Tripp Lite SmartPro 3U Rackmount UPS Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
Owner’s Manual
SmartPro
®
3U Rackmount UPS
Model: SMX5000XLRT3U
(Series Number: AGSM5247)
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2016 Tripp Lite. All rights reserved.
SmartPro
®
is a registered trademark of Tripp Lite.
Important Safety ...............2
Instructions
Mounting ..........................3
Quick Installation ..............5
Optional Installation ..........7
Basic Operation ................9
Storage and Service .......13
Battery Replacement ......14
Español...........................16
Français ..........................31


15-12-015- 932460.indb 1 1/19/2016 4:10:01 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the
installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these
warnings may affect your warranty.
UPS Location Warnings
Use caution when lifting your UPS. Because of the considerable weight of all rackmount UPS
systems, at least two people should assist in lifting and installing them.
Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight.
For best performance, the ambient temperature near your UPS should be between 0° C and
40° C (between 32° F and 104° F).
Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its
vents or fan openings.
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this
manner will seriously inhibit the unit’s internal cooling, eventually causing product damage not
covered under warranty.
UPS Connection Warnings
The UPS contains its own energy source (battery). The output terminals may be live even when
the UPS is not connected to an AC supply.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Do not connect surge suppressors or extension cords to the output of your UPS. This might
overload the UPS and will void the surge suppressor and UPS warranties.
Battery Warnings
Batteries can present a risk of electrical shock and burn from high short-circuit current.
Observe proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or
batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the
UPS before performing battery replacement. Use tools with insulated handles. There are no
user-serviceable parts inside the UPS. Battery replacement should be performed only by
authorized service personnel using the same number and type of batteries (Sealed Lead-Acid).
The batteries are recyclable. Refer to your local codes for disposal requirements or visit
http://www.tripplite.com/support/recycling-program for recycling information. Tripp Lite offers a
complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the
Web at http://www.tripplite.com/products/battery-finder/ to locate the specific replacement
battery for your UPS.
During hot-swap battery replacement, the UPS will not provide backup power in the event of a
blackout or other power interruptions.
Do not operate UPS without batteries.
When adding external battery packs connect only Tripp Lite-recommended battery packs of the
correct voltage and type. Do not connect or disconnect battery packs when the UPS is
operating on battery power.
15-12-015- 932460.indb 2 1/19/2016 4:10:01 PM
3
Mounting
Your UPS may be rackmounted in 4- or 2-post racks. To mount the UPS (power module +
external battery module) in a 2-post rack, purchase the appropriate hardware, sold separately
(order Tripp Lite model # 2POSTRMKITHD). See 2POSTRMKITHD owner’s manual for installation
instructions. To mount the UPS in a 4-post rack, use the included hardware and follow the
procedure outlined below. The procedures are for common rack types and may not be appropriate
for all rack configurations. User must determine the fitness of rackmount hardware and
procedures before mounting.
CAUTION: Rackmount equipment may be extremely heavy—be careful when moving or
lifting equipment. Use one or more assistants if necessary.
4-Post Rack Mounting
Square-Hole Rack Installation
1
The included plastic pegs
A
will
temporarily support the empty
rackmount shelves
B
while you install
the permanent mounting hardware.
Insert a peg near the center of the
front and rear bracket of each shelf as
shown. (Each front bracket has 6 holes
and each rear bracket has 3 holes.)
The pegs will snap into place.
1
2
3
After installing the pegs, expand each shelf to match the depth of your rack rails. The pegs
will fit through the square holes in the rack rails to support the shelves. Refer to the rack unit
labels to confirm that the shelves are level in all directions.
Note: The support ledge of each shelf must face inward.
A
C
C
A
B
B
2
Secure the shelves
B
to the mounting
rails permanently using the included
screws and cup washers
C
as shown.
Place 6 screws total at the front and 4
screws total at the back.
Tighten all screws before proceeding.
Warning: Do not attempt to install
your equipment until you have
inserted and tightened the required
screws. The plastic pegs will not
support the weight of your
equipment.
3
Attach your equipment’s mounting
brackets to the forward mounting holes
of the cabinet using the hardware
included with your equipment. The
mounting bracket “ears” should face
forward. (Some equipment may have
pre-installed or integral mounting
brackets.)
15-12-015- 932460.indb 3 1/19/2016 4:10:03 PM
4
4
With the aid of an assistant (if
necessary), lift your equipment and
slide it into the shelves. Attach the
equipment mounting brackets to the
forward mounting rails with user-
supplied screws and washers
D
.
Tighten all screws securely.
Mounting
Threaded-Hole Rack Installation
4
D
1
Align the mounting rail
A
along the
inside surface of the rack posts
B
so
that the flanges on the ends of the rail
wrap around to the front and rear
surfaces of the posts and the rail holes
meet the threaded holes on the rack
post.
