Tripp Lite SmartOnline 208V SV-Series 3-Phase Modular UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire
1
Owner’s Manual
SmartOnline
®
208V SV-Series
3-Phase Modular UPS Systems
(Series Number: AG-0172) (Series Number: AG-0173) (Series Number: AG-0174)
Input: 120/127V (Ph-N), 208/220V (Ph-Ph)
(Not suitable for mobile applications)
Español 39 • Français 77
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
2
Table Of Contents
1. Introduction 3
2. IMPORTANT SAFETY WARNINGS 4
2.1 Location Warning 4
2.2 EMC 4
2.3 Connection Warning 4
2.4 Battery Warning 5
2.5 Safety Standards 5
3. UPS Layout 6
3.1 SmartOnline SV-Series Layout 6
3.2 Package Contents 8
4. Positioning and Pre-Installation 9
4.1 Important Safety Warning 9
4.2 Transportation 9
4.3 Delivery 9
4.4 Installation Environment 9
4.5 Unpacking the UPS 10
5. Wiring and Block Diagrams 11
5.1 Block Diagram 11
5.2 Function of Core System Elements 11
6. Operating Overview 12
6.1 Operating Modes 12
6.2 Single or Dual Feed Input 12
7. Installation 13
7.1 Breakers and Wiring Terminal Block 13
7.2 STS Module Installation 13
7.2.1 Installing a Power Module 15
7.2.2 Removing a Power Module 16
7.2.3 Installing a Battery Module 16
7.2.4 Removing a Battery Module 16
7.2.5 External Battery Cabinet Connection 17
7.3 Cold Start 17
7.4 Conduit Box Installation 18
(for Small Frame Models)
8. Manual Maintenance Bypass 19
8.1 Transfer to Bypass via STS Module Connector 19
from UPS Mode
8.2 Transfer to Bypass via Control Panel 19
9. Control Panel 20
9.1 Introduction 20
9.2 Audible Alarms 21
9.3 Screen Descriptions 21
9.3.1 Start-Up Screen 21
9.3.2 Home Screen 21
9.3.3 Menu Screen 21
9.3.4 Control Screen 22
9.3.5 Measurement Screen 23
9.3.6 Setup Screen 24
9.3.6.1 General 24
9.3.6.2 System 25
9.3.6.3 Battery 26
9.3.6.4 Pre-Alarm 27
9.3.7 Information Screen 27
9.3.8 Events Screen 28
9.3.8.1 Current Events 28
9.3.8.2 Historical Events 29
9.3.8.3 Reset All Events 29
9.4 Text Summaries and Explanations 29
10. Communication 31
10.1 STS Module 31
10.2 Dry Contact Ports 31
10.2.1 Remote EPO Input Port 31
10.2.2 Maintenance Bypass Switch Port 32
10.3 Connectivity 32
10.3.1 SNMP 32
10.3.2 Serial Port 32
10.3.3 USB Port 32
11. Maintenance 33
11.1 Power Module Replacement 33
11.2 Battery Module Replacement 33
11.3 Installing/Replacing the Air Filters 33
12. Troubleshooting 34
13. Technical Specifications 35
14. UPS and Battery Storage; Battery Disposal 37
14.1 UPS and Battery Storage 37
14.2 Battery Disposal 37
15. Warranty and Product Registration 38
3
1. Introduction
Tripp Lite’s SmartOnline SV-Series Uninterruptible Power Supply (UPS) is a Voltage and Frequency Independent (VFI) true on-line, double
conversion 3-Phase UPS system. This UPS continuously conditions the incoming electrical power supply, eliminating power fluctuations and
interruptions that can otherwise damage sensitive electronic devices and create system downtime. Ranging from 20kVA/18kW to 140kVA/126kW,
this series of UPS systems is designed to the highest quality and performance standards and offers the following features:
True on-line UPS: highest level of UPS protection, fully regulating the incoming power supply and transferring immediately to battery in the
event of an extended mains failure for continuous support of critical loads
Modular system: three frame arrangements with multiple construction possibilities to suit specific application requirements; easy and fast
maintenance with hot-swappable power and battery modules
N+1 redundancy up to 140kVA
High efficiency – lower heat losses reduce cooling costs and extend system lifespan
0.9 output power factor – more actual power allows more equipment to be supported
Automatic and manual bypass increase system reliability and allow for maintenance without removing power from the attached load
Wide input voltage window – the UPS system regulates even poor-quality incoming power without reverting to battery, maximizing system
uptime and protecting battery life
Compact form factor; space-saving design even up to 140kVA in a standard rack footprint
Serial communication as standard; SNMP and volt free contact options for optimum configurability
Dual input design allows standard installation from one or two power sources
Low input current total harmonic distortion; no need to oversize a generator set
The SmartOnline SV UPS is designed for protecting critical electrical equipment for:
Data centers
• Telecommunications
Networks (LAN/WAN)
Corporate infrastructure
• Healthcare
• Security
Light industrial
Financial institutions
4
2. IMPORTANT SAFETY WARNINGS
SAVE THESE INSTRUCTIONS.
