NAPOLEON LV50N2-1 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire
FRENCH
PG. 73
W415-1709 / B / 01.31.18
ADD MANUAL TITLE
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030
Phone 1 (866) 820-8686 • www.napoleonfi replaces.com • hearth@napoleonproducts.com
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES
INSTALLER:
Leave this manual with the appliance
CONSUMER:
Retain this manual for future reference
ADD PRODUCT CODE HERE (TRADE GOTHIC LT STD FONT)
NATURAL GAS MODELS:
PROPANE GAS MODELS:
PRODUCT NAME™
ADD ____ ILLUSTRATED
ADD PRODUCT IMAGE
CSA /
INTERTEK
LOGO
SAFETY INFORMATION
- Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of
this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbour’s phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier, call
the fi re department.
- Installation and service must be
performed by a qualifi ed installer, service
agency, or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certifi ed kit is used.
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death, or
property damage.
WARNING
!
ENGLISH
$10.00
FOR INDOOR USE ONLY
INSTALLATION MANUAL
LV38N-1 / LV50N-2 / LV62N / LV74N / LV38N2-1 / LV50N2-2 / LV62N2 / LV74N2
LV38P-1 / LV50P-2 / LV62P / LV38P2-1 / LV50P2-2 / LV62P2
Vector™ Series
(LV38-1 illustrated)
SAFETY BARRIER
ÉCRAN DE PROTECTION
THIS APPLIANCE IS SUITABLE FOR THE OPTIONAL DYNAMIC
HEAT CONTROL™ SYSTEM
(See Dynamic Heat Control™ installation manual)
PLACE BARCODE LABEL ON THE
OWNER’S MANUAL
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS:
CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES
FOR INDOOR USE ONLY
HEAT CONTROL
TM
PATENT PENDING
W415-1709 / B / 01.31.18
EN
2
safety information
This appliance is hot when operated and
can cause severe burns if contacted.
Any changes or alterations to this
appliance or its controls can be
dangerous and is prohibited.
Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
Ensure the glass door is opened or removed
when lighting the pilot for the fi rst time and
when the gas supply has run out.
Risk of fi re or asphyxiation do not operate
appliance with fi xed glass removed and never
obstruct the front opening of the appliance.
Objects placed in front of the appliance must
be kept a minimum of 4 feet (1.22m) from the
front face of the appliance.
Do not connect 110 volts to the control valve,
with the exception of models; GSST8 and GT8.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing
and operating the appliance. Never obstruct the front opening of the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other
ammable vapors and liquids.
High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at
test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 psig (35mb).
The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance
to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42; these
appliances are suitable for 0°F / -18°C.
Children and adults should be alerted to hazards of high surface temperature and should stay
away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from
furniture and draperies.
Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot
surfaces.
Even after the appliance is off, it will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior
to operating the appliance.
It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and
free from combustible materials, gasoline and other fl ammable vapors and liquids.
If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it
serviced. Keep burner and control compartment clean.
Under no circumstances should this appliance be modifi ed.
LA VITRE CHAUDE CAUSERA
DES BRÛLURES.
NE PAS TOUCHER LA VITRE
AVANT QU’ELLE AIT REFROIDI.
NE JAMAIS LAISSER LES
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
!
AVERTISSEMENT
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
Une barriére conçu à réduire le risque de brûlures
causées par le verre chaud est fourni avec l’appareil et
sera installé pour la protection des enfants et d’autres
personnes à risque.
3.1
!
WARNING
!
WARNING
Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner fl ame
patterns.
Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this
appliance.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person, if equipped.
Do not strike or slam shut the appliance glass door, if equipped.
Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants.
Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have
it serviced by a qualifi ed technician before operating it again.
If equipped, the screen must be in place (closed) when the appliance is in operation.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating
to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of
the exhaust escaping through these openings can also cause the surrounding combustible materials to
overheat and catch fi re.
Carbon monoxide poisoning may lead to death; early signs of carbon monoxide poisoning resemble
the fl u, with headache, dizziness and/or nausea. If you have these signs, the heater may not be working
properly. Get fresh air at once! Have heater serviced. Some people; pregnant women, persons with heart
or lung disease, anemia, those under the infl uence of alcohol, those at high altitudes are more affected by
carbon monoxide than others. Failure to keep the primary air opening(s) of the burner(s) clean may result
in sooting and property damage.
As with any combustion appliance, we recommend having your appliance regularly inspected and
serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and
your family against Carbon Monoxide.(Not applicable for outdoor appliances).
Ensure clearances to combustibles are maintained when building a mantel or shelves above the
appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting,
discolouration or damage to decorations, a T.V. or other electronic components.
For appliances equipped with a safety barrier; the barrier is designed to reduce the risk of
burns from the hot viewing glass is provided with this appliance and shall be installed. If the
barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be
inspected before use and at least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners and circulating air passageways of the
appliance be kept clean.
For outdoor products only: this appliance must not be installed indoors or within any structure that
prevents or inhibits the exhaust gases from dissipating in the outside atmosphere.
If applicable, the millivolt version of this appliance uses and requires a fast acting thermocouple. Replace
only with a fast acting thermocouple supplied by Wolf Steel Ltd.
EN
W415-1709 / B / 01.31.18
3
safety information
This appliance is hot when operated and
can cause severe burns if contacted.
Any changes or alterations to this
appliance or its controls can be
dangerous and is prohibited.
Do not operate appliance before reading and
understanding operating instructions. Failure
to operate appliance according to operating
instructions could cause fi re or injury.
Ensure the glass door is opened or removed
when lighting the pilot for the fi rst time and
when the gas supply has run out.
Risk of fi re or asphyxiation do not operate
appliance with fi xed glass removed and never
obstruct the front opening of the appliance.
Objects placed in front of the appliance must
be kept a minimum of 4 feet (1.22m) from the
front face of the appliance.
Do not connect 110 volts to the control valve,
with the exception of models; GSST8 and GT8.
Risk of burns. The appliance should be turned off and cooled before servicing.
Do not install damaged, incomplete or substitute components.
Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during
installation. Sheet metal edges may be sharp.
Do not burn wood or other materials in this appliance.
Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing
and operating the appliance. Never obstruct the front opening of the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline and other
ammable vapors and liquids.
High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at
test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 psig (35mb).
The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance
to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42; these
appliances are suitable for 0°F / -18°C.
Children and adults should be alerted to hazards of high surface temperature and should stay
away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the
appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk individuals in the house. To
restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable material should not be placed on or near the appliance.