2
Secure the shelves
A
to the mounting
rails permanently using user-supplied
screws and washers
C
for your rack as
shown. Place 6 screws total at the
front and 4 screws total at the back.
Tighten all screws before proceeding.
Warning: Do not attempt to install
your equipment until you have
inserted and tightened the required
screws.
1
B
A
A
B
3
Follow steps
3
and
4
of the Square-Hole Rack Installation instructions (above) to securely
mount your 3U equipment.
Tower Mounting
If you tower mount this UPS, it requires the addition of a
Tripp Lite 2U to 9U tower stand (model: 2-9USTAND, sold
separately). See owner’s manual for installation
procedure.
Rotate the power module’s Control Panel to view it easier
while the UPS is tower mounted. Insert a small
screwdriver, or other tool, in the slots on either side of the
Control Panel. Pop the panel out; rotate it; and pop the
panel back into place.
A
C
C
2
15-12-015- 932460.indb 4 1/19/2016 4:10:07 PM
5
Quick Installation
DANGER!
HIGH VOLTAGE! RISK OF SERIOUS INJURY OR
DEATH! FOR QUALIFIED ELECTRICIANS ONLY!
ELECTRICIANS MUST READ WARNINGS BELOW
AND IN SAFETY SECTION PRIOR TO
INSTALLATION.
connection base step 1
1
Hardwire the UPS System’s
input terminals to a utility
power source.
1
A
B
Input and Output Ratings
Model Voltage Input Current Output Current Wire Size
SMX5000XLRT3U 230V 27A 30A 10 AWG
Before hardwiring, switch OFF the facility’s circuit breaker which is supplying power to the circuit
the UPS System will be connected to. Using a screwdriver, remove the top of the box
A
covering
the UPS System’s input terminals. Pass user-supplied cable through the opening in the box
B
and attach it to the terminals. After hardwiring is complete, switch ON the facility’s circuit breaker
which is supplying power to the circuit the UPS System is connected to. Please note that after the
UPS System is connected to a live utility power source, the UPS (in “Standby” mode) will
automatically charge its batteries,* but will not supply power to its outlets until it is turned ON
(see Step 3 below).
* The BATTERY CHARGE LED will be the only LED illuminated.
Note: UPS system will function properly upon initial startup; however, maximum runtime for the unit’s battery
will only be accessible after it has been charged for 24 hours.
HARDWIRE WARNINGS!
Wiring must be done by a qualified electrician.
When making wiring connections, observe the cable connection regulations appropriate to
your area at all times. Be sure to install an easily accessible disconnect switch in your
installation wiring so you may cut off the UPS’s AC input during fires and other
emergencies. Ensure that cables are fitted with cable sleeves and are secured by
connector clamps. Tighten connections with a torque of not less than 10 inch-pounds
(1.1 NM).
Make sure that your equipment is properly grounded.
Using cables of improper size may damage your equipment and cause fire hazards.
Choose appropriate cabling and protection circuits to make wiring connections (Ground
conductors must be the same size and type as the power conductors used).
15-12-015- 932460.indb 5 1/19/2016 4:10:07 PM
6
Quick Installation
2
Plug your equipment into the
UPS.*
Plug your equipment into the UPS using the
additional power cord(s) that came with the UPS.
Note: Additional interconnection cords (C13 to C14) are
available from Tripp Lite. Visit tripplite.com
(Part # P004-006).
* Your UPS is designed to support only electronic equipment.
You will overload the UPS if the total VA ratings for all the
equipment you connect exceeds the UPS’s Output Capacity.
To find your equipment’s VA ratings, look on their
nameplates. If the equipment is listed in amps, multiply the
number of amps by 230 to determine VA. (Example:
1 amp × 230 = 230 VA). If you are unsure if you have
overloaded the UPS’s outlets, see “OUTPUT LOAD LEVEL
LED description.
3
Turn the UPS ON.
Press and hold the “ON/OFF/STANDBY” button for one
second. The alarm will beep once briefly after one
second has passed. Release the button.
2
3
15-12-015- 932460.indb 6 1/19/2016 4:10:08 PM
7
Optional Installation
These connections are optional. Your UPS will function properly without these
connections.
1a
1b
1
USB and RS-232 Serial Communications
2
Relay Contact-Closure Connection
Use the included DB9 cable (see
2a
) to connect
specialized electronic equipment to the relay contact-
closure port on your UPS System. See diagram
2b
and
chart below to determine signals carried by this port.