This manual contains important instructions and warnings that should be followed during the installation,
operation and maintenance of all Tripp Lite SmartOnline SV 3-phase UPS systems and batteries. Read all
instructions thoroughly before attempting to move, install or operate the UPS. Failure to comply may invalidate
the warranty and cause property damage and/or personal injury.
2.1 Location Warning
This UPS contains LETHAL VOLTAGES. All repairs, service and installation must be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the UPS.
SmartOnline SV UPS systems are designed for commercial and industrial application purposes only.
Cabinets must be installed on a level floor suitable for computer or electronic equipment.
The UPS cabinet is heavy. Closely follow unloading instructions to avoid the risk of injury.
Install the UPS system in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses,
conductive contaminants, dust and direct sunlight. The system is not intended for outdoor use.
Operate the UPS at indoor temperatures between 32° to 104°F (0° to 40°C) only. For best results, maintain indoor temperature between
63° to 77°F (17° to 25°C).
Do not place any object on the UPS system, especially containers of liquid.
Do not install the UPS with the front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit’s internal
cooling, causing product damage not covered under warranty.
Do not tilt the UPS cabinet more than 10°.
Do not attempt to unpack or move the UPS without assistance.
2.2 EMC
WARNING:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense. Changes or modifications not expressly approved by
the party responsible for compliance could void the user’s authority to operate the equipment.
2.3 Connection Warning
BEFORE WORKING ON THIS UPS
Isolate the SmartOnline SV UPS.
Check for hazardous voltages between all terminals, including the protective earth.
Risk of Voltage Backfeed: The isolation device must be able to carry the UPS input current. The backfeed protection device should be
VDE/EN/UL approved and rated 220V (L-N) / 380V (L-L), 630A (Large Frame) / 300A (Medium Frame) / 250A (Small Frame).
Figure 2.1: Backfeed Protection Connections
5
2. IMPORTANT SAFETY WARNINGS
START-UP AND COMMISSIONING
An authorized Tripp Lite engineer must perform the start-up of the UPS and a completed start-up form must be returned to
Tripp Lite in order to activate the SmartOnline SV warranty. Please contact your local supplier or [email protected]
for further details. To find your local contact, go to www.tripplite.com/support/contacts.
This UPS contains LETHAL VOLTAGES. KEEP DOORS LOCKED AT ALL TIMES. All repairs, service and installation must be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
Ensure all power is disconnected before performing installation or service.
The UPS system contains its own energy source (battery). The output terminals may carry live voltage even when the UPS is disconnected from
an AC source.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended.
The Protective Earth Ground must be installed first prior to any power connections made to the equipment.
Installation and wiring must be performed in accordance with local electrical laws and regulations.
The AC disconnection device must break line and neutral conductors: four connectors for three phases (L1, L2, L3 and N).
The DC disconnection device must break line with both the positive and negative conductors.
A readily accessible, external disconnect device to the equipment shall be provided for the AC and DC supplies in the end installation.
2.4 Battery Warning
This UPS contains LETHAL VOLTAGES. The UPS is designed to supply power even when disconnected from utility power. Only AUTHORIZED
SERVICE PERSONNEL should access the interior of the UPS, after disconnecting the utility and DC power.
Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed
only by qualified service personnel, observing proper precautions. Turn off the UPS before connecting or disconnecting internal batteries. Use
tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.