Due to high temperatures, the appliance should be located out of traffi c and away from
furniture and draperies.
Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.
Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot
surfaces.
Even after the appliance is off, it will remain hot for an extended period of time.
Check with your local hearth specialty dealer for safety screens and hearth guards to protect children
from hot surfaces. These screens and guards must be fastened to the fl oor.
Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior
to operating the appliance.
It is imperative that the control compartments, burners and circulating blower and its passageway in the
appliance and venting system are kept clean. The appliance and its venting system should be inspected
before use and at least annually by a qualifi ed service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and
free from combustible materials, gasoline and other fl ammable vapors and liquids.
If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it
serviced. Keep burner and control compartment clean.
Under no circumstances should this appliance be modifi ed.
LA VITRE CHAUDE CAUSERA
DES BRÛLURES.
NE PAS TOUCHER LA VITRE
AVANT QU’ELLE AIT REFROIDI.
NE JAMAIS LAISSER LES
ENFANTS TOUCHER LA VITRE.
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
DANGER
!
AVERTISSEMENT
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals.
Une barriére conçu à réduire le risque de brûlures
causées par le verre chaud est fourni avec l’appareil et
sera installé pour la protection des enfants et d’autres
personnes à risque.
3.1
!
WARNING
!
WARNING
Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner fl ame
patterns.
Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this
appliance.
This appliance must not be connected to a chimney fl ue pipe serving a separate solid fuel burning
appliance.
Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician
to inspect the appliance and to replace any part of the control system and any gas control which has
been under water.
Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualifi ed service person, if equipped.
Do not strike or slam shut the appliance glass door, if equipped.
Only doors / optional fronts certifi ed with the appliance are to be installed on the appliance.
Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants.
Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have
it serviced by a qualifi ed technician before operating it again.
If equipped, the screen must be in place (closed) when the appliance is in operation.
When equipped with pressure relief doors, they must be kept closed while the appliance is operating
to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of
the exhaust escaping through these openings can also cause the surrounding combustible materials to
overheat and catch fi re.
Carbon monoxide poisoning may lead to death; early signs of carbon monoxide poisoning resemble
the fl u, with headache, dizziness and/or nausea. If you have these signs, the heater may not be working
properly. Get fresh air at once! Have heater serviced. Some people; pregnant women, persons with heart
or lung disease, anemia, those under the infl uence of alcohol, those at high altitudes are more affected by
carbon monoxide than others. Failure to keep the primary air opening(s) of the burner(s) clean may result
in sooting and property damage.
As with any combustion appliance, we recommend having your appliance regularly inspected and
serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and
your family against Carbon Monoxide.(Not applicable for outdoor appliances).
Ensure clearances to combustibles are maintained when building a mantel or shelves above the
appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting,
discolouration or damage to decorations, a T.V. or other electronic components.
For appliances equipped with a safety barrier; the barrier is designed to reduce the risk of
burns from the hot viewing glass is provided with this appliance and shall be installed. If the
barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
Installation and repair should be done by a qualifi ed service person. The appliance should be
inspected before use and at least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting, bedding material, etc. It
is imperative that control compartments, burners and circulating air passageways of the
appliance be kept clean.
For outdoor products only: this appliance must not be installed indoors or within any structure that
prevents or inhibits the exhaust gases from dissipating in the outside atmosphere.
If applicable, the millivolt version of this appliance uses and requires a fast acting thermocouple. Replace
only with a fast acting thermocouple supplied by Wolf Steel Ltd.
W415-1709 / B / 01.31.18
EN
4
table of contents
1.0 general information 5
1.1 rates and efficiencies 6
1.2 installation overview 7
1.3 rating plate/lighting instruction
location 9
1.4 mobile home installation 10
1.5 hardware list 10
1.6 lifting handles installation/removal 10
2.0 dimensions 11
2.1 single-sided 11
2.2 see-thru 12
3.0 minimum venting requirements 13
3.1 typical venting installation 15
3.2 minimum air terminal location
clearances 17
3.3 horizontal termination 18
3.4 vertical termination 21
4.0 rough framing - before appliance
installation 22
4.1 minimum framing dimensions 23
4.1.1 minimum clearance to combustible
enclosures 24
5.0 venting installation 27
5.1 firestop spacer assembly 27
5.2 horizontal installation 29
5.3 vertical installation 29
5.4 using flexible vent components 30
5.4.1 horizontal air terminal installation 30
5.4.2 vertical air terminal installation 31
5.4.3 appliance vent connection 31
5.5 restricting vertical vents 32
5.5.1 LV38-1 / LV50-2 32
5.5.2 LV62 / LV74 32
5.6 vent shield installation 33
6.0 electrical information 34
6.1 hard wiring connection 34
6.2 receptacle wiring diagram 34
6.3 in the event of a power failure 34
6.4 battery holder/switch installation 35
6.5 initializing the battery holder/switch
for the first time 35
6.6 access panel 36
6.7 wiring diagram 37
6.8 eFIRE application controller 37
6.8.1 LV38-1/50-2 wiring diagram 38
6.8.2 LV62/74 wiring diagram 39
7.0 gas installation 40
8.0 operation 41
9.0 nailing tab installation 42
10.0 finish framing - after appliance
installation 43
10.1 framing with non-combustibles 43
11.0 finishing 47
11.1 fastener placement restriction 47
11.2 finishing with non-combustibles 48
11.3 installing non-combustible board 50
11.4 minimum combustible mantel
clearances 51
11.5 TV mounting restrictions 52
11.6 safety barrier installation / removal 53
11.7 anti condensation switch 53
11.8 firebox glass door installation /
removal 53
11.9 glass media installation / removal 55
11.10 optional media placement 56
11.11 media tray removal 56
12.0 adjustments 57
12.1 restricting vertical vents 57
12.2 venturi adjustment 57
12.3 pilot burner adjustment 58
12.4 flame characteristics 58
13.0 maintenance 59
13.1 annual maintenance 60
13.2 control access 60
13.3 burner removal 61
13.4 valve removal 61
13.5 control module removal 62
13.6 LED replacement 63
13.7 glass / door replacement 64
13.8 care of glass 64
13.9 care of plated parts 64
14.0 replacements 65
14.1 overview 66
14.2 burner components 67
15.0 troubleshooting 69
The information throughout this manual is believed to be correct at the time of printing. Wolf Steel
Ltd. reserves the right to change or modify any information within this manual at any time without
notice. Changes, other than editorial are denoted by a vertical line in the margin.
note:
EN
W415-1709 / B / 01.31.18
5
general information
Installer: please fill out appliance checklist in the
owner’s manual.
