Pentair HL and SL Series Le manuel du propriétaire

Catégorie
Pompes à eau
Taper
Le manuel du propriétaire

Ce manuel convient également à

293 WRIGHT STREET, DELAVAN, WI 53115 WWW.BERKELEYPUMPS.COM
PH: 888-782-7483
OWNER’S MANUAL
Convertible Deep Well Jet Pumps
© 2013 Pentair, Ltd. All Rights Reserved. BE423 (Rev. 02/25/13)
Installation/Operation/Parts
For further operating, installation, or maintenance assistance:
Call 1-800-782-7483
20
40
60
80
100
2434 0497SR
“HL” and “SL” Series
Safety 2
READ AND FOLLOW
SAFETY INSTRUCTIONS!
This is the safety alert symbol. When you see this
symbol on your pump or in this manual, look for
one of the following signal words and be alert to the
potential for personal injury:
warns about hazards that will cause seri-
ous personal injury, death or major property damage if
ignored.
warns about hazards that can cause seri-
ous personal injury, death or major property damage if
ignored.
warns about hazards that will or can cause
minor personal injury or property damage if ignored.
The label NOTICE indicates special instructions which
are important but not related to hazards.
Carefully read and follow all safety instructions in this
manual and on pump.
Keep safety labels in good condition.
Replace missing or damaged safety labels.
California Proposition 65 Warning
This product and related accessories con-
tain chemicals known to the State of California to cause
cancer, birth defects or other reproductive harm.
ELECTRICAL SAFETY
Capacitor voltage may be hazardous.
To discharge motor capacitor, hold insulated handle
screwdriver BY THE HANDLE and short capacitor ter-
minals together. Do not touch metal screwdriver blade
or capacitor terminals. If in doubt, consult a qualified
electrician.
GENERAL SAFETY
Do not touch an operating motor. Modern
motors can operate at high temperatures. To avoid burns
when servicing pump, allow it to cool for 20 minutes
after shut-down before handling.
Do not allow pump or any system component to freeze.
To do so will void warranty.
Pump water only with this pump.
Periodically inspect pump and system components.
Wear safety glasses at all times when working on pumps.
Keep work area clean, uncluttered and properly lighted;
store properly all unused tools and equipment.
Keep visitors at a safe distance from the work areas.
Pump body may explode if used as a
booster pump unless relief valve capable of passing full
pump flow at 100 psi is installed.
WARNING
Hazardous pressure!
Install pressure relief
valve in discharge pipe.
Release all pressure on
system before working on
any component.
WARNING
Hazardous voltage.
Can shock, burn, or
cause death.
Ground pump before
connecting to power
supply. Disconnect power
before working on pump,
motor or tank.
Wire motor for correct
voltage. See
“Electrical” section of
this manual and motor
nameplate.
Ground motor before
connecting to power
supply.
Meet National
Electrical Code,
Canadian Elec tri cal
Code, and local codes
for all wiring.
Follow wiring
instructions in this
manual when
connecting motor to
power lines.
Table of Contents 3
Page
General Safety .....................................................................................................2
Warranty..............................................................................................................3
Typical Installations .............................................................................................4
Discharge Pipe and Pressure Tank Connections ..................................................5
Electrical ..........................................................................................................6, 7
Preparing To Start The Pump – Deep Well ..........................................................8
Preparing To Start The Pump – Shallow Well .....................................................9
Repair Parts .................................................................................................10,11
Troubleshooting .................................................................................................12
Performance ................................................................................................13, 14
Limited Warranty
BERKELEY warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free
from defects in material and workmanship for the Warranty Period shown below.
Product Warranty Period
Water Systems:
Water Systems Products — jet pumps, small centrifugal pumps, submersible pumps and
related accessories
whichever occurs first:
12 months from date of original installation, or
18 months from date of manufacture
Pro-Source™
Composite Tanks 5 years from date of original installation
Pro-Source™ Steel Pressure Tanks 5 years from date of original installation
Pro-Source™ Epoxy-Lined Tanks 3 years from date of original installation
Sump/Sewage/Effluent Products
12 months from date of original installation, or
18 months from date of manufacture
Agricultural/Commer
cial:
Centrifugals – close-coupled motor drive, frame mount, SAE mount, engine drive, VMS, SSCX,
SSHM, solids handling, submersible solids handling
12 months from date of original installation, or
24 months from date of manufacture
Submersible T
urbines, 6” diameter and larger
12 months from date of original installation, or
24 months from date of manufacture
Our limited warranty will not apply to any product that, in our sole judgement, has been subject to negligence, misapplication,
improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single phase
power through a phase converter will void the warranty. Note also that three phase motors must be protected by three-leg,
ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void.
Your only remedy, and BERKELEY’s only duty, is that BERKELEY repair or replace defective products (at BERKELEY’s choice). You
must pay all labor and shipping charges associated with this warranty and must request warranty service through the installing
dealer as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has
expired. This warranty is not transferable.
BERKELEY SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER.
THE FOREGOING LIMITED WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. THE FOREGOING LIMITED WARRANTIES SHALL NOT EXTEND BEYOND THE DURATION PROVIDED HEREIN.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on the duration of an
implied warranty, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You
may also have other rights which vary from state to state.
This Limited Warranty is effective June 1, 2011 and replaces all undated warranties and warranties dated before June 1, 2011.
In the U.S.: BERKELEY, 293 Wright St., Delavan, WI 53115
In Canada: 269 Trillium Dr., Kitchener, Ontario N2G 4W5
20
40
60
80
100
20
40
60
80
100
Drive Pipe
sends water
down the well
to
drive water
up through the
Suction Pipe
to Pump Suction
Drive
over
Suction
Piping omitted
for clarity
Discharge
1799 0497
Suctio
n
over
Drive
20
40
60
80
100
Suction
Pipe
Drive
Pipe
Well
Head
If well head and pump
don't match, twist
reinforced flexible pipe
to connect drive
and suction pipes.
1800 0497
1903 0497
20
40
60
80
100
Figure 1: Drive and Suction Functions
Figure 2: Reversed Connections
to Well
Figure 3: Mount Ejector –
Shallow Well
Typical Installations 4
Priming
Tee and
Plug
Well
Casing
Foot
Valve
Sanitary
Well Seal
Suction Pipe
From Well
Foot
Valve
Screen
10'
Min.