The batteries are recyclable. Refer to local codes for disposal requirements or visit http://www.tripplite.com/support/recycling-program for
recycling information.
Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings. Escaping electrolytes may be toxic and cause
injury to skin and eyes.
Do not disconnect the batteries while the UPS is in battery mode.
Disconnect the charging source prior to connecting or disconnecting terminals.
The following precautions should be observed:
1. Remove watches, rings and other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries or battery cabinets.
5. Determine whether the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded
battery can result in electric shock. The likelihood of an electric shock is reduced if such grounds are removed during installation and
maintenance.
Battery replacement should be performed only by authorized service personnel, using the same number and type of batteries
(sealed lead acid).
If the UPS system remains off for an extended period of time, it should be turned on periodically and the batteries should be fully charged.
See Section 14.1 UPS and Battery Storage for battery storage recommendations. Failure to recharge the batteries may cause irreversible
battery damage.
2.5 Safety Standards
Item Normative reference
Uninterruptible power systems (UPS) UL 1778, CSA C22.2 No.107.3-14
Notes:
Conducted FCC Part 15, Subpart B Class A
Radiated FCC Part 15, Subpart B Class A
6
3. UPS Layout
3.1 SmartOnline SV-Series Layout
30U FRONT VIEW
(Small Frame)
23.64 in. (600 mm)
79 in. (2010 mm)
42U FRONT VIEW
(Medium/Large Frame)
23.64 in. (600 mm)
34.65 in. (880 mm)
66 in. (1680 mm)
45.28 in. (1150 mm)
43.30 in. (1100 mm)
58 in. (1475 mm)
Figure 3.1: Dimensions
Frame Selection Height Width Depth
Small Frame (30U) 20-60kW with integrated batteries 58 in. (1475 mm) 23.64 in. (600 mm) 43.30 in. (1100 mm)
Medium Frame (42U) 20-80kW with integrated batteries 79 in. (2010 mm) 23.64 in. (600 mm) 43.30 in. (1100 mm)
Large Frame (42U) 20-140kW without battery 79 in. (2010 mm) 23.64 in. (600 mm) 43.30 in. (1100 mm)
7
3. UPS Layout
1
LED and LCD Control Panel
2
Front Door Lock
3
Switch Module
4
Input Breaker
5
Maintenance Bypass Breaker
6
Output Breaker
7
STS Module
8
Power Module/s
9
Battery Module/s (small and medium frame models; see Section 13. Technical Specifications for a full listing)
10
Leveling Feet
11
Casters
12
Rear Door Lock
13
Battery Breaker (small and medium frame models; see Section 13. Technical Specifications for a full listing)
14
Input/Output Terminal Conduit Cover
1
3
7
8
9
10
12
13
1110 10 10
11
4
14
5 6
2
8
3. UPS Layout
3.1 SmartOnline SV-Series Layout
The modularity of the SmartOnline SV-Series allows three frame arrangements with multiple construction possibilities according to the user’s
power rating and battery runtime requirements. The table below indicates the module capacity per frame. Refer to Section 13 Technical
Specifications for detailed breakdown of maximum Power and Battery Modules per frame.
Small Frame Medium Frame Large Frame
Models with
Batteries
Models without
Batteries
Models with
Batteries
Models without
Batteries
Models without
Batteries
Cabinet Height
30U 30U 42U 42U 42U
Switch Module (built into frame)
1 1 1 1 1
STS Module (built into frame)
1 1 1 1 1
Max. Power Module
3 3 4 4 7+1
1
Max. Battery Module
3 0
2
4 0
2
N/A
2
Note: Consider the wiring gauges and external battery space requirements for the large frame. Each battery module is comprised of four trays of batteries. Each
tray contains 10 pieces 12V/9Ah battery. Four trays must be utilized per module; it is not possible to install partial modules.
1
The large frame hosts up to 140kVA/126kW power capacity without battery modules. An additional power module for large frame models may be added for N+1
redundancy.
2
Battery modules are available in small and medium frames only. Large frame models do not contain battery modules.
3.2 Package Contents
Tripp Lite SmartOnline SV UPS * (1)
Owner’s Manual (1)
M4 Screws (40) **
Washers (40) **
M4 Screws (24) ***
Washers (24) ***
Frame Door Keys (4)
Serial Cable (1)
* The Switch/STS module is delivered with the frame; the power module, battery modules and WEBCARDLX are packaged separately.
** Medium frame
*** Small frame
9
4.1 Important Safety Warning
Read this manual thoroughly before undertaking any installation and wiring. An authorized Tripp Lite engineer must perform the start-up of the
UPS and a completed start-up form must be returned to Tripp Lite in order to activate the SmartOnline SV warranty. Contact Tripp Lite at www.
tripplite.com/support/contacts for further details.
4.2 Transportation
WARNING
The UPS is packed on a pallet suitable for handling with a forklift. If using a forklift or other equipment to move the UPS, ensure
its load bearing capacity is sufficient to support the total packing weight of the UPS.
The UPS is fixed on the pallet with four balance supports. When removing them, pay attention to the movement of the casters to
avoid accidents.
The UPS cabinet may be pushed forward or backwards only; it may not be moved sideways. The cabinet has a high center of
gravity; take care to not tip or overturn the cabinet during transportation.
If moving the UPS over long distance, use appropriate equipment such as a forklift. Do not move the UPS cabinet using its
attached casters over long distances. Move the UPS cabinet in its original packaging until at the final destination site.
4.3 Delivery
Inspect the packaging materials and UPS cabinet carefully upon delivery. Do not install a damaged UPS, connect it to a battery or to the utility.
The packing box of the UPS is equipped with an anti-tilt device. Confirm the device does not indicate any shock or excess tilt during transit. If the
device indicates there has been excessive shock or tilt, do not install and contact your local Tripp Lite representative.
4.4 Installation Environment
The UPS is designed for indoor use only. Do not place or install the UPS in an outdoor area.
When moving the UPS to its installation site, ensure all corridors, doors, gates, elevators, floors, etc. are able to accommodate and bear the
combined weight of the UPS system, any associated battery cabinets and all handling equipment. See Section 13. Technical Specifications
for UPS module combined weights.
The installation site should have a dedicated AC circuit available, compatible with the UPS system’s input requirements. See Section 13.
Technical Specifications for input specifications.
Ensure the installation area has sufficient space for maintenance and ventilation of the UPS system.
Maintain the installation area’s temperature below 86°F (30°C) and the humidity below 90%. The highest operating altitude is 6500 ft.
(2000 m) above sea level. Please consider the derating values when operating the UPS over 3280 ft. (1000 m). The optimum operating
temperature for the batteries is 77°F (25°C).
The UPS should be located in an environment with clean air and adequate ventilation to maintain the ambient temperature within the UPS
operating range.
The UPS is air-cooled with the aid of internal fans. Do not cover the ventilation openings of the UPS system.
Install the UPS in an area in which the walls, floors and ceilings are constructed with fireproof materials. The UPS is suitable for mounting on
concrete or other non-combustible surfaces only.
Install a CO
2
or dry powder extinguisher in the installation area.
Maintain a clearance of at least 48 in. (120 cm) from the top of the UPS for maintenance, cabling and ventilation.
Maintain a clearance of at least 40 in. (100 cm) from the rear and front of the UPS for access and ventilation.
4. Positioning and Pre-Installation
10
4. Positioning and Pre-Installation
4.5 Unpacking the UPS
1. Once the UPS system has arrived at the installation site, it may be removed from the packing box. Follow the unpacking procedure below to
remove main carton (Figure 4.1) and protective materials (Figure 4.2).
Figure 4.1
Figure 4.2
2. Place the ramp delivered in the packing box in front of the UPS cabinet and align the hole in the ramp to the metal stud on the pallet and lock
into place (Figure 4.3).
3. Remove the four fixing plates (Figure 4.4) and loosen the leveling feet by rotating them counterclockwise, raising them above the level of the
casters. The UPS cabinet may now be rolled off the pallet and down the ramp. At least three people should be present to move the UPS to
the installation area, two to support either side of the UPS and a third to guide the UPS into its final location.
4. The casters are designed to move on a level surface over a short distance for final UPS placement. Do not move the UPS using the casters
over long distances or across uneven surfaces. This could damage the casters and/or tip the UPS.
5. Once the UPS is in final position, rotate the leveling feet clockwise below the level of the casters to secure in place (Figure 4.5). Do not rest
the UPS permanently on the casters.
Figure 4.3
Figure 4.4
Figure 4.5
11
5. Wiring and Block Diagrams
5.1 Block Diagram
Without
Jumpers
Figure 5.1: Wiring diagram for dual inputs
Figure 5.2: Wiring diagram for single input
5.2 Functions of Core System Elements
Rectifier: Converts AC from the utility into DC voltage and charges the battery.
Inverter: Converts DC voltage into fully regulated, clean AC voltage to power the attached load. Regardless of the AC waveform from the utility,
the load receives a clean, consistent sine wave with stable voltage and frequency.
Automatic Bypass (Static Switch): Transfers the attached load to mains in case of overload or internal failure. The load is kept powered up as
long as the mains power is available.
Manual Bypass (Maintenance Breaker): User-operated physical switch. The user can transfer the load to bypass to perform UPS maintenance
without powering down the load.
12
Small- and Medium-Frame Units
INPUT 1
INPUT 2
Figure 6.3
For dual input installation, red, yellow and black wire jumpers must be
removed as shown in Figure 6.3 (top rear view of cabinet).
Large-Frame Units
INPUT 1 BUSBAR
INPUT 2
Figure 6.4
For dual input installation, busbar jumpers must be removed as shown
in Figure 6.4 (top view of cabinet).
6. Operating Overview
6.1 Operating Modes
Normal (Double Conversion, VFI)
Power flows through the UPS rectifier and inverter. Voltage and
frequency to the load is independent of voltage and frequency from the
input. There are higher efficiency losses in this mode due to the double
conversion process.
Q
2
Maintenance Breaker
Q
1
Input Breaker
Q
3
Output Breaker
Inverter
Relay
Battery Breaker
Rectifier Inverter
STS
Bypass
Main Load
ECO Mode
When utility power quality is stable, power can be diverted through the
automatic bypass of the UPS. If the utility power goes out of tolerance
or is lost, the UPS transfers quickly back to inverter to power the load
in VFI mode. The result is improved efficiency and cost savings when
power conditions are good.
Q
2
Maintenance Breaker
Q
1
Input Breaker
Q
3
Output Breaker
Inverter
Relay
Battery Breaker
Rectifier Inverter
STS
Bypass
Main Load
6.2 Single or Dual Feed Input
The UPS can accept dual inputs for additional redundancy (e.g. in a server rack installation operating on dual AC feeds).
When powering the UPS with dual AC feeds, first remove the jumpers, as shown below.
Figure 6.1 Figure 6.2
13
7. Installation
7.1 Breakers and Wiring Terminal Block
The input breaker, maintenance bypass breaker and output breaker are located at the front of the Switch Module of the UPS system. The battery
breaker and input/output wiring terminal blocks are at the rear of the Switch Module. To access the terminals from the back of the UPS, remove
the protective Plexiglas
®
panel cover. Wiring installation must be made from the top of the UPS cabinet using the two terminal conduit covers
provided. For connection details, refer to Figure 7.1 (large-frame terminal block shown).
Figure 7.1
Function Description
Output Block Connection to the supported load Includes R (L1), S (L2), T (L3) and Neutral terminals
Alternate Input Block (Input 2) Alternate AC input source connection Includes R (L1), S (L2), T (L3) and Neutral terminals
Main Input Block (Input 1) Primary AC input source connection Includes R (L1), S (L2), T (L3) and Neutral terminals
Grounding Terminal For UPS grounding Includes one grounding terminal
Battery Input Block For external battery connection Includes Positive (+), Negative (-) and Neutral (N) terminals
7.2 STS Module Installation
The STS Module and Switch Module are pre-installed in the frame. STS Module comprises:
Control Circuit
Power Circuit
Communication Circuit (including SNMP, Serial [RS-232])
Internal Static Transfer Switch
• Breaker(s)
Power and Battery Modules can be added according to the user’s requirements. The tables on the following page indicate the maximum current
and cable configurations per assembly.
Note: Internal battery modules for Small- and Medium-Frame systems only.
