Tripp Lite SmartOnline SVTX Series Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
Owner’s Manual
SmartOnline
®
SVTX
3-Phase UPS Systems
Models: SVT10KX, SVT20KX, SVT30KX
(Series Number: AG-0149) (Series Number: AG-014A) (Series Number: AG-014B)
Input: 220/230/240V (Ph-N),
380/400/415V (Ph-Ph), 30 4-Wire + PE
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2016 Tripp Lite. All rights reserved.
Español p.33 • Français p.65 • Русский p.97
2
Table of Contents
1. Introduction .......................................................................................................................... 3
2. Important Safety Warnings ..................................................................................................4
2.1 UPS Location Warnings ..................................................................................................................................... 4
2.2 Equipment Connection Warnings ....................................................................................................................... 4
2.3 Battery Warnings .............................................................................................................................................. 4
2.4 Transportation and Storage ............................................................................................................................... 5
2.5 Preparation ....................................................................................................................................................... 5
2.6 Installation ....................................................................................................................................................... 5
2.7 Connection Warnings ........................................................................................................................................ 5
2.8 Operation ......................................................................................................................................................... 6
2.9 Standards ......................................................................................................................................................... 6
3. Installation and Setup .......................................................................................................... 6
3.1 Unpacking and Inspection ................................................................................................................................. 6
3.2 Rear Panel View ................................................................................................................................................ 7
3.3 Internal Battery Connection .............................................................................................................................. 8
3.4 Single UPS Installation ..................................................................................................................................... 9
3.5 UPS Installation for Parallel System ................................................................................................................ 10
3.6 External Battery Connection ........................................................................................................................... 10
4. Operation ...........................................................................................................................11
4.1 Button Operation ............................................................................................................................................ 11
4.2 LED Indicators and LCD Panel ......................................................................................................................... 11
4.3 Audible Alarm ................................................................................................................................................. 13
4.4 Single UPS Operation ...................................................................................................................................... 13
4.5 Parallel UPS Operation .................................................................................................................................... 15
4.6 LCD Panel Abbreviations .................................................................................................................................. 16
4.7 LCD Settings ................................................................................................................................................... 17
4.8 Operating Mode/Status Description ................................................................................................................. 22
4.9 Fault Codes .................................................................................................................................................... 26
4.10 Warning Indicator .......................................................................................................................................... 26
4.11 Warning Code ................................................................................................................................................ 27
5. Communication ...................................................................................................................27
5.1 RS-232 Port .................................................................................................................................................... 27
5.2 SMART Slot ..................................................................................................................................................... 27
5.3 EPO Connector ............................................................................................................................................... 27
6. Troubleshooting ..................................................................................................................28
7. Storage and Maintenance ..................................................................................................29
7.1 Storage .......................................................................................................................................................... 29
7.2 Maintenance ................................................................................................................................................... 29
7.3 Battery ............................................................................................................................................................ 29
7.4 Fan ................................................................................................................................................................. 29
8. Specifications ....................................................................................................................30
9. Warranty ............................................................................................................................. 32
3
1. Introduction
Tripp Lite’s SmartOnline SVTKX-Series Uninterruptible Power Supply (UPS) is a Voltage and Frequency Independent (VFI) true online,
double-conversion 3-phase UPS system. This UPS continuously conditions the incoming electrical power supply, eliminating power
disturbances that will otherwise damage sensitive electronic devices and minimizing system downtime from power fluctuations and
interruptions.
Available in 10kVA, 20kVA and 30kVA models, these UPS systems are designed to the highest quality and performance standards and
offer the following features:
True online UPS – the highest level of UPS protection, fully regulating the incoming power supply and transferring immediately to
battery in the event of an extended mains failure to support critical loads continuously
Paralleling capability (SVT20KX and SVT30KX only) of up to three UPS systems for increased capacity and fault tolerance
ECO mode allowing the UPS to operate on bypass in stable utility conditions, transferring immediately to inverter to support the load if
the utility input drops below tolerance
High output power factor – more actual power, allowing more equipment to be supported
Automatic and manual bypass to increase system reliability and to allow for maintenance without removing power from the attached
load
Wide input voltage window – the UPS system regulates even poor-quality incoming power without reverting to battery, maximizing
system uptime and protecting battery life
Matching external battery cabinets for increased battery autonomy
Emergency shutdown
Compact footprint
SNMP and volt-free contact options for optimum configurability
The SmartOnline SVTKX-Series UPS is ideally suited for protecting critical electrical equipment for:
IT infrastructure
• Telecommunications
Networks (LAN/WAN)
Corporate infrastructure
Security and emergency systems
Light industrial applications
Financial institutions
4
2. Important Safety Warnings
SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation and maintenance
of all Tripp Lite SmartOnline SVT 3-Phase 10kVA, 20kVA and 30kVA UPS Systems and their batteries. Failure to heed these
warnings may affect your warranty.