Relay Contact Closure Chart
Line Fail
Indication
Mid Battery
Indication
Low Battery
Indication
UPS Operating
Conditions
Pins
1 & 6
Pins
2 & 6
Pins
7 & 3
Pins
8 & 3
Pins
4 & 9
Pins
5 & 9
AC Input Voltage OK CLOSED OPEN
AC Input Out of Range OPEN CLOSED
Battery More than 3
Min. Remaining Charge*
OPEN CLOSED
Battery Less than 3 Min.
Remaining Charge*
CLOSED OPEN
Battery More than 2
Min. Remaining Charge*
OPEN CLOSED
Battery Less than 2 Min.
Remaining Charge*
CLOSED OPEN
Contact Action Open on
Line
Failure
Close on
Line
Failure
Battery
Close
Below
Mid
Battery
Open
Below
Mid
Battery
Close
Below
Low
Battery
Open
Below
Mid
Battery
* Times are approximate, at full load.
LINE FAIL
K1 A
LO BATT
K1 0A
1
2
3
4
5
6
7
8
9
OPENS ON LI NE FA IL
CLOSES ON LINE FA IL
CLOSES BE LOW LOW BATTER Y
TOP OF DUAL
DB9 (J5/J34)
NO TE :
CLOSES BELOW MID BATTERY
J5
REMOTE CONTAC TS
COM
MID BAT
K4 A
COM
COM
OPENS
BELOW MID BATT ERY
RELA YS SHOW N DE-ENE RGIZ ED
OPENS BELOW LOW BATTERY
2a
2b
Use the included USB cable (see
1a
) and/or DB9
serial cable (see
1b
) to connect the communication
port on your computer to the communication port of
your UPS. Install on your computer the Tripp Lite
PowerAlert
®
software appropriate to your computer’s
operating system. Consult your PowerAlert manual for
more information.
15-12-015- 932460.indb 7 1/19/2016 4:10:10 PM
8
Optional Installation
3
EPO Port Connection
This optional feature is only for those applications
which require connection to a facility’s Emergency
Power Off (EPO) circuit. When the UPS is connected
to this circuit, it enables emergency shutdown of the
UPS’s inverter.
Using the cable provided, connect the EPO port of
your UPS (see
3a
) to a user-supplied normally closed
or normally open switch according to the circuit
diagram (see
3b
). The EPO port is not a phone line
surge suppressor; do not connect a phone line to this
port.
4-5
connection base step 1
3a
3b
4a
4b
4
External Battery Connection
All UPS models come with a robust internal battery
system; select models feature connectors (see
4a
)
that accept optional external battery packs (sold
separately from Tripp Lite) to provide additional
runtime. Adding external batteries will increase
recharge time as well as runtime. See battery pack
owner’s manual for complete installation instructions.
Make sure cables are fully inserted into their
connectors. Small sparks may result during battery
connection; this is normal. Do not connect or
disconnect battery packs when the UPS is running on
battery power.
If you connect any external batteries, set the Battery
Charge Level Switch (see
4b
) to the down position.
This will increase your UPS’s charger output so the
additional batteries charge faster.
Note: the switch to the right of the Battery Charge Level
Switch is inactive and will not affect UPS operation regardless
of its position.
CAUTION! DO NOT set the Battery Charge Level
Switch to the down position without an external
battery connected. There is a risk of damaging
the UPS’s internal battery system.
15-12-015- 932460.indb 8 1/19/2016 4:10:11 PM
9
Basic Operation
Buttons (Front Panel)
“ON/OFF/STANDBY” Button
When the UPS system is connected to a live AC utility power source, the UPS
System will operate in one of three modes: ON, OFF or STANDBY. Refer to the chart
below for UPS System operating characteristics within each mode.
Mode
UPS Charges Battery
(when utility is present)
UPS Supplies Power to
Outlets (when utility is
present or absent*) UPS Displays LEDs
ON Yes Yes Yes (variety of LEDs,
depending on conditions)
OFF No No No
STANDBY Yes No Yes (“BATTERY CHARGE”
LED only)
To place the UPS in the ON mode: First, have a qualified electrician connect the
UPS System to a utility power source as outlined in the Quick Installation section.
Once the utility power source is live, the UPS System will automatically enter
STANDBY mode. Press and hold the “ON/OFF/STANDBY” button for one second**
and then release it to switch the UPS System from STANDBY mode to ON mode.
OPTIONAL: If the utility power source is not live, you can “cold-start” the UPS
System (i.e.: switch it directly from the OFF mode to the ON mode by supplying
power for a limited time from its batteries*) by pressing and holding the “ON/
OFF/STANDBY” button for one second** and then releasing it.
To place the UPS in the OFF mode: With the UPS System in the ON mode and
receiving utility power, press and hold the “ON/OFF/STANDBY” button for one
second** and then release it to switch the UPS System from ON mode to
STANDBY mode. Switch OFF the facility’s circuit breaker which is supplying power
to the circuit the UPS System is connected to.
