead Red lead
Black lead Red lead
14
OPERATING INSTRUCTIONS
CAPACITANCE
1. Insert RED test lead into VΩ jack
5
, and BLACK test lead into
COM jack
4
, and rotate function selector switch
2
to the
Capacitance
setting.
2. Remove power from circuit.
3. Measure capacitance by connecting test leads across the capacitor.
The meter will auto-range to display the measurement in the most
appropriate range.
ENGLISH
MAINTENANCE
BATTERY REPLACEMENT
When indicator is displayed on LCD, batteries must be replaced.
1. Loosen screw on battery door.
2. Replace 2 x AAA batteries (note proper polarity).
3. Replace battery door and fasten securely with screw.
T
o avoid risk of electric shock, disconnect leads from any voltage
source before removing battery door.
To avoid risk of electric shock, do not operate meter while
battery door is removed.
Black lead Red lead
15
CLEANING
Be sure meter is turned off and wipe with a clean, dry lint-free
cloth.
Do not use abrasive cleaners or solvents.
STORAGE
Remove the batteries when meter is not in use for a prolonged
period of time. Do not expose to high temperatures or
humidity. After a period of storage in extreme conditions
exceeding the limits mentioned in the General Specifications
section, allow the meter to return to normal operating
conditions before using.
WARRANTY
www.kleintools.com/warranty
DISPOSAL / RECYCLE
Do not place equipment and its accessories in the trash.
Items must be properly disposed of in accordance with local
regulations. Please see www.epa.gov or www.erecycle.org
for additional information.
CUSTOMER SERVICE
KLEIN TOOLS, INC.
450 Bond Street
Lincolnshire, IL 60069
1-877-775-5346
www.kleintools.com
NOTES
KLEIN TOOLS, INC.
450 Bond Street
Lincolnshire, IL 60069
1-877-775-5346
www.kleintools.com
ENGLISH
ESPAÑOL
MANUAL DE INSTRUCCIONES
Multímetro digital de
gancho de 2000A
True RMS
Tecnología de
medición
PRUEBA DE VOLTAJE
SIN CONTACTO
CORRIENTE DE
INSERCIÓN
BAJA IMPEDANCIA
RETENCIÓN DE DATOS
RETENCIÓN DE RANGO
CONTINUIDAD POR
INDICADOR AUDIBLE
PRUEBA DE DIODO
CAPACITANCIA
FRECUENCIA
1000V
2000A
60M
Ω
2
m IP40
CL900
4007177
18
ESPAÑOL
ESPECIFICACIONES GENERALES
Klein Tools CL900 es un multímetro digital de gancho de rango automático
con media cuadrática real (TRMS) que mide corriente CA/CD con la pinza;
mide voltaje CA/CD, resistencia, continuidad, frecuencia, ciclo de servicio y
capacitancia; y prueba diodos con cables de prueba. Cuenta con un modo
de baja impedancia (LoZ) para identificar y eliminar voltajes fantasma o
erráticos, y tiene un modo dedicado para capturar la corriente de inserción.
Altitud de funcionamiento: 6562pies (2000m)
Humedad relativa: <80 % sin condensación
Temperatura de operación: 32°F a 122°F (0°C a 50°C)
Temperatura de almacenamiento: 14°F a 140°F (-10°C a 60°C)
Precisión: Valores establecidos según una temperatura ambiente de
65°F a 83°F (18°C a 28°C)
Coeciente de temperatura: 0,1 × (precisión indicada) por cada
°C por encima de los 28°C o por debajo de los 18°C, es necesario
realizar correcciones si la temperatura del ambiente de trabajo se
encuentra fuera del rango de precisión de temperatura
Dimensiones: 10,4" × 3,9" × 1,7" (265mm × 99mm × 43 mm)
Peso: 18,6 oz (526 g) incluidas las baterías
Calibración: Precisa durante un año
Normas: Cumple con las normas UL 61010-1, 61010-2-032
y 61010-2-033.
Certificado según las normas CSA C22.2 N.° 61010-1,
61010-2-032 y 61010-2-033.
IEC EN 61010-1, 61010-2-032,
61010-2-033.
Grado de contaminación: 2
Precisión: ± (% de lectura + cantidad de dígitos menos significativos)
Protección ante caídas: 6,6pies (2m)
Clasicación de seguridad: CATIV 600V, CATIII 1000V, clase2,
doble aislamiento
CATIII: La categoría III de medición es aplicable a los circuitos de
medición y prueba conectados a la distribución de la instalación de
red de bajo voltaje de un edificio.
CATIV: La categoría IV de medición es aplicable a los circuitos de
medición y prueba conectados a la fuente de la instalación de red de
bajo voltaje de un edificio.
Entorno electromagnético: IEC EN 61326-1. Este equipo cumple con
los requisitos apropiados para su uso en entornos electromagnéticos
básicos y controlados, como propiedades residenciales,
establecimientos comerciales e instalaciones de industria ligera.
Especificaciones sujetas a cambios.
19
ESPECIFICACIONES ELÉCTRICAS
Función Rango Resolución Precisión
(50Hz/60Hz)
Voltaje CA
(V CA)
600,0mV 0,1mV ± (1,0% + 8 dígitos)*
6,000V 1mV ± (1,0% + 5 dígitos)
60,00V 10mV
± (1,2% + 5 dígitos)
600,0V 0,1V
1000V 1V ± (1,5% + 5 dígitos)
Voltaje CD
(V CD)
600,0mV 0,1mV ± (0,9% + 8 dígitos)
6,000V 1mV
± (1,0% + 3 dígitos)60,00V 10mV
600,0V 0,1V
1000V 1V ± (1,2% + 3 dígitos)
Impedancia de entrada: 10MΩ Rango de frecuencia: 50Hz a 400Hz
Entrada máxima: 1000V CA RMS o 1000V CD
*Precisión especificada de 5% a 100% del rango de medición
Corriente CA
(A) TRMS
600,0A 0,1A ± (2,0% + 5 dígitos)
2000A 1A ± (2,5% + 8 dígitos)
Corriente CD (A)
600,0A 0,1A ± (2,0% + 5 dígitos)
2000A 1A ± (2,5% + 8 dígitos)
Intervalo de frecuencia de CA: 50Hz a 60Hz, >500mA
CD: >200mA (la corriente baja requiere el uso de la función "DC ZERO"
[CD CERO])
Corriente de
inserción (A)
de CA
600A 0,1A ± (2,5% + 5 dígitos)**
2000A 1A ± (3,0% + 8 dígitos)**
Intervalo de frecuencia de CA: 50Hz a 60Hz cuando el rango
automático es >3A detectable (>2A si se mantiene en un rango
de 600A)
**La precisión especificada supone una onda sinusoidal de CA
Resistencia
600,0Ω 0,1Ω
± (1,5% + 5 dígitos)
6,000kΩ 1Ω
60,00kΩ 10Ω
600,0kΩ 100Ω
6,000MΩ 1kΩ
60,00MΩ 10kΩ ± (2,0% + 10 dígitos)
Entrada máxima: 600V CA RMS o 600V CD
Capacitancia
60,00nF 10pF ± (5,0% + 35 dígitos)
600,0nF 0,1nF
± (3,0% + 5 dígitos)
6,000µF 1nF
60,00µF 10nF
600,0µF 0,1µF
6000µF 1µF ± (5,0% + 5 dígitos)
Entrada máxima: 600V CA RMS o 600V CD
20
ESPAÑOL
ADVERTENCIAS
Para garantizar un funcionamiento y servicio seguros del medidor, siga
estas instrucciones. El incumplimiento de estas advertencias puede
provocar lesiones graves o la muerte.
Antes de cada uso, verifique el funcionamiento del multímetro midiendo un
voltaje o corriente conocidos.
Nunca debe utilizar este multímetro en un circuito con voltajes que excedan la
clasificación correspondiente a la categoría del multímetro.
No utilice el multímetro durante tormentas eléctricas o en clima húmedo.
No utilice el multímetro o los cables de prueba si en apariencia están dañados.
Utilice el multímetro con cables de prueba con clasificación CAT III o CAT IV
únicamente.
Asegúrese de que los cables del multímetro estén correctamente colocados y
mantenga los dedos lejos de los contactos de la sonda de metal al realizar las
mediciones.
Proceda con precaución cuando trabaje con voltajes superiores a 25V CA RMS
o 60V CD. Esos voltajes implican un riesgo de choque eléctrico.
Para evitar lecturas falsas que puedan provocar choques eléctricos, reemplace
las baterías cuando aparezca el indicador de batería baja.
ESPECIFICACIONES ELÉCTRICAS
Frecuencia
9,999Hz 0,001Hz
± (1,0% + 5 dígitos)
99,99Hz 0,01Hz
999,9Hz 0,1Hz
9,999kHz 1Hz
99,99kHz 10Hz
500,0kHz 100Hz
Sensibilidad: > 8V RMS, Entrada máxima: 600V CD o 600V CA RMS
Ciclo de
servicio
0,1% – 99,9% 0,10%
± (1,2% + 2 dígitos)
Ancho de pulso: 0,1ms – 100ms
Ancho de frecuencia: 5Hz a 10kHz
Sensibilidad: >8V RMS
Entrada máxima: 600V CA RMS o 600V CD
OTRAS APLICACIONES DE MEDICIÓN
Prueba de diodo:
1,5mA máx., 3,0V CD de voltaje de circuito abierto aprox.
Vericación de continuidad: Señal audible <50Ω, <0,35mA de
corriente de prueba
Frecuencia de muestreo: 3 muestras por segundo
Baja impedancia (Low Z): Impedancia de entrada: > 3kΩ
Entrada máx.: 600VRMS
Apagado automático: después de aprox. 30minutos de inactividad
Sobrecarga: Se indica "OL" (SOBRECARGA) en pantalla, protección
contra sobrecarga de 1000V RMS en posición de voltaje,
600V RMS en las demás posiciones
Polaridad: "-" en pantalla indica polaridad negativa
Detección de voltaje sin contacto: > 90V CA
Pantalla: LCD de 3-5/6dígitos con recuento de 6000
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Klein Tools CL900 Manuel utilisateur

Catégorie
Mesure, test
Taper
Manuel utilisateur

dans d''autres langues