When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specific recommendations
from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each
additional 1,000ft (305m). Expansion / contraction noises during heating up and cooling down cycles are normal
and are to be expected. Change in flame appearance from “HI” to “LO” is more evident in natural gas than in
propane.
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certified for mobile
home installation.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
There is a switch that controls the function of the appliance. The battery holder/switch must be placed in the
middle position. If the switch is not placed in the middle position, the appliance will not work.
The protective wrap on plated parts is best removed when the assembly is at room temperature but this can
be improved if the assembly is warmed, using a hair dryer or similar heat source. The protective wrap must be
removed before operating the appliance.
This appliance is a decorative product. It is not a source of heat and not intended to burn solid fuel.
This appliance is equipped with a remote control and a wall switch, which requires batteries to be installed. The
remote takes 3 “AAA” batteries and the wall switch takes 4 “AA” batteries.
This appliance is suitable for use with Napoleon’s optional Dynamic Heat Control™ & Dynamic Heat Control™ Plus
systems. THIS MANUAL DOES NOT include detailed information relating to these optional systems. Framing and finishing
are NOT the same. For further details, refer to the Dynamic Heat Control™ installation manual provided with the kit before
starting installation.
note:
Batteries must be disposed of according to the local laws and regulations. Some batteries may be
recycled, and may be accepted for disposal at your local recycling center. Check with your
municipality for recycling instructions.
Les piles doivent être mises au rebut conformément aux lois et à la réglementation locales.
Certaines piles peuvent être recyclées et acceptées dans votre centre de recyclage local. Rensei-
gnez-vous auprès de votre municipalité au sujet des directives de recyclage.
Las baterías deben desecharse de acuerdo con las leyes y regulaciones locales. Algunas baterías
pueden reciclarse, y es posible que su centro de reciclado local las acepte para desecharlas.
Consulte en su municipalidad sobre las instrucciones para el reciclado.
A barrier designed to reduce the risk of burns is provided with the appliance and must be installed. Never
operate the appliance without the barrier installed.
1.0 general information
W415-1709 / B / 01.31.18
EN
6
general information
1.1 rates and efficiencies
Natural Gas Propane (N/A for LV74)
Min. Inlet Gas Supply
Pressure
4.5" w.c. (11mb) 11" w.c. (27mb) 4.5" w.c. (11mb) 11" w.c. (27mb)
Max. Inlet Gas Supply
Pressure
13" w.c. (32mb) 13” w.c. (32mb) 13” w.c. (32mb) 13” w.c. (32mb).
Manifold Pressure (Under
Flow Conditions)
3.5” w.c. (9mb) 10” w.c. (25mb) 3.5 w.c. (9mb) 10” w.c. (25mb)
LV38-1 / LV50-2 / LV62 / LV74
Single-Sided See-thru
Appliance Type
LV38N-1 LV38P-1 LV38N2-1 LV38P2-1
Fuel Type
Natural Gas Propane Natural Gas Propane
Altitude (FT) 0-4,500 0-4,500 0-4,500 0-4,500
Max. Input (BTU/HR) 30,000 28,000 30,000 28,000
Min. Input (BTU/HR) 21,000 24,000 21,000 24,000
Single-Sided See-thru
Appliance Type
LV50N-2 LV50P-2 LV50N2-2 LV50P2-2
Fuel Type
Natural Gas Propane Natural Gas Propane
Altitude (FT) 0-4,500 0-4,500 0-4,500 0-4,500
Max. Input (BTU/HR) 36,000 32,000 36,000 32,000
Min. Input (BTU/HR) 25,000 30,000 25,000 30,000
Single-Sided See-thru
Appliance Type
LV62N LV62P LV62N2 LV62P2
Fuel Type
Natural Gas Propane Natural Gas Propane
Altitude (FT) 0-4,500 0-4,500 0-4,500 0-4,500
Max. Input (BTU/HR) 42,000 34,000 42,000 34,000
Min. Input (BTU/HR) 29,000 30,000 29,000 30,000
LV50-2
Single-Sided See-thru
Appliance Type
LV74N LV74N2
Fuel Type
Natural Gas Natural Gas
Altitude (FT) 0-4,500 0-4,500
Max. Input (BTU/HR) 48,000 48,000
Min. Input (BTU/HR) 30,000 30,000
LV38-1
LV62
LV74
EN
W415-1709 / B / 01.31.18
7
general information
12
11
6
5
9
8
4
7
3
1.2 installation overview
Recommended installation steps:
1. Determine venting requirements before deciding the final location of the appliance.
2. Plan out appliance enclosure, framing, fronts, accessories, etc.
3. Install rough framing (refer to “rough framing” section).
4. Place the appliance in its final position.
5. Install nailing tabs (refer to “nailing tab installation” section).
6. Install appliance venting (refer to “venting installation” section).
7. Install vent shield (refer to “vent shield installation” section).
8. Install all electrical wirings (refer to “electrical information” section).
9. Install gas lines (refer to “gas installation” section).
10. Test appliance.
11. Complete framing (refer to “finish framing” section).
12. Finishing (refer to “finishing” section).
13. Complete installation checklist in the owner’s manual and apply serial number to owner’s manual.
For Dynamic Heat Control™ installation steps, refer to the leaflet provided with the Dynamic Heat Control™ kit.
Start Dynamic Heat Control™ installation before step 3 (place the appliance in its final position)
note:
W415-1709 / B / 01.31.18
EN
8
general information
!
WARNING
Always light the pilot whether for the first time or if the gas supply has run out, with the glass door opened
or removed.
Provide adequate clearance for servicing and operating the appliance.
Provide adequate ventilation.
Never obstruct the front opening of the appliance.
Objects placed in front of the appliance must be kept a minimum of 48” (121.9cm) from the front face of
the appliance.
Surfaces around and especially above the appliance can become hot. Avoid contact when appliance is
operating.
Fire risk. Explosion hazard.
High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PSIG. Close the manual shut-off valve before pressure testing gas line at test
pressures equal to or less than 1/2 PSIG (35mb).
Use only Wolf Steel approved optional accessories and replacement parts with this appliance using non-
listed accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result
in a safety hazard and will void the warranty and certification.
The appliance must not be operated at temperatures below freezing (32ºF / 0ºC). Allow the appliance to
warm, to above freezing prior to operation.
This appliance has been designed and certified for indoor use only.
4.1
THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local
codes. Installation practices vary from region to region and it is important to know the specifi cs that apply to your area, for
example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of
Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas
log.
The appliance off valve must be a “T” handle gas cock.
The fl exible connector must not be longer than 36 inches (0.9m).
A carbon monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.
The installation must conform with local codes or, in absence of local
codes, the National Gas and Propane Installation Code CSA B149.1
in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54
in the United States. Suitable for mobile home installation if installed
in accordance with the current standard CAN/CSA Z240MH Series,
for gas equipped mobile homes, in Canada or ANSI Z223.1 and
NFPA 54 in the United States.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing
of that system at test pressures in excess of 1/2 psig (35 mb).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the
absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National
Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a
properly grounded receptacle. The grounding prong must not be removed from the cord plug.
The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable
and benefi cial location for an appliance is in the center of a building, thereby allowing the most effi cient use of the heat
created. The location of windows, doors and, the traffi c fl ow in the room where the appliance is to be located should be
considered. If possible, you should choose a location where the vent will pass through the house without cutting a fl oor or
roof joist. If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the
appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
Institute
®
(NFI) as NFI Gas
Specialists
www.ncertied.org
EN
W415-1709 / B / 01.31.18
9
general information
KEEP BURNER AND CONTROL
COMPARTMENT CLEAN. SEE
INSTALLATION MANUAL.
APPLIANCE NEEDS FRESH
AIR FOR SAFE OPERATION
AND MUST BE INSTALLED
WITH ADEQUATE PROVISIONS
FOR COMBUSTION
AND VENTILATION AIR.
GARDEZ LE BRÛLEUR ET LE
COMPARTIMENT DES
CONTRÔLES PROPRES.
CONSULTEZ LE MANUEL
D’INSTALLATION. PAR
MESURE DE SÉCURITÉ.
CET APPAREIL DOIT
ÊTRE ALIMENTÉ EN AIR
FRAIS ET AVEC SUFFISANT
D’AIR COMBURANT ET
DE VENTILATION.
WARNING:
IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE
CAN CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF
LIFE. REFER TO INSTALLATION
MANUAL. INSTALLATION AND
SERVICE MUST BE PERFORMED
BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR THE
GAS SUPPLIER.
ATTENTION:
UN INSTALLATION OU UNE
MODIFICATION INAPPROPRIÉE
DU RÉGLAGE, DU SERVICE ET DE
L’ENTRETIEN POURRAIENT ÊTRE
LA CAUSE DE DOMMAGES À LA
PROPRIÉTÉ DE BLESSURES
CORPORELLES OU MÊME LA
MORT. CONSULTER LE MANUEL
D’INSTALLATION. L’INSTALLATION
ET LE SERVICE DOIVENT
ÊTRE EXECUTÉS PAR UN
INSTALLATEUR QUALIFIÉ POUR
LE GAZ, UNE ENTREPRISE DE
SERVICE OU LE FOURNISSEUR
DE GAZ SEULEMENT.
FOR YOUR SAFETY:
DO NOT STORE OR USE GASOLINE
OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN VICINITY OF THIS
OR ANY OTHER APPLIANCE.
CAUTION: DO NOT OPERATE
THE FIREPLACE WITH THE GLASS
REMOVED, CRACKED OR BROKEN.
REPLACEMENT OF THE GLASS
SHOULD BE DONE BY A LICENSED
OR QUALIFIED PERSON.
CAUTION:
HOT WHILE OPERATING. DO NOT TOUCH.
KEEP CHILDREN, CLOTHING, FURNITURE,
GASOLINE OR OTHER FLAMMABLE VAPORS
AWAY.
AVERTISSEMENT:
L’APPAREIL EST CHAUD PENDANT SON
FONCTIONNEMENT. LES ENFANTS, LES
VÊTEMENTS, LES MEUBLES, L’ESSENCE ET
AUTRES LIQUIDES QUI ÉMETTENT DES GAZ
VOLATILS INFLAMMABLES DOIVENT
ÊTRE TENUS ÉLOIGNÉS DE L’APPAREIL.
“This appliance is only for use with the type(s)
of gas indicated on the rating plate and may
be installed in an aftermarket, permanently
located, manufactured home (USA only) or
mobile home, where not prohibited by local
codes. See installation manual for details. This
appliance is not convertible for use with
other gases, unless a certified kit is used.”
«Cet appareil doit être utilisé uniquement
avec les types de gaz indiqués sur la plaque
signalétique et peut être installé dans une
maison préfabriquée (É.-U. seulement) ou
mobile installée à demeure si les règlements
locaux le permettent. Voir le manuel pour
pour plus de renseignements. Cet appareil ne
peut être converti à d’autres gaz, sauf si une
trousse de conversion est utilisée. »
POUR VOTRE
CURITÉ:
NE PAS ENTREPOSER NI UTILISER
D’ESSENCE NI D’AUTRES VAPEURS
OU LIQUIDES INFLAMMABLES
DANS LE VOISINAGE DE CET
APPAREIL OU DE TOUT AUTRE
APPAREIL.
AVERTISSEMENT: NE PAS
UTILISER L’APPAREIL SI LE
PANNEAU FRONTAL EN VERRE
N’EST PAS EN PLACE, EST CRAQUÉ
OU BRISÉ. CONFIEZ LE
REMPLACEMENT DU
PANNEAU À UN
TECHNICIEN
AGRÉÉ.
TITLE: LABEL, RATING PLATE LV38-1
REVISION:
DWG#: W385-2183
DATE: 05.03.17_J.F.K.
MAX SIZE: 8.5" X 4.75"
HOLE TO BE 0.250"Ø
MATERIAL: CLASS III A-2, PERMANENT LABEL, WATERPROOF, .010MIL VELVET MATTE LEXAN AND/OR .050 HI-TEMP POLYESTER, CAPABLE OF WITHSTANDING A
MAXIMUM TEMPERATURE OF 175°F (79°C).
MIN. LETTERING FOR "NOT FOR USE WITH SOLID FUEL. ", "UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC CELUI. " TO BE 10 POINT ARIAL, BOLD FACE,
UPPER CASE AND 2 POINT LEADING SPACING OR EQUIVALENT.
BLACK LETTERING ON WHITE BACKGROUND.
SERIAL NUMBERS TO BE ASCENDING FROM LV38 019817
W385-2183
DIRECT VENT, VENTED GAS FIREPLACES. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING
ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE
WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES,
IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND
SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME
INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A. THIS APPLIANCE MUST BE
INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE CURRENT
ANSI Z223.1, OR CSA B149, INSTALLATION CODES.
FOR USE WITH BARRIER W565-0267.
FOLLOW THE INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
FOYER À GAZ VENTILÉ. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE
SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI
SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE
MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA
NORME DE SÉCURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24
CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE
APPLIQUÉE, SE RÉFÉRER A LA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ
CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES
SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A. CODES. INSTALLER L’APPAREIL SELON LES
CODES OU RÈGLEMENTS LOCAUX, OU EN L’ABSENCE DE TELS RÈGLEMENTS, SELON LES
CODES D’INSTALLATION ANSI Z223.1 OU CSA-B149 EN VIGUER.
POUR UNE UTILISER AVEC
BARRIÈRE
W565-0267
. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE
MANUEL D'INSTALLATION.
UN COMBUSTIBLE SOLIDE NE DOIT PAS ÊTRE UTILISÉ AVEC
CET APPAREIL. UTILISER AVEC LES PORTES VITRÉES
HOMOLOGUÉES SEULEMENT AVEC CETTE APPAREIL.
AVERTISSEMENT: N’AJOUTEZ PAS A CET APPAREIL AUCUN MATÉRIAU DEVANT ENTRER EN CONTACT AVEC
LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE NAPOLEON VENT KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR
INTAKE SYSTEM.
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'ÉVACUATION PROPRE À NAPOLEON. RÉFÉRER AU
MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER ET
RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU SYSTÈME DE PRISE D'AIR.
SERIAL NUMBER/NO. DE SÉRIE: LV38
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CERTIFIED TO CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22-2016 AND ANSI Z21.50-2016 FOR VENTED DECORATIVE GAS FIREPLACES.
CERTIFIÉ SELON LES NORMES NATIONALES CANADIENNES ET AMÉRICAINES: CSA 2.22-2016 ET ANSI Z21.50-2016 POUR LES APPAREILS À GAZ VENTILÉS DÉCORATIFS.
9700539 (WSL) 4001657 (NGZ)
4001658 (NAC) 4001659 (WUSA)
LV38N-1 CLV38N-1 MODEL CLV38P-1 LV38P-1
0-4500FT (0-1370m) ALTITUDE / ÉLÉVATION 0-4500FT (0-1370m)
30,000 BTU/h INPUT / ALIMENTATION 30,000 BTU/h
REDUCED INPUT / ALIMENTATION RÉDUITE
P4
21,000 BTU/h
24,000 BTU/h
38.8%38.8%
NOT FOR USE WITH SOLID FUEL. FOR USE WITH GLASS DOORS
CERTIFIED WITH THIS APPLIANCE ONLY.
WARNING:
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT WITH THE FLAMES, OTHER
THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS / DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES:
SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING AND FINISHING MATERIALS. FOR NON-COMBUSTIBLE FRAMING AND
FINISHING MATERIALS, SEE INSTALLATION MANUAL. DESSUS, CÔTÉS & ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT
POUR LES MATÉRIAUX D'OSSATURE SELON LA MANUEL DE PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION.
TOP / DESSUS 0" RECESSED DEPTH ONE SIDED/ PROFONDEUR D'ENCASTRE UNE FACE 20 1/8"
FLOOR / PLANCHER 0" RECESSED DEPTH SEE THRU/ PROFONDEUR D'ENCASTRE TRAVERS 16 3/16"
SIDES / CÔTÉS 0" BACK / ARRIÈRE 0"
VENT TOP / DESSUS DU CONDUIT D’ÉVENT 3"
VENT SIDES & BOTTOM / CÔTÉS ET DESSOUS DU CONDUIT D'ÉVENT 2"
VERTICAL VENT / CONDUIT D’ÉVENT VERTICAL 1"
MANTEL / TABLETTE 12" *
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 2". SEE INSTALLATION MANUAL FOR GREATER
EXTENSIONS. RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES. SEE INSTALLATION MANUAL FOR
MINIMUM AND MAXIMUM VENT LENGTHS. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE POUR LES LONGUEURS
D'ÉVACUATION MINIMALE ET MAXIMALE. CLEARANCE TO COMBUSTIBLES CAN BE REDUCED BY USING NAPOLEON HEAT
CONTROL. SEE INSTALLATION MANUAL. DÉGAGEMENTS MINIMAUX DES MATÉRIAUX COMBUSTIBLES PEUVENT ÊTRE RÉDUIT PAR
UTILISANT LE CONTRÔLE DE TEMPÉRATURE DE NAPOLÉON. RÉFÉRER AU MANUEL D'INSTALLATION.
ELECTRICAL RATING: 115V, 60HZ. LESS THAN 12 AMPERES
SPÉCIFICATIONS ÉLECTRIQUES: 115V, 60HZ. MOINS DE 12 AMPÈRE
DECORATIVE PRODUCT: NOT FOR USE AS A HEATING APPLIANCE
PRODUIT DÉCORATIF: NE PAS UTILISER COMME APPAREIL DE CHAUFFAGE
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
PRESSION AU COLLECTEUR: 3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE: 4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN: 4.5" D'UNE
COLONNE D'EAU (GN)
MAX. SUPPLY PRESSURE: 7"* W.C. (NG)
PRESSION D'ALIMENTATION MAX: 7"* D'UNE
COLONNE D'EAU (GN)
MANIFOLD PRESSURE: 10 INCHES W.C.(P)
PRESSION AU COLLECTEUR: 10" D'UNE
COLONNE D'EAU (P)
MIN SUPPLY PRESSURE: 11" W.C. (P)
PRESSION D'ALIMENTATION MIN: 11" D'UNE
COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE: 13" W.C. (P)
PRESSION D'ALIMENTATION MAX: 13" D'UNE
COLONNE D'EAU (P)
WOLF STEEL LTD.
*MAXIMUM INLET PRESSURE NOT TO EXCEED 13".
*PRESSION D'ALIMENTATION MAXIMALE NE DEVAIT PAS DÉPASSER 13".
1.3 rating plate/lighting instruction location
Both the rating plate and lighting instructions are attached to a chain located on the left side of the control area
near the valve (access side). Remove the safety barrier and the control cover to gain access to the control area,
refer to the “safety barrier installation / removal” section for detailed removal instructions.
To replace, slide the instructions back into the control area and reinstall the safety barrier assembly.
This illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
SAMPLE
The rating plate must remain with the appliance at all times. It must not be removed.
note:
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33b - 2008, ANSI Z21.88b- 2008 VENTED GAS FIREPLACE HEATER / APPAREIL DE CHAUFFAGE ALIMENTÉ
AU GAZ ET VENTILÉ
VENTED GAS FIREPLACE HEATER. APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE
CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR,
PART 3280. WHEN THIS US STANDARD IS NOT APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOYER DE CHAUFFAGE AU GAZ AVEC ÉVACUATION. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIÉ POUR INSTALLATION DANS UNE
MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉES AU GAZ, EN VIGUEUR AU CANADA OU AUX ÉTATS-UNIS DE LA
NORME DE SECURITÉ ET DE CONSTRUCTION DE MAISONS MANUFACTURÉES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ÉTATS-UNIS NE PEUT ÊTRE APPLIQUÉE, SE RÉFÉRER A LA NORME
RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET LES COMMUNAUTÉS, ANSI/NFPA 501A.
NOT FOR USE WITH
SOLID FUEL. FOR USE
WITH GLASS DOORS
CERTIFIED WITH THIS
UNIT ONLY.
WARNING
:
DO NOT ADD ANY MATERIAL
TO THE APPLIANCE, WHICH WILL COME
IN CONTACT WITH THE FLAMES, OTHER
THAN THAT SUPPLIED BY THE
MANUFACTURER WITH THE APPLIANCE.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS:
TOP 0”
FLOOR 0”
RECESSED DEPTH ONE SIDED 23"
RECESSED DEPTH SEE THRU 13.5”
FRAMING (NOT INCLUDING
FACE MATERIAL)
SIDES 0”
VENT 2"
BACK 0”
MANTLE 15" *
TOP, SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING MATERIALS. FOR FINISHING MATERIALS
SEE OWNERS MANUAL
UN COMBUSTIBLE SOLIDE NE
DOIT PAS ÊTRÉ UTILISÉ AVEC
CET APPAREIL. UTILISER AVEC
LES PORTES VITRÉES
HOMOLOGUÉES SEULEMENT
AVEC CETTE UNITÉ.
AVERTISSEMENT:
N'AJOUTEZ PAS A
CET APPAREIL AUCUN MATÉRIAU DEVANT
ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVEC
CET APPAREIL PAR LE FABRICANT.
DÉGAGEMENTS MINIMAUX DES
MATÉRIAUX COMBUSTIBLES:
DESSUS 0”
PROFONDEUR D'ENCASTRÉ 25"
PLANCHER 0”
ÉVENT 2"
CÔTES 0”
MANTEAU 15" *
ARRIÉRE 0”
MADE IN CANADA / FABRIQUÉ AU CANADA
WOLF STEEL LTD. BARRIE, ONTARIO, CANADA
ALTITUDE / ÉLÉVATION
INPUT / ALIMENTATION
REDUCED INPUT / ALIMENTATION RÉDUITE
ORIFICE / INJECTEUR
MANIFOLD PRESSURE /
PRESSION AU COLLECTEUR
MINIMUM SUPPLY PRESSURE /
PRESSION D'ALIMENTATION MINIMALE
MAXIMUM SUPPLY PRESSURE /
PRESSION D'ALIMENTATION MAXIMALE
0-4500FT (0-1370M)
30,000 BTU/H
23,000 BTU/H
#38
3.5" WATER COLUMN/D'UNE COLONNE D'EAU
4.5" WATER COLUMN/D'UNE COLONNE D'EAU
7.0" WATER COLUMN/D'UNE COLONNE D'EAU
0-4500FT (0-1370M)
30,000 BTU/H
23,000 BTU/H
#53
10" WATER COLUMN/D'UNE COLONNE D'EAU
11" WATER COLUMN/D'UNE COLONNE D'EAU
13" WATER COLUMN/ D'UNE COLONNE D'EAU
THE APPLIANCE MUST BE VENTED USING THE APPROPRIATE
NAPOLEON VENT KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. PROPER REINSTALLATION AND
RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR
INTAKE SYSTEM.
L'APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT L'ENSEMBLE
D'ÉVACUATION PROPRE A NAPOLEON. RÉFÉRER AU MANUEL
D'INSTALLATION DE PROPRIÉTAIRE POUR L'ÉVACUATION
PRÉCISE. IL EST IMPORTANT DE BIEN RÉINSTALLER ET
RESCELLER L'ÉVENT APRÈS AVOIR ASSURÉ LE MAINTIEN DU
SYSTÉME DE PRISE D'AIR.
CLASSIFICATION: 115V 0.82AMP, 60HZ
W385-2007
MODEL NATURAL GAS /
GAZ NATURAL
LHD50NT
MODEL PROPANE
LHD50PT
SERIAL NUMBER/NO. DE SÉRIE: LV50
ELECTRICAL RATING: 115V 0.82AMP, 60HZ
REFERENCE #
W/N 16131
* MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION
HORIZONTALE MAXIMALE: 2". SEE INSTRUCTION MANUAL FOR GREATER EXTENSIONS.
SEE OWNER'S INSTRUCTION MANUAL FOR MINIMUM AND MAXIMUM VENT LENGTHS.
DESSUS, COTÉS & ARRIÈRE: SELON LES ESPACEURS DE DÉGAGEMENT POUR LES MATÉRIAUX D'OSSATURE
SELON LE MANUEL DE PROPRIÉTAIRE POUR LES MATÉRIAUX DE FINITION.
* L'EXTENSION HORIZONTALE MAXIMALE: 2". RÉFÉRER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS
PLUS GRANDES. RÉFÉRER AU MANUEL D'INSTALLATION DE PROPRIÉTAIRE.
Pilot location
Rating plate
location
access side
W415-1709 / B / 01.31.18
EN
10
general information
note:
1.4 mobile home installation
1.5 hardware list
Description Quantity
LV38-1 LV50-2 LV62 LV74
1
Hex Head Sheet Metal Screw 22 22 22 22
2
Round Head Sheet Metal Screw 4 4 4 4
3
Hex Head Sheet Metal Bolt 18 18 18 18
1
2
3
Only fasteners supplied with the appliance are illustrated.
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home
Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas
indicated on the rating plate.
This mobile/manufactured home listed appliance comes factory equipped with a means to secure the appliance. The
shipping brackets that secure the appliance to the pallet can be used to secure the appliance to the floor for mobile
home installation. For mobile home installations, the appliance must be secured.
This appliance is certified to be installed in an aftermarket permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible
for use with other gases, unless a certified kit is used.
Conversion Kits
This appliance is field convertible between Natural Gas (NG) and Propane (P). Propane not available for LV74.
To convert from one gas to another, consult your Authorized dealer/distributor.
Remove 4 screws each side (8 total) then install the
lifting handles to the side of the appliance and secure
using 4 screws each side (8 total). Once the appliance
is in place remove the four screws from each handle to
the appliance. Discard the lifting handles.
1.6 lifting handles installation/removal
note:
The lifting handles MUST be removed prior to rough
framing the appliance.
Safety barrier
EN
W415-1709 / B / 01.31.18
11
dimensions
2.0 dimensions
2.1 single-sided
LV38-1 LV50-2 LV62 LV74
A
(Finishing Flange)
40 3/4”
(1035mm)
52 3/4”
(1340mm)
64 3/4”
(1645mm)
76 3/4”
(1949mm)
B
53 5/16”
(1354mm)
65 5/16”
(1659mm)
77 5/16”
(1964mm)
89 5/16”
(2269mm)
C
57 5/16”
(1456mm)
69 5/16”
(1761mm)
81 5/16”
(2065mm)
93 5/16”
(2370mm)
41 3/16"
1046mm
7 1/16"
179mm
18 5/8"
473mm
3 1/8"
80mm
19 7/8"
1/2”
[12.7mm]
505mm
32 3/4"
832mm
39 11/16"
1008mm
8 1/16"
205mm
8 1/16"
205mm
Ø 8"
203mm
Ø 5"
127mm
A
B
C
SAFETY BARRIER
*
*Finishing flange depth (the finishing flange defines the perimeter of the fireplace opening.
Framing or finishing materials must NEVER encroach inside the finishing flange).
Base of air collar
W415-1709 / B / 01.31.18
EN
12
dimensions
LV38-1 LV50-2 LV62 LV74
A
(Finishing Flange)
40 3/4”
(1035mm)
52 3/4”
(1340mm)
64 3/4”
(1645mm)
76 3/4”
(1949mm)
B
53 5/16”
(1354mm)
65 5/16”
(1659mm)
77 5/16”
(1964mm)
89 5/16”
(2269mm)
C
57 5/16”
(1456mm)
69 5/16”
(1761mm)
81 5/16”
(2065mm)
93 5/16”
(2370mm)
2.2 see-thru
41 3/16"
1046mm
7 1/16"
179mm
18 5/8"
473mm
3 1/8"
80mm
32 3/4"
832mm
39 11/16"
1008mm
16 3/16"
411mm
8 1/16"
205mm
8 1/16"
205mm
Ø 8"
203mm
Ø 5"
127mm
1/2"
[12.7mm]
1/2"
[12.7mm]
A
B
C
SAFETY BARRIER
*
*
*Finishing flange depth (the finishing flange defines the perimeter of the fireplace opening. Framing
or finishing materials must NEVER encroach inside the finishing flange).
Base of air collar
EN
W415-1709 / B / 01.31.18
13
minimum venting requirements
3.0 minimum venting requirements
7.2B
!
WARNING
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
If venting is included with spacers, the vent system must be supported every 3’(0.9m) for both vertical and
horizontal runs. Use support ring assembly W010-0067 or equivalent non-combustible strapping to maintain
the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the
inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required
for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is
maintained. These spaces must not be removed.
This appliance uses a 5” (127mm) exhaust / 8” (203.2mm) air intake vent pipe system. Refer to the
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is
recommended.
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
ue collar which must be sealed using the black high temperature sealant Mill Pac.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
to verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of
vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections)
when using fl exible venting.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4” (21mm) rise per foot/meter using fl exible venting. For safe and
proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single
family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼”
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
Vent
Manufacturer
Starter Adapter Part
Number
Supplier Website
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DNA Metal-Fab www.mtlfab.com
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
following vent systems and may be purchased from the corresponding supplier:
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
alternate constructions, such as a chimney as part of the vent system, is not permitted.
note:
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on termina-
tion shape (i.e. round, or round and square). See appropriate templates folder.
The vent terminal may be painted with high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is
recommended. Appliance should be off.
All vent measurements start at the base of the air collar of the appliance.
This appliance uses a 5” (127mm) exhaust / 8” (203.2mm) air intake vent pipe system. Refer to the
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent
configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement,
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
insulated with the insulation wrapped in a protective sleeve to minimize condensation.
Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a
firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
alternate constructions, such as a chimney as part of the vent system, is not permitted.
note:
For ease of installation, the front frame can be removed. The front frame must be
reinstalled prior to installing the nailing tabs.
important:
The venting configurations outlined in this section are for natural gas models
only. Consult your local authorized dealer for more information.
important:
Horizontal vent sections: A minimum clearance of 3” (76mm) on the top outside of the enclosure and 2”
(51mm) on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to com-
bustibles is required. Horizontal vent sections within enclosures require a minimum clearance of 6”(152mm) at the
top of the vent pipe.
Vertical vent sections: A minimum of 1” (25mm) all around the vent pipe on all vertical runs to combustibles is
required except for clearances in appliances enclosures. Vertical vent sections within enclosures require a mini-
mum clearance of 1” (25mm) around the vent pipe.
W415-1709 / B / 01.31.18
EN
14
minimum venting requirements
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed using
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer
intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection
to the appliance flue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel flexible components with the wall
terminal kit GD422R-2, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12 roof terminal kit GD411,
flat roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With flexible venting, in
conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent
kit GD430.
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to
a minimum.
Horizontal runs may have a 0” (0mm) rise per foot/meter however for optimum performance it is
recommended that all horizontal runs have a minimum 1/4” (21mm) rise per foot/meter using flexible
venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
to verify that it is unobstructed and undamaged.
Rigid and flexible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable
horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum
number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal
connections) when using flexible venting.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single
family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼”
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
Vent
Manufacturer
Starter Adapter Part
Number
Supplier Website
Duravent W175-0170 Wolf Steel www.duravent.com
Amerivent 5DSC-N2 American Metal www.americanmetalproducts.com
Direct Temp 5DT-AA Selkirk www.selkirkcorp.com
SuperSeal 5DNA Metal-Fab www.mtlfab.com
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
following vent systems and may be purchased from the corresponding supplier:
EN
W415-1709 / B / 01.31.18
15
minimum venting requirements
LV38-1 LV50-2 LV62 LV74
D
40” (101.6cm) 46 1/2” (118.1cm) N/A* N/A*
LV38-1 LV50-2 LV62 LV74
D
40” (101.6cm) 46 1/2” (118.1cm) 52 1/2” (133.4cm) 58 1/2” (148.6cm)
30”
(76.2cm)
LV38-1 & LV50-2: 30” (76.2cm) min
LV62 & LV74: 48” (121.9cm) min
LV38-1 & LV50-2: 62 3/4” (159.4cm)
min plus rise
LV62 & LV74: 80 3/4” (205.1cm)
min plus rise
62 3/4"
(159.4cm)
18"
(45.7cm)
SINGLE-SIDED
SINGLE-SIDED
SEE-THRU
SEE-THRU
3.1 typical venting installation
minimum plus rise
maximum
minimum
base of
air collar
base of
air collar
D
maximum
special vent installation (periscope termination)
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when
final grading is completed, the bottom air slot is located a minimum 12” (30.5cm) above grade. The maximum
allowable vent length is 10’ (3m).
12"
(30.5cm)
minimum
to grade
minimum
30”
(76.2cm)
base of air collar
12"
(30.5cm)
minimum
to grade
base of air collar
LV38-1 & LV50-2: 30” (76.2cm) min
D
maximum
*Periscope cannot be used for the models indicated.
W415-1709 / B / 01.31.18
EN
16
minimum venting requirements
40 ft (12m)
maximum
6 ft (1.83m)
minimum
16" (40.6cm)
minimum
SINGLE-SIDED OR SEE-THRU
base of air collar
A 6’ (1.83m) minimum vertical rise is
considered the minimum practical dimen-
sion for the specific appliance enclosure
and a minimal building structure. However,
a greater minimum vertical rise may be
needed to suit the specific application con-
straints or local codes and / or regulatory
requirements.
note:
EN
W415-1709 / B / 01.31.18
17
minimum venting requirements
3.2 minimum air terminal location clearances
Covered balcony applications
††*
Q
MIN
R
MAX
MAX
R
= 3 feet
(0.9m)
= 2 x
≤ 15 feet
(4.6m)
Q
ACTUAL
R
Q
S
G
P
INSTALLATIONS
CANADA U.S.A.
A
12” (30.5cm) 12” (30.5cm) Clearance above grade, veranda porch, deck or balcony.
B
12” (30.5cm)
Δ
9” (229mm)
Δ
Clearance to windows or doors that open.
C
12” (30.5cm)* 12” (30.5cm)* Clearance to permanently closed windows.
D
18”
(45.7cm)**
18”
(45.7cm)**
Vertical clearance to ventilated soffi ts located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
E
12” (30.5cm)** 12” (30.5cm)** Clearance to unventilated soffi t.
F
0” (0mm) 0” (0mm) Clearance to an outside corner wall.
G
0” (0mm)*** 0” (0mm)***
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).
2” (51mm)*** 2” (51mm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).
H
3’(0.9m) 3’(0.9m)****
Clearance to each side of the center line extended above the meter / regulator assembly to a maxi-
mum vertical distance of 15’ (4.6m).
I
3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J
12” (30.5cm) 9” (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.
K
6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
L
7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M
12” (30.5cm)†† 12” (30.5cm)**** Clearance under a veranda, porch or deck.
N
16” (40.6cm) 16” (40.6cm) Clearance above the roof.
O
2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
P
8’ (2.4m) 8’ (2.4m)
Roof must be non-combustible without openings.
Q
3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R
6’ (1.8m) 6’ (1.8m)
See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
S
12” (30.5cm) 12” (30.5cm) Clearance under a covered balcony
Δ The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffi ts.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements, check local codes.
3 feet above if within 10 feet horizontally.
A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the fl oor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
Clearances are to be in accordance with local
installation codes and the requirements of the gas
supplier. In their absence, clearances are to be as
listed above and are based on national codes.
note:
9.1A
note:
Wall terminals are for illustration purposes only. Size and
shapes may vary.
W415-1709 / B / 01.31.18
EN
18
minimum venting requirements
3.3 horizontal termination
0’
0’
Base of
air collar
10’
10’
15’
15’
20’
25’
20’
30’
40’
5’
3 7/8’
(46 1/2”)
1 1/2’
(18”)
2 1/2’
(30”)
38 1/2’
(462”)
5’
1 elbow zone
1-2 elbow zone
1-3 elbow zone
1-4 elbow zone
1-5 elbow zone
1-6 elbow zone
H
V
V+H ≤ 40 ft. (For longer vent runs, a power
vent is required).
H ≤ 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
LV38-1 / LV50-2 / LV62 / LV74 SINGLE-SIDED
&
LV38-1 / LV50-2 SEE-THRU (NATURAL GAS ONLY)
EN
W415-1709 / B / 01.31.18
19
minimum venting requirements
0’
0’
Base of
air collar
10’
10’
15’
15’
20’
25’
20’
30’
40’
5’
4 7/8’
(58 1/2”)
1 1/2’
(18”)
4’
(48”)
5’
1 elbow zone
1-2 elbow zone
1-3 elbow zone
1-4 elbow zone
1-5 elbow zone
1-6 elbow zone
H
V
V+H ≤ 40 ft. (For longer vent runs, a power
vent is required).
H ≤ 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
38 1/2’
(462”)
LV62/ LV74 SEE-THRU (NATURAL GAS ONLY)
W415-1709 / B / 01.31.18
EN
20
minimum venting requirements example
10’
10’
15’
15’
20’
20’
30’
40’
5’
5’
1-3 elbow zone
H
V
V
1
V
2
H
2
H
1
V
=
V
1
+
V
2
= 8 ft
H
=
H
1
+
H
2
= 10 ft
90°
90°
V
1
V
2
H
1
H
2
V and H are measured from the center of the vent elbows
This example represents a vent that has a maximum of three 90º elbows, a combined horizontal vent length (H ) of
10 feet and a combined vertical vent length (V) of 8 feet.
0’
0’
Base of
air collar
Base of
air collar
Since the vent is located in the dark shaded area, it is within the acceptable vent configuration
4 3/4”
(57”)
(NATURAL GAS ONLY)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144

NAPOLEON LV50N2-1 Le manuel du propriétaire

Catégorie
Cheminées
Taper
Le manuel du propriétaire

dans d''autres langues