14
7. Installation
AC Input and Output Maximum Current & Power Cable Configuration
Note: Use copper wire with minimum temperature rating of 221°F (105°C).
Small-Frame Units (30U) with and without Battery Module(s)
20kVA 40kVA 60kVA
Recommended Installation Breaker Size 250A 250A 250A
Max Current 60A 120A 180A
Power and Ground Cable 250 MCM
120 mm
2
250 MCM
120 mm
2
250 MCM
120 mm
2
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m
Medium-Frame Units (42U) with and without Battery Module(s)
20kVA 40kVA 60kVA 80kVA
Recommended Installation Breaker Size 300A 300A 300A 300A
Max Current 60A 120A 180A 240A
Power and Ground Cable 300 MCM
150 mm
2
300 MCM
150 mm
2
300 MCM
150 mm
2
300 MCM
150 mm
2
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m
Large Frame (42U) without Battery Modules
20kVA 40kVA 60kVA 80kVA 100kVA 120kVA 140kVA
Recommended Installation Breaker Size 460A 460A 460A 460A 460A 460A 460A
Max Current 60A 120A 180A 240A 300A 360A 420A
Power and Ground Cable 600 MCM
300 mm²
600 MCM
300 mm²
600 MCM
300 mm²
600 MCM
300 mm²
600 MCM
300 mm²
600 MCM
300 mm²
600 MCM
300 mm²
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m
DC Input Maximum Current and Power Cable Configuration
Nominal Battery Voltage: +/-120V DC
Small Frame (30U) with and without Battery Module(s)
20kVA 40kVA 60kVA
Recommended External Battery Breaker 100A 200A 300A
Power and Ground Cable 3 AWG
25 mm
2
4/0 AWG
95 mm
2
300 MCM
150 mm
2
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m
Medium Frame (42U) with and without Battery Module(s)
20kVA 40kVA 60kVA 80kVA
Recommended External Battery Breaker 100A 200A 300A 400A
Power and Ground Cable 3 AWG
25 mm
2
4/0 AWG
95 mm
2
300 MCM
150 mm
2
600 MCM
300 mm
2
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m
Large Frame (42U) without Battery Modules
20kVA 40kVA 60kVA 80kVA 100kVA 120kVA 140kVA
Recommended External Battery Breaker 100A 200A 300A 400A 500A 600A 700A
Power and Ground Cable 3 AWG
25 mm
2
4/0 AWG
95 mm
2
300 MCM
150 mm
2
500 MCM
240 mm
2
250 MCM x 2
120 mm
2
x 2
300 MCM x 2
150 mm
2
x 2
500 MCM x 2
240 mm
2
x 2
Fixation Torque Force 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m 2.26 N·m
15
7. Installation
7.2.1 Installing a Power Module
WARNING:
Ensure all Power Modules contain identical firmware versions prior to installation.
Each Power Module capacity is 20kVA/18kW and comprises:
Power Factor Correction Rectifier
Battery Charger
• Inverter
Control Circuit
Figure 7.2
The hot-swappable Power Module allows for quick maintenance and system expansion. A latch located at the front of each module fixes and
locks the module in its assigned slot. To install the Power Module, follow the procedure below.
1. Using the DIP switch on the front panel of each Power Module, set the module ID (0-7). The module ID should be exclusive per module.
Note: The default position is 0 for all DIP switches.
Module ID Module DIP Switch
0 POWER
1 POWER
2 POWER
3 POWER
4 POWER
5 POWER
6 POWER
7 POWER
Table 7.1
2. Place the ready switch on the front panel of the Power Module in the unlocked position by rotating the knob counterclockwise.
3. Remove blanking panel and insert Power Module into its identified frame position and slide into cabinet (retain the four screws to install Power
Module in step 4).
16
7. Installation
4. Secure the module to the frame via the fixing bracket using the four screws. Ensure both sides of the Power Module are secured to the frame.
5. Place the ready switch into the locked position by rotating the knob clockwise.
Note: For initial startup and powering on the UPS, refer to Section 9.1 Control Panel – Introduction After the UPS has been successfully powered ON, refer to
Section 9.3.6.2 System to adjust total power and redundancy settings of the UPS based on power modules installed.
