Ryobi RY907000FI Le manuel du propriétaire

Catégorie
Groupes électrogènes
Taper
Le manuel du propriétaire

Ce manuel convient également à

NEUTRAL BONDED TO FRAME
CONNECTEUR NEUTRE RELIÉ AU CADRE
PUNTO NEUTRO CONECTADO AL MARCO
WARNING: To reduce the risk of
injury, the user must read and understand
the operator’s manual before using this
product.
TABLE OF CONTENTS
Important Safety Instructions ............3-4
Specific Safety Rules ...........................4
Symbols ............................................5-7
Electrical ...........................................8-9
Features .............................................10
Assembly ......................................11-12
Operation ......................................12-15
Maintenance .................................15-18
Troubleshooting .................................19
Parts Ordering / Service ....... Back Page
AVERTISSEMENT : Pour
réduire les risques de blessures,
l’utilisateur doit lire et veiller à bien
comprendre le manuel d’utilisation avant
d’employer ce produit.
TABLE DES MATIÈRES
Instructions importantes
concernant la sécurité ......................3-4
Règles de sécurité particulières ........... 4
Symboles ..........................................5-7
Caractéristiques électriques .............8-9
Caractéristiques ................................. 10
Assemblage ..................................11-12
Utilisation ......................................13-16
Entretien ........................................16-20
Dépannage .........................................20
Commande de pièces /
réparation ............................Páge arrière
ADVERTENCIA: Para reducir el
riesgo de lesiones, el usuario debe leer
y comprender el manual del operador
antes de usar este producto.
ÍNDICE DE CONTENIDO
Instrucciones de seguridad
importantes .......................................3-4
Reglas de seguridad específicas ......... 4
Símbolos ...........................................5-7
Aspectos eléctricos ..........................8-9
Características ...................................10
Armado .........................................11-12
Funcionamiento ............................13-16
Mantenimiento ..............................16-20
Corrección de problemas ..................20
Pedidos de piezas/
servicio ............................ Pág. posterior
OPERATOR’S MANUAL
MANUEL D’UTILISATION
MANUAL DEL OPERADOR
7,000 WATT GENERATOR
GÉNÉRATRICE DE 7 000 WATTS
GENERADOR 7 000 WATTS
RY907000FI
SAVE THIS MANUAL FOR
FUTURE REFERENCE
CONSERVER CE MANUEL
POUR FUTURE RÉFÉRENCE
GUARDE ESTE MANUAL
PARA FUTURAS CONSULTAS
NOTICE AVIS AVISO
Do not use E15 or E85 fuel in this
product. It is a violation of federal law
and will damage the unit and void your
warranty. Only use unleaded gasoline
containing up to 10% ethanol.
Ne pas utiliser d’essence E15 ou E85 dans ce produit. Une
telle utilisation représente une violation de la loi fédérale
et endommagera l’appareil et annulera la garantie. Utiliser
seulement de l’essence sans plomb ne contenant pas plus
de 10 % d’éthanol.
No utilice combustibles E15 o E85 con este producto. Esto
constituye una violación a la ley federal, dañará la unidad y
anulará la garantía. Utilice únicamente gasolina sin plomo
que contiene hasta 10% de etanol.
ii
See this fold-out section for all of the figures referenced in the operator’s manual.
Consulter l’encart à volets afin d’examiner toutes les figures mentionnées dans le manuel d’utilisation.
Consulte esta sección desplegable para ver todas las figuras a las que se hace referencia en el manual del operador.
Fig. 2
D
Q
A - Handle lock pin (goupille de blocage de la
poignée, pasador de seguro del mango)
B - Fuel cap (réservoir de carburant, tapa del tanque
de combustible)
C - Fuel tank (réservoir de carburant, tanque de
combustible)
D - Ground terminal (borne de terre, terminal de
conexión a tierra)
E - 120 volt AC circuit breaker (disjoncteur de C.A.
de 120 V, disyuntor de circuito de CA 120 V)
F - Two 120 volt AC duplex 20 amp GFCI protected
receptacles (deux prise de courant double de
fuite à la terre 120 V c.a. 20 A , dos receptáculo
120 V doble de 20 A con GFCI)
G - 240 volt AC circuit breaker (disjoncteur de C.A.
de 240 V disyuntor de circuito de CA 240 V)
H - 120/240 volt AC 30 amp receptacle (réceptacle
120/240 volts, 30A; 120/240 V de CA 30 A
receptáculos)
I - Fuel valve (robinet de carburant, válvula de
combustible)
J - Oil cap/dipstick (bouchon/jauge d’huile, tapa de
relleno de aceite/varilla medidora de aceite)
K - Oil drain plug (huiler le bouchon d’égout, tapón
de drenaje del aceite)
L- Engine switch (commutateur de moteur,
interruptor del motor)
M- Digital display (affichage numérique, pantalla
digital)
N
- Recoil starter grip (poignée du démarreur à
rappel, mango del arrancador retráctil)
O - Air filter (filtre à air, filtro de aire)
P - Fuel tank vapor vent (évent de vapeur du
réservoir de carburant, respirador del vapor del
tanque de combustible)
Q - Muffler (silencieux, silenciador)
R - Handle release knob (bouton de verrouillage de
la poignée, perilla de liberación del mango)
S - Spark screen (pare-étincelles, parachispas)
T - Battery maintainer outlet (mainteneur de pile,
cargador de mantenimiento de batería)
U - Check engine indicator LED (témoin d’anomalie
lumineux à DEL, verificación de la luz led
indicadora DEL motor)
A
A - Reset button (bouton réinitialiser, botón de
reajuste)
B - Test button (bouton de test, botón de prueba)
Fig. 1
B
O
N
K
J
T
H
G
F
E
A
C
B
P
L
M
I
R
S
U
iii
A - Bolt (boulon, perno)
B - Frame (renfort transversal, través del
travesaño)
C - Foot bracket (support de pied, soporte del pie)
D - Lock nut (écrou frein, tuerca de bloqueo)
Fig. 4
A - Socket wrench (clé à douille, llave de
casquillo)
B - Combination wrench (clé à molette, llave de
combinación)
C - Phillips screwdriver (tournevis à pointe
cruciforme, destornillador de cabeza Phillips)
A
B
Fig.6
A - Axle (essieu, eje)
B - Wheel (roue, rueda)
C - Washer (rondelle, arandela)
D - Bracket (support, soporte)
E - Hitch pin (goupille d’attelage, pasador del
enganche)
Fig. 8
A - Battery bracket (support de batterie, soporte
de la batería)
B - Positive (+) terminal [borne positive (+), tapa
del terminal positiva (+)]
C - Negative (–) terminal [borne négative (–),
terminal negativa (–)]
D - Black wire (–) [fil noir (–) cable negro (–)]
E - Screw (vis, tornillo)
F - Washer (rondelle, arandela)
G - Nut (écrou, tuerca)
H - Red wires (+) [fils rouge (+), cables rojo (+)]
I - Negative terminal connection (borne
négative, conexión de terminal negativa)
J - Positive terminal connections (borne positive,
conexiones de terminales positivas)
Fig. 7
A
A
C
I
G
D
B
H
E
F
J
C
Fig. 5
Fig. 3
10
9
1
2
3
4
6
11
5
8
7
A
C
B
D
B
E
D
C
A
A - Handle (poignée, mango)
