Rinnai Q175CN Mode d'emploi

Catégorie
Chauffe-eau
Taper
Mode d'emploi

Ce manuel convient également à

- Donotstoreorusegasolineorotherammablevaporsand
liquidsinthevicinityofthisoranyotherappliance.
- WHAT TO DO IF YOU SMELL GAS
- DoNOTtrytolightanyappliance.
- DoNOTtouchanyelectricalswitch.
- DoNOTuseanyphoneinyourbuilding.
- Immediatelycallyourgassupplierfromaneighborsphone.
Followthegassuppliersinstructions.
- Ifyoucannotreachyourgassupplier,calltheredepartment.
8W.51.40.07 / 01.17 Changes reserved.
Installation & Servicing
Instructions
Theseinstructionstoberetainedbyuser.
CAUTION!
Read this manual thoroughly before installing, servicing, putting
into operation or using this boiler and vent system.
WARNING!
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury
(exposure of hazardous materials)* or loss of life. Refer to the
user's information manual provided with this boiler. Installation
and service must be performed by a licensed professional, service
agency or the gas supplier (who must read and follow the supplied
instructions before installing, servicing, or removing this boiler).
CAUTION!
The user manual is part of the documentation that is delivered
to the installation's operator. Go through the information in this
manual with the owner/operator and make sure that they are
familiar with all necessary operating instructions.
NOTICE!
Installation and service must be performed by a licensed
professional,servicetechnicianorthegassupplier.
Pictured: Q85SN, Q130SN
Q85SP, Q130SP
Higheciencycondensinggasboiler
Q85SN/Q130SN/Q175SN/Q205SN/Q175CN
Q85SP/Q130SP/Q175SP/Q205SP/Q175CP
WARNING!
Ifyoudonotfollowtheseinstructionsexactly,areorexplosion
mayresultcausingpropertydamage,personalinjuryorlossoflife.
Address:103InternationalDrive,PeachtreeCity,GA,30269
Toll-free:1-800-621-9419Fax:678-829-1666www.rinnai.us
Français:voirpage103
Installation & Servicing Instructions Rinnai Q-Series
2
Contentsofinstructions
These installation instructions contain important information for the safe installation, start-up and maintenance of
boilers with capacities 85,000 through 205,000 BTU/hr.
These installation instructions are intended for licensed professionals, who have the necessary knowledge and
are approved for working on heating and gas systems.
Subjecttotechnicalchanges
Changes may be made without notice to the illustrations, process steps and technical data as a result of our policy
of continuous improvement.
Updatingofdocumentation
Please contact us if you have any suggestions for improvements or corrections.
Find our contact details on the back of this manual.
1 Safety and general instructions ........................................................4
1.1 Designated use ...................................................................4
1.2 Hazarddenitions ................................................................4
1.3 Symboldenitions ...............................................................4
1.4 The following instructions must be followed ........................5
1.5 Follow these instructions for the space heating water .........6
1.6 Tools, materials and additional equipment ..........................6
1.7 Relevant Installation, Service and User manuals ................6
1.8 Disposal ...........................................................................7
2 Regulations and guidelines ..............................................................7
3 Description of the boiler ...................................................................8
4 Packaging and transportation ..........................................................9
4.1 Scope of delivery .................................................................9
4.2 Transportation .....................................................................9
5 Installation .........................................................................10
5.1 Requirements for the installation room .............................10
5.2 Fitting the boiler .................................................................11
5.3 Dimensions ........................................................................12
5.3.1 Plumbing Kits.....................................................................15
5.3.2 Clearences from the boiler ................................................16
5.4 Technicalspecications .....................................................17
6 Connecting the boiler .....................................................................18
6.1 Central heating system ......................................................18
6.1.1 Plumbing Kits and installation ...........................................20
6.1.2 Side mounting kit for the Low Loss Header .......................24
6.1.3 Safety valve .......................................................................24
6.1.4 Lowwatercuto ...............................................................24
6.2 Boiler expansion tank ........................................................25
6.3 Underoorheatingsystem(plasticpipes) ...........................25
6.4 Gas connection .................................................................26
6.5 Hot water supply (Combi boiler Q175CNQ175CP) ...........28
6.5.1 Domestic Water quality ......................................................28
6.5.2 Domestic water treatment Accessory ................................29
6.5.3 DHW Expansion Tank ........................................................29
6.5.4 Installing a valve kit ...........................................................29
6.5.5 Pressure relief Valve for Combi boilers .............................30
6.6 Condensate drain pipe ......................................................30
6.7 Vent system and air supply system ...................................31
6.7.1 Intake / Exhaust Guidelines ...............................................31
6.7.2a Examples vent and air supply systems (concentric) .........32
6.7.2b Examples vent and air supply systems (parallel) ..............33
6.7.3 Installation of the vent system ...........................................34
6.7.3.1 Boiler conversion from concentric to parallel ....................35
6.7.3.2 Installingairlter...............................................................35
6.7.4 Recommended vent/air intake terminal position ...............36
6.7.5 Direct vent closet and alcove installation ........................38
6.7.6 Dimensioning of the exhaust and air intake duct .............39
6.7.7 Combustion air and vent piping lengths. ...........................40
6.7.8 Calculation of compensation factor ...................................41
6.7.9 Room Air System (indoor combustion air) .........................42
Installation & Servicing Instructions Rinnai Q-Series
3
Content
1 Safety and general instructions ........................................................4
1.1 Designated use ...................................................................4