2.1 UPS Location Warnings
Install the UPS indoors, away from heat, direct sunlight, dust, and excess moisture or other conductive contaminants.
Install the UPS in a structurally sound area. The UPS is extremely heavy; take care when moving and lifting the unit.
Only operate the UPS at indoor temperatures between 0° C and 40° C.
Optimum UPS performance and maximum battery life is met when the operating temperature is maintained between 17° C and 25° C.
Ensure the installation area has sufficient space for maintenance and ventilation of the UPS system. Maintain a minimum clearance of
50 cm from the rear, front and both sides of the UPS for maintenance and ventilation.
Do not install the UPS near magnetic storage media, as this may result in data corruption.
2.2 Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
The UPS system contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an
AC supply.
2.3 Battery Warnings
The UPS does not require routine maintenance. Do not open the UPS for any reason. There are no user-serviceable parts inside.
Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of
the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Disconnect and
turn off the UPS before performing battery replacement. Use tools with insulated handles. Battery replacement should be performed
only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries are recyclable.
Refer to your local codes for disposal requirements or visit http://www.tripplite.com/support/recycling-program for recycling information.
Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at
http://www.tripplite.com/products/battery-finder/ to locate the specific replacement battery for your UPS.
Connect only Tripp Lite battery modules to your UPS system’s external battery hardware terminals.
Do not operate the UPS without batteries.
Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number
and type.
Potentially lethal voltages exist within this unit as long as the battery supply is connected. Service and repair should be done only by
trained personnel. During any service work, the UPS should be turned off or put into manual bypass and fuses should be removed from
all connected battery modules.
Do not connect or disconnect the battery modules while the UPS is operating from the battery supply.
WARNING: In order to avoid any hazardous conditions during UPS installation and maintenance, these tasks may
be performed only by qualified and experienced electricians.
5
2. Important Safety Warnings
Please read this Owner’s Manual and the safety instructions carefully before installing or using the unit.
2.4 Transportation and Storage
Transport the UPS system only in the original packaging to protect against shock and impact.
The UPS must be stored in a room that is dry and ventilated.
2.5 Preparation
Condensation may occur if the UPS system is moved directly from a cold to warm environment. The UPS system must be completely
dry before being installed. Please allow at least two hours for the UPS system to adjust to the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system in direct sunlight or near heat sources.
Do not the block ventilation holes on the UPS system’s housing.
2.6 Installation
Do not connect appliances or devices that could overload the UPS (i.e., equipment with large electrical motors) to the UPS output
sockets or terminal.
Carefully arrange cables so that no one can step on or trip over them.
Do not block the UPS system’s air vents. The UPS must be installed in a location with good ventilation. Ensure adequate ventilation
space on each side of the unit.
The UPS contains an earthed terminal. In the final installed system configuration, ensure equipotential earth grounding to the external
UPS battery cabinet by connecting the earth terminals of both cabinets together.
The UPS should only be installed by qualified maintenance personnel.
An appropriate disconnect device such as short-circuit backup protection must be provided in the building wiring installation.
An integral single-emergency switching device should be included in the building wiring installation.
Connect the earth ground before connecting to the building wiring terminal.
Installation and wiring must be performed in accordance with local electrical codes and regulations.
2.7 Connection Warnings
The UPS system does not contain standard backfeed protection inside. Isolate the UPS before working on this circuit. The isolation
device must be able to carry the UPS input current.
This UPS should be connected with TN earthing system.
The power supply for this unit must be 3-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of
the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Connect the UPS power module’s grounding terminal to a grounding electrode conductor.
The UPS is connected to a DC energy source (battery). The output terminals may still be live even when the UPS is not connected to
an AC supply.
When installing the unit, verify that any maintenance bypass panel used is
configured correctly before applying power to the unit.
Before working on this circuit
- Isolate Uninterruptible Power System (UPS)
- Then check for Hazardous Voltage between all
terminals including the protective earth.
Risk of Voltage Backfeed
6
2. Important Safety Warnings
2.8 Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals at any time, as this will cancel the protective
earth of the UPS system.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
2.9 Standards
*Safety
IEC/EN 62040-1
*EMI
Conducted Emission...............................:IEC/EN 62040-2 Category C3
Radiated Emission..................................:IEC/EN 62040-2 Category C3
*EMS
ESD......................................................:IEC/EN 61000-4-2 Level 4
RS........................................................:IEC/EN 61000-4-3 Level 3
EFT.......................................................:IEC/EN 61000-4-4 Level 4
SURGE..................................................:IEC/EN 61000-4-5 Level 4
CS........................................................:IEC/EN 61000-4-6 Level 3
Power-Frequency Magnetic Field..............:IEC/EN 61000-4-8 Level 4
Low-Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial applications in the second environment. Installation restrictions or
additional precautions may be needed to prevent disturbances.