B - Handle lock pin (goupille de blocage de la
poignée, pasador de seguro del mango)
C - Handle release knob (bouton de verrouillage
de la poignée, perilla de liberación del mango)
A
C
B
A - Oil cap/dipstick (bouchon/jauge d’huile,
tapa de relleno de aceite/varilla medidora
de aceite)
B - Oil fill hole (orifice de remplissage d’huile,
agujero de llenado de aceite)
B
A
Fig. 9
iv
Fig. 13
A - Engine switch (commutateur de moteur,
interruptor del motor)
B
- Recoil starter grip (poignée du démarreur à
rappel, mango del arrancador retráctil)
Fig. 14
Fig. 15
Fig. 16
B
A
Fig. 10
Fig. 12
A
A - Fuel cap (bouchon de carburant, tapa del
tanque de combustible)
B - Fuel tank (réservoir de carburant, tanque de
combustible)
B
Mode
Fig. 11
A - Digital display (affichage numérique, pantalla
digital)
B - Mode button (bouton « mode », botón mode)
A
B
A - Knob (bouton, perilla)
B - Air filter cover (couvercle du filtre à air, tapa
del filtro de aire)
C - Filter element (élément du filter, elemento
de filtro)
D - Air filter unit (unité de filtre à air, unidad del
filtro de aire)
A
D
B
C
A - Oil drain plug (huiler le bouchon d’égout,
tapón de drenaje del aceite)
B - Oil cap/dipstick (bouchon / jauge d’huile,
tapa de relleno de aceite/varilla medidora
de aceite)
B
A
OFF
A - Engine switch in ON position (le
commutateur de moteur dans de la position
MARCHE, coloque el interruptor del motor
en la posición ENCENDIDO)
B - Lock button (bouton de verrouillage , botón
del seguro)
C - Engine switch in START position (le
commutateur de moteur dans de la position
OUVERT, coloque el interruptor del motor
en la posición de ARRANQUE)
D - Engine switch in OFF position (le
commutateur de moteur dans de la position
ARRET, coloque el interruptor del motor en
la posición del APAGADO)
1
2
D
B
A
C
A - Fuel valve (robinet de carburant, válvula de
combustible)
B - Recoil starter grip (poignée du démarreur à
rappel, mango del arrancador retráctil)
C - On (marche, encendido)
D - Off (arret, apagado)
A
D
C
B
v
Fig. 20
Fig. 21
Fig. 19
Fig. 18
Fig. 17
Fig. 22
A - Fuel line (conduite de carburant, conducto de
combustible)
B - Hose barb (raccord à tuyau cannelé, conector
de manguera dentada)
C - Fuel valve (robinet de carburant, válvula de
combustible)
A
B
C
B
A
A - Fuel line (conduite de carburant, conducto de
combustible)
B - Fuel filter (filtre de carburant, filtro de
combustible)
A
A - Fuel valve (robinet de carburant, válvula de
combustible)
B - Hose barb (raccord à tuyau cannelé, conector
de manguera dentada)
C - Fuel line (conduite de carburant, conducto de
combustible)
B
C
A - Fuse holder (porte-fusible, sujetador de la
fusible)
B - Fuse (fusible, fusible)
A
B
A - Spark plug (bougie, bujía)
B - Spark plug cap (capuchon de bougie, tapa de la bujía)
C - Engine cover (couverture de moteur, cobertura de motor)
D - Screws (vis, tornillos)
A
B
C
D
Fig. 24
A - Battery maintainer charger (cargador
mantenedor de la batería)
B - Connection port (puerto de conexión)
A
B
Fig. 23
A - Check engine indicator LED (témoin
d’anomalie lumineux à DEL, verificación de la
luz led indicadora DEL motor)
A
A
2 — English
KEEP AT LEAST
20 FT. AWAY
CO Detector
in Living Areas
Only use OUTSIDE and
FAR AWAY from windows,
doors, and vents.
Exhaust (CO)
Direct exhaust AWAY
from all windows, doors,
and vents.
LOCATE GENERATOR AT LEAST 20 FT.* AWAY TO REDUCE THE
RISK OF CARBON MONOXIDE GETTING INSIDE THE HOME
* Minimum distance as recommended by U.S. Department of Health and Human
Services Centers for Disease Control and Prevention (www.cdc.gov/co). Your specific
home and/or wind conditions may require additional distance.
To register your Ryobi product,
please visit: www.ryobitools.com
WARNING:
GROUNDING THE GENERATOR
If this generator will be used only with cord and plug-connected
equipment, National Electric Code does not require that the unit be
grounded. However, other methods of using the generator may re-
quire grounding to reduce the risk of shock or electrocution. Consult
a qualified electrician, electrical inspector, or local agency having
jurisdiction for local codes or ordinances to find out if grounding is
needed in your situation before using the generator.
When grounding is required, the nut and ground terminal on the
frame are used to connect the generator to a suitable ground source.
The ground path should be made with #8 size wire. Connect the
terminal of the ground wire between the lock washer and the nut,
and tighten the nut fully. Connect the other end of the wire securely to a suitable ground source that is in contact with
the soil for a minimum distance of 8 ft.
The National Electric Code contains several practical ways in which to establish a good ground source. If a steel or
iron rod is used, it should be at least 5/8 in. diameter, and if a nonferrous rod is used, it should be at least 1/2 in. di-
ameter and be listed as material for grounding. If a rock bottom is encountered before reaching a depth of 8 ft., drive
the ground rod in at an angle of up to 45°. If the rock bottom is again encountered, the rod can be buried in a trench
that is at least 30 in. deep. In all cases, the upper end of the grounding rod should either be flush with (or below) the
ground or must be otherwise protected from physical damage.
All electrical tools and appliances operated from this generator must be properly grounded by use of a third wire or
be “Double Insulated.”
It is recommended to:
1. Use electrical devices with 3-prong grounded plugs.
2. Use an extension cord intended for outdoor use with a 3-pole receptacle and a 3-prong plug at opposite ends to
ensure continuity of the ground protection from the generator to the appliance.
Check and adhere to all applicable federal, state, and local regulations relating to grounding specifications. Consult a
qualified electrician or service personnel if the grounding instructions are not completely understood or if in doubt as
to whether the generator is properly grounded.
3 — English
DANGER:
Carbon Monoxide. Using a generator indoors CAN KILL
YOU IN MINUTES.
Generator exhaust contains high levels of carbon mon-
oxide (CO), a poisonous gas you cannot see or smell. If
you can smell the generator exhaust, you are breathing
CO. But even if you cannot smell the exhaust, you could
be breathing CO.
Never use a generator inside homes, garages, crawl-
spaces, or other partly enclosed areas. Deadly levels
of carbon monoxide can build up in these areas. Us-
ing a fan or opening windows and doors does NOT
supply enough fresh air.
ONLY use a generator outdoors and far away from
open windows, doors, and vents. These openings
can pull in generator exhaust.
Even when you use a generator correctly, CO may
leak into the home. ALWAYS use a battery-powered or
battery-backup CO alarm in the home.