1.2 Hazarddenitions ................................................................4
1.3 Symboldenitions ...............................................................4
1.4 The following instructions must be followed ........................5
1.5 Follow these instructions for the space heating water .........6
1.6 Tools, materials and additional equipment ..........................6
1.7 Relevant Installation, Service and User manuals ................6
1.8 Disposal ...........................................................................7
2 Regulations and guidelines ..............................................................7
3 Description of the boiler ...................................................................8
4 Packaging and transportation ..........................................................9
4.1 Scope of delivery .................................................................9
4.2 Transportation .....................................................................9
5 Installation .........................................................................10
5.1 Requirements for the installation room .............................10
5.2 Fitting the boiler .................................................................11
5.3 Dimensions ........................................................................12
5.3.1 Plumbing Kits.....................................................................15
5.3.2 Clearences from the boiler ................................................16
5.4 Technicalspecications .....................................................17
6 Connecting the boiler .....................................................................18
6.1 Central heating system ......................................................18
6.1.1 Plumbing Kits and installation ...........................................20
6.1.2 Side mounting kit for the Low Loss Header .......................24
6.1.3 Safety valve .......................................................................24
6.1.4 Lowwatercuto ...............................................................24
6.2 Boiler expansion tank ........................................................25
6.3 Underoorheatingsystem(plasticpipes) ...........................25
6.4 Gas connection .................................................................26
6.5 Hot water supply (Combi boiler Q175CNQ175CP) ...........28
6.5.1 Domestic Water quality ......................................................28
6.5.2 Domestic water treatment Accessory ................................29
6.5.3 DHW Expansion Tank ........................................................29
6.5.4 Installing a valve kit ...........................................................29
6.5.5 Pressure relief Valve for Combi boilers .............................30
6.6 Condensate drain pipe ......................................................30
6.7 Vent system and air supply system ...................................31
6.7.1 Intake / Exhaust Guidelines ...............................................31
6.7.2a Examples vent and air supply systems (concentric) .........32
6.7.2b Examples vent and air supply systems (parallel) ..............33
6.7.3 Installation of the vent system ...........................................34
6.7.3.1 Boiler conversion from concentric to parallel ....................35
6.7.3.2 Installingairlter...............................................................35
6.7.4 Recommended vent/air intake terminal position ...............36
6.7.5 Direct vent closet and alcove installation ........................38
6.7.6 Dimensioning of the exhaust and air intake duct .............39
6.7.7 Combustion air and vent piping lengths. ...........................40
6.7.8 Calculation of compensation factor ...................................41
6.7.9 Room Air System (indoor combustion air) .........................42
7 External domestic hot water tanks .................................................45
8 Electrical connections ....................................................................45
9 Boiler controls .........................................................................49
9.1 Explanation of the function buttons ...................................50
10 Starting up: Filling and de-aerating the boiler and installation .......51
10.1 Requirements of the water system ....................................51
10.2 Filling the heating system ..................................................52
10.3 Hot water supply (only Q175C) .........................................53
11 Adjustments .........................................................................55
11.1 Altering adjustments ..........................................................55
11.2 Activating factory settings (green button function) ...........58
12 Isolating the boiler .........................................................................58
13 Commissioning .........................................................................60
13.1 Testing for gas leaks ..........................................................61
13.2 TestingtheIgnitionSafetyshutodevice .........................61
13.3 Checking the O
2
at full load (Step 1/3) ...............................62
13.3.1 Checking the O
2
at low load (Step 2/3) ..............................63
13.3.2 Settings on the gas valve (Step 3/3) .................................64
13.4 Measuring the ionization current .......................................65
13.5 Installing the casing ...........................................................66
14 Maintenance .........................................................................66
14.1 Periodic examination of venting systems and boiler .........66
14.2 Inspection .........................................................................66
14.3 Maintenance activities .......................................................68
14.3.1 Reset service interval counter ...........................................70
14.4 Limited warranty ................................................................70
15 Parts of the boiler .........................................................................71
16 Blocks and Errors .........................................................................72
17 Spare parts .........................................................................80
18 Parts list vent system .....................................................................98
19 Common venting guidelines .........................................................100
Appendix A - Outoor Reset Sensor Data ...........................................101
Appendix B - Resistance table NTC sensors .....................................102
Installation & Servicing Instructions Rinnai Q-Series
4
1 Safetyandgeneralinstructions
Please observe these instructions in the interest of your own safety.