* If batteries are fully charged. ** The alarm will beep once briefly after the interval has passed.
“MUTE/TEST” Button
To Silence (or “Mute”) UPS Alarms: briefly press and release the MUTE/TEST
button.*
To Run a Self-Test: with your UPS connected to a live utility power source and
turned ON, press and hold the MUTE/TEST button for two seconds.* Continue
holding the button until the alarm beeps several times and the UPS performs a self
test. See “Results of a Self-Test” below.
Note: you can leave connected equipment on during a self-test. Your UPS, however, will not
perform a self-test if the UPS is not turned on (see “ON/OFF/STANDBY” Button description).
Results of a Self-Test: the test will last approximately 10 seconds as the UPS
switches to battery to test its load capacity and battery charge.
If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm continues to
sound after the test, the UPS’s outlets are overloaded. To clear the overload,
unplug some of your equipment and run the self-test repeatedly until the
“OUTPUT LOAD LEVEL” LED is no longer lit red and the alarm is no longer
sounding.
CAUTION! Any overload that is not corrected by the user immediately
following a self-test may cause the UPS to shut down and cease supplying
output power in the event of a blackout or brownout.
15-12-015- 932460.indb 9 1/19/2016 4:10:11 PM
10
Basic Operation
If the “BATTERY WARNING” LED remains lit and the alarm continues to sound
after the test, the UPS batteries need to be recharged or replaced. Allow the UPS
to recharge continuously for 12 hours, and repeat the self-test. If the LED
remains lit, contact Tripp Lite for service. If your UPS requires battery
replacement, visit http://www.tripplite.com/products/battery-finder/ to locate the
specific Tripp Lite replacement battery for your UPS.
* The alarm will beep once briefly after the indicated interval has passed.
Indicator Lights (Front Panel)
All Indicator Light descriptions apply when the UPS is connected to a live utility power source and
turned ON.
“POWER” LED: this green LED lights continuously when the UPS is ON and
supplying connected equipment with AC power from a utility source. The LED
flashes and an alarm sounds (4 short beeps followed by a pause) to indicate the
UPS is operating from its internal batteries during a blackout or severe brownout. If
the blackout or severe brownout is prolonged, you should save files and shut down
your equipment since internal battery power will eventually be depleted. See
“BATTERY CHARGE” LED description below.
VOLTAGE CORRECTION” LED: this green LED lights continuously whenever the
UPS is automatically correcting high or low AC voltage on the utility line without the
assistance of battery power. The UPS will also emit a slight clicking noise. These
are normal, automatic operations of the UPS, no action is required on your part.
“OUTPUT LOAD LEVEL” LED: this multicolored LED indicates the approximate
electrical load of equipment connected to the UPS’s AC outlets. It will turn from
green (light load) to yellow (medium load) to red (overload). If the LED is red (either
illuminated continuously or flashing), clear the overload immediately by unplugging
some of your equipment from the outlets until the LED changes from red to yellow
(or green).
CAUTION! Any overload that is not corrected by the user immediately may
cause the UPS to shut down and cease supplying output power in the event
of a blackout or brownout.
“BATTERY CHARGE” LED: when the UPS is operating from utility power, this LED
indicates the approximate charge state of the UPS’s internal batteries: red indicates
the batteries are beginning to charge; yellow indicates the batteries are roughly
midway through charging; and green indicates the batteries are fully charged. When
the UPS is operating from battery power during a blackout or severe brownout, this
LED indicates the approximate amount of energy (ultimately affecting runtime)
which the UPS’s batteries will provide: red indicates a low level of energy; yellow
indicates a medium level of energy; and green indicates a high level of energy.
Since the runtime performance of all UPS batteries will gradually deplete over time,
it is recommended that you periodically perform a self-test (see MUTE/TEST Button
description) to determine the energy level of your UPS batteries BEFORE a blackout
or severe brownout occurs. During a prolonged blackout or severe brownout, you
should save files and shut down your equipment since battery power will eventually
be depleted. When the LED turns red and an alarm sounds continuously, it
indicates the UPS’s batteries are nearly out of power and UPS shut down is
imminent.
15-12-015- 932460.indb 10 1/19/2016 4:10:12 PM
11
Basic Operation
“BATTERY WARNING” LED: this LED lights red and an alarm sounds intermittently
after you complete a self test (See “MUTE/TEST” Button description) to indicate the
UPS batteries need to be recharged or replaced. Allow the UPS to recharge
continuously for 12 hours, and repeat the self-test. If the LED continues to light,
contact Tripp Lite for service. If your UPS requires battery replacement, visit
http://www.tripplite.com/products/battery-finder/ to locate the specific Tripp Lite
replacement battery for your UPS.