3. Installation and Setup
3.1 Unpacking and Inspection
Unpack the unit and inspect the contents. The shipping packaging contains:
One (1) UPS
One (1) Owner’s Manual
One (1) Parallel Cable (For SVT20KX and SVT30KX model)
One (1) Share Current Cable (For SVT20KX and SVT30KX model)
Note: Do not turn on the unit. Make sure to inspect the unit prior to installation. Be sure that nothing inside the package was damaged during
transportation. Notify the carrier and dealer immediately if there is any damage or missing parts. Please keep the original packaging in a safe place for
future use.
7
3. Installation and Setup
3.2 Rear Panel View
1
8
7
1
11
1
2
1
2
1
2
3
3
4
44
5
5
6
6 6
7
77 8
88
10
9
10
9
10
9
Diagram 1: SVT10KX Rear Panel Diagram 2: SVT20KX Rear Panel Diagram 3: SVT30KX Rear Panel
1
Emergency Power Off (EPO)
Connector
2
RS-232 Port
3
Share Current Port
(For SVT20KX / SVT30KX Model)
4
SNMP Accessory Slot
5
Parallel Ports
(For SVT20KX / SVT30KX Model)
6
Fans
7
External Battery Connector
8
Input/Output Terminal Conduit
Cover Box
9
Line Input Circuit Breaker
10
Maintenance Bypass Switch
(For Service Personnel Use Only)
11
Output Grounding Terminal
12
Output Terminal
(Connects to
Mission-critical Loads)
13
Line Input Terminal
14
Input Grounding Terminal
14131211
Diagram 4: SVT10KX / SVT20KX / SVT30KX Input/Output Terminal
8
3. Installation and Setup
3.3 Internal Battery Connection
DANGER! LETHAL HIGH VOLTAGE HAZARD!
Potentially lethal high voltage exists within the batteries, even when not connected to a UPS system. Battery
connection should be performed by qualified service personnel only, following all the precautions listed in this
manual and adhering to local electrical codes.
Internal battery connection is required for all models prior to installation. The red wire for each battery string must be connected prior to
installation, as shown below.
Internal Battery Connection Procedure
Figure 3-1 Figure 3-2
Figure 3-3: Location of red terminals
1) Remove all screws labeled #1; loosen all screws labeled #2 (Figure 3-1).
2) Remove top plate and side plate (Figure 3-2).
3) The BAT(+) red wires are disconnected and the terminals are covered with
insulation tape. Remove the tape and reconnect the BAT(+) wires.
SVT10KX SVT20KX SVT30KX
1
1
1
1
1
1
1
1
1
2
2
2
1
1
1
1
4) Replace top and side panels.
5) Replace and tighten all screws from Step 1 with a torque of 1Nm.
9
3.4 Single UPS Installation
Installation and wiring must be performed in accordance with local electrical codes/regulations and should only be performed by qualified
personnel.
1) Make sure the mains wire and breakers in the building can sustain the rated capacity of the UPS to avoid the hazards of electric
shock or fire.
Note: Using a wall receptacle as the input power source for the UPS may result in the receptacle burning or otherwise being destroyed.
2) Switch off the mains switch in the building prior to installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG) [cross-sectional area in mm
2
]
Input (Ph) Output (Ph) Neutral Cable Length Ground
SVT10KX 10 [5] 10 [5] 8 [8] 10 Meters Maximum 8 [8]
SVT20KX 8 [8] 8 [8] 6 [13] 10 Meters Maximum 6 [13]
SVT30KX 6 [10] 6 [10] 4 [21] 10 Meters Maximum 4 [21]
Notes:
• The SVT10KX cable should be able to withstand over 40A current. It is recommended to use 10 AWG or thicker wire for Phase and 8 AWG or thicker
wire for Neutral.
• The SVT20KX cable should be able to withstand over 63A current. It is recommended to use 8 AWG or thicker wire for Phase and 6 AWG or thicker
wire for Neutral.
• The SVT30KX cable should be able to withstand over 63A current. It is recommended to use 6 AWG or thicker wire for Phase and 4 AWG or thicker
wire for Neutral.
• The selection of wire color should follow local electrical codes and regulations.
3. Installation and Setup
5) Remove the terminal block cover to access the UPS system’s input, output
and grounding connection terminals. Circular knockouts must be made on the
terminal block cover to allow wiring conduits to pass through.