1.1 Designateduse
The boiler is designed for heating water for a central heating system and, if applicable,
generating domestic hot water. The boiler is delivered with a burner controller
(MCBA)pre-installed.Theboilercanbettedwithamodulatingoutdoorresetsensor
ARV12(includedwiththeboiler)oranOn/Othermostatorrelaypanelendswitch
(accessories).
1.2 Hazarddenitions
Thefollowingdenedtermsareusedthroughoutthedocumentationtobringattention
to the presence of hazards of various risk levels. Notices give important information
concerning the operation of the product.
DANGER:
Indicates the presence of hazards that will cause severe personal injury, death or
substantial property damage.
WARNING:
Indicates the presence of hazards that can cause severe personal injury, death or
substantial property damage.
CAUTION:
Indicates presence of hazards that will or can cause minor personal injury or property
damage.
CAUTION:
Risk of electric shock. Indicates presence of hazards due to electric shock.
NOTICE:
Indicates special instructions on installation, operation or maintenance that are
important but not related to personal injury or property damage.
1.3 Symboldenitions
The following (safety) symbols may be encountered in these installation instructions
and on the unit:
Thissymbolindicatesthattheunitmustbestoredawayfromfreezingconditions.
Thissymbolindicatesthatthepackagingand/orcontentscanbedamagedas
aresultofinsucientcaretakenduringtransport.
Thissymbolindicatesthat,whilestillinitspackaging,theunitmustbeprotected
fromweatherconditionsduringtransportandstorage.
!
CAUTION
CAUTION
!
WARNING
NOTICE
i
!
DANGER
Installation & Servicing Instructions Rinnai Q-Series
5
1.4 Thefollowinginstructionsmustbefollowed
- The boiler must only be used for its designated purpose, as described in the
Installation Instructions.
- Eachunitisttedwithadataplate.Consultthedetailsonthisplatetoverifywhether
the boiler is compliant with its intended location, e.g.: gas type, power source and
ventingclassication.
-
Only use the boiler with the accessories and spare parts listed.
- Other combinations, accessories and consumables may only be used if they are
specicallydesignedfortheintendedapplicationanddonotaectthesystem
performance and the safety requirements.
- Maintenance and repairs must be performed by a licensed professional.
- Installation of a condensing gas boiler must be reported to the relevant gas utility
company and have it approved.
- You are only allowed to operate the condensing gas boiler with the vent system
thathasbeenspecicallydesignedandapprovedforthistypeofboiler.
- Please note that local permission for the vent system and the condensate water
connection to the public sewer system may be required.
You must also respect:
- The local building codes stipulating the installation rules.
- The local building codes concerning the air intake and outlet systems and the
chimney connection.
- The regulations for the power supply connection.
- The technical rules established by the gas utility company concerning the
connection of the gas connection to the local gas mains.
- The instructions and standards concerning the safety equipment for the water/
space heating system.
- The Installation Instructions for building heating systems.
- The boiler must be located in an area where leakage of the boiler or connections
willnotresultindamagetotheareaadjacenttotheboilerortoloweroorsof
the structure. When such locations cannot be avoided, it is recommended that a
suitable drain pan be installed under the boiler.
- The boiler must be installed in such way that the all components are protected
from water (dripping, spraying, rain etc.) during boiler operation and service.
- The boiler must not be installed on or against carpeting.
- Do not restrict or seal any air intake or outlet openings.
- Ifyoundanydefects,youmustinformtheownerofthesystemofthedefectand
the associated hazard in writing.
Infailuretoproperlycommissiontheboilerasdescribedinsection13mayresult
unreliableburneroperation,reducedcomponentlife,andunsafeboileroperation.
DANGER.Gasisammableandmaycauseanexplosion.
Bewareifyousmellgas:theremaybeanexplosionhazard!
Iftheinformationintheseinstructionsisnotfollowedexactly,areorexplosionmay
result causing property damage, personal injury or death.
- Donotstoreorusegasolineorotherammablevaporsandliquidsinthevicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do NOT try to light any appliance.
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
- Ifyoucannotreachyourgassupllier,calltheredepartment.
Shouldoverheatingoccurorthegassupplyfailtoshuto,donotturnoor
disconnecttheelectricalsupplytothepump.Instead,shutothegassupply
atalocationexternaltotheboiler.
!
DANGER
!
WARNING
!
WARNING
!
WARNING
Installation & Servicing Instructions Rinnai Q-Series
6
Chemicalsthatarecorrosiveinnatureshouldnotbestoredorusednearthe
boilerorventtermination.
1.5 Followtheseinstructionsforthespaceheatingwater
Unsuitableheatingsystemwatercancausetheformationofscaleorsludge,whichaects
systemeciency.Itcanalsocausecorrosionandreducelifeoftheheatexchanger.
You must follow Rinnai guidelines for boiler water quality.
– Thoroughlyushthesystempriortolling.
Follow the Rinnai cleaning instructions.
Never use water that has been treated by a reverse osmosis, D.I., or distilled water
tosoftenthewatertolltheheatingsystem.
Do not use inhibitors or other additives unless approved by Rinnai for that purpose.
When freeze protection of the heating system is desired, only use Rinnai-approved
antifreezes. The allowed maximum concentration is 50%.