C13/230V
C19/230V
Charge Rate
Setting (when
External
Batteries are
not connected)
Charge Rate
Setting (when
External
Batteries are
connected)
Other UPS Features (Rear Panel)
AC Receptacles: Your UPS features C13 outlets, and select models also feature
C19 outlets. These output receptacles provide your connected equipment with AC
line power during normal operation and battery power during blackouts and
brownouts. The UPS protects equipment connected to these receptacles against
damaging surges and line noise. If you have a serial or USB connection to your
UPS, you can remotely reboot connected equipment by turning the receptacles
OFF and ON using Tripp Lite’s PowerAlert software.
Input Terminal block: Use these terminals to connect the UPS System to
utility power. Unscrew and remove the cover over the block for access.
Communications Ports (USB or RS-232): These ports connect your UPS to any
workstation or server. Use with Tripp Lite’s PowerAlert software and included cables
to enable your computer to automatically save open files and shut down equipment
during a blackout. Also use PowerAlert software to monitor a wide variety of AC line
power and UPS operating conditions. Consult your PowerAlert software manual or
contact Tripp Lite Customer Support for more information. See “USB and RS-232
Serial Communications” in the “Optional Installation” section for installation
instructions.
Relay Contact Interface Port: This female DB9 port sends contact-closure
signals to indicate line-fail and low battery status. See “Optional Installation”
section for installation instructions.
EPO (Emergency Power Off) Port: Your UPS features a EPO port that may be
used to connect the UPS to a contact closure switch to enable emergency inverter
shutdown. See “EPO Port Connection” in the “Optional Installation” section for
more information.
Battery Charge Level Switch: Controls the UPS system’s battery charge rate. If
you connect any external batteries, set the Battery Charge Level Switch to the
down position. This will increase your UPS’s charger output so the additional
batteries charge faster. Note: the switch to the right of the Battery Charge Level
Switch is inactive and will not affect UPS operation regardless of its position.
CAUTION! DO NOT set the Battery Charge Level Switch to the down position
without an external battery connected. There is a risk of damaging the
UPS’s internal battery system.
15-12-015- 932460.indb 11 1/19/2016 4:10:13 PM
12
Basic Operation
Accessory Slot: Remove the small cover panel from this slot to install optional
accessories to remotely monitor and control your UPS. Refer to your accessory’s
manual for installation instructions. Visit tripplite.com for more information,
including a list of available SNMP, network management and connectivity products.
Power Sensitivity Adjustment: This dial is normally set fully counter-clockwise,
which enables the UPS to provide maximum protection against waveform
distortions in its AC input. When such distortion occurs, the UPS will normally
switch to providing sine wave power from its battery reserves for as long as the
distortion is present. In areas with poor utility power or where the UPS’s input
power comes from a backup generator, chronic waveform distortion could cause
the UPS to switch to battery too frequently, draining its battery reserves. You may
be able to reduce how often your UPS switches to battery due to moderate
waveform distortion by experimenting with different settings for this dial. As the dial
is turned clockwise, the UPS becomes more tolerant of variations in its input
power’s AC waveform.
Note: The further the dial is adjusted clockwise, the greater the degree of waveform distortion
the UPS will allow to pass to connected equipment.
When experimenting with different settings for this dial, operate connected
equipment in a safe test mode so that the effect on the equipment of any
waveform distortions in the UPS’s output can be evaluated without disrupting
critical operations.
External Battery Connector: Use to connect Tripp Lite external battery packs for
additional runtime. Refer to instructions available with the battery pack for
complete connection information and safety warnings.
Output Breaker(s): Protect your UPS from output overload. If one or more
breakers trip, remove some of the load on the circuit(s), then reset them by
pressing the breaker switch(es) in.
Ground Screw: Use this to connect any equipment that requires a chassis ground.
15-12-015- 932460.indb 12 1/19/2016 4:10:14 PM
13
Storage and Service
Storage
Before storing your UPS, turn it completely OFF. If you store your UPS for an extended period of
time, recharge the UPS batteries for 4 to 6 hours once every three months. Note: after you
connect the UPS to utility power, it will automatically begin charging its batteries. If you leave
your UPS batteries discharged for an extended period of time, they will suffer a permanent loss of
capacity.