If additional power modules are being installed after initial startup, you may skip Section 9.1 and go to Section 9.3.6.2 to adjust total power and redundancy settings.
The Power Module’s LED indicator displays its operational status as follows
No. Behavior LED Display
1 Indicates the system is abnormal FAULT – constant red LED
2 Indicates the parallel system is abnormal
FAULT – flashing red LED
3 Normal operation of the Primary UPS POWER – flashing green LED
4 Normal operation of the Subordinate UPS
POWER – constant green LED
7.2.2 Removing a Power Module
WARNING
Before removing any Power Module, ensure the remaining Power Modules can support the attached load and the UPS is in Line- or
Bypass-mode.
1. Place the ready switch on the Power Module’s front panel to the unlocked position by rotating the knob counterclockwise.
2. The red FAULT LED will illuminate to indicate the Power Module output is off and disconnected from the UPS.
3. Wait five minutes after unlocking the Power Module before servicing.
4. Remove the four screws used to attach to the fixing bracket.
5. Completely remove the Power Module from the frame.
Notes:
When a power module is removed from the frame, the Redundancy Set Fail alarm will sound. Refer to Section 9.3.6.2 System to adjust the Total Power and
Redundancy settings based on power modules removed.
The Power Module is heavy and will require two or more people to move it.
To replace a Power Module, refer to Section 11.1 Power Module Replacement.
7.2.3 Installing a Battery Module
Each Battery Module is comprised of four battery trays. Trays are shipped separately in individual boxes (four boxes per module), fully assembled.
Refer to Section 9.3.6.3 Battery for configuring the Amh hour rating when adding Battery Modules. The default value is 18Ah. For medium and
small frames, each additional installed Battery Module (4 x trays) is 18Ah.
1. Insert battery tray into open slot in the frame position and slide into cabinet, ensuring the +/- connectors make full contact.
2. Secure each battery tray with two screws (provided in accessory bag).
Figure 7.3
7.2.4 Removing a Battery Module
Remove two bottom screws on front panel of the battery tray and pull out the Battery Module using the handle provided.
17
7. Installation
7.2.5 External Battery Cabinet Connection
Once the battery installation is completed, ensure the corrected nominal battery voltage (+/- 120V DC), battery capacity and maximum charging
current data is programmed into the LCD settings. If the actual installation settings differ from the default settings in the LCD, the UPS alarm may
sound continuously. See Section 9.3.6.3: Battery for details.
N
+
-
N
+
-
External
Battery
Input/Output
Breaker and
Disconnect
External battery
cabinet
External battery
cabinet
Back panel of Switch Unit
Figure 7.4
Once all modules are assembled and installation cabling is complete, switch the UPS main breaker on the front of the UPS to “On”. The UPS
system is now on bypass. Enter the Controls Screen on the Control Panel to place the UPS system in full operation. See Section 9.3.4 Control
Screen for details.
7.3 Cold Start
Start Up of the UPS System should be undertaken via the Control Panel. It is possible to start the UPS without an AC input via the “Cold Start”
button on the Power Module:
1. Press the “Cold Start” button as shown in the figure below.
Cold Start Button
POWER
Figure 7.5
2. The UPS will enter standby mode. Immediately press the “Power On/Off” button and hold for 2 seconds, and the UPS will enter Battery Mode.
The Inverter and Battery LEDs will be illuminated. Cold Start procedure is complete.
If more than one Power Module is installed in the frame, performing the cold start procedure on one will translate to all other Power Modules
installed automatically.
Note: The UPS system will function correctly upon initial startup. However, maximum system battery runtime will be available only after the UPS system has been
charged for approximately 24 hours.
18
7. Installation
7.4 Conduit Box Installation (for Small Frame Models)
1. Remove the terminal block cover located on the top-front of the UPS to access the UPS system’s input, output and grounding connection
terminals.
2. The terminal block cover will be replaced with the terminal conduit box found inside the UPS (see illustration).
3. Prepare the terminal box cover with circular cutouts to allow wiring conduits to pass through.
4. Attach the terminal box cover to the top of the UPS system after flexible conduit has been attached.
Notes:
Make sure the wires are tightly connected to the terminals.
Cabling should be protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover.
Conduit box part number: 103509A
Example of conduit
box with circular
cutouts installed
Example of conduit
box located inside
UPS frame
19
8. Manual Maintenance Bypass
The SmartOnline SV Series is equipped with both an automatic bypass and a Manual Maintenance Bypass, allowing the UPS system to be
bypassed without removing power from the attached load.
8.1 Transfer to Bypass via STS Module Connector from UPS Mode
Confirm Bypass Mode is enabled via the LCD prior to performing Maintenance Bypass.
1. Open the front door and locate the Maintenance Bypass Breaker (Q2).
2. Remove the two screws covering the protective plate over the Maintenance Bypass Breaker (Q2).
3. Confirm the UPS system is operating in bypass mode (LCD will show bypass path as below; bypass
LED will illuminate and an alarm will sound).
208.0V
208.0V
208.0V
208.0V
208.0V
208.0V
208.0V
208.0V
208.0V
Figure 8.2
4. Turn ON Maintenance Bypass Breaker (Q2).
5. Turn OFF Output Breaker (Q3).
6. Turn OFF Main Input Breaker (Q1).
7. Turn OFF Internal/External Battery Breakers.
The UPS system is now on Maintenance Bypass. It is now safe to perform routine maintenance, inspection and repairs to the UPS.
To return to normal operation, simply reverse the above steps:
1. Turn ON Internal/External Battery Breakers.
2. Turn ON Main Input Breaker (Q1).
3. Confirm the UPS is in Bypass Mode (LCD will show bypass path and bypass LED will illuminate).
4. Turn ON Output Breaker (Q3).
5. Turn OFF Maintenance Bypass Breaker (Q2)
6. Replace the protective plate over the maintenance bypass breaker unit using the two screws provided.
7. Press the Power button for 2 seconds until the beep to start the inverter is heard.
8.2 Transfer to Bypass via Control Panel
1. Via the Home Screen on the Control Panel, use the Down/Right key to access Menu – Control.
2. Scroll down to “Transfer to Bypass”, select “YES” then press “Enter” key (also see Section 9.3.4 Control Screen).
3. The UPS will transfer to bypass mode; confirm LCD shows bypass path and bypass LED is illuminated.
Note: The transfer to bypass Enable/Disable setting may only be changed when the inverter is turned OFF. The default setting is Enabled.
Figure 8.1
20
9. Control Panel
9.1 Introduction
Turn UPS ON
Once all modules are assembled and installation cabling is complete:
1. Switch on internal/external battery breakers.
2. Switch the UPS Main Breaker Q1 on the front of the breaker panel (“Bypass Mode” will display on the LCD panel).
3. Press the Power button for two seconds. The UPS will now be in Line Mode.
4. Switch on Output Breaker Q3. Parameters can now be viewed, adjusted and programmed via the control panel located on the front of the
UPS system.
Turn UPS OFF
WARNING: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm all power
loads are turned off.
1. Press the Power button for two seconds.
2. If the bypass is disabled, the UPS will transfer to Bypass Mode or Standby Mode.
Note: The UPS will have no output when in Standby Mode.
3. Switch off Output Breaker Q3.
4. Switch off Input Breaker Q1.
5. Wait one minute, then shut off battery breakers.
Note: UPS must be disconnected from AC input in order to be fully de-energized.
The Control Panel is the user control and interface for all measured parameters, UPS and battery status and alarms and is divided into three
areas:
1
LCD Display – Graphic display and all measured parameters
2
LED Indicators – refer to table 9.1
3
Control Keys – refer to table 9.2
1
3
2
Figure 9.1
LED Color Status Definition
INPUT Green On Input source is normal
Flashing Input source is abnormal
Off No input source
BYPASS Amber On Load is on bypass
Flashing Input source is abnormal
Off Bypass is not functioning
INVERTER Green On Load is on inverter
Off Inverter is not functioning
BATTERY Red On Load is on battery
Flashing Low battery
Off Normal operation, battery is charging
ALARM Red On UPS fault
Flashing UPS alarm
Off No alarms
Table 9.1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116

Tripp Lite SmartOnline 208V SV-Series 3-Phase Modular UPS Systems Le manuel du propriétaire

Catégorie
Alimentations sans interruption (UPS)
Taper
Le manuel du propriétaire