Kozyheat Callaway 50 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire
HUSSONG MANUFACTURING CO., INC.
READ ALL THESE STEPS
BEFORE STARTING INSTALLATION.
LEAVE THESE INSTRUCTIONS WITH THE
APPLIANCE.
This kit must be installed by a qualied installer,
service agency, or gas supplier at the time of
the heater installation. These instructions must
be used in conjunction with the installation and
operation manual provided with the appliance.
Please read the appliance owner’s manual
completely before performing any procedures in
these instructions.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
KOMFORT ZONE KIT
#KZK-054
For use with the Callaway-50 #CLW-50
Direct Vent Gas Fireplace
Starting Serial Number: 19 501780 50
This optional convection duct kit redistributes the
warm air ow away from the replace opening to
a more desirable location using natural convection
without the use of a fan. The warm air ow may be
relocated to a position higher up the wall, out the
sidewalls, or even to an adjacent room. The result
is much cooler wall temperatures above the re-
place opening for locating televisions, artwork, etc.
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d’installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez
www.kozyheat.com
.
Hussong Manufacturing Co., Inc.
P.O. Box 577, 204 Industrial Park Drive
Lakeeld, MN 56150-0577, USA
Rev. 3, 5/20
1.0 INTRODUCTION .......................................................................3
1.1 Kit Contents..........................................................................................3
1.2 Suggested Congurations .............................................................. 4
1.3 Dimensions and Overview .............................................................5
1.4 Air Duct Run ......................................................................................... 6
2.0 FRAMING AND CLEARANCES ................................................7
2.1 Clearance to Sprinkler ...................................................................... 7
2.2 Framing..................................................................................................8
2.3 #KZK-054 Clearances ........................................................................ 9
3.0 FACING AND FINISHING .......................................................10
3.1 Non-combustible Requirements ................................................ 10
3.2 Combustible Finish .......................................................................... 11
3.3 Hearth and Mantel Clearances ....................................................13
4.0 INSTALLATION .......................................................................14
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 3
1.1 Kit Contents
ALL kit contents must be installed.
(1) 54" plenum kit: KZK-054
(1) plenum discharge trim: KZK-054DT
(8) 6" collars - (4) to attach to the bottom of the plenum; (4) to
attach to the unit where the cover plates are removed
(1) KZK-410-6 is used for a 10' vent run. If installing beyond 10' vent
run, you will need to order (1) KZK-CPL6.
KZK-CPL6 is (6) 6" couplers that connect (2) KZK-410-6. You will only
need (4) 6" couplers for installation.
1.0 INTRODUCTION
56⁄
(1425mm
4
⁄
(103mm)
(4) take o collars included
#KZK-054
Figure 1.1, #KZK-054
Figure 1.2, #KZK-410-6
(4) - 10’ x 6” (aluminum ex) listed to UL-181Class 0 Air Duct
#KZK-410-6
4 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
1.2 Suggested Congurations
Figure 1.3, #KZK-054 Suggested Congurations
#KZK-054 front wall outlet #KZK-054 rear wall outlet
#KZK-054 corner installation
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 5
1.3 Dimensions and Overview
12½
(317mm)
16
¾
(425mm)
9
¾
(247mm)
39”
(990mm)
34
½ (876mm) MIN
20’ (6m) MAX
2
½
(63mm)
Ceiling
Minimum
clearance to
ceiling
The tubing that connects the plenum to the replace must be UL181 Class 0 approved air duct.
If you are mounting the plenum above the replace 10’ (3m) or less, use (1) #KZK-410-6 kit.
If you are mounting the plenum above the replace between 10’ (3m) to 20’ (6m)
you will need (2) #KZK-410-6 kits and (1) #KZK-CPL6 coupler kit.
Minimum
½” (12mm)
clearance to
combustibles
around pipe
Figure 1.4, #KZK-054 Dimensions
Figure 1.5, #KZK-054 Overview
54¼
(1378mm)
14”
(355mm)
½
(12mm)
stand-o
1
½
(38mm)
stand-o
½
(12mm)
stand-o
6”
(152mm)
4”
(102mm)
8
⁄ (220mm)
2
⁄
(54mm)
2”
(50mm)
stand-o
12”
(304mm)
3
½
(89mm)
14”
(355mm)
14”
(355mm)
#KZK-054
6 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
1.4 Air Duct Run
IMPORTANT: The air duct pipe cannot run horizontally without a
vertical rise.
IMPORTANT: The 1/2" clearance around the air duct pipes must be
maintained.
Use #KZK-410-6 UL181 Class 0 Air Duct piping to connect the plenum(s)
to the unit.
Hussong Mfg. Co., Inc. requires pipes to be listed as UL181 Class 0 Air
Duct to connect the plenum(s) to the unit.
Figure 1.6, Minimum Vent Pipe Run
WHEN INSTALLING AIR DUCT PIPE MAINTAIN A MINIMUM 4" VERTICAL RISE FOR EVERY 12" HORIZONTAL RUN
12”
(304mm)
4” (102mm)
Minimum bend radius=5” (127mm)
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FRAMING AND CLEARANCES 7
2.0 FRAMING AND CLEARANCES
Figure 2.1, KZK Clearance to Sprinkler
2.1 Clearance to Sprinkler
In a situation where a sprinkler head is installed within the
proximity to a #KZK discharge opening, the diagram below
MUST be followed.
The distance between a sprinkler head and discharge opening
cannot be less than 60" (1524mm) in length at every point from
the origin of the discharge opening. You must also verify the
sprinkler head sensor is set to the proper heat setting so it does
not activate when the room heats up from normal replace
operation.
Please follow local building codes to determine what
temperature setting is relevant for your installation.
60”
(1524mm)
2
½
(63mm)
min
min
Ceiling
Sprinkler Head
8 FRAMING AND CLEARANCES Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
5¾
(146mm)
55
¼
(1403mm)
Rough Opening for Plenum
2.2 Framing
Shown below are rough opening dimensions for the plenum, unit
installation, and unit installation with a TV recess construction. See
the following page for clearances.
Rough opening framing dimensions should allow for wall covering
thickness and facing materials. Please refer to Section 3.0 on page
10 for specic facing and nishing options.
Figure 2.2, #KZK-054 Plenum Rough Opening
Figure 2.3,CLW-50 Unit Wall Enclosure Rough Opening
76”
(1930mm)
48”
(1219mm)
64
½
(1638mm)
22”
(559mm)
44
½
(1130mm)
4
¼
(108mm)
76”
(1930mm)
64
½
(1638mm)
22”
(559mm)
44
½
(1130mm)
4
¼
(108mm)
Steel Framing Required
Steel Framing Required
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FRAMING AND CLEARANCES 9
5”
(127mm)
5
¾
(146mm)
22”
(558mm)
STEEL
FRAMING
Steel Stud (required)
Figure 2.4, Minimum Clearance from Air Discharge to Ceiling
Figure 2.5, #KZK-054 and CLW-50 Framed Opening and Clearances
2½
(54mm)
5” (127mm)
½
(12mm)
2” (50mm)
½
(12mm)
Ceiling
2.3 #KZK-054 Clearances
Shown below are minimum clearances for the air discharge opening
and #KZK-054 installation.
10 FACING AND FINISHING Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
3.0 FACING AND FINISHING
3.1 Non-combustible Requirements
21½
(545mm)
66”
(1676mm)
6
⁄
(161mm)
48
¾
(1238mm)
53
½
(1359mm)
16
¾
(425mm)
10
½
(267mm)
Combustible Material Allowed
Non-Combustible Material Only
Steel Framing Required
Lower Cover Panel
Combustible Material Allowed
Non-combustible
material only
Combustible material
allowed
Combustible material allowed
see image below for acceptable
screw locations
3¾
(95mm)
13”
(330mm)
9
¾
(248mm)
1
½
(38mm)
13”
(330mm)
3
¾
(95mm)
No Screws Allowed
No Screws Allowed
No Screws Allowed
Non-Combustible Material Only
SCREW PATTERN LOCATIONS
Figure 3.1, Minimum Non-combustible Finishing Dimensions
Figure 3.2, Minimum Non-combustible Finishing Dimensions Screw Locations
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FACING AND FINISHING 11
3.2 Combustible Finish
3.2.1 Trim Installation
NOTE: It is not required to use the #KZK-054 discharge trim (#KZK-
054DT) if desired to run nishing material up to the nishing material
stando. Finishing material must not block the opening and must be
run evenly along the plenum opening.
WARNING! RISK OF OVERHEATING AND FIRE! Ensure the KZK duct
system is installed in accordance to this manual AND the convection
bae is removed when using these combustible clearances.
Figure 3.3, Drywall Finish
Figure 3.4, Combustible Finish Material up to 1" Thick
Figure 3.5, Non-combustible Material Trim Finish
21⁄8
(54mm)
Discharge Trim
Combustible
Material
Drywall stops at nishing material standos
around KZK discharge opening. The discharge
trim covers these edges completely.
43⁄8
(111mm)
Discharge Trim
Combustible
Material up to
1” (25mm) thick
Up to 1” (25mm) thick combustible material up to the edge
of discharge trim. 1” (25mm) combustible material cannot go
closer to discharge opening.
1” (25mm) combustible material goes on top of any
required non-combustible material on the replace.
2¼
(57mm)
Non-Combustible
Material up to
discharge opening
Non-combustible materials, such as tile or stone,
up to the air discharge opening. Minimum air discharge
opening must be maintained the entire length of the
air discharge opening.
Discharge trim is optional for this installation.
12 FACING AND FINISHING Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
3.2.2 Combustible Wall Finish
Figure 3.6 shows installation of combustible wall nish up to 1"
thick. This combustible material goes on any required non-
combustible materials as shown in Figure 3.1 on page 10.
This 1" (25mm) combustible material is able to go down to the
replace nishing edge.
See Figure 3.4 on page 11 for up to 1" (25mm) thick
combustible material installation around the discharge trim of
the KZK air discharge opening.
Figure 3.6, #KZK-054 Combustible Wall Finish
½
(13mm) clearance
around pipe
Combustible wall nish
up to 1” (25mm) thick
may be installed over
cement board
Finishing Edge
Fireplace Enclosure Floor
Non-combustible zone
Steel
Framing
Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FACING AND FINISHING 13
3.3 Hearth and Mantel Clearances
The following drawings show the hearth and mantel clearances
allowed for the CLW-50 with no surround or optional surrounds
installed. Follow the drawings for the minimum distance needed
between the hearth and mantel when installing an optional surround
to allow for proper servicing clearances.
3.3.1 Finishing Guidelines for Optional Surrounds
Figure 3.7 shows where to end nishing materials, when
measuring from the nishing edge, to allow installation of any
optional surround. Most nishing material will not t behind the
optional surround(s) when it is installed.
Measurement 'A' shows the space to leave on each side.
Measurement 'B' shows the space to leave on the top and the
bottom.
Figure 3.7, Finishing Guidelines for Optional Surrounds
Steel
Framing
Non-Combustible Zone
16¾
(425mm)
26
½
(673mm)
9
¾
(248mm)
12” (305mm)
9” (229mm)
6” (152mm)
12” (305mm)
9” (229mm)
6” (152mm)
Combustible wall nish
may be installed over cement
board and butt up to the nshing
edge around the opening
Each square represents
1” (25mm)
of mantel projection
Finishing Edge
Fireplace Enclosure Floor
Finishing Edge
½ (13mm) clearance
around pipe
No Surround
Figure 3.8, Hearth and Mantel Clearances for No Surround
Surround A B
CW50-RS 3/4" (19mm) 1-1/2" (38mm)
CW50-RS4 2-5/8" (66mm) 2-5/8" (66mm)
CW50-GS 6" (152mm) 2-1/2" (64mm)
CW50-FS 3-1/8" (79mm) 3-1/8" (79mm)
B
A
Finishing Trim Edge
Surround Edge
14 INSTALLATION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3
4.0 INSTALLATION
The Kozy Zone Kit requires that the convection bae, located above
the rebox inside the appliance metal cabinet, to be removed to
allow the hot airow to convect upwards into the air ducts installed
on the replace.
1. Remove the convection bae from the appliance. The bae
is secured by (2) screws right behind the upper edge of the
replace opening. Recycle this panel as it is no longer needed.
2. Remove (4) cover plates on top of the appliance (4 screws each).
3. Align the take o collars to the corresponding holes on top of
the appliance. Secure with screws previously removed. Install
the take o collars to the corresponding opening(s) on the
plenum(s). Use supplied screws.
4. Frame a rough opening at the desired location. See previous
pages of this manual for allowable plenum positions and rough
frame opening sizes.
5. Install the plenum into the rough frame opening maintaining
minimum clearances to combustibles as listed (see previous
pages). Fix the plenum to the framing using nails or screw
through the top mounting bracket.
NOTE: Mounting brackets are not intended to carry the weight
of the plenum and pipes. Provide support to the underside of
the plenum and ensure the plenum is level and its outlet is not
distorted.
6. Use metal strapping (all-around, not supplied) as required to
further secure the plenum to framing.
Take-o collar
Convection airow
with bae removed
Convection
bae to be
removed
Convection airow
with bae in place
7. Attach the piping from all (4) plenum take o collars to all (4)
take o collars on the replace. If you are mounting the plenum
10' or less above the replace, use (1) #KZK-410-6 kit or UL-181
Class 0 approved air duct. If you are mounting the plenum
between 10' to 20' above the replace then you will need (2)
#KZK-410-6 kits and #KZK-CPL6 or UL-181 Class 0 approved air
duct.
8. An upward slope must be maintained in horizontal sections of
pipes for proper convection. Support horizontal sections every
24 inches.
9. Install the #KZK-054DT discharge trim to the plenum after the
wall nish is completed using (2) screws, if using the #KZK-054
plenum. Finishing material must not block and should run
evenly along plenum opening. The #KZK-054DT discharge trim is
optional depending on nishing material choice.
10. Continue with replace installation.
Figure 4.1, Air Flow with Convection Bae Removed
Figure 4.2, Convection Bae Removed
Figure 4.3, Cover Plate Removal
Figure 4.4,Trim Installation
HUSSONG MANUFACTURING CO., INC.
LISEZ TOUTES CES ÉTAPES
AVANT DE COMMENCER L’INSTALLATION.
LAISSEZ CE MANUEL AVEC L APPAREIL.
Ce kit doit être installé par un centre de service
ou un installateur qualié, ou par le fournisseur
de gaz, au moment d’installer l’appareil de
chauffage. Ces instructions doivent être utilisées
conjointement avec le manuel d’installation
et d’utilisation fourni avec l’appareil. Veuillez
lire complètement le manuel d’installation de
l’appareil avant de commencer les procédures
de ce manuel d’instructions.
INSTALLATEUR : Laissez ce manuel avec l’appareil.
PROPRIÉTAIRE : Conservez ce manuel pour le consulter.
KIT KOMFORT ZONE
nº KZK-054
Pour utiliser avec le foyer au gaz à évacuation
directe Callaway-50 nº CLW-50
Début du numéro de série : 19 501780 50
Ce kit optionnel de conduits d’air de convection re-
distribue l’air chaud du foyer vers le (ou les) lieux
de votre choix grâce à la convection naturelle,
sans besoin de ventilateur. La sortie d’air chaud
peut être dirigée plus haut sur le mur, à travers les
murs adjacents, ou même vers la pièce adjacente.
Cela permet de réduire beaucoup la température
des murs au-dessus du foyer, pour pouvoir y in-
staller une télévision, des objets d’art ou autres.