Service
Before returning your UPS for service, follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service
problem does not originate from a misreading of the instructions. Also, check that the UPS
System’s circuit breaker(s) are not tripped. This is the most common cause of service inquiries
which can be easily remedied by following the resetting instructions in this manual.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit
www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the “Request Return
(RMA)” link. From here you can request a Returned Material Authorization (RMA) number,
which is required for service. This simple on-line form will ask for your unit’s model and serial
numbers, along with other general purchaser information. The RMA number, along with
shipping instructions will be emailed to you. Any damages (direct, indirect, special or
consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite
service center are not covered under warranty. Products shipped to Tripp Lite or an authorized
Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on
the outside of the package. If the product is within its warranty period, enclose a copy of your
sales receipt. Return the product for service using an insured carrier to the address given to
you when you request the RMA.
15-12-015- 932460.indb 13 1/19/2016 4:10:14 PM
14
Battery Replacement
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing
regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are
entitled to:
Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on
the country)
Send the new equipment back for recycling when this ultimately becomes waste
Battery replacement should be performed only by authorized service personnel using the same
number and type of batteries (sealed Lead-Acid). Under normal conditions, the original batteries
in your UPS will last many years. See Safety section before replacing batteries. The batteries are
designed for hot-swap replacement (i.e. leaving the UPS in ON mode), but some qualified service
personnel may wish to put the UPS in the OFF mode and disconnect equipment before
proceeding.
Procedure
1
Remove Front Panel and Battery Holding Plate
2
Disconnect Batteries
3
Remove/Dispose of Batteries
4
Add Batteries
5
Connect Batteries
Attach connectors: black-to-black and red-to-red.
6
Replace Front Panel
WARNING!
Batteries can present a risk of electrical shock
and burn from high short-circuit current result-
ing in serious injury or death. Battery terminals
are in close proximity to UPS cabinet and spe-
cial care must be taken to avoid shorting the
batteries including not touching metal
cabinet and battery terminals simultaneously.
2 5
1 6
3 4
UPS and Battery Recycling
Please recycle Tripp Lite Products. The batteries used in Tripp Lite products are sealed Lead-
Acid batteries. These batteries are highly recyclable. Please refer to your local codes for disposal
requirements.
You can call Tripp Lite for recycling info at 1-773-869-1234.
You can go to the Tripp Lite Website for up-to-date information on recycling the batteries or any
Tripp Lite product. Please follow this link: http://www.tripplite.com/support/recycling-program/
15-12-015- 932460.indb 14 1/19/2016 4:10:15 PM
15
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been
assigned a unique series number. The series number can be found on the product nameplate label, along
with all required approval markings and information. When requesting compliance information for this product,
always refer to the series number. The series number should not be confused with the marketing name or model
number of the product.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V : DC Voltage
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
15-12-015- 932460.indb 15 1/19/2016 4:10:15 PM
16
Manual del propietario
UPS SmartPro
®
para Instalación de
3U en Rack
Modelo: SMX5000XLRT3U
(Número de Serie: AGSM5247)
No conveniente para los usos móviles.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright ©2016 Tripp Lite. Todos los derechos reservados.
SmartPro
®
es una marca comercial registrada de Tripp Lite.
Instrucciones de .............17
seguridad importantes
Montaje ..........................18
Instalación rápida ...........20
Instalación opcional ........22
Operación básica ............24
Almacenamiento ............28
y servicio
Reemplazo de batería .....29
English ..............................1
Français ..........................31


15-12-015- 932460.indb 16 1/19/2016 4:10:16 PM
17
Instrucciones de seguridad importantes
GUARDE ESTAS INSTRUCCIONES
Este manual contiene importantes instrucciones que deben seguirse durante la
instalación, operación y el almacenamiento de todos los UPS de Tripp Lite. La falta de
observar estas advertencias podría afectar su garantía.
Advertencias sobre la ubicación del UPS
Tenga cuidado al levantar el UPS. Debido al gran peso de los UPS para montaje en bastidor, se
requieren por lo menos dos personas para que le ayuden a levantarlos e instalarlos.
Instale su UPS bajo techo, lejos de la humedad, el calor, el polvo o la luz solar directa.
Para un mejor funcionamiento, la temperatura ambiente cerca de su UPS debe estar entre 0°
C y 40° C (32° F - 104° F)
Deje una cantidad adecuada de espacio alrededor de todos los lados del UPS para sua
adecuada ventilación. No obstruya sus respiraderos ni las aberturas de ventilación.
No monte esta unidad con el panel frontal o con el panel trasero hacia abajo (Bajo ningún
ángulo o inclinación). Si lo monta de esta manera, inhibirá seriamente el sistema de
enfriamiento interno de la unidad; lo que finalmente causará daños al producto que no están
cubiertos por la garantía.
Advertencias sobre la conexión del UPS
El UPS contiene su propia fuente de energía (batería). Los terminales de salida pueden estar
con energía incluso cuando el UPS no está conectado a un suministro de corriente alterna.