5–10'
Cased
Well
Open
Water
Strainer
1836 0695
Figure 5: Typical Shallow Well Installations
To Household
Water System
Pressure
Switch
Suction Pipe
From Well
Air Volume
Control
Air Volume
Control Tube
Priming Te e
and Plug
Relief Valve
Drive Pipe
To Well
Standard
Tank
2096 0497
20
40
60
80
100
Venturi
Suction (Larger)
Pipe from Well
Well
Head
Drive
(Smaller)
Pipe to
Well
Nozzle
Ejector
Foot Valve
Strainer
41
JET NO.
J32P-
24
Well Casing
serves as
Drive Pipe
Leather
Cup Seals
"Double Pipe"
(4" and Larger
Diameter Well)
"Single Pipe"
(2" and 3"
Diameter Well
)
1834 0695
Figure 4: Typical Deep Well Installations
To Household
Water System
Not
to
Scale
Relief Valve
Drive
Point
Precharged
Tank
Check
Valve
2097 0497
20
40
60
80
100
Priming
Tee and
Plug
Drive
Coupling
Drive
Point
Check
Valve
Drive point
below water
level
Pressure Gauge
Pre-charged
Tank
PRE-CHARGE TANK CONNECTION (Figure 6)
If your system uses a pre-charged tank, it should be
connected to the pump as shown in Figure 6. The relief
valve must be capable of passing the entire pump capac-
ity at 100 PSI pressure.
Check the pre-charge of air in the tank with an ordinary
tire gauge. the pre-charge is measured when there is
no water pressure in the tank. Disconnect power to the
pump and drain the tank before checking the pre-charge.
Your pump has a 30/50 PSI switch, so the tank pre-
charge pressure should be 28 PSI (that is, it should be 2
PSI lower than the cut-in pressure of the pressure switch.
No AVC is required for a pre-charged tank; the
1/8" NPT AVC port on the pump body should be
plugged.
STANDARD TANK CONNECTION (Figure 7)
If your system uses a standard tank, connect it to the
pump as shown in Figure 7. The relief valve used with
a standard tank must be capable of passing the entire
pump capacity at 75 PSI pressure.
Connect the Air Volume Control (AVC) tube to the
1/8" NPT AVC port on the pump body. Run the tubing
from the pump’s AVC port to the AVC mounted on the
tank. See the instructions provided with tank and AVC
for details.
Discharge Pipe and Pressure Tank Connections 5
To Household
Water System
Pressure
Switch
Suction Pipe
From Well
Air Volume
Control
Air Volume
Control Tube
Priming Te e
and Plug
Relief Valve
Drive Pipe
To Well
Standard
Tank
2096 0497
20
40
60
80
100
Figure 6: Pre-charged Tank Connections
Figure 7: Standard Tank Connections
From
Well
To Household
Water System
Relief Valve
Pre-Charged
Tank
20
40
60
80
100
Pressure Gauge
Pressure
Switch
2110 0497
Pre-charged
Tank
Sealing Pipe Joints
Use only PTFE pipe thread sealant tape for making
all threaded connections to the pump itself. Do not
use pipe joint compounds on plastic pumps: they
can react with the plastic in pump components.
Make sure that all pipe joints in the suction pipe are
air tight as well as water tight. If the suction pipe
can suck air, the pump will not be able to pull water
from the well.
Electrical 6
Plug Type Voltage Selector
Voltage is factory set to 230 volts. To change to 115 volts:
1. Make sure power is off.
2. Pull the voltage change plug off of the tabs.
3. Move the voltage change plug to the 115 volt posi-
tion. The plug will now cover 2 metal tabs and the
arrow on the plug will line up with the 115V arrow on
the label (see Figure 9).
4. Attach the incoming power leads to the two outer
screws on the pressure switch as shown in Figure 8.
5. Attach the ground wire to one of the grounding
connections, shown in Figure 8.
6. If there are other wires, they should be capped.
7. Reinstall the Motor end cover.
Dial Type Voltage Selector
Voltage is factory set to 230 volts. To change to 115 volts:
1. Make sure power is off.
2. Turn the dial counter-clockwise until 115 shows in
the dial window as shown in Figure 11.
3. Attach the incoming power leads to the two outer
screws on the pressure switch as shown in Figure 10.
4. Attach the ground wire to the grounding connections
as shown in Figure 10.
5. If there are other wires, they should be capped.
6. Reinstall the Motor end cover.
Disconnect power before working on pump, motor, pressure switch, or wiring.
NOTE: 1/2 HP motors are wired for 115 volts only, and have no motor wiring to change.
3/4 HP or 1 HP motor terminal boards (located under the motor end cover) should look like one of those below.
If the motor can operate at either 115 or 230 volts, it is set at the factory to 230 volts. Do not change motor wiring
if line voltage is 230 volts, or if you have a single voltage motor.
Never wire a 115 volt motor to a 230 volt line.
MOTOR SWITCH SETTINGS
Figure 8: Voltage set to 230 volts, Plug Type
Ground Wire Connection
Voltage Change Plug
Pressure Switch
Power Connections
4530
Figure 9: Voltage set to 115 volts, Plug Type
Figure 10: Voltage set to 230 volts, Dial Type
Ground Wire Connection
Power Supply Connections
Voltage
Change
Dial
Pressure Switch
Figure 11: Voltage set to 115 volts, Dial Type
Electrical 7
Hazardous voltage. Can shock, burn, or
kill. Connect ground wire before connecting power sup-
ply wires. Use the wire size (including the ground wire)
specified in the wiring chart. If possible, connect the
pump to a separate branch circuit with no other appli-
ances on it.
Explosion hazard. Do not ground to a gas
supply line.
WIRING CONNECTIONS
Fire hazard. Incorrect voltage can cause a
fire or seriously damage the motor and voids the warran-
ty. The supply voltage must be within ±10% of the motor
nameplate voltage.
NOTICE: Dual-voltage motors are factory wired for 230
volts. If necessary, reconnect the motor for 115 volts, as
shown. Do not alter the wiring in single voltage motors.
Install, ground, wire, and maintain your pump in com-
pliance with the National Electrical Code (NEC) or the
Canadian Electrical Code (CEC), as applicable, and with
all local codes and ordinances that apply. Consult your
local building inspector for code information.
Connection Procedure:
Step 1. Connect the ground wire first as shown in Figure
11. The ground wire must be a solid copper wire
at least as large as the power supply wires.
Step 2. There must be a solid metal connection between
the pressure switch and the motor for motor
grounding protection. If the pressure switch is
not connected to the motor, connect the green
ground screw in the switch to the green ground
screw under the motor end cover. Use a solid
copper wire at least as large as the power supply
wires.
Step 3. Connect the ground wire to a grounded lead in
a service panel, to a metal underground water
pipe, to a metal well casing at least ten feet (3M)
long, or to a ground electrode provided by the
power company or the hydro authority.
Step 4. Connect the power supply wires to the pressure
switch as shown in Figure 11.
Table I: Wiring Chart – Recommended Wire and Fuse Sizes
Branch Distance in Feet (Meters);
Max Fuse Wire Size AWG (mm
2
)
Load Rating 0-100 101-200 201-300 301-400 401-500
Model HP Amps Amps (0-30) (31-61) (62-91) (92-122) (123-152)
115Volts:
5SL 1/2 9.9 15 14(2) 10(5.5) 8(8.4) 8(8.4) 6(14)
5HL 1/2 12.2 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
7SL 3/4 12.2 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
7HL 3/4 14.8 20 12(3) 8(8.4) 6(14) 6(14) 4(21)
10SL 1 14.8 20 12(3) 8(8.4) 6(14) 6(14) 4(21)
10HL 1 19.9 25 10(5.5) 8(8.4) 6(14) 4(21) 4(21)
15SL 1-1/2 19.9 25 10(5.5) 8(8.4) 6(14) 4(21) 4(21)
230 Volts:
5SL 1/2 5.0 15 14(2) 14(2) 14(2) 14(2) 12(3)
5HL 1/2 6.2 15 14(2) 14(2) 14(2) 12(3) 12(3)
7SL 3/4 6.2 15 14(2) 14(2) 14(2) 12(3) 12(3)
7HL 3/4 7.4 15 14(2) 14(2) 14(2) 12(3) 10(5.5)
10SL 1 7.4 15 14(2) 14(2) 14(2) 12(3) 10(5.5)
10HL 1 9.9 15 14(2) 14(2) 12(3) 10(5.5) 10(5.5)
15SL 1-1/2 9.9 15 14(2) 14(2) 12(3) 10(5.5) 10(5.5)
Never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding
persons handling pump.
Never run pump dry. Running pump without
water may cause pump to overheat, damaging seal and
possibly causing burns to persons handling pump. Fill
pump with water before starting.
Step 1. Open the control valve as far as possible (see
Figure 12). Then remove the priming plug
from the pump and fill the pump, fill all piping
between the pump and the well, and make sure
that all piping in the well is full. If you have also
installed a priming tee in the suction piping,
remove the plug from the tee and fill the suction
piping.
Step 2. Replace all fill plugs and close the control valve
completely (Figure 13).
Step 3. Power on! Start the pump and watch the pressure
gauge. The pressure should build rapidly to 50
PSI as the pump primes.
Step 4. After 2 or 3 minutes, the gauge should show pres-
sure. If not, stop the pump, remove the fill plugs,
reopen the control valve, and refill the pump and
piping. You may have to repeat this two or three
times in order to get all the trapped air out of the
piping. Don’t forget to close the control valve each
time before you start the pump.
Step 5. When pressure has built up and stabilized at
about 50 PSI, slowly open the control valve (see
Figure 14) and let the pressure drop until the
pressure gauge needle starts to flutter. When the
needle flutters, close the valve just enough to
stop the flutter (see Figure 14). Your pump is now
operating at its most efficient point.
Step 6. After the pump has built up pressure in the
system and shut off, check the pressure switch
operation by opening a faucet or two and run-
ning enough water out to bleed off pressure until
the pump starts. The pump should start when
pressure drops to 30 PSI and stop when pressure
reaches 50 PSI. Run the pump through one or
two complete cycles to verify correct operation.
This will also help clean the system of dirt and
scale dislodged during installation.
NOTICE: Packer jets (2" and 3" single pipe wells) do not
form a perfect seal. Normal irregularities in the cup seal
leather and the inner walls of the casing will allow the
pressure in a dormant system to leak off over time. This
will cause the pump to cycle periodically to maintain the
system pressure level.
Open control valve
as far as possible
and fill pump and
piping through
priming tee.
To Household
Water System
20
40
60
80
100
Pressure
Gauge
2117 0497
Figure 13: Prime Pump
Figure 14: Set Control Valve
C-Close Control Valve until Pressure
Stabilizes
2146 0497
A-Open Control Valve
B-Watch for Pressure Gauge to Flutter
60
80
100
40
20
60
80
100
40
20
60
80
100
40
20
Figure 12: Fill Pump
Replace all
fill plugs and
close control
valve completely.
2120 0497
To Household
Water System
20
40
60
80
100
Preparing to Start the Pump – Deep Well 8
Preparing to Start the Pump – Shallow Well 9
Never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding
persons handling pump.
Never run pump dry. Running pump without
water may cause pump to overheat, damaging seal and
possibly causing burns to persons handling pump. Fill
pump with water before starting.
Step 1. Open the control valve as far as possible (see
Figure 15). Then remove the priming plug
from the pump and fill the pump, fill all piping
between the pump and the well, and make sure
that all piping in the well is full. If you have also
installed a priming tee in the suction piping,
remove the plug from the tee and fill the suction
piping.
Step 2. Replace all fill plugs. Leave the control valve
open (in a shallow well installation, the control
valve always stays open).
Step 3. Power on! Start the pump. The pump should
pump water in two or three minutes.
Step 4. If you don’t have water after 2 or 3 minutes, stop
the pump and remove the fill plugs. Refill the
pump and piping. You may have to repeat this
two or three times in order to get all the trapped
air out of the piping. The control valve remains
open throughout this procedure.
Step 5. After the pump has built up pressure in the
system and shut off, check the pressure switch
operation by opening a faucet or two and run-
ning enough water out to bleed off pressure until
the pump starts. The pump should start when
pressure drops to 30 PSI and stop when pressure
reaches 50 PSI. Run the pump through one or
two complete cycles to verify correct operation.
This will also help clean the system of dirt and
scale dislodged during installation.
Open control valve
as far as possible
and fill pump and
piping through
priming port
or priming tee.
2411 0497
To Household
Water System
60
80
100
40
20
Figure 15: Open Control Valve
Repair Parts 10
2
3
4
5
6
7
7A
8
14
9
10
11
16
17
18
19
20
21
1623 0497
12
13
15A
15
22
20
40
60
80
100
11
Repair Parts 11
Repair Parts – “HL” Series Cast Iron Jet Pumps
SERVICE KITS
Key Part 5HL 7HL 10HL
No. Description Qty. 1/2 HP 3/4 HP 1 HP
1 Motor 1 J218-590PKG J218-596PKG J218-601PKG
#§2 Water Slinger 1 17351-0009 17351-0009 17351-0009
3 Seal Plate 1 N3-1043P L3-10 L3-10
#§4 Seal Plate Gasket 1 N20-35 C20-21 C20-21
#§5 Shaft Seal 1 U109-6A U109-6A U109-6A
#6 Impeller 1 J105-86P J105-85P J105-22PA
#7 Diffuser 1 L1-48P L1-47P L1-23P
7A 8-32x3/4" Rd. Hd. Capscrew 3 U30-489SS U30-489SS
#§8 Diffuser Ring 1 L21-1 L21-1 L21-1
9 Quick Connect – Straight 1 U11-217P U11-217P U11-217P
10 Pressure Gauge 1 U239-2 U239-2 U239-2
11 Control Valve Assembly 1 01322 L262-5PS L262-5PS
12 Pump Body 1 L76-48A L76-49A L76-49A
13 Pipe Plug 1 U78-56ZPS U78-56ZPS U78-56ZPS
14 Drain Plug 1 U78-941ZPV U78-941ZPV U78-941ZPV
15 Base 1 J4-9 J104-9C J104-9C
15A Motor Pad 1 C35-5 C35-5 C35-5
16 3/8-16x1-1/2" Capscrew 2 U30-76ZP U30-76ZP
17 Switch Tube 1 U37-672P U37-672P U37-677P
18 Quick Connect – Elbow 1 U11-218P U11-218P U11-218P
19 Pressure Switch 1 U217-1216 U217-1216 U217-1216
20 Lock Nut 1 U36-112ZP U36-112ZP U36-112ZP
21 Connector 1 L43-5C L43-5C L43-5C
22 3/8-16x1-1/4" Capscrew U30-75ZP (4) U30-75ZP (2) U30-75ZP (2)
§ Seal and Gasket Kit PP1550 PP1551 PP1551
# Overhaul Kit PP1565 PP1566 PP1564
NOTE: § Included in Seal and Gasket Kit. # Included in Overhaul Kit.
(†) Quantity required is indicated after the part number.
Repair Parts – “SL” Series Cast Iron Jet Pumps
SERVICE KITS
Key Part 5SL 7SL 10SL 15SL
No. Description Qty. 1/2 HP 3/4 HP 1 HP 1-1/2 HP
1 Motor 1 J218-582APKG J218-590PKG J218-596PKG J218-601PKG
#§2 Water Slinger 1 17351-0009 17351-0009 17351-0009 17351-0009
3 Seal Plate 1 N3-1043P N3-1043P L3-10 L3-10
#§4 Seal Plate Gasket 1 N20-35 N20-35 C20-21 C20-21
#§5 Shaft Seal 1 U109-6A U109-6A U109-6A U109-6A
#6 Impeller 1 J105-40P J105-86P J105-85P J105-22PA
#7 Diffuser 1 L1-25P L1-48P L1-47P L1-23P
7A 8-32x3/4" Rd. Hd. Capscrew 3 U30-489SS U30-489SS
#§8 Diffuser Ring 1 L21-1 L21-1 L21-1 L21-1
9 Quick Connect – Straight 1 U11-217P U11-217P U11-217P U11-217P
10 Pressure Gauge 1
11 Control Valve Assembly 1 01322 01322 L262-5PS L262-5PS
12 Pump Body 1 L76-48A L76-48A L76-49A L76-49A
13 Pipe Plug 1 U78-56ZPS U78-56ZPS U78-56ZPS U78-56ZPS
14 Drain Plug 1 U78-941ZPV U78-941ZPV U78-941ZPV U78-941ZPV
15 Base 1 J4-9 J4-9 J104-9C J104-9C
15A Motor Pad 1 C35-5 C35-5 C35-5 C35-5
16 3/8-16x1-1/2" Capscrew 2 U30-76ZP U30-76ZP
17 Switch Tube 1 U37-676P U37-677P U37-672P U37-677P
18 Quick Connect – Elbow 1 U11-218P U11-218P U11-218P U11-218P
19 Pressure Switch 1 U217-1225 U217-1225 U217-1225 U217-1225
20 Lock Nut 1 U36-112ZP U36-112ZP U36-112ZP U36-112ZP
21 Connector 1 L43-5C L43-5C L43-5C L43-5C
22 3/8-16x1-1/4" Capscrew U30-75ZP (4) U30-75ZP (4) U30-75ZP (2) U30-75ZP (2)
§ Seal and Gasket Kit PP1550 PP1550 PP1551 PP1551
# Overhaul Kit PP1560 PP1565 PP1566 PP1564
NOTE: § Included in Seal and Gasket Kit. # Included in Overhaul Kit.
(†) Quantity required is indicated after the part number.
Troubleshooting 12Troubleshooting 12
Symptoms Things to Do:
A. Motor will not run. A. Check that the disconnect switch is ON and that the circuit breaker
has not tripped or the fuse has not blown.
DISCONNECT POWER and make sure that wires connecting motor to
power supply and pressure switch are tight and correctly connected
(see Page 6).
If the remedies above do not solve the problem, call your well
professional.
B. Motor runs hot and overload trips. B. Turn to electrical instructions on Page 6 and verify that motor is
correctly wired.
Check with the power company or hydro authority to make sure
that the voltage at the pump is within + 10% of the motor’s rated
nameplate voltage.
DISCONNECT POWER and make sure that the wires connecting the
motor to the power supply are sized according to Table I, Page 7.
If not, rewire according to the instructions on Page 6.
If the pump is cycling too frequently, see Section E, below.
C. Motor runs but no water is delivered. C. FIRST, check the prime; that is, make sure that the pump and all the
suction piping plus the piping in the well are full of water. If they
aren’t, fill them up.
In cold weather, make sure that the pipes and pump are not frozen.
If they are, thaw them, watching out for split pipes and fittings as you
work. Heat the pump pit or pump house and bury all piping below
the frost line.
Other possible causes (call your pump professional if you suspect one
of these): Air leaks in the suction line, dropping water level in the well,
foot valve stuck or plugged, ejector plugged, impeller plugged, foot
valve or strainer stuck in the mud in the bottom of the well, a shallow
well pump installed on a well with more than 25 ft depth to water
(in this case a deep well jet pump is needed).
D. Pump does not deliver water to full capacity. D. Possible causes are: the well water level is lower than estimated,
making a different nozzle/venturi combination necessary; steel piping
(if used) is corroded or limed, restricting capacity and increasing
friction; or the piping is too small for the installation. Consult your
well professional for any of these conditions.
E. Pump cycles too frequently or does not shut E. Make sure no faucets have been left open.
off at all. If system has a standard tank, make sure it isn’t waterlogged. If it is,
drain it down to the level of the air volume control. Make sure the
AVC isn’t defective and that there are no leaks at any connections.
If system has a precharged tank, disconnect power, open all system
faucets and bleed all pressure off of tank. Use a tire gauge to check
the air pressure in the tank. This should be lower than the cut-in setting
of the pressure switch by 2 PSI (that is, if the pressure switch starts the
pump at 30 PSI, the precharge should be 28 PSI). Check the air valve
for leaks (use a soap solution) and replace the core if necessary.
If you suspect any of the following conditions, consult your well
professional: leaky pipes, leaky foot valve, water level in the well
lower than estimated, clogged ejector or impeller.
F. Air spurts from faucets. F. Pump may still be priming; when priming is complete all air will have
been ejected from the system.
If you suspect leaks in the suction piping, gasses in the well, or that the
pump is intermittently overpumping the well (that is, drawing the water
level down below the foot valve), consult your well professional.
G. Pump leaks around clamp. G. Tighten clamp nut 1-2 turns. Do not overtighten.
Table III – 2” Single Pipe Deep Well Performance and Ejector Chart -
Ejector Package BK4830 or BK4840
Model 05SL Model 07SL Model 10SL
1/2 HP 3/4 HP 1 HP
Feet to Pressure in psi Pressure in psi Pressure in psi
Water 20 30 40 50 20 30 40 50 20 30 40 50
GPH w/J32P-24 Venturi & #54 Nozzle GPH w/J32P-32 Venturi & #55 Nozzle GPH w/J32P-24 Venturi & #54 Nozzle
30’ 580 420 260 125 900 660 400 140 1,070 865 635 385
40 485 325 180 48 720 520 260 – 850 660 445 215
GPH w/J32P-18 Venturi & #52 Nozzle
50 275 215 155 100 285 235 185 140 655 480 280 66
60 225 175 120 66 250 200 155 115 330 280 225 180
70 190 135 90 42 215 170 125 80 300 245 195 150
80 – 180 135 95 – 260 210 160 120
90 – 150 105 – 225 180 135 90
100 – 120 80 – 195 150 105 65
110 – – – – – 150 110 75 40
Table IV – Shallow Well Performance and Ejector Chart - Ejector Package BK4855
Model 05SL Model 07SL Model 10SL
1/2 HP 3/4 HP 1 HP
Feet to Pressure in psi Pressure in psi Pressure in psi
Water 20 30 40 50 20 30 40 50 20 30 40 50
GPH w/N32P-66B Venturi & #45 Nozzle GPH w/N32P-75B Venturi & #51 Nozzle GPH w/N32P-67B Venturi & #52 Nozzle
5’ 537 537 469 250 856 856 831 450 900 900 856 787
10 537 537 432 230 787 787 765 414 828 828 787 724
15 430 430 375 200 685 685 665 360 720 720 685 630
20 365 365 319 170 582 582 565 306 612 612 582 535
25 323 323 282 150 513 513 498 270 540 540 513 472
Performance 13
Table II – 4” Double Pipe Deep Well Performance and Ejector Chart - Ejector Package BK4800
Model 05SL Model 07SL Model 10SL
1/2 HP 3/4 HP 1 HP
Feet to Pressure in psi Pressure in psi Pressure in psi
Water 20 30 40 50 20 30 40 50 20 30 40 50
GPH w/J32P-24 Venturi & #51 Nozzle GPH w/J32P-32 Venturi & #55 Nozzle GPH w/J32P-33 Venturi & #51 Nozzle
30’ 525 390 245 120 900 690 420 150 1,200 915 585 180
40 450 315 190 77 700 540 130 960 690 360 155
GPH w/32P-24 Venturi & #51 Nozzle GPH w/J32P-29 Venturi & #54 Nozzle
50 390 245 120 500 385 240 120 715 515 310 150
60 300 175 70 410 300 180 60 505 350 300 150
GPH w/J32P-24 Venturi & #51 Nozzle
70 – 335 240 110 – 430 340 245 150
80 – 240 150 45 – 325 255 175 90
90 – – – – 250 195 120 45
NOTE: psi = Pounds per square inch (pressure).
Table VI – 4” Double Pipe Deep Well Performance and
Ejector Chart - Ejector Package BK4800
Model 15SL
1-1/2 HP
Feet to Pressure in psi
Water 20 30 40 50
GPH w/J32P-33 Venturi & #55 Nozzle
30’ 1,490 1,200 925 660
40 1,310 1,030 760 500
50 1,160 900 640 400
GPH w/J32P-29 Venturi & #55 Nozzle
60 710 620 510 360
70 640 565 450 310
80 550 470 355 215
GPH w/J32P-22 Venturi & #54 Nozzle
90 400 345 290 230
100 350 300 250 190
110 310 265 215 160
Performance 14
Model 15SL
1-1/2 HP
Feet to Pressure in psi Pressure in psi
Water 20 30 40 50 20 30 40 50
GPH w/J32P-29 Venturi & #54 Nozzle GPH w/J32P-18 Venturi & #52 Nozzle
30’ 1,115 935 740 520 450 390 340 295
40 915 745 555 360 405 350 300 255
50 740 540 385 195 370 325 275 235
60 585 420 240 66 340 295 250 210
70 305 260 220 180
80 275 235 195 155
90 240 200 165 125
100 215 180 145 105
110 165 135 105 75
120 135 110 80 54
Table VII – 2” Single Pipe Deep Well Performance and Ejector Chart -
Ejector Package BK4830 and BK4840
NOTE: psi = Pounds per square inch (pressure).
Table V – Shallow Well Performance and Ejector Chart -
Ejector Package BK4855
Model 15SL
1-1/2 HP
Feet to Pressure in psi
Water 20 30 40 50
GPH w/N32P-69B Venturi & #55 Nozzle
5’ 1,340 1,320 1,295 1,130
10 1,200 1,190 1,180 1,130
15 1,025 1,015 995 970
20 855 845 835 820
25 615 600 590 575
20
40
60
80
100
2434 0497SR
293 WRIGHT STREET, DELAVAN, WI 53115 WWW.BERKELEYPUMPS.COM
PH: 888-782-7483
NOTICE D’UTILISATION
Pompe à éjecteur transformables
pour puits profonds
© 2013 Pentair, Ltd. All Rights Reserved. BE423 (Rév. 25/02/13)
Installation/Fonctionnement/Pièces
Pour plus de renseignements concernant l’utilisation, l’installation ou l’entretien,
Composer le 1 (888) 782-7483
Série «HL» et «SL»
Sécurité 2
LIRE TOUTES CES INSTRUCTIONS
ET LES SUIVRE!
Ce symbole indique qu'il faut être prudent.
Lorsque ce symbole apparaît sur la pompe ou dans
cette Notice, rechercher une des mises en garde qui
suivent, car elles indiquent un potentiel possible de bles-
sures corporelles :
avertit d'un danger qui causera des blessures
corporelles, la mort ou des dommages matériels importants
si on l'ignore.
avertit d'un danger qui risque de causer
des blessures corporelles, la mort ou des dommages matéri-
els importants si on l'ignore.
avertit d'un danger qui causera ou qui
risquera de causer des blessures corporelles, la mort ou des
dommages matériels importants si on l'ignore.
Le mot NOTA indique des instructions spéciales et
importantes n'ayant aucun rapport avec les dangers.
Lire attentivement toutes les consignes de sécurité
contenues dans cette Notice ou collées sur la pompe.
Garder les autocollants de sécurité en bon état; les
remplacer s'ils manquent ou s'ils ont été endommagés.
Avertissement lié à la Proposition 65 de la Californie
Ce produit et les accessoires connexes
contiennent des produits chimiques reconnus dans l’État
de la Californie comme pouvant provoquer des cancers,
des anomalies congénitales ou d’autres dangers relatifs à la
reproduction.
SÉCURITÉ CONCERNANT L'ÉLECTRICITÉ
La tension du condensateur peut être
dangereuse. Pour décharger le condensateur du moteur,
tenir un tournevis à manche isolé PAR LE MANCHE et
mettre en court-circuit les bornes du condensateur. Ne pas
toucher la lame métallique du tournevis ni les bornes du
condensateur. En cas de doute, consulter un électricien
qualifié.
SÉCURITÉ GÉNÉRALE
Ne pas toucher un moteur qui fonctionne. Les
moteurs modernes peuvent fonctionner à des températures
élevées. Pour ne pas se brûler lorsque l'on interviendra sur la
pompe, la laisser refroidir pendant 20 minutes après l'avoir
arrêtée avant de la toucher.
Ne pas laisser geler la pompe ni aucun autre élément du
système, sinon la garantie sera annulée.
Ne pomper que de l'eau avec cette pompe.
Périodiquement, inspecter la pompe et tous les éléments du
système.
Toujours porter des lunettes de sécurité lorsque l'on
intervient sur une pompe.
Garder la zone de travail propre, non encombrée et bien
éclairée; tous les outils et tout l'équipement non utilisés
doivent être entreposés correctement.
Ne pas laisser les visiteurs s'approcher de la zone de travail.
Le corps de la pompe peut exploser si la
pompe est utilisée en tant que pompe de surpression, à
moins qu'une soupape de sûreté pouvant laisser passer le
débit maximum de la pompe à 100 lb/po
2
soit posée.
AVERTISSEMENT
Pression dangereuse!
Poser une soupape de sûreté
sur le tuyau de refoulement.
Dissiper toute la pression
du système avant d'intervenir
sur un élément.
AVERTISSEMENT
Tension dangereuse. Risque
de secousses électriques, de
brûlures, voire de mort.
Mettre à la terre la pompe
avant de la brancher sur le
courant électrique. Couper
l'arrivée de courant avant d'in-
tervenir sur la pompe, sur le
moteur ou sur le réservoir.
Câbler le moteur en
fonction de la bonne
tension. Voir la
Section «Électricité»
de cette Notice et la
plaque signalétique du
moteur.
Mettre à la terre le
moteur avant de le
brancher sur le cou-
rant électrique.
Conforme au Code
national de l'électric-
ité, au Code canadien
de l'électricité et aux
codes municipaux
pour tous les câblages.
Respecter les instructions de câblage figurant
dans cette Notice lorsque l'on branche le moteur
sur une ligne haute tension.
Table des matières 3
Page
Sécurité ................................................................................................................................ 2
Garantie ............................................................................................................................... 3
Installations typiques ............................................................................................................ 4
Branchements du tuyau de refoulement et sur un réservoir sous pression ............................ 5
Électricité ......................................................................................................................... 6, 7
Préparations avant le démarrage de la pompe - Puits profond ............................................. 8
Préparations avant le démarrage de la pompe - Puits peu profond....................................... 9
Pièces de rechange ....................................................................................................... 10,11
Diagnostic des pannes ....................................................................................................... 12
Rendement .................................................................................................................... 13,14
Garantie limitée
BERKELEY garantit au consommateur initial (ci-après appelé l’« Acheteur ») que les produits énumérés dans les présentes sont exempts de
défaut de matériau et de fabrication pendant la durée des garanties à compter de la durée des garanties indiquées ci-dessous.
Produits Durée des garanties
Systèmes d’eau :
Produits de systèmes d’eau — Pompes à éjecteur, petites pompes centrifuges, pompes
submersibles et tous les accessoires connexes
Selon le premier terme atteint :
12 mois à compter de la date de la première installation ou
18 mois à compter de la date de fabrication
Réservoirs composites Pro-Sour
ce™ 5 ans à compter de la date de la première installation
Réservoirs sous pression en acier Pro-Source™ 5 ans à compter de la date de la première installation
Réservoirs revêtus d’époxyde Pro-Source™ 3 ans à compter de la date de la première installation
Produits de puisard/d’égout/d’effluents
12 mois à compter de la date de la première installation ou
18 mois à compter de la date de fabrication
Agricole/commercial:
Centrifuges – entr
aînement par moteur monobloc, monté sur cadre, monté sur SAE,
entraînement par moteur à combustion, multiétagé vertical, SSCX, SSHM, pompes
pour les matières solides, pompes submersibles pour les matières solides
12 mois à compter de la date de la première installation ou
24 mois à compter de la date de fabrication
Turbines submersibles, diamètre de 6po et plus gr
and
12 mois à compter de la date de la première installation ou
24 mois à compter de la date de fabrication
Nos garanties limitée ne s’appliquent pas aux produits ayant fait l’objet de négligence, d’une mauvaise utilisation, d’une mauvaise
installation ou d’un manque d’entretien adéquat. Sans aucune limitation des présentes, la garantie des moteurs triphasés submersibles
sera nulle et non avenue si ces moteurs sont branchés et fonctionnent sur le courant monophasé par l’intermédiaire d’un déphaseur. Il faut
également noter que les moteurs triphasés doivent être protégés par un relais de surcharge tripolaire thermocompensé à déclenchement
extrêmement rapide du calibre recommandé, sinon la garantie sera nulle et non avenue.
Le seul recours de l’Acheteur et la seule responsabilité de BERKELEY consistent à réparer ou à remplacer (au choix de BERKELEY) les
produits qui se révéleraient défectueux. L’Acheteur s’engage à payer tous les frais de main d’œuvre et d’expédition du produit couvert par
sa garantie et de s’adresser au concessionnaire-installateur ayant procédé à l’installation dès qu’un problème est découvert pour obtenir
un service sous garantie. Aucune demande de service en vertu de sa garantie ne sera acceptée après expiration de la durée de sa garantie.
Ces garanties ne sont pas transférables.
BERKELEY DÉCLINE TOUTE RESPONSABILITÉ POUR TOUT DOMMAGE INDIRECT OU FORTUIT QUEL QU’IL SOIT.
LA GARANTIE LIMITÉE SUSMENTIONNÉE EST EXCLUSIVE ET REMPLACE TOUTES LES AUTRES GARANTIES EXPRESSES ET TACITES, Y
COMPRIS, MAIS SANS S’Y LIMITER, LES GARANTIES DE QUALITÉ MARCHANDE ET D’ADAPTATION À UN USAGE PARTICULIER. LA
GARANTIE LIMITÉE SUSMENTIONNÉE NE DOIT PAS ÊTRE PROLONGÉE AU-DELÀ DE LA DURÉE PRÉVUE AUX PRÉSENTES.
Certains états, territoires et certaines provinces ne permettent pas l’exclusion ou la limitation des dommages indirects ou fortuits, ni les
limitations relatives à la durée des garanties tacites. Par conséquent, il se peut que les limitations ou les exclusions stipulées dans les
présentes ne s’appliquent pas dans ce cas. Ces garanties accordent des droits juridiques précis, bien que l’on puisse bénéficier d’autres
droits, selon la province, le territoire ou l’état dans lequel on réside.
La présente garantie limitée est entrée en vigueur le 1er juin 2011 et remplace toute garantie non datée ou antérieure à cette date.
Aux États-Unis : BERKELEY, 293 Wright St., Delavan, WI 53115
Au Canada : 269 Trillium Dr., Kitchener, Ontario N2G 4W5
20
40
60
80
100
Suction
Pipe
Drive
Pipe
Well
Head
If well head and pump
don't match, twist
reinforced flexible pipe
to connect drive
and suction pipes.
1800 0497
1903 0497
20
40
60
80
100
Figure 1 : Fonctions eau motrice et
aspiration
Figure 2 : Branchement inversé
dans le puits
Figure 3 : Montage de l’éjecteur -
puits peu profonds
Installations typiques 4
Figure 5 : Installations typiques dans un puits peu profond
Tuyau d’eau
motrice
(le plus petit)
Tête du
puits
Tuyau
d’aspiration
(le plus gros)
Si la tête du puits et la pompe
ne s’assortissent pas, utiliser un
adaptateur inverseur ou bien
croiser le tuyau souple renforcé
pour brancher la pompe sur la
tête du puits.
20
40
60
80
100
20
40
60
80
100
Drive Pipe
sends water
down the well
to
drive water
up through the
Suction Pipe
to Pump Suction
Drive
over
Suction
Piping omitted
for clarity
Discharge
1799 0497
Suctio
n
over
Drive
Tuyau d’eau
motrice
Renvoie l’eau dans
le puits où elle est
Eau
motrice,
puis
aspiration
Aspiration,
puis eau
motrice
Refoulement
Tuyauterie non mon-
trée pour plus de clarté
refoulée dans le
tuyau d’aspiration, puis
aspirée par la pompe
To Household
Water System
Pressure
Switch
Suction Pipe
From Well
Air Volume
Control
Air Volume
Control Tube
Priming Te e
and Plug
Relief Valve
Drive Pipe
To Well
Standard
Tank
2096 0497
20
40
60
80
100
Vers le système
d’eau de la maison
Contrôleur
d’air
Tube du
contrôleur d’air
Té d’amorçage
et bouchon
Soupape de sûreté
Manocontacteur
Réservoir
standard
Tuyau d’aspiration
provenant du puits
Tuyau d’eau
motrice vers le
puits
Venturi
Suction (Larger)
Pipe from Well
Well
Head
Drive
(Smaller)
Pipe to
Well
Nozzle
Ejector
Foot Valve
Strainer
41
JET NO.
J32P-
24
Well Casing
serves as
Drive Pipe
Leather
Cup Seals
"Double Pipe"
(4" and Larger
Diameter Well)
"Single Pipe"
(2" and 3"
Diameter Well
)
1834 0695
«Deux tuyaux» «Un seul tuyau»
(puits de 4 po de dia. (puits de 2
et plus grand) et 3 po)
Tuyau d’aspiration
(le plus gros) provenant
du puits
Tuyau d’eau
motrice (le plus
petit) vers le
puits
Tête du
puits
Tubage du puits
servant de tuyau
d’eau motrice
Venturi
Éjecteur
Buse
Clapet de pied
Crépine
Coupelles d’étanchéité
en cuir
Priming
Tee and
Plug
Well
Casing
Foot
Valve
Sanitary
Well Seal
Suction Pipe
From Well
Foot
Valve
Screen
10'
Min.
5–10'
Cased
Well
Open
Water
Strainer
1836 0695
Tamis
5 à
10 pi
Clapet
de pied
Minimum
de 10 pi
Tubage du
puits
Joint sanitaire
du puits
d’amorçage
et bouchon
Tuyau d’aspiration
provenant du puits
Eau à ciel
ouvert
Puits à
tubage
Clapet
de pied
Crépine
To Household
Water System
Not
to
Scale
Relief Valve
Drive
Point
Precharged
Tank
Check
Valve
2097 0497
20
40
60
80
100
Priming
Tee and
Plug
Drive
Coupling
Drive
Point
Check
Valve
Drive point
below water
level
Pressure Gauge
Réservoir
récharge
Clapet
anti-retour
Soupape de sûreté
Manomètre et orifice
d’amorçage
Vers le système
d’eau de la maison
d’amorçage
et bouchon
Clapet
Pointe filtrante
plus basse que
le niveau de l’eau
Tube
d’enfoncement
de la pointe
Pointe
filtrante
Pas
à
l’échelle
Figure 4 : Installations typiques dans
un puits profond
Pointe
filtrante
BRANCHEMENT SUR UN RÉSERVOIR
PRÉCHARGÉ (Figure 6)
Si le système est branché sur un réservoir préchargé, il devra
être branché sur la pompe, comme il est illustré à la Figure 6.