– Whenusingoxygen-permeablepipes,e.g.forunderoorheatingsystems,you
must separate the system from the boiler using plate heat exchangers.
– Valveoboilerwhileushingsystem,donotintroduceanysystemcleanerintothe
boilerloop.Flushsystemthoroughlytoremoveallsystemcleanerbeforellingboiler.
Approvedantifreeze: • Rhomar RhoGard Mutli-Metal (AL safe) • Sentinel X500
(max. concentration 50%) • Noble Noburst AL • Fernox Alphi 11
Approvedsystemcleaner: • Noble Noburst Hydronic System Cleaner • Fernox F3 Cleaner
Rhomar Hydro-Solv 9100 Sentinel X400
ThesystemcleanersfromNoBurst,Rhomar,andFernoxarenottobeusedin
theboiler.Theboilermustbeclosedo(valvedo)fromtherestofthesystem
ornotconnectedwhilethecleanersareinthesystem.Thesystemshouldthen
be drained and then thoroughly ushed with clean water to remove all the
systemcleaner.
Approvedinhibitors: • Rhomar Pro-tek 922 • Sentinel X100
Noble Noburst AL inhibitor
See the Rinnai Boiler Applications Manual or Chapter 6 and 10 of this manual for
additional information.
Ifproblemsoccurwhenusingsanitarywaterwithachlorinecontent
higher than 150mg/l, no recoursecan bemade to theterms ofthelimited
warranty.
1.6 Tools,materialsandadditionalequipment
For the installation and maintenance of the boiler you will need:
– Standardtoolsforspaceheating,gasandwatertting
Digital manometer that is capable of reading both positive and negative pressures
Combustion analyzer (intended for use with condensing boilers)
Digital multimeter
pH digital meter
Metric Allen wrenches
Metric socket wrenches
In addition, a handtruck with a fastening belt is useful.
For maintenance of the boiler you will need, apart from standard tools for space
heating,gasandwaterttingsthefollowingitems:
- Rinnai toolkit Q and E-Series
NOTICE
i
NOTICE
i
NOTICE
i
Installation & Servicing Instructions Rinnai Q-Series
7
1.7 RelevantInstallation,ServiceandUsermanuals
Approved vent system
Rinnai Boiler Applications Manual
User manual
1.8 Disposal
Dispose of the boiler packaging in an environmentally sound manner.
Dispose of components of the heating system (e.g. boiler or control device), that
must be replaced in an environmentally responsible manner.
2 Regulationsandguidelines
The installation must comply to the requirements of the authority having jurisdiction
or, in the absence of such requirements, to the latest edition of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54. In Canada, installation must be in accordance with
the requirements of CAN/CSA B149.1, Natural Gas and Propane Installation Code.
Where required by the authority having jurisdiction, the installation must comply to
the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/
ASME CSD-1.
Install CO detectors per local regulations. Boiler requires an inspection every 2 years or
4000 hours and maintenance every 4 years or 8000 hours. See maintenance section
chapter 14.
Operating Limits of the boiler:
Max. boiler temperature: 176 °F (80 °C)
Max. operating pressure: 45 psi (3 bar)
Max. Allowable Working Temperature ASME: 200 °F (93 °C)
Max. Allowable Working Pressure ASME: 45 psi (3 bar)
The hot water distribution system must comply with all applicable codes and
regulations. When replacing an existing boiler, it is important to check the condition
of the entire hot water distribution system to ensure safe operation.
Installation & Servicing Instructions Rinnai Q-Series
8
3 Descriptionoftheboiler
The Rinnai Q boiler is a room sealed, condensing and modulating central heating
boiler, with an optional integrated DHW cylinder (integrated DHW on the Q175C only).
The QxxS boiler models have the ability to control a domestic hot water indirect tank.
The boiler is provided with a compact stainless steel heat exchanger with smooth
tubes. This design is a well engineered principle using durable materials.
The boiler burns gas for supplying heat. The heat is transferred in the heat exchanger
to the water in the central heating system. By cooling down the exhaust gases
condensateisformed.This results in high eciency.Thecondensate,whichhas
noeectontheheatexchangerandthefunctionoftheboiler,isdrainedthrougha
condensate collector trap.
The boiler is provided with an intelligent control system (CMS Control Management
System). The boiler anticipates the heat demand of the central heating system or the
domestic hot water facility system.
When an outdoor sensor is connected to the boiler it will operate weather dependantly
using outdoor reset. This means that the boiler control measures the outside
temperature and supply temperature. With this data the boiler calculates the optimal
supply temperature for the installation.
Explanation of the type indication: Rinnai Q205SN
Q = Type
205 = Nominal load in (x1,000) BTU
S = System/Solo (C = Combi)
N = Natural Gas (P = Propane Gas)
Dierentboilertypes:
Roomsealedboiler
The boiler retreives its
combustion air from outside
then discharges the ue
gasses to the outside.
Condensing
Retrieves heat as much as
possiblefromtheuegasses.
Water condensates on the
heat exchanger.