Advertencias sobre la conexión de equipos
El uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo
pueda razonablemente hacer suponer que causará fallas en el equipo de soporte de vida o
afecte significativamente su seguridad o efectividad, no está recomendado. No use este equipo
en la presencia de una mezcla anestésica inflamable con aire, oxigeno u óxido nitroso.
No conecte supresores de sobretensiones ni cordones de extensión a la salida de su UPS. Esto
puede sobrecargarlo y anular su garantía y la del supresor de sobretensiones.
Advertencias sobre la batería
Debido a que las baterías presentan un peligro de choque eléctrico y quemaduras por
las altas corrientes de cortocircuito, tome las precauciones adecuadas. No deseche las
baterías en un incinerador. No abra las baterías. No ponga los terminales de la batería en
corto o en puente con ningún objeto. Apague y desconecte el UPS antes de reemplazar la
batería. Sólo debe cambiar las baterías personal técnico debidamente capacitado. Use
herramientas con mangos aislados y reemplace las baterías existentes con el mismo número y
tipo de baterías nuevas (plomo-ácido selladas). Las baterías del UPS son reciclables. Consulte
la reglamentación local para los requisitos de disposición de desechos o visita
http://www.tripplite.com/support/recycling-program para reciclar información. Tripp Lite ofrece
una línea completa de Cartuchos de reemplazo de batería para UPS (R.B.C.). Visite Tripp Lite
en la web en http://www.tripplite.com/products/battery-finder/ para localizar la batería de
reemplazo específica para su UPS.
Durante el reemplazo de baterías en operación (hot-swap), el UPS no proporcionará energía de
respaldo en el caso de una falla del servicio eléctrico u otras interrupciones de energía.
No opere el UPS sin baterías.
Al agregar bancos de baterías externas, sólo emplee bancos recomendados por Tripp Lite del
voltaje y tipo correctos. No conecte ni desconecte bancos de baterías cuando el UPS esté
funcionando con energía de las baterías.
15-12-015- 932460.indb 17 1/19/2016 4:10:16 PM
18
Montaje
Su UPS puede instalarse en rack de 4 o 2 postes. Para instalar el UPS (módulo de potencia +
módulo de baterías externas) en un rack de 2 postes, compre los accesorios apropiados, se
venden por separado (ordene # modelo 2POSTRMKITHD de Tripp Lite). Para instrucciones de
instalación, vea el manual del propietario del 2POSTRMKITHD. Para instalar el UPS en un rack de
4 postes, use los accesorios incluidos y siga el procedimiento detallado a continuación. Los
procedimientos son para tipos comunes de racks y pueden no ser apropiados para todas las
configuraciones de rack. Antes de la instalación, el usuario debe determinar la adecuación de los
accesorios y procedimientos.
PRECAUCIÓN: El equipo para instalación en rack puede ser extremadamente pesado—
tenga cuidado al mover o levantar el equipo. De ser necesario, use uno o más ayudantes.
Instalación en Rack de 4 Postes
Instalación en Rack con Orificios Cuadrados
1
Las espigas de plástico
A
incluidas
soportarán temporalmente los
entrepaños
B
para instalación en rack,
vacíos, mientras usted instala los
accesorios de instalación permanentes.
Inserte una espiga cerca del centro del
soporte frontal y posterior de cada
entrepaño, como se muestra. (Cada
soporte frontal tiene 6 orificios y cada
soporte trasero tiene 3 orificios). Las
espigas abrocharán es su lugar.
1
2
3
Después de instalar las espigas, expanda cada entrepaño para hacer coincidir la profundidad
de los rieles de su rack. Las espigas ajustarán a través de los orificios cuadrados en los rieles
del rack para soportar los entrepaños. Consulte las etiquetas en la unidad de rack para
confirmar que los entrepaños estén nivelados en todas direcciones.
Nota: El borde de apoyo de cada entrepaño debe apuntar hacia adentro.
A
C
C
A
B
B
2
Asegure permanentemente los
entrepaños
B
a los rieles de
instalación usando los tornillos y las
arandelas de copa
C
como se
muestra. Coloque 6 tornillos en total
en el frente y 4 tornillos en total en la
parte posterior.
Apriete todos los tornillos antes de
continuar.
Advertencia: No intente instalar su equipo hasta que haya insertado y apretado los
tornillos requeridos. Las espigas de plástico no soportarán el peso de su equipo.
3
Coloque los soportes de instalación de
su equipo a los orificios de instalación
del frente del gabinete usando los
accesorios incluidos con su equipo.
Las “orejas” del soporte de instalación
deben apuntar al frente. (Algún equipo
puede tener preinstalados o integrados
los soportes de instalación).