If you start to feel sick, dizzy, or weak after the generator
has been running, move to fresh air RIGHT AWAY. See
a doctor. You could have carbon monoxide poisoning.
WARNING:
Read and understand all instructions. Failure to follow
all instructions listed below could result in electrocution,
fire, and/or carbon monoxide poisoning, which can cause
death or serious injury.
WARNING:
In some applications, National Electric Code requires
generator to be grounded to an approved earth ground.
Before using the ground terminal, consult a qualified
electrician, electrical inspector, or local agency having
jurisdiction for local codes or ordinances that apply to
the intended use of the generator.
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be
followed during installation and maintenance of the generator.
Do not connect to a building’s electrical system unless
the generator and transfer switch have been properly
installed and the electrical output has been verified by
a qualified electrician.
The connection must isolate the
generator power from utility power and must comply with
all applicable laws and electrical codes.
Do not allow children or untrained individuals to use this
unit.
Do not start or operate the engine in a confined space,
building, near open windows, or in other unventilated space
where dangerous carbon monoxide fumes can collect.
Carbon monoxide, a colorless, odorless, and extremely
dangerous gas, can cause unconsciousness or death.
Keep all bystanders, children, and pets at least 10 feet away.
Wear sturdy and dry shoes or boots. Do not operate while
barefoot.
Do not operate generator when you are tired or under the
influence of drugs, alcohol, or medication.
Keep all parts of your body away from any moving parts
and all hot surfaces of the unit.
Do not touch bare wire or receptacles.
Do not use generator with electrical cords which are worn,
frayed, bare, or otherwise damaged.
Before storing, allow the engine to cool for 30 minutes
and drain fuel from the unit.
Do not operate or store the generator in rain, snow, or
wet weather.
Store the generator in a well-ventilated area with the fuel
tank empty. Fuel should not be stored near the generator.
Empty fuel tank, close fuel valve, and restrain the unit
from moving before transporting in a vehicle.
Provide a plastic sheet or absorbent pad below the
generator to catch any drips of fuel or lubricant when
transporting.
To reduce the risk of fire and burn injury, handle fuel with
care. It is highly flammable.
Do not smoke while handling fuel.
Store fuel in a container approved for gasoline.
Position the unit on level ground, stop engine, and allow
to cool for five minutes before refueling.
Loosen fuel cap slowly to release pressure and to keep
fuel from escaping around the cap.
Tighten the fuel cap securely after refueling.
Wipe spilled fuel from the unit.
Never attempt to burn off spilled fuel under any circum-
stances.
Generators vibrate in normal use. During and after the
use of the generator, inspect the generator as well as
extension cords and power supply cords connected to
it for damage resulting from vibration. Have damaged
items repaired or replaced as necessary. Do not use plugs
or cords that show signs of damage such as broken or
cracked insulation or damaged blades.
For power outages, permanently installed stationary gen-
erators are better suited for providing back-up power to
the home. Even a properly connected portable generator
can become overloaded. This may result in overheating
or stressing the generator components, possibly leading
to generator failure.
IMPORTANT SAFETY INSTRUCTIONS
4 — English
Use only recommended or equivalent replacement parts
and accessories and follow instructions in the Maintenance
section of this manual. Use of any other parts or failure
to follow maintenance instructions may create a risk of
shock or injury.
Maintain the unit per maintenance instructions in this
Operator’s Manual.
Inspect the unit before each use for loose fasteners, fuel
leaks, etc. Replace damaged parts.
DANGER:
Risk of fire and serious burns: Never remove fuel cap
when unit is running. Shut off engine and allow the unit
to cool at least five minutes. Remove cap slowly.
WARNING:
When this generator is used to supply a building
wiring system: generator must be installed by a quali-
fied electrician and connected to a transfer switch as
a separately derived system in accordance with NFPA
70, National Electrical Code. The generator shall be
connected through a transfer switch that switches all
conductors other than the equipment grounding con-
ductor. The frame of the generator shall be connected to
an approved grounding electrode. Failure to isolate the
generator from power utility can result in death or injury
to electric utility workers.
Do not use this generator to provide power for emergency
medical equipment or life support devices.
This generator has a neutral bonded condition. This means
the neutral conductor is electrically connected to the
frame of the machine.
Always use a battery-powered carbon monoxide detec-
tor when running the generator. If you begin to feel sick,
dizzy, or weak while using the generator, shut it off and
get to fresh air immediately. See a doctor. You may have
carbon monoxide poisoning.
Place the generator on a flat, stable surface with a slope
of no more than 4°.
Operate outdoors in a well-ventilated, well-lit area isolated
from working areas to avoid noise interference.
Operating the generator in wet conditions could result in
electrocution. Keep the unit dry.
Keep the generator a minimum of 3 feet away from all
types of combustible material.
Do not operate generator near hazardous material.
Do not operate generator at a gas or natural gas filling
station.
Do not touch the muffler or cylinder during or immediately
after use; they are HOT and will cause burn injury.
Do not allow the generator’s gas tank to overflow when
filling. Fill to 1 in. below the top neck of the gasoline tank
to allow for fuel expansion. Do not cover the fuel tank cap
when the engine is running. Covering the fuel tank cap
during use may cause engine failure and/or damage to
the tool.
Do not smoke when filling the generator with gasoline.
Shut down the engine and allow to cool for five minutes
before adding gasoline or lubricant to the generator.
Do not remove the lubricant dipstick or the fuel tank cap
when the engine is running.
Pay close attention to all safety labels located on the
generator.
Keep children a minimum of 10 feet away from the gen-
erator at all times.
The unit operates best in temperatures between 23°F and
104°F with a relative humidity of 90% or less.
Operating voltage and frequency requirement of all
electronic equipment should be checked prior to plug-
ging them into this generator. Damage may result if the
equipment is not designed to operate within a +/- 10%
voltage variation, and +/- 3 hz frequency variation from
the generator name plate ratings. To avoid damage, al-
ways have an additional load plugged into the generator
if solid state equipment (such as a television set) is used.
A power line conditioner is recommended for some solid
state applications.
When battery is not in use, keep it away from other metal
objects like paper clips, coins, keys, nails, screws, or other
small metal objects that can make a connection from one
terminal to another. Shorting the battery terminals together
may cause burns or a fire.
For outdoor use only.
Save these instructions. Refer to them frequently and use
them to instruct others who may use this product. If you loan
someone this product, loan them these instructions also.
IMPORTANT SAFETY INSTRUCTIONS
SPECIFIC SAFETY RULES
5 — English
Some of the following symbols may be used on this product. Please study them and learn their meaning. Proper
interpretation of these symbols will allow you to operate the product better and safer.
SYMBOL NAME DESIGNATION/EXPLANATION
Safety Alert Indicates a potential personal injury hazard.
Read Operator’s Manual
To reduce the risk of injury, user must read and understand
operator’s manual before using this product.
Wet Conditions Alert Do not expose to rain or use in damp locations.
Electric Shock
Failure to use in dry conditions and to observe safe practices can
result in electric shock.
Toxic Fumes
Running generator gives off carbon monoxide, an odorless, color-
less, poison gas. Breathing carbon monoxide can cause nausea,
fainting, or death.
Fire/Explosion
Fuel and its vapors are extremely flammable and explosive. Fire
or explosion can cause severe burns or death.
Hot Surface and Exhaust
Gases
To reduce the risk of injury or damage, avoid contact with any
hot surface and do not place any body parts in the path of hot
exhaust gases.
Lifting Hazard
To reduce the risk of serious injury, avoid attempting to lift the
generator alone.
Ground
Consult with local electrician to determine grounding requirements
before operation.
Recycle Symbol
This product uses lead acid (Pb) batteries. Local, state or federal
laws may prohibit disposal of batteries in ordinary trash. Consult
your local waste authority for information regarding available re-
cycling and/or disposal options.
The following signal words and meanings are intended to explain the levels of risk associated with this product.
SYMBOL SIGNAL MEANING
DANGER:
Indicates a hazardous situation, which, if not avoided, will result in death or
serious injury.
WARNING:
Indicates a hazardous situation, which, if not avoided, could result in death or
serious injury.
CAUTION:
Indicates a hazardous situation, that, if not avoided, may result in minor or
moderate injury.
NOTICE:
(Without Safety Alert Symbol) Indicates information considered important, but
not related to a potential injury (e.g. messages relating to property damage).
SYMBOLS
6 — English
SAFETY LABELS
The information below can be found
on the generator. For your safety,
please study and understand all
of the labels before starting the
generator.
If any of the labels come off the unit
or become hard to read, contact cus-
tomer service or a qualifed service
center for replacement.
You WILL be KILLED or SERI-
OUSLY HURT if you do not follow
the Operator’s Manual instruc-
tions.
Risk of Fire. Do not add fuel while the product is operat-
ing.
Generator is a potential source of electric shock. Do not
expose to moisture, rain, or snow. Do not operate with
wet hands or feet.
Exhaust contains poisonous carbon monoxide gas that
can cause unconsciousness or DEATH. Operate in well-
ventilated, outdoor areas away from open windows or
doors.
Some of the following symbols may be used on this product. Please study them and learn their meaning. Proper
interpretation of these symbols will allow you to operate the product better and safer.
SYMBOL NAME DESIGNATION/EXPLANATION
V Volts Voltage
A Amperes Current
Hz Hertz Frequency (cycles per second)
W Watt Power
hrs Hours Time
gal Gallon Volume
qt Quart Volume
SYMBOLS
Do not expose to rain or use in damp locations.
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is a
poison you cannot see or smell.
NEVER use inside a home or garage, EVEN IF doors and
windows are open.
Only use OUTSIDE and far away from windows, doors,
and vents.
DANGER
DANGER
PELIGRO
L’utilisation d’une génératrice à l’intérieur PEUT VOUS TUER ENQUELQUES MINUTES.
Les génératrices produisent du monoxyde de carbone, un gaz mortel incolore et inodore.
NE JAMAIS utiliser à l’intérieur d’une maison ou d’un garage,MÊME SI les portes et
les fenêtres sont ouvertes.
Utiliser uniquement À L’EXTÉRIEUR et loin des fenêtres, des portes et des évents.
Usar un generador en el interior PUEDE MATARLO EN POCOS MINUTOS.
Los gases de escape del generador contienen monóxido de carbono. Es un veneno
que no puede verse ni olerse.
NUNCA lo use dentro de su hogar o del garaje, INCLUSO con las puertas y las
ventanas abiertas.
Sólo utilícelo AL AIRE LIBRE y lejos de ventanas, puertas y respiraderos.
Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains carbon monoxide. This is a
poison you cannot see or smell.
NEVER use inside a home
or garage, EVEN IF doors
and windows are open.
Only use OUTSIDE and
far away from windows,
doors, and vents.
7 — English
FUEL CAP WARNING
Never remove fuel cap when unit is running. Shut off engine
and allow the unit to cool at least five minutes. Remove cap
slowly to release any pressure built up in the fuel system
and to avoid the heat from the muffler igniting fuel vapors.
FUEL WARNING
No smoking when filling with gaso-
line. Do not overfill. Full level is 1 in.
below the top of the fuel neck. Stop
the engine for five minutes before
refueling to avoid the heat from the
muffler igniting fuel vapors.
ENGINE LUBRICANT WARNING
You must add lubricant before first
operating the generator. Always
check the lubricant level before
each operation. The lubricant level
should always register between
the hatched areas on the dipstick.
The unit is equipped with a sensor
which will automatically shut off the engine if the lubricant
level falls below a safe limit.
GROUNDING WARNING
This generator does not include a
ground rod or copper wire. Call a
qualified electrician for local ground-
ing requirements.
SPARK ARRESTOR
Operation of this equipment may create sparks that can
start fires around dry vegetation. A spark arrestor may be
required. The operator should contact local fire agencies for
laws or regulations relating to fire prevention requirements.
HOT SURFACE WARNING
Do not touch the muffler or aluminum cylinder of the engine.
They are very HOT and will cause severe burns. Don’t put
body parts or any flammable or combustible materials
in the direct path of the exhaust.
CLEARANCE WARNING
While operating and storing, keep at least 3 feet
of clearance on all sides of this product, including
overhead. Allow a minimum of 30 minutes of “cool
down” time before storage. Heat created by muffler
and exhaust gases could be hot enough to cause seri-
ous burns and/or ignite combustible
objects.
SYMBOLS
940513029-02
Product does not include ground rod or copper wire. Call a qualified electrician for local
grounding requirements.
Le produit ne comprend pas de piquet de terre ou de fil en cuivre. Appeler un électricien qualifié
pour connaître les exigences locales de mise à la terre.
El producto no incluye el ealambre de cobre ni la barra de conexión a tierra. Comuniquese con un
electrista calificado para todo lo relacionado con los requistos de conexión a tierra.
AVERTISSEMENTWARNING ADVERTENCIA
940680075-01
SURFACE ET D’ECHAPPEMENT CHAUDS
SUPERFICIE Y DE ESCAPE ESTEN CALIENTE
HOT SURFACE AND EXHAUST
CHECK LUBRICANT
Add lubricant to full mark to start. Engine will not start or will shut off if sensor detects
low lubricant level. Ajouter de lubrifiant jusqu’au repère de remplissage pour
dèmarrer. Le moteur ne démarre pas ou s’éteint si le capteur détecte le niveau de
lubrifiant faible. Añada lubricante hasta la marca de ileno para arrancar. El motor no
arranca o se apaga si sensor detecta el nivel de lubricante de baja.
940708019-04
DANGER
RISK OF FIRE AND SERIOUS BURNS:
Never remove fuel cap when unit is
running. Shut off engine and allow
the unit to cool at least five minutes.
Remove cap slowly.
Risk of Fire. Check for any fuel overflow or leaking. Stop the engine before refueling.
DANGERDANGER PELIGRO
Risque d’incendie. Vérifier l'absence de débordement ou de fuite de carburant.
Arrêter le moteur avant de fair le plein.
Riesgo de incendio. Revise si hay algún derrame o fuga de combustible. Apague el
motor antes de poner combustible.
940974007-04
8 — English
EXTENSION CORD CABLE SIZE
Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load.
Inadequate size cables can cause a voltage drop, which can burn out the appliance and overheat the cord.
Current in
Amperes
Load in Watts Maximum Allowable Cord Length
At 120V At 240V #8 Wire #10 Wire #12 Wire #14 Wire #16 Wire
2.5 300 600 1000 ft. 600 ft. 375 ft. 250 ft.
5 600 1200 500 ft. 300 ft. 200 ft. 125 ft.
7.5 900 1800 350 ft. 200 ft. 125 ft. 100 ft.
10 1200 2400 250 ft. 150 ft. 100 ft. 50 ft.
15 1800 3600 150 ft. 100 ft. 65 ft.
20 2400 4800 175 ft. 125 ft. 75 ft.
25 3000 6000 150 ft. 100 ft.
30 3600 7200 125 ft. 65 ft.
40 4800 9600 90 ft.
ELECTRIC MOTOR LOADS
It is characteristic of common electric motors in normal operation to draw up to six times their running current while starting.
This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails to start or
reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the requirements
of the tool or appliance being used compared to the rated output of the generator.
Motor Size (H.P.) Running Watts
Watts Required to Start Motor
Universal Capacitor Split Phase
1/8 275 N/A 850 1200
1/6 275 600 850 2050
1/4 400 800 1050 2400
1/3 450 950 1350 2700
1/2 600 1000 1800 3600
3/4 850 1200 2600
1 1100 N/A 3300
NOTICE:
Operating voltage and frequency requirement of all
electronic equipment should be checked prior to plug-
ging them into this generator. Damage may result if the
equipment is not designed to operate within a +/- 10%
voltage variation, and +/- 3 hz frequency variation from
the generator name plate ratings. To avoid damage, al-
ways have an additional load plugged into the generator
if solid state equipment (such as a television set) is used.
A power line conditioner is recommended for some solid
state applications.
GROUND FAULT CIRCUIT INTERRUPTER
See Figure 1.
The 20 amp, 120 volt receptacles on the generator are
protected by a Ground Fault Circuit Interrupter (GFCI),
which guards against the hazards of ground fault currents.
An example of ground fault current is the current that would
flow through a person who is using an appliance with faulty
insulation and, at the same time, is in contact with an electrical
ground such as a plumbing fixture, wet floor, or earth.
GFCI receptacles do not protect against short circuits,
overloads, or shocks.
The GFCI receptacles can be tested with the TEST and
RESET buttons.
To test:
Depress the TEST button. This should cause the Reset
button to pop out.
To restore power, depress the RESET button.
Perform this test monthly to ensure proper operation of the
GFCI. If the generator is stored outdoors, unprotected from
the weather, test the GFCI receptacle before each use.
ELECTRICAL
9 — English
GENERATOR CAPACITY
Make sure the generator can supply enough continuous (run-
ning) and surge (starting) watts for the items you will power
at the same time. Follow these simple steps.
1. Selecttheitemsyouwillpoweratthesametime.
2. Totalthecontinuous(running)wattsoftheseitems.This
is the amount of power the generator must produce to
keep the items running. See the wattage reference chart
at right.
3. Estimatehowmanysurge(starting)wattsyouwillneed.
Surge wattage is the short burst of power needed to
start electric motor-driven tools or appliances such as a
circular saw or refrigerator. Because not all motors start
at the same time, total surge watts can be estimated by
adding only the item(s) with the highest additional surge
watts to the total rated watts from step 2.
Example:
Tool or Appliance
Running
Watts*
Starting
Watts*
Window AC,
10,000 BTU
1200 1800
Refrigerator 700 2200
1/3 HP Well Pump 1000 2000
27 in. Television 500 0
Light (75 Watts) 75 0
3475 Total
Running Watts
2200 Highest
Starting Watts
Total Running Watts 3475
Highest Starting Watts + 2200
Total Starting Watts Needed 5675
POWER MANAGEMENT
To prolong the life of the generator and attached devices,
it is important to take care when adding electrical loads to
the generator. There should be nothing connected to the
generator outlets before starting its engine. The correct and
safe way to manage generator power is to sequentially add
loads as follows:
1. With nothing connected to the generator, start the engine
as described later in this manual.
2. Plug in and turn on the first load, preferably the largest
load you have.
3. Permit the generator output to stabilize (engine runs
smoothly and attached device operates properly).
4. Plug in and turn on the next load.
5. Again, permit the generator to stabilize.
6. Repeat steps 4 and 5 for each additional load.
Never add more loads than the generator capacity. Take
special care to consider surge loads in generator capacity
as previously described.
Application/Equipment
Estimated
Running
Watts*
Estimated
Starting
Watts*
Emergency / Home Standby
Clock Radio 50 0
Lights (qty. 4 x 75 W) 300 0
Refrigerator 700 2200
Furnace Fan 800 2350
Water Well Pump 1000 1500
Microwave 1000 1000
Sump Pump 1050 2200
Electric Range (per element) 2100 0
Job Site
ElectricDrill−1/2HP 600 900
AirlessSprayer−1/3HP 600 1200
Quartz Halogen Work Light 1000 1000
Reciprocating Saw 960 1920
AirCompressor−1HP 1600 4500
CircularSaw−7-1/4in. 1400 2300
Planer/Jointer−6in 1800 1800
MiterSaw−10in. 1800 1800
TableSaw/RadialArmSaw−10in. 2000 2000
*Wattages listed are approximate. Check tool or appliance for actual wattage.
NOTICE:
Do not overload the generator’s capacity. Exceeding the
generator’s wattage/amperage capacity may damage
the generator and/or electrical devices connected to it.
ELECTRICAL
10 — English
KNOW YOUR GENERATOR
See Figure 2.
The safe use of this product requires an understanding of the
information on the product and in this operator’s manual as
well as a knowledge of the project you are attempting. Before
use of this product, familiarize yourself with all operating
features and safety rules.
AC CIRCUIT BREAKERS
The circuit breakers are provided to protect the generator
against electrical overload. The circuit breaker may be reset
by pressing the circuit breaker reset button.
AIR FILTER
The air filter helps to limit the amount of dirt and dust drawn
into the unit during operation.
BATTERY CHARGING FUSE
The battery charge circuit fuse protects the battery.
BATTERY MAINTAINER
Using the battery maintainer when storing the generator helps
keep your generator’s battery charged and ready at all times.
CHECK ENGINE INDICATOR LIGHT
The LED indicator light in the control panel will illuminate to
indicate a fault in the engine’s fuel injection system. Please
contact customer service or a qualified service center for
assistance.
DIGITAL DISPLAY
The digital display shows AC voltage output, frequency, how
long the engine has been running during the current usage
period, and the total number of hours the unit has been used.
ENGINE SWITCH
The engine switch is used alone or in combination with the
recoil starter grip to start the engine. It is also used to turn
the engine off.
FUEL TANK
The fuel tank has a capacity of 6 gallons.
FUEL VALVE
Fuel flow from the fuel tank to the engine is turned on and
off using the fuel valve.
GROUND TERMINAL
The ground terminal is used to assist in properly grounding
the generator to help protect against electrical shock. Consult
with a qualified local electrician for grounding requirements
in your area.
LOW OIL SHUT DOWN PROTECTOR
The low oil sensor causes the engine to stop if the level of
lubricant in the crankcase is insufficient.
OIL CAP/DIPSTICK
Remove the oil fill cap to check and add lubricant to the
generator when necessary.
OIL DRAIN PLUG
When changing the engine lubricant, unscrew and remove
the oil drain plug to allow old engine lubricant to be drained.
RECEPTACLES
Your generator has the following single phase, 60 Hz outlets:
two 120 Volt AC duplex 20 Amp GFCI protected receptacles,
and one 240 Volt AC, 30 Amp receptacle. These can be used
for operating appropriate appliances, electrical lighting, tools,
and motor loads.
RECOIL STARTER GRIP
The recoil starter grip is used (along with the engine switch)
to start the generator’s engine.
PRODUCT SPECIFICATIONS
ENGINE
Engine Type ........................................................ 420cc, EFI
Spark Plug ......................................... F6RTC or equivalent
Fuel Volume ................................................................ 6 gal.
Lubricant Fill Volume .................................... approx. 32 oz.
GENERATOR
Rated Voltage ...................................................120 V/240 V
Rated Amps ................................................... 58.3 A/29.1 A
Rated Output*..........................................................7000 W
Starting Watts .......................................................... 8750 W
Rated Frequency ........................................................60 Hz
FEATURES
*Rated output determined by PGMA Standard G300
11 — English
UNPACKING
This product requires assembly.
Carefully cut the box down the sides then remove the
machine and any accessories from the box. Make sure
that all items listed in the loose parts list are included.
NOTE: This machine is heavy and requires a minimum of
two people to lift. To avoid back injury, lift with your legs
and not your back.
WARNING:
Do not use this product if any parts in the Loose Parts List
are already assembled to your product when you unpack
it. Parts on this list are not assembled to the product by
the manufacturer and require customer installation. Use
of a product that may have been improperly assembled
could result in serious personal injury.
Inspect the unit carefully to make sure no damage oc-
curred during shipping.
Do not discard the packing material until you have carefully
inspected and satisfactorily operated the product.
If any parts are damaged or missing, please call
1-800-860-4050 for assistance.
WARNING:
If any parts are damaged or missing do not operate
this product until the parts are replaced. Use of this
product with damaged or missing parts could result in
serious personal injury.
WARNING:
Do not attempt to modify this product or create acces-
sories not recommended for use with this product. Any
such alteration or modification is misuse and could result
in a hazardous condition leading to possible serious per-
sonal injury.
WARNING:
Do not attempt to operate the generator until assembly
is complete. Failure to comply could result in possible
serious personal injury.
LOOSE PARTS LIST
See Figure 3.
The following items are included with the generator:
Key
No. Description Qty.
1 Wheel ...................................................................2
2 Axle ......................................................................2
3 Washer ................................................................. 2
4 Hitch Pin ..............................................................2
5 Bolt ......................................................................4
6 Right Foot Bracket ..............................................1
7 Left Foot Bracket .................................................1
8 Lock Nut .............................................................4
9 Battery Maintainer ..............................................1
10 Engine Lubricant..................................................1
11 Battery Hardware Kit ...........................................1
Operator’s Manual (not shown) ...........................1
TOOLS NEEDED
See Figure 4.
The following tools (not included or drawn to scale) are
needed for assembly:
Socket Wrenches and/or Combination Wrenches
Philips Screwdriver
NOTE: Do not put fuel or lubricant in the generator before
installing the feet, frame support, wheels and handle.
INSTALLING THE FEET
See Figure 5.
Locate the following items:
Right foot bracket
Left foot bracket
4 lock nuts
4 bolts
Insert bolts through the right foot bracket and holes in
the generator frame as shown.
Thread lock nuts onto bolts and tighten one full turn past
snug.
NOTE: Be careful not to overtighten so that foot mate-
rial collapses.
Repeat with the left foot.
ASSEMBLY
12 — English
INSTALLING THE WHEELS
See Figure 6.
Wheels are provided to assist in moving the generator to
the desired location and should be installed on the same
side as the handle.
Locate the following items:
2 axles
2 hitch pins
2 washers
2 wheels
Raise the end of the generator where the handle is located
high enough to gain access to the frame bottom; securely
position props underneath to support.
Slide the axle through the hole in the center of the wheel.
Slide a washer onto the axle, then slide the axle into the
wheel mounting hole as shown.
Insert hitch pin to secure.
NOTE: The hitch pin should be pushed into the axle until
the center of the pin rests on top of the axle.
Repeat with the second wheel.
CONNECTING/DISCONNECTING BATTERY
See Figure 7.
WARNING:
To reduce the risk of electrocution or explosion, do not
short circuit the battery terminals or charge in a sealed
container. Keep sparks and flame away.
ASSEMBLY
WARNING:
Keep metal objects away from the battery terminals.
Metal objects can make a connection from one terminal
to another. Shorting the battery terminals together can
cause sparks, burns, or a fire.
NOTICE:
The battery may require charging before the generator
can be started using either the engine switch or the recoil
starter. Once the generator is started, the battery will
charge as the unit runs.
The battery cables must be connected before the generator
can be operated.
To connect battery cables:
Connect the red wires to the positive (+) terminal first,
then connect the black wire to the negative (-) terminal.
Make sure all connections are tight.
NOTE: Be careful not to short across the terminals when
installing. Shorting the terminals together can cause
sparks, damage to the battery or generator, or even burns
or explosions.
Cover the terminals with the rubber covers.
When removing the battery for replacement: disconnect
the negative (black) post, then the positive (red) post, being
careful not to short across the terminals. Always abide by the
safety warnings provided with the battery. Remove the battery
and dispose of according to local and state regulations.
OPERATION
DANGER:
Carbon Monoxide. Using a generator indoors CAN KILL YOU IN MINUTES.
Generator exhaust contains high levels of carbon monoxide (CO), a poisonous gas you cannot see or smell. If you can
smell the generator exhaust, you are breathing CO. But even if you cannot smell the exhaust, you could be breathing CO.
Never use a generator inside homes, garages, crawlspaces, or other partly enclosed areas. Deadly levels of carbon
monoxide can build up in these areas. Using a fan or opening windows and doors does NOT supply enough fresh
air.
ONLY use a generator outdoors and far away from open windows, doors, and vents. These openings can pull in
generator exhaust.
Even when you use a generator correctly, CO may leak into the home. ALWAYS use a battery-powered or battery-backup
CO alarm in the home.
If you start to feel sick, dizzy, or weak after the generator has been running, move to fresh air RIGHT AWAY. See a doc-
tor. You could have carbon monoxide poisoning.
13 — English
WARNING:
If this generator will be used only with cord and plug-
connected equipment, National Electric Code does
not require that the unit be grounded. However, other
methods of using the generator may require grounding
to reduce the risk of shock or electrocution. Consult a
qualified electrician, electrical inspector, or local agency
having jurisdiction for local codes or ordinances to find
out if grounding is needed in your situation before using
the generator.
WARNING:
Do not allow familiarity with this product to make you
careless. Remember that a careless fraction of a second
is sufficient to inflict serious injury.
WARNING:
Do not use any attachments or accessories not
recommended by the manufacturer of this product. The
use of attachments or accessories not recommended
can result in serious personal injury.
NOTICE:
This product is equipped with a spark arrestor that has
been evaluated by the USDA Forest Service; however,
product users must comply with Federal, State, and local
fire prevention regulations. Check with appropriate au-
thorities. Contact customer service or a qualified service
center to purchase a replacement spark arrestor.
NOTICE:
Before each use, inspect the entire product for damaged,
missing, or loose parts such as screws, nuts, bolts,
caps, etc. Tighten securely all fasteners and caps and
do not operate this product until all missing or damaged
parts are replaced. Please contact customer service or
a qualified service center for assistance.
APPLICATIONS
This generator is designed to supply electrical power for
operating compatible electrical lighting, appliances, tools,
and motor loads.
BEFORE OPERATING THE UNIT
Only use OUTSIDE and at least 20 feet away from win-
dows, doors, and vents as recommended by the U.S
Department of Health and Human Services Centers for
Disease Control and Prevention. Your specific home and/
or wind conditions may require additional distance.
OPERATION
NEVER use inside a home or garage, EVEN IF doors and
windows are open.
Always position the generator on a flat firm surface.
SPECIAL REQUIREMENTS:
There may be General or State Occupational Safety and
Health Administration (OSHA) regulations, local codes or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction:
In some areas, generators are required to be registered
with local utility companies.
If the generator is used at a construction site, there may
be additional regulations which must be observed.
RAISING AND LOWERING THE HANDLE
See Figure 8.
To raise the handle (for moving the generator): pull the
handle release knob out, raise the handle, then release
the knob so it snaps into the locking position. Insert the
handle lock pin to secure the handle in place.
To lower the handle (for storing or transporting the
generator): remove the handle lock pin, then pull the
handle release knob out and lower the handle to the down
position.
Never use the handle to lift the generator. The handle should
only be used for moving the unit by rolling it on its wheels.
CHECKING/ADDING LUBRICANT
See Figure 9.
NOTICE:
Attempting to start the engine before it has been properly
filled with lubricant will result in equipment failure.
NOTE: If a separate engine manual is provided for this
product, please follow the instructions provided in the
engine manual instead of the information listed below.
Engine lubricant has a major influence on engine performance
and service life. For general, all-temperature use, SAE 10W-
30 full synthetic is recommended. Always use a 4-stroke
motor lubricant that meets or exceeds the requirements for
API service classification SJ.
This engine comes with a feature that will shut off the engine
when a specific lubricant level is not maintained. The engine
will not restart until an appropriate lubricant level is reached.
NOTE: Non-detergent or 2-stroke engine lubricants will
damage the engine and should not be used.
Unscrew the oil cap/dipstick and remove.
Wipe dipstick clean and re-seat in hole; do not re-thread.
Remove dipstick again and check lubricant level. Lubri-
cant level should fall between the hatched areas on the
dipstick.
14 — English
WARNING:
Always shut off engine before fueling. Never remove
fuel cap or add fuel to a machine with a running or hot
engine. Make sure the unit is sitting on a flat, level sur-
face and only add fuel outdoors. If the engine is hot, let
the unit cool for at least five minutes before adding fuel.
After fueling, immediately replace fuel cap and tighten
securely. Move at least 30 ft. from refueling site before
starting engine. Do not smoke and stay away from open
flames and sparks! Failure to follow these instructions
could result in a fire and cause serious personal injury.
NOTE: Always use unleaded gasoline with a pump octane
rating of 86 or higher. Never use old, stale, or contaminated
gasoline, and do not use a lubricant/gas mixture. Do not
allow dirt or water into the fuel tank. Do not use E85 fuel.
DIGITAL DISPLAY
See Figure 11.
Press and release the mode button to cycle through the
following displays:
Voltage (V) displays the operating voltage of the generator.
Frequency (F) displays the frequency in hertz at which the
generator is running.
The Run/Maintenance Timer displays the amount of time
the generator has run since being started. This timer resets
each time the generator is shut off.
When a cumulative run time of 25 hours has been reached,
P25 will display on the meter as a reminder to change the
engine lubricant after the initial 25 hours of run time.
When a cumulative time of 50 hours is reached, P50 will
display on the meter to remind you to clean the air filter.
When a cumulative time of 100 hours is reached, P100 will
display on the meter to remind you to change/clean the fuel
filter, clean the air filter, and change the engine lubricant.
ELECTRIC START
This generator model is provided with both electric start and
recoil start capabilities. Avoid prolonged cranking, as it can
damage the engine.
The battery provided is a nominal 12 volt sealed rechargeable
lead-acid battery and can be operated in any position without
leakage. It complies with non-spillable battery regulations.
NOTE: Brand new generators are shipped with the battery
connections disconnected. The positive and negative
terminals must be connected to the battery before the Electric
Start feature will work.
For initial battery connection, see Connecting/Disconnecting
Battery.
OPERATION
If level is low, add engine lubricant until the fluid level rises
to the upper portion of the dipstick.
Replace and secure the oil cap/dipstick.
USING FUEL STABILIZER
Fuel gets old, oxidizes, and breaks down over time. Adding
a fuel stabilizer (not included) extends the usable life of fuel
and helps prevent deposits from forming that can clog the
fuel system. Follow fuel stabilizer manufacturer’s directions
for correct ratio of stabilizer to fuel.
Mix fuel stabilizer and gasoline prior to filling the tank
by using a gas can or other approved fuel container and
shaking gently to combine.
NOTE: To control the amount of fuel stabilizer being added
to the engine, always mix fuel stabilizer with gasoline
before fueling the tank rather than adding fuel stabilizer
directly into the generator’s fuel tank.
Replace and secure the fuel tank cap.
Start and run the engine for at least 5 minutes to allow
stabilizer to treat the entire fuel system.
ETHANOL-BLENDED FUELS
NOTICE:
Do not use E15 or E85 fuel in this product. It is a viola-
tion of federal law and will damage the unit and void
your warranty. Only use unleaded gasoline containing
up to 10% ethanol.
ADDING FUEL
See Figure 10.
DANGER:
Risk of fire and serious burns: Never remove fuel cap
when unit is running. Shut off engine and allow the unit
to cool at least five minutes. Remove cap slowly.
WARNING:
Gasoline and its vapors are highly flammable and ex-
plosive. To prevent serious personal injury and property
damage, handle gasoline with care. Keep away from igni-
tion sources, handle outdoors only, do not smoke while
adding fuel, and wipe up spills immediately.
When adding gas to the generator, make sure the unit is sitting
on a flat, level surface. If the engine is hot, let the generator
cool for five minutes before adding gas. ALWAYS fill the fuel
tank outdoors with the machine turned off.
Turn the fuel valve to the OFF (O) position.
Remove the fuel cap slowly.
Fill the fuel tank to 1 in. below the top of the fuel neck.
Replace and secure the fuel cap.
15 — English
STARTING THE ENGINE
See Figures 12 - 14.
NOTICE:
On a level surface with the engine off, check the lubricant
level before each use of the generator.
NOTE: If location of generator is not level, the unit may not
start or may shut down during operation.
This generator is equipped with electronic fuel injection.
Starting the generator will require a brief wait to allow the
fuel to travel from the tank.
Unplug all loads from the generator.
Turn the fuel valve to the ON ( I ) position.
To start the engine using the electric start:
1
Put the engine switch in the ON position.
2
Wait 30 seconds to allow fuel to travel through the
line.
NOTE: The engine will not start until the fuel has
reached the fuel injector and the proper operating
pressure is acheived.
3
Slide down and hold the lock button while pushing
the engine switch to the START position.
NOTE: The battery may require charging before the gen-
erator can be started using either the engine switch or the
recoil starter. Once the generator is started, the battery will
charge as the unit runs. If the engine switch will not start
the unit once the battery has been fully charged, check
the circuit protector fuse and replace if needed following
instructions in Changing Engine Battery Charge Curcuit
Fuse in the Maintenance section of this manual.
To start the engine using the recoil starter:
1
Put the engine switch in the ON position.
2
Wait 30 seconds to allow fuel to travel through the
line.
NOTE: The engine will not start until the fuel has
reached the fuel injector and the proper operating
pressure is acheived.
3
Pull the recoil starter grip until the engine runs.
NOTE: Do not allow the grip to snap back after starting;
return it gently to its original place.
STOPPING THE ENGINE
See Figures 13 and 14.
To stop the engine under normal operating conditions:
Remove any load from the generator.
Push in at the bottom of the switch to place the engine
switch in the OFF ( O ) position.
Turn the fuel valve to the OFF ( O ) position.
To stop the engine in an emergency situation:
Push in at the bottom of the switch to place the engine
switch in the OFF ( O ) position.
WARNING:
While operating and storing, keep at least 3 feet of clear-
ance on all sides of this product, including overhead.
Allow a minimum of 30 minutes of “cool down” time
before storage. Heat created by muffler and exhaust
gases could be hot enough to cause serious burns and/
or ignite combustible objects.
OPERATION
MAINTENANCE
Normal maintenance, replacement or repair of emission con-
trol devices and systems may be performed by any qualified
repair establishment or individual with original or equivalent
parts. Warranty and recall repairs must be performed by an
authorized service center; please contact customer service
for assistance.
WARNING:
Before inspecting, cleaning, or servicing the machine,
shut off engine, wait for all moving parts to stop, and
disconnect spark plug wire and move it away from spark
plug. Allow 30 minutes of cool down time before perform-
ing any maintenance. Failure to follow these instructions
can result in serious personal injury or property damage.
WARNING:
When servicing, use only recommended or equivalent
replacement parts. Service or maintenance performed
by unqualified personnel or use of any other parts could
result in a personal injury hazard or property damage.
NOTICE:
Periodically inspect the entire product for damaged,
missing, or loose parts such as screws, nuts, bolts,
caps, etc. Tighten securely all fasteners and caps and
do not operate this product until all missing or damaged
parts are replaced. Please contact customer service or
a qualifed service center for assistance.
16 — English
GENERAL MAINTENANCE
Keep the generator in a clean and dry environment where it
is not exposed to dust, dirt, moisture, or corrosive vapors.
Do not allow the cooling air slots in the generator to become
clogged with foreign material such as leaves, etc.
Do not use a garden hose to clean the generator. Water en-
tering the fuel system or other internal parts of the unit can
cause problems that will decrease the life of the generator.
To clean the unit:
Use a soft bristle brush and/or vacuum cleaner to loosen
and remove dirt and debris.
Clean air vents with low pressure air that does not exceed
25 psi.
Wipe the exterior surfaces of the generator with a damp
cloth.
CHECKING/CLEANING AIR FILTER
See Figure 15.
For proper performance and long life, keep air filter clean.
Turn the knob on the bottom of air the filter cover to re-
lease. Remove cover and set aside.
Remove the filter element.
If the filter element is dirty, clean with warm, soapy water.
Rinse and let dry.
Apply a light coat of engine lubricant to the element, then
squeeze it out.
Replace the element in the air filter unit.
Replace the air filter cover and latch to secure.
NOTE: Do not run the generator without the air filter. Rapid
engine wear will result.
CHANGING ENGINE LUBRICANT
See Figure 16.
Remove the oil cap/dipstick.
Place a container underneath the oil drain plug to collect
used lubricant as it drains.
Unscrew the oil drain plug and remove.
Allow lubricant to drain completely.
NOTE: Drain the lubricant while the engine is still warm
but not hot. Warm lubricant will drain quickly and more
completely.
WARNING:
Do not change engine lubricant while it is hot. Accidental
contact with hot engine lubricant could result in serious burns.
Reinstall the oil drain plug and tighten securely.
Refill with lubricant following the instructions in the Checking/
Adding Lubricant section. For amount of lubricant needed
to refill, see Product Specifications earlier in this manual
or the accompanying engine manual, if applicable.
Reinstall the oil cap/dipstick.
NOTE: Used lubricant should be disposed of at an approved
disposal site. See your local oil retailer for more information.
SPARK PLUG MAINTENANCE
See Figure 17.
The spark plug must be properly gapped and free of deposits
in order to ensure proper engine operation. To check:
Locate and remove four screws on the side of the engine
cover. Remove cover and set aside.
Remove the spark plug cap.
Clean any dirt from around base of spark plug.
Remove spark plug using wrench (not included).
Inspect spark plug for damage, and clean with a wire
brush before reinstalling. If insulator is cracked or
chipped, spark plug should be replaced. For replacement
spark plug, see Product Specifications earlier in this
manual or the accompanying engine manual, if applicable.
Measurepluggap.Thecorrectgapis0.028−0.031in.
(0.7-0.8 mm). To widen gap, if necessary, carefully bend
the ground (top) electrode. To lessen gap, gently tap
ground electrode on a hard surface.
Seat spark plug in position; thread in by hand to prevent
cross-threading.
Tighten with wrench to compress washer. If spark plug
is new, use 1/2 turn to compress washer appropriate
amount. If reusing old spark plug, use 1/8 to 1/4 turn for
proper washer compression.
NOTE: An improperly tightened spark plug will become
very hot and could damage the engine.
Reinstall the spark plug cap.
Reinstall the engine cover. Tighten screws to secure.
CLEANING THE EXHAUST PORT AND
MUFFLER
Depending on the type of fuel used, the type and amount of
lubricant used, and/or your operating conditions, the exhaust
port and muffler may become blocked with carbon deposits.
If you notice a power loss with your gas-powered products,
you may need to remove these deposits to restore perfor-
mance. We highly recommend that only qualified service
technicians perform this service.
SPARK ARRESTOR
See Figure 18.
NOTICE:
This product is equipped with a spark arrestor that has
been evaluated by the USDA Forest Service; however,
product users must comply with Federal, State, and local
fire prevention regulations. Check with appropriate au-
thorities. Contact customer service or a qualified service
center to purchase a replacement spark arrestor.
MAINTENANCE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Ryobi RY907000FI Le manuel du propriétaire

Catégorie
Groupes électrogènes
Taper
Le manuel du propriétaire
Ce manuel convient également à