Modulating
Stepless higher or lower
burning according to the heat
demand.
System/Solo boilers: Combi boiler with integrated DHW cylinder
Q85SN, Q130SN Q175SN, Q205SN Q175CN
Q85SP, Q130SP Q175SP, Q205SP Q175CP
Installation & Servicing Instructions Rinnai Q-Series
9
4 Packagingandtransportation
4.1 Scopeofdelivery
The boiler is supplied ready for use.
Please check if the packaging is intact.
Check if all the items listed are included in the delivery.
The supply kit contents:
!
CAUTION
4.2 Transportation
Theboilermaybedamagedwhennotsecuredproperly.
- Only transport the boiler using appropriate transportation equipment, such as a
handtruck with a fastening belt or special equipment for maneuvering steps.
- When shipping the boiler must be secured on the transportation equipment to
preventitfromfallingo.
- Protect all parts against impacts if they are to be transported.
- Follow the transportation markings on the packaging.
Packaged boilers must always be lifted and carried by two people, or you must
use a handtruck or special equipment for transport.
Description
Q85S
Q130S
Q175S
Q205S
Q175C
Boilerwith:
Outdoor reset sensor ARV12 1 1 1
Compression ring Ø15 brass 4
Compression ring Ø22 brass 2
Compression ring Ø28 brass 2
Compression ring Ø35 brass 2 2
Bolt M5X16mm 1 1 1
Cover air supply Ø120/Ø80 1 1 1
Gasket vent system ø80 1 1 1
Power cable pull safety Q-Series 1 1 1
Flue pipe Ø 80 PP 1 1 1
Nut 15mm compression fitting 2
Nut W1.1/8x1/14 22 Compression fitting 1
Nut W1.3/8"x1/14 28 compression fitting 2
Nut W1.610x1/14 35 compression fitting 2 2
Screw 6X60mm 5 5 5
Lip-ring flue pipe ø80 1 1 1
Feed through + plug flue gas 1 1 1
Cap de-aerator 1 1 1
Adapter fitting 15mm x 3/4"NPT ext. 2
Adapter fitting 22mm x 3/4"NPT ext. 1
Flue adapter Ø80/Ø3" pps UL appr. 2 2 2
Flow restriction MR01 FG 21,0L red 1
Wall mounting suspension bracket 1 1 1
Plumbing kit Q85S/Q130S 1 1
Plumbing kit Q175S/Q175C/Q205S 1
3/4" Gas valve 1 1 1
Template on inside of package 1 1 1
Installation & Service Instructions 1 1 1
User information manual 1 1 1
Warranty document 1 1 1
ICSL book 1 1 1
A
moun
t
Installation & Servicing Instructions Rinnai Q-Series
10
5 Installation
5.1 Requirementsfortheinstallationroom
- Theroomwheretheboilerwillbeplacedmustalwaysbefreefromfreezing
conditions.
- Donotstoreorusegasolineorotherammablevaporsandliquidsinthe
vicinityofthisoranyotherappliance.
- Neveruseorstoreanychlorinateddetergentsorhalogenatedhydrocarbons
(e.g.inspraycans,solventsanddetergents,paints,adhesives)inproximity
oftheboiler.
- Theboilermustbeinstalledinsuchawaythatitisprotectedfromwater
(dripping, spraying, rain, etc.) during operation and service (circulator
replacement,condensatetrap,controlreplacement,etc.)
- Thisboilerisforintendedforindoorinstallationsonly.
Productstoavoidpresentinboilerroom
and/oraroundcombustionairintake
Spray cans containing chloro-/fluorcarbons
Ammonium and/or ammonium solutions
Permanent wave solutions (hair product)
Chlorinated waxes and/or cleaners
Swimming pool chemicals based on chlorine
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
Adhesives used to fasten building products and
other similar products
Areaslikel
tohavecontaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
!
DANGER
Installation & Servicing Instructions Rinnai Q-Series
11
5.2 Fittingtheboiler
- Remove the packaging materials.
- Donot tear thepackaging.Take noticeofthe presence ofthemounting
templateattheinsideofthecartonwrapper.
- Laytheboileronitsbackduringunpacking.Whenunpacking,thecasingcan
beremovedfromtheboiler.Thispartcanbekeptapartduringinstallation.It
mustbeplacedontheboilerandxedwiththescrewbehindthedoorbefore
theboilerisstartedup.
Turntheboilertoitssideandremovethewallbracketfromthebackofthe
boilerbyremovingthe2screws.
The boiler can be mounted practically to any wall with the suspension bracket and the
enclosed mounting equipment.
- Thewallmustbeatandofsucientstrengthinordertobeabletosecurelyhold
and support the boiler weight with its water content.
- Take note of the necessary space around the boiler for installation of venting
system, pipework and servicing. See drawing in section 5.3.
The location of the boiler can be determined by using the template which is printed
on the inside the boiler package wrapping. Remember to account for the spacing of
the plumbing kit.
- Drill the necessary holes using the template
- Install the mounting bracket to the wall using the supplied mounting materials
Liftingandcarryingprecautions.