15-12-015- 932460.indb 18 1/19/2016 4:10:17 PM
19
4
Con la ayuda de un asistente (si fuera
necesario), levante su equipo y
deslícelo en los entrepaños. Coloque
los soportes de instalación del equipo
en los rieles de instalación delanteros
con los tornillos y arandelas
suministrados por el usuario
D
. Apriete
con firmeza todos los tornillos.
Montaje
Instalación en Rack con Orificios Roscados
4
D
1
Alinee el riel de instalación
A
a lo
largo de la superficie interior de los
postes del rack
B
de modo que las
bridas en los extremos del riel
envuelvan las superficies frontal y
posterior de los postes y los orificios
del riel coincidan con los orificios
roscados en el poste del rack.
2
Asegure permanentemente los
entrepaños
A
los rieles de instalación
usando tornillos y arandelas,
suministradas por el usuario,
C
para
su rack como se muestra. Coloque 6
tornillos en total en el frente y 4
tornillos en total en la parte posterior.
Apriete todos los tornillos antes de
continuar.
1
B
A
A
B
Advertencia: No intente instalar su equipo hasta que haya insertado y apretado los
tornillos y tuercas requeridos.
3
Siga los pasos
3
y
4
de las instrucciones de Instalación en Rack con Orificios Cuadrados
(arriba) para instalar firmemente su equipo de 3U.
Montaje de torre
Si monta en torre este UPS, debe agregar un pedestal de
torre Tripp Lite de 2U a 9U (modelo: 2-9USTAND, vendido
por separado). Consulte el procedimiento de instalación
en el manual del propietario.
Gire el panel de control del módulo de potencia para
obtener mejor visibilidad mientras el UPS esté montado
en torre. Introduzca un pequeño destornillador u otra
herramienta en las ranuras en cualquier lado del panel de
control. Saque el panel, gírelo y colóquelo en posición
nuevamente.
A
C
C
2
15-12-015- 932460.indb 19 1/19/2016 4:10:20 PM
20
Instalación rápida
¡PELIGRO!
¡ALTO VOLTAJE! ¡RIESGO DE LESIONES GRAVES
O MUERTE! ¡SÓLO PARA ELECTRICISTAS
EXPERIMENTADOS! LOS ELECTRICISTAS DEBEN
LEER LAS ADVERTENCIAS DE LA SECCIÓN
SEGURIDAD ANTES DE LA INSTALACIÓN.
connection base step 1
1
Conecte los terminales de
entrada del UPS a una fuente
de energía de la red.
1
A
B
Capacidades de entrada y salida
Modelo
Voltaje de
entrada
Capacidad máxima
de corriente de
entrada
Capacidad máxima
de corriente de
salida
Calibre de
alambre usual
SMX5000XLRT3U 230V 27A 30A 10 AWG
Antes de cablear, APAGUE el interruptor automático que suministra energía al circuito al que
estará conectado el UPS. Con un destornillador, retire la parte superior de la caja
A
que cubre
los terminales de entrada del UPS. Pase el cable suministrado por el usuario a través de la
abertura en la caja
B
y conéctelo a los terminales. Después de completar el cableado,
ENCIENDA el interruptor automático que suministra energía al circuito al que está conectado el
UPS. Tenga en cuenta que después de conectar el UPS en una fuente activa de energía de la red
pública, el UPS (en modo de espera) cargará automáticamente sus baterías, pero no suministrará
energía a sus tomacorrientes hasta que se ENCIENDA (ver paso 3 a continuación).
* El LED BATTERY CHARGE (CARGA DE BATERÍA) será el único iluminado.
Nota: El sistema UPS funcionará adecuadamente desde la puesta en marcha inicial, no obstante, la
autonomía máxima de la batería de la unidad solo se alcanzará después de que se haya cargado durante 24
horas.
¡ADVERTENCIAS DE CABLEADO!
El cableado debe ser realizado por un electricista calificado.
Al conectar conductores, observe en todo momento los reglamentos de conexión de
cables adecuados para su área. Asegúrese de instalar un interruptor de desconexión
fácilmente accesible en su cableado de modo que pueda cortar la entrada de corriente
alterna al UPS durante incendios y otras emergencias. Asegúrese que los cables cuenten
con mangas y estén asegurados con abrazaderas de conectores. Apriete las conexiones
con un torque no menor que 10 libras-pulgada (1.1 Nm)
Asegúrese que su equipo esté puesto a tierra adecuadamente.
El uso de cables de calibre inadecuado puede dañar su equipo y causar riesgos de
incendio. Elija cables y circuitos de protección adecuados para realizar las conexiones de
cableado (Los conductores de tierra deben ser del mismo tipo y calibre que los
conductores de energía utilizados).
15-12-015- 932460.indb 20 1/19/2016 4:10:21 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Tripp Lite SmartPro 3U Rackmount UPS Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire