NAPOLEON GDS28 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone 1 (866) 820-8686 • www.napoleon replaces.com • [email protected]
1.28H
$10.00
LA VITRE CHAUDE CAUSERA
DES BRÛLURES.
NE PAS TOUCHER LA VITRE
AVANT QU’ELLE AIT REFROIDI.
NE JAMAIS LAISSER LES
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
!
AVERTISSEMENT
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this appliance
and shall be installed for the protection of children
and other at-risk individuals.
Une barriére conçu à réduire le risque de brûlures
causées par le verre chaud est fourni avec l’appareil
et sera installé pour la protection des enfants et
d’autres personnes à risque.
SAFETY INFORMATION
!
WARNING
- Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbours phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
re department.
- Installation and service must be performed by a
qualifi ed installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certifi ed kit is used.
If the information in these instructions
are not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
FOR INDOOR USE ONLY
Certified to American National Standards: ANSI Z21.50 and CSA 2.22 for vented decorative gas appliances.
SAFETY BARRIER
EN
FR
PG
49
W415-1426 / B / 12.05.17
GDS28N & GS28N
NATURAL GAS
GDS28P & GS28P
PROPANE
Model GS28 is made up of Model GDS28 and Natural Vent
Adapter Kit GS-150KT
W415-1426 / B / 12.05.17
2
EN
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
table of contents
1.0 installation overview 3
2.0 introduction 4
2.1 dimensions 5
2.2 general instructions 6
2.3 general information 7
2.4 rating plate information 8
3.0 venting 9
3.1 venting lengths and components 9
3.2 typical vent installation 101
3.3 special vent installations 112
3.3.1 periscope termination 112
3.4 vent terminal clearances 123
3.6 venting application flow chart 134
3.5 definitions 134
3.7 elbow vent length values 134
3.8 top exit horizontal termination 145
3.9 top exit vertical termination 167
3.10 vertical through existing chimney 18
4.0 installation 19
4.1 minimum clearances to combustibles 19
4.2 wall and ceiling protection 20
4.2.1 horizontal installation 20
4.2.2 vertical installation 21
4.2.3 horizontal air terminal installation - model
GDS28 21
4.2.4 vertical air terminal installation 22
4.3 appliance vent connection 23
4.4 mobile home installation - model GDS28 23
4.5 gas installation 24
4.6 optional wall switch / remote 24
4.7 natural vent specifics 25
4.7.1 chimney installation 25
4.7.2 installing natural vent 26
4.7.3 natural vent 26
4.7.4 combustion air 27
4.7.5 adding vent sections 27
5.0 finishing 28
5.1 safety screen installation and removal 28
5.2 door closing and opening 29
5.3 log placement 29
5.4 glowing embers 31
5.5 charcoal embers 31
5.6 logo placement 31
6.0 operation 31
6.1 operating/lighting instructions 32
7.0 adjustment 33
7.1 pilot burner adjustment 33
7.2 venturi adjustment 33
7.3 flame characteristics 34
8.0 maintenance 35
8.1 annual maintenance 36
8.2 care of glass 36
8.3 blower replacement 37
9.0 replacements 38
10.0 overview 39
11.0 valve train assembly 40
12.0 accessories 41
13.0 troubleshooting 42
14.0 warranty 45
15.0 service history 46
16.0 notes 47
SAFETY BARRIER
Door, see “DOOR CLOSING /
OPENING” section.
Rating plate, see
“RATING PLATE” section.
Logo, see “LOGO
PLACEMENT” section.
Vent, see “VENTING” section.
W415-1426 / B / 12.05.17
3
EN
1.0 installation overview
W415-1426 / B / 12.05.17
4
EN
2.0 introduction
THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
ANY CHANGES TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND ARE PROHIBITED.
Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to
operating instructions could cause  re or injury.
Risk of  re or asphyxiation do not operate appliance with  xed glass removed.
Do not connect 110 volts to the control valve.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective footwear, gloves and safety glasses during installation. Sheet metal edges may be
sharp.
Do not burn wood or other materials in this appliance.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns
or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is
recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot
surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These
screens and guards must be fastened to the  oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the
appliance.
The appliance is a vented gas- red appliance. Do not burn wood or other materials in the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other  ammable vapors and liquids.
Under no circumstances should this appliance be modi ed.
This appliance must not be connected to a chimney  ue pipe serving a separate solid fuel burning appliance.
Do not use this appliance if any part has been under water. Immediately call a quali ed service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a
licensed or quali ed service person.
Do not strike or slam shut the appliance glass door.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes
containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also
cause the surrounding combustible materials to overheat and catch  re.
Only doors / optional fronts certifi ed with the unit are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic bags, these
are not toys and should be kept away from children and infants.
As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a
Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide.
Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures
on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a T.V. or other electronic
components.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance or sold as a
mandatory option and shall be installed.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before use and
at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of
the appliance be kept clean.
The millivolt version of this appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple
supplied by Wolf Steel Ltd.
3.1G
!
WARNING
W415-1426 / B / 12.05.17
5
EN
2.1 dimensions
GAS LINE ACCESS HOLE LOCATED
IN PEDESTAL BASE
26 3/4"
680mm
22 1/2"
572mm
11 1/4"
286mm
7"
178mm
Ø AIR INTAKE
10"
254mm
12"
305mm
17 3/4"
451mm
18 1/2"
470mm
5 1/2"
127mm
4"
102mm
Ø FLUE
SAFETY
BARRIER
1 3/4"
44mm
W415-1426 / B / 12.05.17
6
EN
2.2 general instructions
4.1C
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER
to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the
commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an
appliance insert or gas log.
The appliance off valve must be a “T” handle gas cock.
The fl exible connector must not be longer than 3 feet (91.4cm).
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA
Z240MH Series, for gas equipped mobile homes, in
Canada or ANSI Z223.1 and NFPA 54 in the United
States.
As long as the required clearance to combustibles is
maintained, the most desirable and benefi cial location for an appliance is in the center of a building, thereby
allowing the most effi cient use of the heat created. The location of windows, doors and the traffi c fl ow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a fl oor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
Institute
®
(NFI) as NFI Gas
Specialists
www.ncertied.org
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
!
WARNING
W415-1426 / B / 12.05.17
7
EN
2.3 general information
GDS28 GS28
NG P NG P
Altitude (FT) 0-4,500 0-4500 0-4500 0-4500
Max. Input (BTU/HR) 30,000 26,000 30,000 26,000
Max. Output (BTU/HR) 25,500 22,360 24,600 21,600
Max. Steady State
Efficiency (w/the fan on)
85% 86% 82% 83%
Max. A.F.U.E. 64% 65%
Min. Inlet Gas Supply
Pressure
4.5" (11mb) Water
Column
11" (27mb)
Water Column
4.5" (11mb) Water
Column
11" (27mb)
Water Column
Max. Inlet Gas Supply
Pressure
7" (17mb)
Water Column
13" (32mb) Water
Column
7" (17mb)
Water Column
13" (32mb) Water
Column
Manifold Pressure
(Under Flow Conditions)
3.5" (9mb)Water
Column
10" (25mb)
Water Column
3.5" (9mb)Water
Column
10" (25mb)
Water Column
When the appliance is installed at elevations above 4,500 ft (1372m), and in the absence of specific recommendations
from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each
additional 1,000 ft (305m).
Change in flame appearance from "HI" to "LO" is more evident in natural gas than in propane.
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance may be installed in an aftermarket permanently located, manufactured mobile home, where not
prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
This appliance is approved for bedroom and bed-sitting room installations.
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
W415-1426 / B / 12.05.17
8
EN
For rating plate location, see “INSTALLATION OVERVIEW” section.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
2.4 rating plate information
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and must be installed.
REVISION: B: UPDATED CSA DATE & DESCRIPTION || 08.16.17_C.L.
DWG#: W385-1998
DATE: 12.11.14
W385-1998 / B
GDS28
GDS28-N
NATURAL GAS MODEL
PAGE 1 OF 2
CONFORMS TO / CONFORME AUX: ANSI Z21.50-2016, CERTIFIED TO / CERTIFIÉ CSA 2.22-2016 VENTED DECORATIVE GAS APPLIANCE / FOYER À GAZ VENTILÉ.
DIRECT VENT GAS FIREPLACE APPROVED FOR BEDROOM, BATHROOM & BEDSITTING ROOM
INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED
STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280.
WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR
MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. FOR USE ONLY WITH
BARRIER W565-0195. FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
FOYER À GAZ VENTILÉS À ÉVACUATION DIRECTE. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER,
UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION
CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES EQUIPÉES AU GAZ, EN
VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA NORME DE SÉCURITÉ ET DE CONSTRUCTION DE MAISONS
MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT PAS ÊTRE
APPLIQUÉE, SE RÉFÉRER À LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR
LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A. POUR
UNE UTILISATION SEULEMENT AVEC BARRIÈRE W565-0195. SUIVEZ LES INSTRUCTIONS D'INSTALLATION DANS LE
MANUEL D'INSTALLATION.
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
PRESSION AU COLLECTEUR: 3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
COLONNE D'EAU (GN)
MAX. SUPPLY PRESSURE: 7" W.C. (NG)
PRESSION D'ALIMENTATION MAX: 7" D'UNE
COLONNE D'EAU (GN)
MANIFOLD PRESSURE: 10 INCHES W.C.(LP)
PRESSION AU COLLECTEUR: 10" D'UNE
COLONNE D'EAU (P)
MIN SUPPLY PRESSURE: 11" W.C. (LP)
PRESSION D'ALIMENTATION MIN: 11" D'UNE
COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE: 13" W.C. (LP)
PRESSION D'ALIMENTATION MAX: 13" D'UNE
COLONNE D'EAU (P)
SERIAL NUMBER / NO. DESERIE
WOLF STEEL LTD.
CDVS280-N
GDS28-P
CDVS280-P
PROPANE MODEL
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
9700539 (WSL) 4001657 (NGZ)
4001658 (NAC) 4001659 (WUSA)
UTILISER AVEC LES PORTES VITRÉES HOMOLOGUÉES SEULEMENT AVEC
CETTE APPAREIL.
AVERTISSEMENT: N'AJOUTEZ PAS À CET APPAREIL AUCUN MATÉRIAU
DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI
EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPAREIL DE CHAUFFAGE
*LES CONDITIONS DE BAISSE D’ÉVALUATION SELON L’ALTITUDE
S’APPLIQUENT AU CANADA SEULEMENT
ALTITUDE / ÉLÉVATION
(0-1370m)
30,000 BTU/h *INPUT / ALIMENTATION*
18,000 BTU/h REDUCED INPUT / ALIMENTATION REDUITE
25,500 BTU/h OUTPUT(MODEL GDS28) RENDEMENT
24,600 BTU/h OUTPUT(MODEL GS28) RENDEMENT
GS28-N
CS280-N
GS28-P
CS280-P
0-4500FT 0-4500FT
26,000 BTU/h
15,000 BTU/h
22,360 BTU/h
21,600 BTU/h
(0-1370m)
*ALTITUDE DOWNRATING CONDITIONS APPLY
TO CANADA ONLY /
P4 (NG/LP) / (GN/PL): 57.4%
57.4%
FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO THE APPLIANCE,
WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER THAN
THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL /
DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES:
A 7" D 17½"
B 2" E 6¼"
C 1" F 9½"
20" TO CEILING FROM STOVE TOP
20" ENTRE LE DESSUS DU FOYER ET LE PLAFOND
ELECTRICAL RATING / CLASS.: 115V 1.5AMP 60HZ
NOT FOR USE WITH SOLID FUEL
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE
UTILISÉ AVEC CET APPAREIL
MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 25 INCHES AND 20 FEET RESPECTIVELY.
LES LONGUEURS HORIZONTALES MINIMALE ET MAXIMALE SONT 25 POUCES ET 20 PIEDS RESPECTIVEMENT.
B-VENT MODELS GS28/CS280
APPROVED FOR BEDROOM, & BEDSITTING ROOM INSTALLATION.
THIS APPLIANCE MUST BE VENTED USING THE APPROPIATE
NAPOLEON VENT KIT. SEE OWNERS INSTALLATION MANUAL FOR
VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS
NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.
MATERIAL: CLASS III A-2, PERMANENT LABEL, .010 VELVET MATTE LEXAN AND/OR .050 HI-TEMP POLYESTER, WATERPROOF,
NON-WATER SOLUBLE ADHESIVE, CAPABLE OF WITHSTANDING A MAXIMUM TEMPERATURE OF 175° F (79° C).
MIN LETTERING FOR "NOT FOR USE WITH SOLID FUEL", "UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CELUI" TO BE
10 POINT ARIAL, BOLD FACE, UPPER CASE OR EQUIVALENT AND 2 POINT LEADING SPACING
BLACK LETTERING ON WHITE BACKGROUND
MAX OVERALL DECAL SIZE: 8.5" x 4.75"
SERIAL NUMBERS TO BE ASCENDING FROM GDS28
TITLE: RATING PLATE LABEL GDS28 / CDVS280
B-VENT MODELS GS28/CS280
HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER ET UN STUDIO.
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE
À NAPOLÉON. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR
L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BEIN RÉINSTALLER ET RESCELLER
L'EVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU SYSTÈME DE PRISE D'AIR.
DIRECT VENT MODEL
‘B’ VENT MODEL
THIS APPLIANCE MUST BE INSTALLED USING AN ADAPTER KIT GS-150KT. CET APPAREIL DOIT
ÊTRE INSTALLÉ EN UTILISANT UN ENSEMBLE ADAPTATEUR GS-150KT.
035149
B
SAMPLE
W415-1426 / B / 12.05.17
9
EN
3.0 venting
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between
two single family dwellings and serves both dwellings. Local codes or regulations may require different
clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled
tight. A 1-1/4" (25.4mm - 6.4mm) air gap all around between the inner liner and outer appliance pipe is
required for safe operation. Use a firestop when penetrating interior walls, floor or ceiling.
7.1F
THIS APPLIANCE USES A 4” (102mm) EXHAUST / 7” (178mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme
vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a
requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl
spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide
a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor
paint suitable for 400°F (204°C). Application and performance of paint is the consumer’s responsibility. Spot
testing is recommended.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0370 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
W415-1426 / B / 12.05.17
10
EN
3.1 venting lengths and components
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal
locations for either system are set out in this manual and must be adhered to. For Simpson Dura-Vent, Selkirk
Direct Temp, American Metal Amerivent and Metal-Fab follow the installation procedure provided with the venting
components.
A starter adaptor must be used with the following vent systems and may be purchased from the corresponding
supplier:
* For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab follow the
installation procedure found on the website for your venting supplier.
For vent systems that provide seals on the inner exhaust  ue, only the outer air intake joints must be sealed using a
red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake vent
pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance  ue collar
which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel termination kits: wall terminal kit GD175
(7/12’ of venting included), or 1/12 to 7/12 pitch roof terminal kit GD110, 8/12 to 12/12 roof terminal kit GD111,  at
roof terminal kit GD112 or periscope kit GD180 (for wall penetration below grade) in conjunction with the appropriate
venting components.
For optimum fl ame appearance and appliance operation, keep the vent length and number of elbows to a
minimum. It is recommended that all horizontal runs have a minimum 1/4” (6.4mm) rise per foot /meter. The
air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged. Rigid and exible venting systems must not be combined. Different
venting manufacturers components must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6m). The maximum allowable vertical vent length is 40 feet (12m). The maximum number of vent
connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when
using exible venting.
Deviation from the minimum vertical vent length can create diffi culty in burner start-up and/or carboning.
Use an adjustable pipe as the fi nal length of rigid piping to the stove for ease of installation.
VENT
MANUFACTURER
STARTER ADAPTER
PART NUMBER
SUPPLIER WEBSITE
Duravent GDS924N Wolf Steel www.duravent.com
Amerivent 4DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 4DT-AAN Selkirk www.selkirkcorp.com
SuperSeal 4DNA Metal-Fab www.mtlfab.com
8.5B
W415-1426 / B / 12.05.17
11
EN
3.2 typical vent installation
29" (73.7cm)
Minimum
16" (40.6cm)
Minimum
Use the periscope kit to locate the air termination above grade. The periscope must
be installed so that when fi nal grading is completed, the bottom air slot is located a
minimum 12” (30.5cm) above grade. The maximum allowable vent length is 10’ (3m)
for a fi replace and 8’ (2m) for a stove.
9.1B
Utilisez l’ensemble périscopique afi n de positionner la terminaison au-dessus
du niveau du sol. L’ensemble périscopique doit être installé de façon à ce que la
fente d’air du bas soit située à un minimum de 12 pouces (30,5cm)
au-dessus du niveau du sol. La longueur maximale permise de
l’évent est 10 pieds (3,1m) pour un foyer et 8 pieds (2,4m) pour
un poêle.
9.1B
3.3 special vent installations
29" (73.7CM)
MINIMUM
12" (30.5CM)
MIN. TO
GRADE
26 3/4" (68cm)
3.3.1 periscope termination
55 3/4" (141.6cm)
Minimum plus rise*
34" (86.4cm)
Maximum
40 ft (12m)
Maximum
3 ft (1m)
Minimum
W415-1426 / B / 12.05.17
12
EN
3.4 vent terminal clearances
12.1F
NOTE: Clearances are to be in accordance with local installation codes and the requirements of the gas supplier. In their
absence, clearances are to be as listed above and are based on national codes.
COVERED BALCONY APPLICATIONS ††*
Q
MIN
R
MAX
MAX
R
= 3 feet
(0.9m)
= 2 x
≤ 15 feet
(4.6m)
Q
ACTUAL
R
Q
S
G
P
INSTALLATIONS
CANADA U.S.A.
A
12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony.
B
12” (30.5cm)
Δ
9” (229mm) Clearance to windows or doors that open.
C
12” (30.5cm)* 12” (30.5cm) * Clearance to permanently closed windows.
D
18”
(45.7cm)**
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
E
12” (30.5cm)** 12” (30.5cm)** Clearance to unventilated soffi t.
F
0” (0mm) 0” (0mm) Clearance to an outside corner wall.
G
0” (0mm)*** 0” (0mm)***
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” (51mm)*** 2” (51mm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H
3’(0.9m) 3’(0.9m)****
Clearance to each side of the center line extended above the meter / regulator assembly to a maxi-
mum vertical distance of 15’ (4.6m).
I
3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J
12” (30.5cm) 9” (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K
6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
L
7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
N
16” (40.6cm) 16” (40.6cm) Clearance above the roof.
O
2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
P
8’ (2.4m) 8’ (2.4m)
Roof must be non-combustible without openings.
Q
3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R
6’ (1.8m) 6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
S
12” (30.5cm) 12” (30.5cm) Clearance under a covered balcony
Δ The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
NOTE: Wall terminals are for illustration purposes only. Size and shapes may vary.
W415-1426 / B / 12.05.17
13
EN
3.5 vent flow charts
14.1
For the following symbols used in the venting calculations and examples are:
> - greater than
>
- equal to or greater than
< - less than
<
- equal to or less than
H
T
- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
H
R
- combined horizontal vent lengths in feet
H
O
- offset factor: .03 (total degrees of offset - 90°*) in feet
V
T
- combined vertical vent lengths in feet
13.1A
TOP EXIT
Horizontal Termination
Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
Horizontal run +
vertical rise to
Horizontal run +
vertical rise to
4.2 times the
vertical rise equal to
or greater than the
horizontal run
3 times the vertical
rise equal to or
greater than the
horizontal run
maximum of 40 feet
(12m)
maximum of 40 feet
(12m)
3.6 definitions
15.1A
FEET INCHES MILLIMETERS
0.03 0.5 12.7
15° 0.45 6.0 152.4
30° 0.9 11.0 279.4
45° 1.35 16.0 406.4
90°* 2.7 32.0 812.8
* The fi rst 90° offset has a zero value and is shown in the formula as - 90°
3.7 elbow vent lengths
W415-1426 / B / 12.05.17
14
EN
16.10A
Simple venting confi guration (only one 90° elbow)
0
2.5
(0.8)
5
(1.5)
7.5
(2.3)
10
(3.1)
12.5
(3.8)
15
(5.6)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
17.5
(5.3)
20
(6.1)
39 (11.9)
REQUIRED
VERTICAL RISE
IN FEET
(METERS)V
T
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) H
T
90°
90°
90°
V
1
V
2
H
1
H
2
(H
T
) < (V
T
)
For vent confi gurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
Example:
V
1
= 3 FT (0.9m)
V
2
= 8 FT (2.4m)
V
T
= V
1
+ V
2
= 3 FT (0.9m) + 8 FT (2.4m) = 11 FT (3.4m)
H
1
= 2.5 FT (0.8m)
H
2
= 2 FT (0.6m)
H
R
= H
1
+ H
2
= 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m)
H
O
= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m)
H
T
= H
R
+ H
O
= 4.5 FT (1.4m) + 5.4 FT (1.7m) = 9.9 FT (3m)
H
T
+ V
T
= 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
Formula 1: H
T
< V
T
9.9FT (3m) < 11 FT (3.4m)
Formula 2: H
T
+ V
T
< 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m)
Since both formulas are met, this vent con guration is acceptable.
See graph to determine the required vertical
rise V
T
for the required horizontal run H
T
.
The shaded area within the lines represents
acceptable values for H
T
and V
T
90°
90°
90°
V
1
V
2
H
1
H
2
3.8 horizontal termination
W415-1426 / B / 12.05.17
15
EN
(H
T
) > (V
T
)
Simple venting configuration (only one 90° elbow)
See graph to determine the required vertical rise V
T
for
the required horizontal run H
T
.
REQUIRED
VERTICAL RISE
IN INCHES
(MILLIMETERS) V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
T
The shaded area within the lines represents acceptable
values for H
T
and V
T
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H
T
< 4.2 V
T
Formula 2: H
T
+ V
T
< 24.75 feet (7.5m)
Example:
V
1
= V
T
= 6FT (1.8m)
H
1
= 3 FT (0.9m)
H
2
= 5 FT (1.5m)
H
R
= H
1
+ H
2
= 3FT (0.9m)+ 5FT (1.5m) = 8FT (2.4m)
H
O
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7FT (0.8m)
H
T
= H
R
+ H
O
= 8FT (2.4m)+ 2.7FT (0.8m) = 10.7FT (3.3m)
H
T
+ V
T
= 10.7FT (3.3m) + 6 FT (1.8m) = 16.7FT (5.1m)
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2FT (1.3m) x 6FT (1.8m) = 25.2 FT (7.7m)
Formula 2: H
T
+ V
T
< 24.75 FT (7.5m)
16.7 FT (5.1m) < 24.75 (7.5m)
Since both formulas are met, this vent configuration is acceptable.
90°
V
1
H
1
H
2
90°
Example:
V
1
= 4 FT (1.2m)
V
2
= 1.5 FT (0.5m)
V
T
= V
1
+ V
2
= 4 FT (1.2m) + 1.5 FT (0.5m)= 5.5 FT (1.7m)
H
1
= 2 FT (0.6m)
H
2
= 1 FT (0.3m)
H
3
= 1 FT (0.3m)
H
4
= 1.5 FT (0.5m)
H
R
= H
1
+ H
2
+ H
3
+ H
4
= 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5FT (1.7m)
H
O
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1FT (2.5m)
H
T
= H
R
+ H
O
= 5.5FT (1.7m) + 8.1FT (2.5m) = 13.6FT (4.2m)
H
T
+ V
T
= 13.6FT (4.2m) + 5.5FT (1.7m) = 19.1FT (5.8m)
Formula 1: H
T
< 4.2 V
T
4.2 V
T
= 4.2FT (1.3m) x 5.5FT (1.7m) = 23.1FT (7m)
13.6FT (4.2m) < 23.1FT (7m)
Formula 2: H
T
+ V
T
< 24.75 FT (7.5m)
19.1FT (5.8m) < 24.75 (7.5m)
Since both formulas are met, this vent configuration is acceptable.
90°
90°
90°
90°
H
1
H
2
V
1
V
2
H
3
H
4
0
5
(1.5)
15
(4.6)
20 (6.1)
100 (2540)
50 (1270)
150 (3810)
12.5
(3.8)
29 (736.6)
57 (1447.8)
147 (3733.8)
2.8
(0.9)
10
(3.1)
19.5
(5.9)
16.1_3B
W415-1426 / B / 12.05.17
16
EN
3.9 top exit vertical termination
(H
T
) < (V
T
)
Simple venting configurations.
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED
VERTICAL
RISE IN FEET
(METERS) V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
T
For vent configurations requiring one or more 90° elbows the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
Example:
V
1
= 5 FT (1.5m)
V
2
= 6 FT (1.8m)
V
3
= 10 FT (3.1m)
V
T
= V
1
+ V
2
+ V
3
= 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21FT (6.4m)
H
1
= 8 FT (2.4m)
H
2
= 2.5 FT (0.8m)
H
R
= H
1
+ H
2
= 8FT (2.4m) + 2.5FT (0.8m) = 10.5 FT (3.2m)
H
O
= .03 (four 90° elbows - 90°)
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
T
= H
R
+ H
O
= 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)
H
T
+ V
T
= 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)
Formula 1: H
T
< V
T
18.6FT (5.7m) < 21FT (6.4m)
Formula 2: H
T
+ V
T
< 40 FT (12.19m)
39.6FT (12.1m) < 40FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
90°
V
1
V
2
H
1
H
2
The shaded area within the lines represents acceptable
values for H
T
and V
T
90°
90°
90°
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
3 (0.9)
V
3
18.1A
W415-1426 / B / 12.05.17
17
EN
(H
T
) > (V
T
)
Simple venting configurations.
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED
VERTICAL
RISE IN FEET
(METERS) V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
T
For vent configurations requiring more than two 90° elbows the following formulas apply:
Formula 1: H
T
< 3V
T
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
Example:
V
1
= 2 FT (0.6m)
V
2
= 1 FT (0.3m)
V
3
= 1.5 FT (0.5m)
V
T
= V
1
+V
2
+V
3
= 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5FT (1.4m)
H
1
= 6 FT (1.8m)
H
2
= 2 FT (0.6m)
H
R
= H
1
+ H
2
= 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
H
O
= .03 (four 90° elbows - 90°)
= .03 (360° - 90°) = 8.1 FT (2.5m)
H
T
= H
R
+ H
O
= 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
H
T
+ V
T
= 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6 FT (6.3m)
Formula 1: H
T
< 3V
T
3V
T
= 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)
16.1FT (4.9m) > 13.5FT (4.1m)
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
20.6FT (6.3m) < 40 (12.2m)
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration
will need to be established to satisfy both formulas.
The shaded area within the lines represents acceptable
values for H
T
and V
T
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
10 (3.1)
20 (6.1)
3 (0.9)
25
(7.6)
30
(9.1)
19 (5.8)
90°
V
1
V
2
H
1
H
2
90°
90°
90°
V
3
18.1_2B
W415-1426 / B / 12.05.17
18
EN
3.10 vertical through existing chimney
7.6B
This appliance is designed to be attached to a 3” (76.2mm) co-linear aluminum fl ex vent system running the
full length of a masonry chimney.
The fl ex liners accommodate any contours of a
masonry chimney, however, it is necessary to keep
the fl exible liners as straight as possible. The inlet air
collar of the termination cap must be connected to
the air intake fl ex liner and the exhaust collar must be
connected to the exhaust fl exible liner.
Both Simpson Duravent and Selkirk co-linear to
co-axial adaptors have been approved on this
appliance
(
NOTE: A vent adaptor will be required directly off
the appliance
).
Follow vent manufacturer’s installation instructions.
Different manufacturer’s venting components
must not be combined. Once the preferred
manufacturer’s appliance adaptor has been
attached, the remainder of the system must
be that of the same manufacturer.
The only exception to this rule is to use Wolf
Steel’s approved 3” (76.2mm) fl ex liner and
co-linear termination.
!
WARNING
RISK OF FIRE!
CO-AXIAL TO CO-LINEAR VENTING CONFIGURATIONS MUST ONLY BE USED IN A
NON-COMBUSTIBLE CHIMNEY OR ENCLOSURE. INSTALLATION IN A COMBUSTIBLE ENCLOSURE
COULD RESULT IN A FIRE.
AIR
INTAKE
EXHAUST
FLUE
FLEX
LINER
* 40 FT (12.2m)
MAX.
10 FT (3.1m)
MIN
COAXIAL TO
CO-LINEAR
ADAPATOR
APPLIANCE
VENT ADAPTOR
TERMINATION
* Measured from appliance fl ue collar to
termination fl ue collar
W415-1426 / B / 12.05.17
19
EN
4.0 installation
4.1 minimum clearances to combustibles
Back Wall
Side Wall
Back Wall
Side Wall
Alcove
A
A
A
B
B
C
D
E
F
45°
Back Wall
Side Wall
A
7" (178mm)
D
14 3/4" (375mm)
B
2" (51mm)
E
4" (102mm)
C
1" (25mm) *
F
9 1/2" (241mm)
- A minimum 20" (508mm) from appliance top to ceiling.
- A minimum 1" (25mm) clearance to combustibles from bottom and sides of vent pipe.
* At a distance of 1" (25mm) from the wall, access to the blower switch, on/off switch or the blower power cord
may not be practical.
GDS28:
HORIZONTAL VENT SECTIONS: A minimum clearance of 2" (51mm) at the top and 1" (25mm) at the bottom
and sides of the vent pipe on all horizontal runs is required.
VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required.
GS28:
A minimum of 1" (25mm) all around the B vent pipe on both horizontal and vertical runs to combustibles is
required.
!
WARNING
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE, ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL EXHAUST AND INTAKE VENT PIPE JOINTS MUST BE SEALED USING RED RTV HIGH TEMP
SILICONE SEALANT (W573-0002) (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC (W573-0007)
(NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR WHICH MUST
BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, A MINIMUM OF 3 SCREWS MUST ALSO
BE USED TO ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2D
W415-1426 / B / 12.05.17
20
EN
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal location, cut
and frame a hole in the exterior wall as illustrated to accommodate
the  restop assembly. Dry  t the  restop assembly before
proceeding to ensure the brackets on the rear surface  t to
the inside surface of the horizontal framing.
The length of the vent shield may be cut shorter
for combustible walls that are less than 8 1/2”
(215.9mm) thick but the vent shield must extend the
full depth of the combustible wall.
A. Assemble the shield to the spacer as
shown, using 3 screws.
B. Place the  restop top so that the vent shield
covers the top of the vent within the opening.
Ensure that both spacer and shield maintain the required
clearance to combustibles.
C. Secure the spacer in place using 4 screws. Once the
vent pipe is installed in its  nal position, apply sealant
between the pipe and the  restop spacer.
DETERMINE
THE
CORRECT
HEIGHT
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
FINISHING
MATERIAL
CAULKING
20.5D
!
WARNING
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
ADD FASTENER TYPE
NOTE: The above is for illustration
purposes only. Vents do not always
pass through center of frame.
ADD
HEIGHT
ADD
WIDTH
4.2 wall and ceiling protection
For optimum performance, it is recommended that all horizontal runs have a minimum 1/4" (6.4mm) rise per foot
when venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
!
WARNING
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
70.1
4.2.1 horizontal installation
10 11/16"
(27.1cm)
10 11/16"
(27.1cm)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

NAPOLEON GDS28 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire

dans d''autres langues