La soupape de sûreté doit pouvoir laisser passer tout le débit de
la pompe à une pression de 100 lb/po
2
.
Vérifier la précharge d’air dans le réservoir avec un manomètre
pour pneu. La précharge se mesure lorsque le réservoir n’est
pas sous pression d’eau. Couper le courant électrique par-
venant à la pompe et vider le réservoir avant de vérifier la
précharge. Cette pompe neuve est équipée d’un manocon-
tacteur de 30-50 lb/po
2
; la pression de précharge du réservoir
devra donc être réglée à 28lb/po
2
, ce qui représente 2 lb/po
2
de moins que le réglage de la pression d’enclenchement du
manocontacteur de la pompe.
Aucun contrôleur d’air n’est requis dans le cas d’un réservoir
préchargé; l’orifice de 1/8 de pouce NPT prévu pour le con-
trôleur d’air et pratiqué dans le corps de la pompe devra être
bouché.
BRANCHEMENT SUR UN
RÉSERVOIR STANDARD (Figure 7)
Si le système est branché sur un réservoir standard, le brancher
sur la pompe comme il est illustré à la Figure 7. La soupape de
sûreté utilisée avec un réservoir standard doit pouvoir laisser
passer tout le débit de la pompe à une pression de 75 lb/po
2
.
Brancher le tube du contrôleur d’air sur l’orifice de 1/8 de
pouce NPT pratiqué dans le corps de la pompe. Amener le
tube de l’orifice du contrôleur d’air de la pompe jusqu’au
contrôleur d’air monté sur le réservoir. Pour plus de détails, se
reporter aux instructions fournies avec le réservoir et le con-
trôleur d’air.
Branchements du tuyau de refoulement et du réservoir sous pression 5
Figure 7 : Branchements sur un réservoir standard
To Household
Water System
Pressure
Switch
Suction Pipe
From Well
Air Volume
Control
Air Volume
Control Tube
Priming Te e
and Plug
Relief Valve
Drive Pipe
To Well
Standard
Tank
2096 0497
20
40
60
80
100
Contrôleur
d’air
Réservoir
standard
Tuyau d’eau motrice
vers le puits
Tube du
contrôleur
d’air
Soupape de sûreté
En provenance
du puits
Manocontacteur
Té d’amorçage
et bouchon
Vers le système
d’eau de la maison
Étanchéité des raccords des tuyaux
Effectuer tous les raccordements filetés à la pompe
seulement avec du ruban d’étanchéité en PTFE
pour filetage. Ne pas utiliser de pâte pour raccords
filetés sur les pompes en plastique : cette pâte peut
réagir avec les éléments en plastiques de la pompe.
S'assurer que tous les raccords du tuyau d'aspiration
sont bien étanches, aussi bien à l'air qu'à l'eau. Si
le tuyau d'aspiration aspire de l'air, la pompe ne
pompera pas l'eau du puits.
Figure 6 : Branchements sur un réservoir préchargé
From
Well
To Household
Water System
Relief Valve
Pre-Charged
Tank
20
40
60
80
100
Pressure Gauge
Pressure
Switch
2110 0497
Manocontacteur
Réservoir
récharge
Manomètre et
bouchon d’amorçage
Vers le système
d’eau de la maison
Soupape de sûreté
En provenance
du puits
Électricité 6
Sélecteur de tension à fiche
La tension est réglée en usine à 230 volts. Pour passer au
courant de 115 volts :
1. S’assurer que le courant est coupé.
2. Décrocher la fiche de sélection de tension de ses pattes.
3. Déplacer la fiche sur le courant de 115 volts. Sur cette
position, la fiche couvre 2 pattes métalliques et la flèche
sur la prise est alignée sur la flèche 115V de l’étiquette
(figure 9).
4. Fixer les fils d’arrivée de courant aux deux vis extérieures
du manostat (figure 8).
5. Relier le fil de terre à l’une des bornes de mise à la terre
(figure 8).
6. S’il y a d’autres fils, leurs bouts doivent être isolés.
7. Reposer le couvercle d’extrémité du moteur.
Sélecteur de tension à cadran
La tension est réglée en usine à 230 volts. Pour passer au
courant de 115 volts :
1. S’assurer que le courant est coupé.
2. Tourner le cadran dans le sens des aiguilles d’une
montre jusqu’à ce que le nombre 115 soit visible dans la
fente du cadran (figure 11).
3. Fixer les fils d’arrivée de courant aux deux vis extérieures
du manostat (figure 10).
4. Relier le fil de terre aux bornes de raccord de mise à la
terre (figure 10).
5. S’il y a d’autres fils, leurs bouts doivent être isolés.
6. Reposer le couvercle d’extrémité du moteur.
Débrancher le courant électrique avant d'intervenir sur la pompe, le moteur, le manostat ou le câblage.
REMARQUE : Les moteurs de 1/2 ch sont câblés pour fonctionner sur un courant de 115 volts seulement; il ne faut donc changer
aucun câble.
Les plaquettes de connexions des moteurs de 3/4 ch ou de 1 ch (situées sous le couvercle arrière du moteur) ressemblent à l’un des
types décrits ci-dessous. Si le moteur peut fonctionner sur courant de 115 ou de 230 volts, il est réglé en usine pour un courant de
230 volts. Ne pas modifier le câblage du moteur si le courant est de 230 volts ou s’il s’agit d’un moteur à une tension.
Ne jamais relier un moteur de 115 volts à une canalisation de 230 volts.
RÉGLAGES DE L’INTERRUPTEUR DU MOTEUR
Figure 8 : Tension réglée à 230 volts sur sélecteur à fiche
Figure 9 : Tension réglée à 115 volts sur sélecteur à fiche
Figure 10 : Tension réglée à 230 volts sur sélecteur à
cadran
Figure 11 : Tension réglée à 115 volts sur sélecteur à
cadran
Ground Wire Connection
Voltage Change Plug
Pressure Switch
Power Connections
4530
Fiche de sélection
de tension
Manocontacteur
Bornes de
branchement électrique
Borne du fil de mise à la terre
Ground Wire Connection
Power Supply Connections
Voltage
Change
Dial
Pressure Switch
Cadran de
sélection
de tension
Manocontacteur
Bornes de branchement électrique
Borne du fil de mise à la terre
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

Pentair HL and SL Series Le manuel du propriétaire

Catégorie
Pompes à eau
Taper
Le manuel du propriétaire
Ce manuel convient également à

dans d''autres langues