Toavoidpersonalinjurypleasefollowtheserecommendations:
- Alwayslifttheboilerwith2peopleorusespecialequipment.
- Whenliftingtheboiler,bendtheknees,andkeepthebackstraightandfeet
apart.
- Donotliftandtwistatthesametime.
- Liftandcarrytheboilerclosetothebody.
- Wearprotectiveclothingandglovestoprotectfromanysharpedges.
Lifttheboileronlybytheboiler'srearwall.Donotliftusingthepipesonthe
bottomoftheboilerortheventconnectionsonthetopoftheboiler.
- Dispose the packaging materials.
!
CAUTION
NOTICE
i
NOTICE
i
!
WARNING
Installation & Servicing Instructions Rinnai Q-Series
12
5.3 Dimensions
dimensionsQ85S,Q130S,Q175SandQ205S gure1
C
E
F
A
T
B
Q
R
B
H
J
K
G
H
J
K
D
W
C
E
F D
Q
G
A
P
U
T
P
U
R
X
Y
X
Y
Z
dimensionsQ175C gure2
T
B
R
H
J
K
G
D
aa
C
E
F
Q
S
A
P
U
X
Y
Z
O
N
L
aa
V1
aa
V2
V1
V2
V1
V2
Installation & Servicing Instructions Rinnai Q-Series
13
dimensions table 1
Boilertype Combi
Q85SN/Q85SP Q175SN/Q175SP
Q130SN/Q130SP Q205SN/Q205SP Q175CN/Q175CP
inch / mm inch / mm inch / mm
A Height 26.8" / 680 26.8" / 680 26.8" / 680
B Width 19.7" / 500 26" / 660 39.4" / 1000
C Depth 15.2" / 385 15.2" / 385 15.2" / 385
D Left side / vent 13.2" / 335 19.5" / 495 19.5" / 496
E Center to center / vent and air supply 4.7" / 120 4.7" / 121 4.7" / 122
F Back / vent 10.6" / 270 10.6" / 270 10.6" / 270
G Left side / gas pipe 2.6" / 65 2.6" / 65 2.6" / 65
H Left side / supply pipe 7.8" / 199 7.8" / 199 7.8" / 199
J Left side / return pipe 16.8" / 428 19.8" / 504 19.8" / 504
K Left side / condensate pipe 14.6" / 370 20.9" / 530 20.9" / 530
L Left side / expansion pipe 23.2" / 590
N Left side / cold water pipe 34.8" / 885
O Left side / hot water pipe 37.6" / 955
P Pipe length of g* 0.7" / 18 0.7" / 18 0.7" / 18
Q Pipe length of c* 2" / 50 2" / 50 2" / 50
R Pipe length of f and r* 17.7" / 450 18.5" / 470 18.5" / 470
S Pipe length of e, k and w* 3.5" /89
T Back / Center of pipe c* 1" / 25 1" / 25 1" / 25
U Back / Center of pipe g* 1.6" / 40 1.6" / 40 1.6" / 40
V1
Back / Center of pipe f, r, e, k and w* 2" / 50 2" / 50 2" / 50
V2
Back / Center of pipe f and r* 2.1" / 54 2.1" / 54 2.1" / 54
W
Pipe length vent co-axial
Pipe length vent parallel
2.6" / 65
5.8" / 147
2.6" / 65
5.8" / 147
2.6" / 65
5.8" / 147
X Bottom side boiler to center safety valve 7.7" / 195 8" / 200 8" / 200
Y
Bottom side boiler to center header 10.2" / 260 10.4" / 265 10.4" / 265
Z
Center to center of f and r* 9" / 229 12" / 305 12" / 305
aa
Depth plumbing kit 5.6" / 142 5.6" / 142 5.6" / 142
*) See figure 3
Solo
Dimensions
Installation & Servicing Instructions Rinnai Q-Series
14
connection diameters table 2
boilerconnections gure3
Connection for combustion air supply and vent system
Boilertype Combi
Q85SN/Q85SP Q175SN/Q175SP
Q130SN/Q130SP Q205SN/Q205SP Q175CN/Q175CP
Vent system / Combustion air supply
80/125mm 80/125mm 80/125mm
Gas pipe
g 3/4"M-NPT 3/4"M-NPT 3/4"M-NPT
Supply pipe boiler side - f1
28mm 35mm 35mm
system side - f2
1¼"M-NPT 1½"M-NPT 1½"M-NPT
Return pipe boiler side - r1
28mm 35mm 35mm
system side - r2
1¼"M-NPT 1½"M-NPT 1½"M-NPT
Condensate pipe c
0.95" / 24mm 0.95" / 24mm 0.95" / 24mm
Expansion pipe e
0.87"x ¾"M-NPT /
22mm
Cold water pipe k
0.6"x ¾"M-NPT /
15mm
Hot water pipe w
0.6"x ¾"M-NPT /
15mm
Supply pipe indirect tank.
In case of optional internal
3 way valve.
t 1"M-NPT
Solo
Dimensions
gf1 r1c
f2 r2
gf1 r1c
ekw
f2 r2
gf1r1c
t
f2r2
Installation & Servicing Instructions Rinnai Q-Series
15
5.3.1 PlumbingKits
Rinnai boilers are supplied with a Plumbing kit from factory. Find below the dimensions.
See chapter 6.1 for additional information.
2.0”
50mm
2.1”
54mm
142
[5.6”]
9”
229mm
3.9”
100mm
8.6”
219mm
4.7”
119mm
5.2”
131mm
14.2”
360mm
16.4”
416mm
17.6”
448mm
2.0”
50mm
2.1”
54mm
[5.6”
142mm
10.2”
260mm
12”
305mm
15”
381mm
4.7”
120mm
5.2”
133mm
17.2”
438mm
19.7”
501mm
18.6”
474mm
PlumbingKit3
Suitable for:
Q175SN / Q175SP
Q175CN / Q175CP
Q205SN / Q205SP
PlumbingKit2
Suitable for:
Q85SN / Q85SP
Q130SN / Q130SP
Plumbing kit 2 gure 4
Plumbing kit 3 gure 5
Installation & Servicing Instructions Rinnai Q-Series
16
5.3.2 Clearencesfromtheboiler
Minimumrequiredclearances
tocombustibles
Minimumrequiredclearances
tonon-combustibles
Recommended
serviceclearances
Alltypes
A
lltypes
A
lltypes
inch / mm inch / mm inch / mm
Top of boiler 2" / 50 2" / 50 10" / 250
Back of boiler 0" 0" 0
Front of boiler 6" / 150 6" / 150 24" / 600
Left side of boiler 2" / 50 2" / 50 2" / 50
Right side of boiler 2" / 50 2" / 50 2" / 50
Floor / Ground to
bottom of boiler
12" / 300 12" / 300 30" / 762
Floor/ Ground to
bottom Low loss
header
0" 0" 12" / 300
Vent 0" 0" 0"
clearances to the boiler table 3
wall
2"
50
ceiling
Min. 10" /
250mm
15.7"
400
24"
600
serviceclearancestotheboiler  gure6
For closet installation: clearance is 1” / 25mm from the front.
LowLossHeader
Clearancestocombustibleandnon-combustibleis0inchforsides,top,frontandoor/ground
The recommended service clearance to the bottom of the low loss header is 12 inches.
2"
50
Installation & Servicing Instructions Rinnai Q-Series
17
5.4 Technicalspecications
Technicalspecications Table4
Combi
Q175CN Q85SN Q130SN Q175SN Q205SN
Boiler type Q175CP Q85SP Q130SP Q175SP Q205SP
Input CH BTU/hr 175,000 85,000 130,000 175,000 205,000
kW 51 25 38 51 60
Input DHW BTU/hr 175,000 N/A N/A N/A N/A
kW 51 N/A N/A N/A N/A
Heating capacity BTU/hr 162,000 78,000 119,000 162,000 186,000
kW 47.5 22.9 34.9 47.5 54.5
O
2
(at full load)
%
Electr. power consumption max. W 210 137 144 210 234
Electr. power consumption stand by W
Current V/Hz
Fuse rating A
Degree of protection acc. EN 60529
Weight (empty) lbs / kg 196 / 89 110 / 50 117 / 53 141 / 64 141 / 64
Water content CH gallon / liter 1.8 / 7 0.9 / 3.5 1.3 / 5 1.8 / 7 1.8 / 7
Water content DHW gallon / liter 3.7 / 14
Water content Plumbing Kit gallon / liter 0.74 / 2.8
After run time pump CH min
After run time pump DHW min
P
MS
Water pressure min.-max.
PSI / bar
120Vac/60Hz
5AF & 4AT
0.58 / 2.2 0.74 / 2.8
Q-Series
Natural gas: 4.4 - 4.7 (Propane: 4.8 - 5.1)
IPX0D
5
1
14-43 / 1-3
14
MS
p
P
MW
Water pressure DHW max.
PSI / bar 150 / 10
n.a. n.a. n.a. n.a.
Flow temperature max. °F / °C
Pump type UPER 20-78 UPER 20-58 UPER 20-78 UPER 20-78 UPER 20-78
A
vailable
p
um
p
hei
g
ht CH
(
T = 25K
)
PSI / kPa 2.9 / 20 5.2 / 36 3.0 / 21 2.9 / 20 5.5 / 38
Approvals ASME, CSA ASME, CSA ASME, CSA ASME, CSA ASME, CSA
DHW flow
(
at T50°F
)
gallon/min 6.2
DHW flow
(
at T27.8°C
)
liter/min 23.5
DHW flow
(
at T75°F
)
gallon/min 4.1
DHW flow
(
at T41.7°C
)
liter/min 15.5
Max. DHW flow rate gallon/min 6.2
liter/min 23.5
Pressure difference DHW PSI / bar 4.3 / 0.3
CSA number
CRN number
8101.7CL
2183087
176 / 80
Installation & Servicing Instructions Rinnai Q-Series
18
6 Connectingtheboiler
The boiler has the following connection pipes;
- The central heating circuit pipes.
These must be connected to the Plumbing Kit by means of adapter ttings.
See further chapter 6.1;
- The gas supply pipe.
It is provided with a 3/4" male thread into which the tail piece of the gas valve can
be screwed. See further chapter 6.4;
- The condensation drain pipe.
It consists of an oval 1" (24 mm) plastic pipe. The drain pipe can be connected to
this by means of an open connection. If the open connection is tted in a dierent
location, then the pipe can be lengthened by means of a 1 1/4" (32 mm) PVC
sleeve. See further chapter 6.6;
- The vent system and air supply system.
It consists of a concentric connection 3"/5" (80/125 mm). The boiler can be converted
to a twin pipe connection that will accept 80mm ue and intake air or with the use
of the included adapters 3” PVC / CPVC ue and intake. See further chapter 6.7.
- Cold and hot water pipes for domestic hot water (DHW).
Combi boilers only: These consist of 3/4" (15 mm) copper pipe and can be
connected to the installation by means of 3/4" M-NPT adapter ttings. See further
chapter 6.5;
Thepipestobeconnectedtotheboilermustbecleanedbeforeconnectingin
ordertopreventdirtfromenteringanddamagingtheboiler.
6.1 Centralheatingsystem
Connect the central heating system according to its instructions.
Theboilerpipescanbeconnectedtotheinstallationbymeansofcompressionttings.
Reducers should be used for connecting to thick-walled pipe (welded or threaded).
Whenremovingtheplasticsealingcapsfromthepipes,dirtytestingwatermay
drainfromtheboiler.
APlumbingKitmustbettedtotheboiler.
The boiler, when used in connection with a refrigeration system, must be
installedsothechilledmediumispipedinparallelwiththeboilerwithappropriate
valvestopreventthechilledmediumfromenteringtheboiler.
Theboilerpipingsystemofahotwaterboilerconnectedtoheatingcoilslocated
inairhandlingunitswheretheymaybeexposedtorefrigeratedaircirculation
mustbeequippedwithowcontrolvalvesorotherautomaticmeanstoprevent
gravitycirculationoftheboilerwaterduringthecoolingcycle.
NOTICE
i
NOTICE
i
NOTICE
i
NOTICE
i
NOTICE
i
Installation & Servicing Instructions Rinnai Q-Series
19
Boiler basic piping gure 7
T
P
Low Loss Header
V1
Service valve
V2
Service valve
1
2
3
4
56
7
8 9
1. shutovalve
2. system circulator
3. check valve
4. balancing valve
5. boiler drain valve
6. dirt trap
7. air separator
8. automaticllvalve
9. backowpreventer
10. expansion tank
11. bypass for system cleaning
10
11
Installation & Servicing Instructions Rinnai Q-Series
20
6.1.1 PlumbingKitinstallation
RinnaisuppliesspecicPlumbingKitswitheachboilertype,whichmustbetted
directly underneath the boiler on the supply and return pipe. Find in chapter 5.3 the
dimensions. Use of the Rinnai boiler without the plumbing kit will void the warranty.
Toprotecttheentireheatingsystemwerecommendinstallingadirtparticletrap
inthereturncircuit.Whentheboilerisinstalledtoanexistingheatingsystem
thistrapisrequired.UseofaYstrainerisnotpermittedasasubstitutefora
dirttrap.
- Installshut-ovalvesimmediatelybeforeandafterthedirtparticleltertoallow
the trap to be cleaned.
- Position3(gure8)isagardenhosethreadboilerdrainthatcanbeusedtodrain
the boiler or add water treatment additives to the system such as inhibitors or
glycol.
- Position4(gure8)isthesupplyconnectionforanindirecttankwhenusedwith
the optional 3-way valve kit.
- Forinformationonlocatingtheexpansiontankandsystemll,pleaseseethe
Rinnai Boiler Applications Manual.
NOTICE
i
Plumbing Kit installation gure 8
Compression fittings.
Parts:
1. Nut
2. Ferrule
3. Fitting
Fitting instructions:
Clean pipe ends thor-
oughly. The outside
surface has to be
smooth before fitting.
1. Push the complete
fitting over the pipe as
far as possible. Ferrule
should be over the
pipe completely.
2. Turn the nut handtight
clockwise.
3. Use 2 wrenches, one
to hold the fitting in
place, the other for
tighten the nut clock-
wise in 3/4 turn.
21
3
!
WARNING
NOTICE
i
Donotovertightenthesettingswhen
connectingowandreturnpipetothe
plumbing kit. Max. 150Nm / 100 foot-
pounds (ft lb) / 1327 inch-pounds (in
lb).Failuretofollowtheseinstructions
mayresultinleakagecausingproperty
damage and would not be covered
underwarranty.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190

Rinnai Q175CN Mode d'emploi

Catégorie
Chauffe-eau
Taper
Mode d'emploi
Ce manuel convient également à

dans d''autres langues