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d’installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez
www.kozyheat.com
.
Hussong Manufacturing Co., Inc.
P.O. Box 577, 204 Industrial Park Drive
Lakeeld, MN 56150-0577, USA
Rev 3, 5/20
1.0 INTRODUCTION .......................................................................3
1.1 Contenu du Kit ....................................................................................3
1.2 Congurations suggérées ............................................................... 4
1.3 Dimensions et vue d'ensemble.....................................................5
1.4 Installation des conduit d'air .........................................................6
2.0 ENCADREMENT ET DÉGAGEMENTS .....................................7
2.1 Dégagement aux gicleurs ...............................................................7
2.2 Encadrement .......................................................................................8
2.3 Dégagements d'encadrement ...................................................... 9
3.0 FAÇADE ET FINITION ............................................................10
3.1 Exigences de matériaux incombustibles .................................10
3.2 Matériaux de nition combustibles ..........................................11
3.3 Dégagements de l’âtre et du manteau ....................................13
4.0 INSTALLATION .......................................................................14
Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 3
1.1 Contenu du Kit
Toutes les composants de ce kit est requis et doit être installé.
(1) plénum de 54 po du kit KZK-054
(1) garniture de sortie d'air du plénum KZK-054DT
(8) collets de 6 po - (4) collets à xer au bas du plénum; (4) collets
à xer au foyer, à l'endroit où les couvercles sont retirés.
(1) KZK-410-6 est utilisé pour conduits d’air de 10 pieds (3,05 m). Pour
installer des conduits de plus de 10 pieds (3,05 m), il faut commander
(1) KZK-CPL6.
KZK-CPL6 inclut (6) coupleurs de 6 po qui raccordent (2) KZK-410-6.
Vous n'aurez besoin que de (4) coupleurs de 6 po pour l'installation..
1.0 INTRODUCTION
56⁄
(1425mm
4
⁄
(103mm)
(4) collets de xation (fournis)
KZK-054
Figure 1.1, Plénum, collets et garniture de sortie du kit n KZK-054
Figure 1.2, Item n KZK-410-6
(4) - section de 10 pieds x 6 po conduit exible (aluminium)
homolgué UL-181, Conduit d’air De Classe 0
KZK-410-6
4 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3
1.2 Congurations suggérées
Figure 1.3, Congurations suggérées du KZK-054
KZK-054 sortie mural avant KZK-054 sortie mural arrre
KZK-054 installations dans coin
Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 5
1.3 Dimensions et vue d'ensemble
12½
(317mm)
16
¾
(425mm)
9
¾
(247mm)
39”
(990mm)
34
½ (876mm) MIN
20’ (6m) MAX
2½
(63mm)
Plafond
Dégagement
minimal
au plafond
Les conduits qui raccordent le plénum au foyer doivent être homologués UL-181, Conduits d’air de Classe 0.
Si vous installez le plénum à moins de 10 pieds (3 m) au-dessus du foyer, utilisez un (1) kit nº KZK-410-6.
Si vous installez le plénum à plus de 10 pieds (3 m) et moins de 20 pieds (6 m) au-dessus du foyer,
vous aurez besoin de deux (2) kits nº KZK-410-6 et du kit de coupleurs nº KZK-CPL6.
Dégagement
minimal de
1/2 po (13mm)
aux matériaux
combustibles,
autour des conduits
Figure 1.4, Dimensions du KZK-054
Figure 1.5, Vue d'ensemble du kit KZK-054
54¼
(1378mm)
14”
(355mm)
½
(12mm)
espaceur de
dégagement
1
½
(38mm)
espaceur de
dégagement
½
(12mm)
espaceur de
dégagement
6”
(152mm)
4”
(102mm)
8
⁄ (220mm)
2
⁄
(54mm)
2”
(50mm)
espaceur de
dégagement
12”
(304mm)
3
½
(89mm)
14”
(355mm)
14”
(355mm)
KZK-054
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31

Kozyheat Callaway 50 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire

dans d''autres langues