Notes:
• Make sure the wires are connected tightly to the terminals.
• Install the output breaker between the output terminal and the load. The breaker should
be qualified with leakage current protective function.
• Cabling should be protected by flexible conduit and routed through the appropriate
knockouts in the terminal block cover.
6) Replace the terminal block cover of the UPS system with flexible conduit
attached.
Terminal Block Wiring Diagram (All Models)
Warning:
Make sure the UPS is not turned on prior to installation. The UPS should not be turned on until all wiring has been
completed and checked.
Warning:
If an external battery pack is installed, switch off the battery breaker before installation.
Note: Set the battery pack breaker in the “OFF” position, then install the battery pack.
Pay close attention to the rated battery voltage posted on the rear panel. Connecting battery packs with the incorrect voltage may
cause permanent damage to the UPS.
Pay close attention to the polarity markings on the external battery terminal block and make sure the correct battery polarity is
connected. Wrong connection may cause permanent damage to the UPS.
Ensure the protective earth ground wiring is correct. The wire current spec, color, position, connection and conductance reliability
should be carefully observed.
Ensure the utility input and output wiring is correct. The wire current spec, color, position, connection and conductance reliability
should be checked carefully. Make sure the R, S, T and N wiring is correct, not reversed and not short-circuited.
10
3. Installation and Setup
3.5 UPS Installation for Parallel System
Warning:
Installation and wiring must be performed in accordance with the local codes/regulations and installed using the
following instructions by a qualified service technician only.
If the UPS is only for single operation, you may skip this section and proceed to section 3.6.
1) Parallel configuration supports up to three UPS systems. Do not attempt to link more than three UPS systems via parallel
configuration.
2) Install and wire the UPS system according to the section 3.4 guidelines.
3) The total length of the input cable must be equal to the total length of the output cable for a parallel configuration on all units.
4) Connect the input wiring of each UPS to an input breaker. Breaker specification for SVT20KX / SVT30KX is 300V, 63A.
5) Connect the output wiring of each UPS to an output breaker. Breaker specification for SVT20KX / SVT30KX is 300V, 63A.
6) Connect all output breakers to a main output breaker. This main output breaker will directly connect to the loads.
7) If an external battery pack is used, each UPS must be connected to an independent battery pack.
Note: The parallel system cannot use a common external battery pack. This will cause permanent damage to the entire system.
8) Refer to the following wiring diagram for parallel installation:
Wiring Diagram of Parallel System (SVT20KX / SVT30KX Models)
3.6 External Battery Connection
The UPS comes with a robust internal battery system; external batteries
are needed only to extend runtime. Adding external batteries will increase
runtime and require additional recharge time. This UPS supports Tripp Lite
external battery model BP240V135*.
The illustration at right shows the location of the UPS system’s external
battery connector
A
where the battery pack connects. Follow the
installation instructions for your battery pack as they appear in your battery
pack Owner’s Manual. Ensure the cables are fully inserted into their
connectors. Small sparks may occur during battery connection; this is
normal.
Do not connect or disconnect battery packs when the UPS is running on
battery power.
*Limit three external battery packs per UPS.
A
11
4. Operation
4.1 Button Operation
Button Function
ON/Enter Button Turn on the UPS: Press and hold for more than 0.5 seconds to turn on the UPS.
Enter Button: Press to confirm a selection in the settings menu.
OFF/ESC Button Turn off the UPS: Press and hold for more than 0.5 seconds to turn off the UPS.
Esc Button: Press to return to the previous menu in the settings menu.
Test/Up Button Battery test: Press and hold for more than 0.5 seconds to test the battery while in Online mode and
Freq. Converter* mode.
UP Button: Press to display the next selection in the settings menu.
Mute/Down Button
Mute the alarm: Press and hold for more than 0.5 seconds to mute the buzzer.
Refer to section 4.4.9 for details.
Down Button: Press to display the previous selection in the settings menu.
Test/Up + Mute/Down Button Press and hold the two buttons simultaneously for more than 1 second to enter/exit the menu.
4.2 LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on front panel to show the UPS operation status:
Mode / LED Bypass Line Battery Fault
Initialization
Standby mode
Bypass mode
Online mode
Battery mode
Freq. Converter* mode
Battery test
ECO mode
Fault
Note: means LED is illuminated, and means LED is off.
* Freq. Converter means Constant Output Voltage and Constant Output Frequency.
12
4. Operation
LCD Panel:
Display Function
Backup Time Information
Shows the battery discharge time.
H: hours, M: minutes, S: seconds
Fault Information
A warning or fault has occurred.
Displays the fault codes. Codes are listed in
further detail in Section 3.9.
Alarm Status
The UPS alarm is disabled.
Output & Battery Voltage Information
Shows the output voltage, frequency or
battery voltage.
VAC: output voltage, VDC: battery voltage,
Hz: frequency
Load Information
Shows load level by 0-25%, 26-50%,
51-75% and 76-100%.
Overload.
The load or output is shorted.
Display Function
Mode Operation Information
The UPS is connected to the mains (utility)
power.
The battery is working.
The bypass circuit is working.
ECO mode is enabled.
The inverter circuit is working.
Power output is working.
Battery Information
Shows battery capacity by 0-25%, 26-50%,
51-75% and 76-100%.
Battery is not connected.
Indicates low battery level and low battery
voltage.
Input & Battery Voltage Information
Displays input voltage, frequency or battery
voltage.
VAC: input voltage, VDC: battery voltage,
Hz: input frequency
13
4. Operation
4.3 Audible Alarm
Description Buzzer status Mutable
UPS status
Bypass mode Beeps once per 2 seconds.
YesBattery mode Beeps once per 4 seconds.
Fault mode Beeps continuously.
Warning
Overload Beeps twice per second.
No
All other warnings Beeps once per second.
Fault
All Beeps continuously. Yes
4.4 Single UPS Operation
4.4.1 Turning the UPS on (Online mode)
1) Once the power supply is connected correctly, switch the UPS input breaker to “ON” position. At this time, the fan will be running
and the UPS will proceed to power-on mode for initialization. Several seconds later, the UPS will operate in Bypass mode and supply
power to the connected loads via the bypass.
Note: In Bypass mode, the load is not protected by the UPS. To protect connected devices, turn on the UPS as shown in Step 2.
2) Press and hold the “ON” button for 0.5 seconds to turn on the UPS. The buzzer will beep once.
3) A few seconds later, the UPS will enter Online mode. If utility power is abnormal, the UPS will operate in Battery mode without
interruption.
Note: When the UPS is running low on battery power, it will shut down automatically in Battery mode. The UPS will auto restart in Online mode as
soon as utility power is restored.
4.4.2 Turning on the UPS without utility power supply (Battery mode)
1) Make sure that the battery pack breaker is set to “ON” position.
2) Press the “ON” button to set up the power supply for the UPS. The UPS will enter power-on mode. After initialization, the UPS will
enter Standby mode. When this happens, press and hold the “ON” button for 0.5 seconds to turn on the UPS. The buzzer will beep
once.
3) A few seconds later, the UPS will be turned on and enter Battery mode.
4.4.3 Connecting devices to UPS
1) After the UPS has been turned on, devices may be connected and powered on one by one. The UPS system’s LCD panel will display
the total load level.
2) When connecting devices with inductive loads (such as a printer), the in-rush current should be calculated carefully to confirm it
meets the capacity of the UPS. Power consumption of such loads may cause an overload.
3) If the UPS is overloaded, the buzzer will beep twice every second.
4) In case of overload, remove non-essential devices immediately. It is recommended to have the total load connected to the UPS no
more than 80% of its nominal power capacity to prevent overload and ensure system safety.
5) If the overload time is higher than the acceptable time listed in Online mode, the UPS will automatically transfer to Bypass mode.
After the overload is removed, it will return to Online mode. If the overload time is higher than acceptable time listed in Battery mode,
the UPS will go to fault status. At this time, if the bypass is enabled, the UPS will supply power to the load via bypass. If the bypass
function is disabled or the input power is not within acceptable bypass range, it will cut off output directly.
4.4.4 Charging the batteries
1) After the UPS is connected to the utility power, the charger will charge the batteries automatically, except in Battery mode or during
battery self-test.
2) It is recommended to charge the batteries at least 10 hours prior to use. Otherwise, the backup time may be shorter than expected.
14
4. Operation
4.4.5 Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different battery capacities. If the battery capacity is greater than
25%, the buzzer will beep once every 4 seconds. If the battery voltage drops to the alarm level, the buzzer will beep quickly (once
every second) to alert users that the battery is at low level and the UPS will automatically shut down soon. Users may switch off some
non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no more load to remove, proceed to shut
down all loads as soon as possible to protect devices and save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, users can press the Mute button to disable the buzzer.
3) Backup time depends on both internal and external battery capacity.
4) Backup time may vary due to different environments, temperatures and load types.
5) When setting the backup time for the default value of 16.5 hours (16.5 is the default value because of value set #09 on page 17
of the LCD settings; the default value is 990 minutes, or 16.5 hours), the UPS will shut down automatically to protect the battery
after discharging 16.5 hours. This battery discharge protection can be enabled or disabled through the LCD control panel. (Refer to
section 4.7 for more information.)
4.4.6 Testing the batteries
1) To check the battery status when the UPS is in Online mode/Freq. Converter mode, you can press the “Test” button for the UPS to
perform a battery self-test.
2) Users may set battery self-tests through the network management card.
4.4.7 Turning the UPS off with utility power present in Online mode
1) Turn off the UPS inverter by pressing the “OFF” button for at least 0.5 seconds. The buzzer will beep once and the UPS will enter
Bypass mode.
Notes:
If the UPS has been set to bypass output, it will bypass voltage from utility power to the output terminal, even though the UPS inverter has been
turned off.
After turning off the UPS, be aware that the UPS is operating in Bypass mode and there is risk of power loss for connected devices.
2) In Bypass mode, UPS output voltage is still present. In order to cut off the output, switch off the line input breaker. Within a few
seconds, the unit’s LCD panel will be blank and the UPS will be completely off.
4.4.8 Turning the UPS off with no utility power present in Battery mode
1) Turn off the UPS by pressing the “OFF” button for at least 0.5 seconds. The buzzer will sound once.
2) The UPS will cut off power to output and the LCD panel will be blank.
4.4.9 Muting the buzzer
1) To mute the buzzer, press the “Mute” button for at least 0.5 seconds. If the Mute button is pressed after the buzzer is muted, the
buzzer will reactivate.
2) Some warning alarms cannot be muted unless the error is fixed. Refer to section 4.3 for more details.
4.4.10 Operation in warning status
1) When Fault LED flashes and the buzzer sounds once every second, the UPS is encountering problems with its operation. Users may
view the warning indicator from the LCD panel. Check the troubleshooting table in section 6 for more details.
2) Some warning alarms cannot be muted until the error is fixed. Refer to section 4.3 for more details.
4.4.11 Operation in Fault mode
1) When the Fault LED illuminates and the buzzer sounds continuously, there is a fatal error in the UPS. Users can view the fault code
from the LCD panel. Check the troubleshooting table in section 6 for more details.
2) Check the loads, wiring, ventilation, utility, battery, etc. after a fault occurs. Do not attempt to turn on the UPS again until the problem
is resolved. If the problem cannot be fixed, please contact Tripp Lite Tech Support.
3) In case of an emergency, immediately cut off the connection from utility, external battery, and output to avoid further risk or danger.
15
4. Operation
Warning: (Only for parallel system setups)
Before turning on the parallel system to activate inverter, make sure all units’ maintenance switches are set to
the same position.
When the parallel system is turned on to work through the inverter, do not operate the maintenance switch of any unit.
4.5 Parallel UPS Operation (SVT20KX and SVT30KX)
4.5.1 Parallel system initial startup
Before initial startup, first ensure all of the UPS systems can be connected in parallel and have the same configuration.
1) Turn on each UPS to Online mode (refer to section 4.4.1). Then, using a multimeter, measure the inverter output voltage of each
phase for each UPS to confirm that the inverter voltage difference between actual output and setting value is less than 1.5V (typically
1V). If the difference is greater than 1.5V, calibrate the voltage by configuring the inverter voltage adjustment (refer to Program Codes
15, 16 and 17, in section 4.7) in the LCD setting. If the voltage difference after calibration remains greater than 1.5V, contact
Tripp Lite Technical Support for further assistance.
2) Calibrate the output voltage measurement by configuring the output voltage calibration (refer to Program Codes 18, 19, and 20,
section 4.7) in the LCD panel to ensure the difference between the real output voltage and the detected value of the UPS is less
than 1V.
3) Turn off each UPS (refer to section 4.4.7), then follow the wiring procedure in section 3.5.
4) Remove the metal cover to access the parallel communication ports on the UPS; connect each UPS one by one (maximum of three
units for parallel installation) with the parallel cable and shared current cable. Follow the parallel communication cable configuration
as shown in the figure below:
= Current Sharing Cables
= Parallel Cable
4.5.2 Turning a parallel system on in Online mode
1) Turn on the line input breaker of each UPS. When all UPS systems enter Bypass mode, measure the output voltage between two
UPS systems for the same phase to ensure the phase sequence is correct. If these two voltage differences are near zero, then all
connections are correct. If not, check to see if the wirings are connected correctly.
2) Turn on the output breaker of each UPS.
3)
Turn on each UPS one at a time. The UPS systems will then enter to Online mode synchronously and the parallel system is completed.
4.5.3 Turning on the parallel system in Battery mode
1) Turn on the battery breaker and output breaker of each UPS.
Note: Do not share one battery pack in a parallel system. Each UPS must be connected to its own battery pack.
2) Turn on any UPS. A few seconds later, the UPS will enter Battery mode.
3) Then, turn on another UPS. A few seconds later, the UPS will enter Battery mode and add to the parallel system.
4) If there is a third UPS in the setup, follow the same procedure as outlined above. The parallel system is complete.
4.5.4 Adding a new unit to the parallel system
1) A new unit cannot be added to the parallel system when the whole system is in operation. The load must be powered off and the UPS
system shut down.
2) Make sure all UPS systems can be connected in parallel and follow the wiring instructions in section 3.5.
4.5.5 Removing a unit from the parallel system
There are two methods to remove a unit from the parallel system:
Method 1:
1)
Press the “OFF” key twice, each time for more than 0.5 seconds. The UPS will enter into Bypass mode or Standby mode without output.
2) Turn off the unit’s output breaker and input breaker.
3) After the unit shuts down, turn off the battery breaker and remove the parallel cable and share current cables. Then remove the unit
from the parallel system.
16
4. Operation
Method 2:
1) If the UPS indicates a bypass abnormal error code, you cannot remove the UPS without interruption and must first power down the
load and the UPS system.
2) Make sure the bypass setting is enabled in each UPS, then turn off the running system. All UPS systems will transfer to Bypass mode.
Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “BPS”. Turn off all input breakers and
battery breakers in the parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS to be removed, then remove the unit
from the parallel system.
4) Turn on the input breaker of the remaining UPS system(s). The system(s) will transfer to Bypass mode. Set the maintenance switches
from “BPS” to “UPS” and reattach the maintenance bypass covers.
5) Turn on the remaining UPS systems.
4.6 LCD Panel Abbreviations
Abbreviation Display content Meaning
ADD Add
ATO Auto
BAT Battery
CF Freq. Converter mode
CHE Check
DIS Disable
ENA Enable
FBD
Forbidden
N.L Neutral line loss
NCF Normal mode (not Freq. Converter mode)
OFF Off
ON On
OP.V Output voltage
OPN Allow
PAR Parallel, 001 means the first UPS
RES Reserved
RN First phase
RS First line
SN Second phase
ST Second line
SUB Subtract
TN Third phase
TR Third line
17
4. Operation
4.7 LCD Settings
There are three parameters to set up the UPS. Refer to the illustration below.
Parameter 1 is for program alternatives. Refer to below tables for the programs to set up.
Parameter 2 and Parameter 3 are the setting options or values for each program.
Note: Use the “Up” or “Down” button to change the programs or parameters.
Programs Available for Parameter 1:
Code Description
Bypass /
Standby mode AC mode
ECO
mode
Freq.
Converter
mode
Battery
mode
Battery
Test
01
Output voltage
02
Output frequency
03
Voltage range for bypass
04
Frequency range for bypass
05
ECO mode enable/disable
06
Voltage range for ECO mode
07
Frequency range for ECO mode
08
Bypass mode setting
09
Maximum battery discharge time setting
10
Reserved Reserved for future options
11
Reserved Reserved for future options
12
Neutral loss detection
13
Battery voltage calibration
14
Charger voltage adjustment
15
Inverter A voltage adjustment
16
Inverter B voltage adjustment
17
Inverter C voltage adjustment
18
Output A voltage calibration
19
Output B voltage calibration
20
Output C voltage calibration
A in chart indicates the program can be set in the mode listed.
Note: All parameter settings will be saved only when the UPS shuts down normally with internal or external battery connection. (Normal UPS shutdown
means turning off input breaker in Bypass/Standby mode).
18
4. Operation
01: Output voltage
Interface Setting
Parameter 3: Output voltage
You may choose the following output voltage in Parameter 3:
220: Output voltage is 220V AC.
230: Output voltage is 230V AC.
240: Output voltage is 240V AC.
02: Output frequency
Interface Setting
60Hz, Freq. Converter mode
50Hz, Normal mode
ATO
Parameter 2: Output Frequency
Set the output frequency. You may choose three options in Parameter 2:
50.0Hz: Output frequency is 50.0Hz.
60.0Hz: Output frequency is 60.0Hz.
ATO: If selected, output frequency will be decided according to the latest normal utility frequency. If
it is between 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is between 56Hz to 64Hz, the
output frequency will be 60.0Hz. Automatic (ATO) is the default setting.
Parameter 3: Frequency mode
Freq. Converter mode has two options to choose from in Parameter 3:
CF: Set UPS to Freq. Converter mode. If selected, the output frequency will be fixed at 50Hz or
60Hz according to the setting in Parameter 2. The input frequency can range from 46Hz to 64Hz.
NCF: Set UPS to Normal mode (not Freq. Converter mode). If selected, the output frequency will
synchronize with the input frequency within 46~54Hz at 50Hz or within 56~64Hz at 60Hz accord-
ing to the setting in Parameter 2. If 50Hz is selected in Parameter 2, the UPS will transfer to battery
mode when the input frequency is outside 46~54Hz. If 60Hz is selected in Parameter 2, the UPS
will transfer to battery mode when the input frequency is outside 56~64Hz.
*If Parameter 2 is ATO, Parameter 3 will show the current frequency.
Note: A single UPS unit will have bypass output for a couple of seconds after the unit is powered on. To avoid damage to connected devices, it is strongly
recommended to add an additional Output relay board for Freq. Converter application.
03: Voltage range for bypass
Interface Setting
Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 110V to 209V.
The default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass. Setting range is from 231V to 276V.
The default value is 264V.
04: Frequency range for bypass
Interface Setting
Parameter 2: Set the acceptable low frequency for bypass.
50Hz system: Setting range is from 46.0Hz to 49.0Hz.
60Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3: Set the acceptable high frequency for bypass.
50Hz: Setting range is from 51.0Hz to 54.0Hz.
60Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
19
4. Operation
05: ECO mode enable/disable
Interface Setting
Parameter 3: Enable or disable ECO function. You may choose one of the following two options:
DIS: Disable the ECO function.
ENA: Enable the ECO function.
If ECO function is disabled, voltage range and frequency range for ECO mode still can be set, but is
inconsequential unless the ECO function is enabled.
DIS is the default value.
06: Voltage range for ECO mode
Interface Setting
Parameter 2: Low voltage point in ECO mode. The setting range is from -11V to -24V of the
nominal voltage.
Parameter 3: High voltage point in ECO mode. The setting range is from +11V to +24V of the
nominal voltage.
07: Frequency range for ECO mode
Interface Setting
Parameter 2: Set low voltage point for ECO mode.
50Hz system: Setting range is from 46.0Hz to 48.0Hz.
60Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3: Set high voltage point for ECO mode.
50Hz: Setting range is from 52.0Hz to 54.0Hz.
60Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Bypass mode setting
Interface Setting
Parameter 2:
OPN: Bypass allowed. When selected, the UPS will run in Bypass mode depending on the bypass
enabled/disabled setting.
FBD: Bypass not allowed. When selected, the UPS is not allowed in Bypass mode under any
situation.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual bypass is not
allowed. Under Manual bypass, the user can manually switch the UPS into Bypass mode by pressing
the OFF button while in the Online mode.
09: Maximum battery discharge time setting
Interface Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999 min. The UPS will shut down to
protect its battery if the discharge time elapses before the battery is under voltage. The default
value is 990 minutes.
DIS: Disable battery discharge protection. Backup time will depend on battery capacity.
20
4. Operation
10: Reserved
Interface Setting
Reserved for future options.
11: Reserved
Interface Setting
Reserved for future options.
12: Neutral loss detection
Interface Setting
Parameter 2:
N.L: Indicates neutral loss detection function.
Parameter 3:
DIS: Disable the neutral loss detection function. The UPS will not detect the neutral loss.
ATO: The UPS will automatically detect if the neutral is lost. If neutral loss is detected, an alarm
will sound. If the UPS is turned on, it will transfer to battery mode. When neutral is restored
and detected, the alarm will be muted automatically and the UPS will go back to Normal mode
automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral loss is detected, an alarm will
sound. If the UPS is turned on, it will transfer to battery mode. When neutral is restored, the alarm
will NOT be muted automatically and the UPS will NOT go back to normal mode automatically.
You must mute the alarm and put the UPS back to Normal mode manually using these steps:
1) Enter this menu and press the “Enter” key to make the “CHE” flash. 2) Press the “Enter” key
again to activate the neutral detection (check). If neutral is detected, the alarm will be muted and
the UPS will go back to normal mode. If neutral is not detected, the UPS will continue sounding
an alarm and stay on the latest status until the neutral is properly detected at the next manual
checking operation.
CHE is the default setting.
13: Battery voltage calibration
Interface Setting
Parameter 2: Select Add or Sub function to adjust battery voltage to actual figure.
Parameter 3: The voltage range is from 0V to 9.9V. The default value is 0V.
14: Charger voltage adjustment
Interface Setting
Parameter 2: Choose Add or Sub to adjust charger voltage
Parameter 3: The voltage range is from 0V to 9.9V. The default value is 0V.
Notes:
Battery disconnect should be performed by qualified service personnel only.
Before making voltage adjustments, be sure to first disconnect all batteries to get the accurate charger voltage.
• Any modifications must be within range of the batteries’ specifications.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128

Tripp Lite SmartOnline SVTX Series Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire